Fireye NXTSD104-CG Touch Screen User Manual
- June 9, 2024
- fireye
Table of Contents
NXTSD104-CG Touch Screen
User Manual
Overview
- The NXTSD104 touch-screen display system has the following options for connectivity.
- USB Port. Always fitted.
- Optional 8P8C(known as RJ45) socket for 100BASETX Ethernet. The Mini USB is not used.
- Modbus TC/IP is supported.
For more information and wiring diagram, consult the NXOGTSD-6101 Operator’s Guide for Touch-screen bulletin.
1.1 USB Port
This is currently only used for firmware updates, but in the future could
allow burner configuration information and event logs etc, to be copied from
the touch-screen for viewing / archiving on a PC.
1.1.1 MMC Card
Older NXTSD104 used an MMC card behind a small vented cover to update the
screen firmware.
1.2 Ethernet connection
This is the normal, and recommended, method to connect to the touch- screen.
Connection is made into a socket at the side of the display module.
Normally, an Ethernet ‘patch’ cable (1 to 1) will be required to connect the
touch-screen to an Ethernet switch (or router). Another patch cable is then
used to connect from the switch (or router) device to PC’s.
If a direct connection between the touch-screen and a laptop/PC is required, then an Ethernet ‘cross-over’ cable should be used, to eliminate the need for an Ethernet switch. A direct connection of the PC and the TSD to a router can also be used rather than a crossover cable.
1.2.1 Modbus TC/IP
Modbus TC/IP is supported on all NXTSD104 with firmware version 2.300 onwards.
Modbus communications can be sent over the Ethernet, all Modbus registers
listed in Fireye bulletin MOD-6101 are supported.
1.3 CANBUS Display Connection
Connect the touch-screen display to the NX6100 or the PPC6000 using shielded
cable from positions PA1-PA4 or PB1-PB4. Terminate wires to the 4 position
terminal block on the back of the touch-screen display.
1.4 Display Connection with PPC6000 and BurnerLogix YB110
Connect the touch-screen display to the PPC6000 using shielded cable from
positions PA1-PA4 or PB1-PB4.
Terminate wires to the 4 position terminal block on the back of the touch-
screen display.
Connect the YB110 using the three terminal connector labeled A+, B-, 0 volt.
The A+ & B– connections are connected to the Fireye ED610 terminal block
(purchased separately) on terminals 10 & 9 (A & B), the 0 volt connection is
not used. The ED610 is connected to the YB110 via an ED512-4 cable (purchased
separately).
TSD104 setup for use with YB110
After wiring the YB110 to the TSD as shown above, the TSD must be told to
communicate to the YB110 via Modbus. With the burner off, enter full
commissioning mode. (see section 5.3.1.1) by pressing: Menu, Burner Setting
(enter suppliers passcode LV3), then , Menu, Screen Configuration, Display.
Press the Modbus Configuration button. The default is Integrated NX6100. Next
set the Modbus Node id to match the YB110, for example,1. See Fireye bulletin
BL1001 for details as to configuring the Modbus in the BurnerLogix. At this
point you will set the current Modbus configuration to PPC/BurnerLogix. When
the dialog box appears, press Change. Next, press the RS485 Comms button and
select the baud rate that matches the BurnerLogix YB110. The default is
9600,N,1. The currently displayed message from the YB110 display should now
appear in the lower right section of the TSD. Any status or lockout messages
for the YB110 will be displayed here also. The fault numbers assigned to YB110
lockouts is the Modbus message number (found in BL-1001) plus 200. For
example, if the YB110 locked out during PTFI, the message on the TSD104 would
be: F207 LOCKOUT FLAME FAILURE_PTFI. That is, Modbus message number 7+200=
F207.
1.5 Relay Connections
The NXTSD104 contains four user programmable relays, 1,2,3 & 9. The relay
function is selected by either option 17, various other options or via the
Abacus blocks programming software. Abacus is not discussed in this
publication. Depending on whether the relay will be used as an alarm output,
such as flue temperature, or general purpose such as energized when a
particular profile is selected, will determine how the relay is wired. The
tables below are taken from the main bulletin, NEX-6101, please refer to that
publication for complete details.
Option Parameter| Relay Output| GENERAL PURPOSE Connection
Detail
---|---|---
17.1| 1| Display, Low or Line voltage| PR1 PR2 PR3| Common Normally Closed
Normally Open
17.2| 2| Display, Low or Line voltage| PR4 PR5 PR6| Common Normally Closed
Normally Open
17.3| 3| Display, Low or Line voltage| PR7 PR8 PR9| Common Normally Closed
Normally Open
17.4| 4| NX6100, PE1 PE4 Line voltage output ONLY
---|---|---
17.5| 5| N/A
17.6| 6| N/A
17.7| 7| NXDBVSD, PZ15, PZ16, Low voltage <50V AC/DC, 200mA
17.8| 8| NXDBVSD, PZ17, PZ18, Low voltage <50V AC/DC, 200mA
17.9| 9| Available on NXTSD104 display ONLY PR10 Common PR11 Normally Closed
PR12 Normally Open
For Alarm Purpose use, the following shows the correct connections to the “PR” terminals.
Option Parameter| Relay Out put| ALARM Function Connection
Detail
---|---|---
17.1| 1| Display, Low or Line voltage| PR1 PR2 PR3| Common Normally Open
Normally Closed
17.2| 2| Display, Low or Line voltage| PR4 PR5 PR6| Common Normally Open
Normally Closed
17.3| 3| Display, Low or Line voltage| PR7 PR8 PR9| Common Normally Open
Normally Closed
17.4| 4| NX6100, PE1 PE4 Line voltage output ONLY
17.5| 5| N/A
17.6| 6| N/A
17.7| 7| NXDBVSD, PZ15, PZ16, Low voltage <50V AC/DC, 200mA
17.8| 8| NXDBVSD, PZ17, PZ18, Low voltage <50V AC/DC, 200mA
17.9| 9| Available on NXTSD104 display ONLY| PR10
PR11
PR12| Common
Normally Open
Normally Closed
1.6 Line Voltage Status Inputs
The NXTSD104 includes 10 line voltage (120-230 volt) inputs that may be
used to indicate the present status of various interlocks or other related
devises. For example, many of the items in the non-recycling running interlock
circuit can be monitored by the input and their status viewed on the NXTSD104.
These inputs can be labeled on the NXTSD104 as required.
Software Configuration.
2.1 IP Addresses
Devices on an Ethernet communicate using IP addresses and these need to be
assigned to each device on the network. These addresses can be assigned
manually or automatically.
2.2 DHCP – automatically assigned IP addresses.
If the touch-screen and PC are connected together via a router device, or on a
home / office network, it is likely that the router device (or a DHCP server
on a company network) will automatically assign IP addresses to both the PC
and the touch-screen. Ensure that the both the PC and the touch screen are set
to ‘automatic (DHCP)’. Both the touch-screen and PC will have this setting as
a default.
2.2.1 Touch-Screen Ethernet settings :
Select the MENU button and then SCREEN CONFIGURATION button to reveal the
setup screen.
Select the Ethernet tab to reveal the Ethernet settings screen show on the
left. Click the Unlock button to enter the commissioning password which will
allow you to set DHCP or fixed IP options.
Tap the Automatic (DHCP) button to enable this mode. This is confirmed as set
when the indicator within the button is green.
2.2.2 Windows Ethernet settings :
To check the Ethernet settings for the PC, select Network Connections’ from
‘Control Panel’ and then right click on the ‘Local area connection..’ icon.
From the menu select ‘Properties’ to reveal the window shown on the left.
Scroll though the list of connection protocols until ‘Internet Protocol
(TCP/IP)’ is highlighted.
Select the ‘Properties’ button to setup the connection settings.
select the ‘radio’ buttons for automatic IP addressing and automatic server
addressing as shown in the pic-ture on the left, then click on ‘OK’.
Once these settings have been made then the connection may be diagnosed via
the ‘diagnostics’ box on the touchscreen Ethernet page. As in the example
below, the diagnostics for ‘eth0’ (Ethernet) contains the line : inet addr :
192.168.0.161
This means that the touch-screen has made acquired it’s IP address
successfully. If it does not show ‘inet addr’, then tap the ‘refresh’ button a
few times to prompt the touch-screen to fix the connection.
2.3 Manual assignment of IP addresses
If the Touchscreen and PC are not connected to a network which assigns
addresses automatically (for example: a cross-over cable is used to make a
direct connection between them, or a basic switch device is used only), then
the addresses must be assigned manually.
In the Touchscreen, turn ‘Automatic (DHCP)’ off for the Ethernet (eth0)
interface. Next, enter IP Addr, Mask and Gateway in the box below this, using
the keypad:
It is vital that ALL three lines are entered with valid data if automatic is
turned off. For local area networks, it is normal to use 192.168.x.x or
10.10.x.x for IP addresses. Other ranges are used for the internet. In the
example above, I have chosen 192.168.0.150 as the address for the screen. The
network mask is 255.255.255.0 – this mask is ok to use in nearly all
circumstances. The gateway here is 192.168.0.1. A valid IP address must be
entered here, but it will only be used if the Touchscreen requires internet
access (for example for a firmware update or to allow remote access from the
internet). It is ok to use a gateway address that doesn’t actually exist if
neither of these are required – or you can just use the IP address of your PC.
Once you have entered the required information, don’t forget to ‘Apply
Changes’. Note that the USBnet should be left at Automatic since this is
unsupported at the moment.
The IP settings information must then be entered into the PC, if it does not have an address assigned already:
The subnet mask and gateway must be the same as in the Touchscreen, but the last three digits (only) of the IP address must be different (assuming the mask is 255.255.255.0). Here I have used 192.168.0.57 for my pc.
Using the Ethernet features
Open a web browser on your PC and enter the IP address of the Touchscreen into
the URL line, followed by: 5800 192.168.0.150:5800
The browser should insert http:// at the beginning, so you get:
http://192.168.0.150:5800
A ‘java‘ page should open and then shortly after (give it a couple of minutes
if necessary), a new window titled ‘TightVNC‘ will open asking for a password.
On some browsers, this window may open behind the main browser window, so you
may have to go looking for it on your desktop.
Enter the remote access password (the default is ‘test‘, but this may change)
and you should almost immediately get access to the Touchscreen from your PC.
From this window, you can perform all actions that you can on the Touchscreen
except for :
— Entering the full commission ratio passcode
— Initiating ‘safety tests‘.
— Calibrating the Touchscreen
On firmware versions 1.100 onwards (products shipped after summer 2008), you
can simply enter the IP address into your browser without the :5800 on the
end. You will get a menu page where you can directly read fault I event logs
and some other information. You can click the ‘remote control‘ link from that
screen to get the screen access as given by the ‘:5800‘.
If the Touchscreen Ethernet settings seem ok, but it does not work, try
rebooting the Touchscreen by powering off for a few seconds.
More Information
The Touchscreen access is provided using the VNC protocol (virtual network
computing). This uses port 5900 so if the Touchscreen is behind a firewall I
NAT, this port must be forwarded. You can download a free VNC viewer from
http://www.tightvnc.com and use this directly to access the Touchscreen.
This allows the screen to be stretched to fit the PC screen, which is useful
for demonstration etc.
On port 5800 (and later firmware, port 80), the Touchscreen runs a web server
which can be used to download a Java version of the VNC viewer program. This
will allow screen access as described above in any Java-enabled browser on
almost any personal computer platform. This has been tested on windows 98,
2000, XP, Vista, Apple Mac OSX and Linux. It has been tested with Firefox,
Internet explorer and Safari web browsers – however, you may need to download
Sun Java (free) if it is not installed already from http://www.java.com
If the touch-screen is behind a firewall or NAT device, then port 5800 (or
port 80 on later firmware) must be forwarded to allow the VNC program to be
downloaded from the touch-screen.
Internet Explorer version 7 and later will allow you to view multiple tabs to keep track of many boilers on the same screen. To set up multiple tabs, go to Tools, Internet Options, General and enter each IP address on a separate line.
When you start the browser all of your touch-screens will appear, each in a separate tab. You must login to each control screen.
Troubleshooting:
Communication issues: If the communication light on the router fails to come
on with the touch-screen attached, first, check that the Ethernet cables are
plugged in to each port. Next, change cables to rule out a bad cable. Next,
check that the router is in DHCP mode and is transmitting IP addresses. (In
command mode on the attached PC, run ipconfig /all in command mode to
determine the broadcast IP address) On the touch-screen configuration page,
Ethernet tab, check to see if there is an inet addr:, Bcast: and Mask: line
present in the Diagnostics box. If there are no values showing in inet addr:,
switch to Fixed IP mode (press Automatic (DHCP) button to shut off) – enter
valid addresses (see section 2.3).With cables detached and a valid fixed IP
address, press Apply Changes and then Refresh—you should immediately see your
IP address (inet addr:) in the second line of the diagnostics window. If you
do not see any values at this time, contact your local Fireye representative.
On some fixed IP networks, the remote (VNC) screen will freeze after several
minutes of inactivity. If the screen is frozen, press the disconnect button to
close the session, then restart the session.
FIREYE®
3 Manchester Road
Derry, New Hampshire 03038 USA
www.fireye.com
NXTSD104-CG APRIL 5, 2013
Supersedes June 8, 2012
Documents / Resources
|
Fireye NXTSD104-CG Touch
Screen
[pdf] User Manual
NXTSD104-CG Touch Screen, NXTSD104-CG, Touch Screen, Screen
---|---
References
- Fireye | Flame Safeguard and Combustion Controls
- TightVNC: VNC-Compatible Free Remote Desktop Software
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>