POLARIS Edge Series 350 MCM Submersible Pedestal Connector Instruction Manual

June 9, 2024
Polaris

POLARIS Edge Series 350 MCM Submersible Pedestal Connector

INSTALLATION INSTRUCTIONS EDGE SERIES  350 MCM

All Polaris Edge connectors meet or exceed ANSI C119.1 standards for temporary submersion in wet or damp environments, in freshwater or saltwater. Not suited for continuous submersion. Additionally, the ISPBS350 in-line spice is UL486D listed.

  1. Conductor must have insulation acceptable for wet or damp locations.
  2. Wipe any contaminant including dirt, water or oil off the conductor’s insulation.
  3. Mark the conductor insulation 1-1/8″ using the strip length indicated on the connector and 4″ from the end as a reference mark.
  4. Remove the conductor insulation up to the 1-1/8″ strip length, being sure not to score or nick the bare wire. For wire sizes 250 and larger, bevel the insulation’s edge.
  5. Clean aged or oxidized bare conductors with a wire brush.
  6. Remove conductor sleeve from connector. Discard sleeve for 300 – 350 kcmil (if discarded go to step 9).
  7. Cut off the port sleeve at the step indicated on the sleeve. Make sure to cut straight across the end of the appropriately-sized step.
  8. Reinsert the conductor sleeve into the conductor port.
  9. Remove the set screw access plug and loosen the set screw to allow conductor insertion.
  10. For easier assembly, lubricate the exterior of conductor insulation with the included dielectric silicone grease.
  11. Insert the conductor until the 4″ reference mark is even with the end of the port and the conductor hits the back of the connector.
  12. Tighten the pressure screws to the recommended torque below.
  13. Replace set screw access plug.

ISPB 350 SERIES

WIRE RANGE

(MCM/AWG)

| MAX TORQUE (IN/LB)
---|---

10| 35

8| 75

4 – #6| 110

1 – #3| 150

350 MCM – 1/0 AWG| 400

INSTALLATION INSTRUCTIONS EDGE SERIES 600 MCM

All Polaris Edge connectors meet or exceed ANSI C119.1 standards for temporary submersion in wet or damp environments, in freshwater or saltwater. Not suited for continuous submersion. Additionally, the ISPBS350 in-line spice is UL486D listed.

  1. Conductor must have insulation acceptable for wet or damp locations.
  2. Wipe any contaminant including dirt, water or oil off the conductor’s insulation.
  3. Mark the conductor insulation 1-3/8″ and 5-3/16″ from the end.
  4. Remove the conductor insulation up to the 1-3/8″ strip length, be sure not to “score” or “nick” conductor (bare wire). Tip – For wire sizes 400 and larger bevel edge of insulation.
  5. Clean aged or oxidized bare conductors with a wire brush.
  6. Remove the conductor insulation up to the 1-1/8″ strip length, being sure not to score or nick the bare wire. For wire sizes 400 and larger, bevel the insulation’s edge.
  7. Cut off the port sleeve at the step indicated on the sleeve. Make sure to cut straight across the end of the appropriately-sized step.
  8. Reinsert the conductor sleeve into the conductor port.
  9. Remove the set screw access plug and loosen the set screw to allow conductor insertion.
  10. Insert the conductor until the 4″ reference mark is even with the end of the port and the conductor hits the back of the connector.
  11. Tighten the pressure screws to the recommended torque below.
  12. Replace set screw access plug.

ISPB 600 SERIES

WIRE RANGE

(MCM/AWG)

| MAX TORQUE (IN/LB)
---|---

10| 35

8| 75

4 – #6| 110

1 – #3| 150

350 MCM – 1/0 AWG| 400
600 – 400 MCM| 500

INSTALLATION INSTRUCTIONS EDGE SERIES 2/0 AWG

All Polaris Edge connectors meet or exceed ANSI C119.1 standards for temporary submersion in wet or damp environments, in freshwater or saltwater. Not suited for continuous submersion. Additionally, the ISPBS350 in-line spice is UL486D listed.

  1. Conductor must have insulation acceptable for wet or damp locations.
  2. Wipe any contaminant including dirt, water or oil off the conductor’s insulation.
  3. Mark the conductor insulation 3/4″ using the strip length indicated on the connector and 2-1/4″ from the end as a reference mark.
  4. Remove the conductor insulation up to the 3/4″ strip length, being sure not to score or nick the bare wire. For wire sizes #1 AWG and larger, bevel the insulation’s edge.
  5. Clean aged or oxidized bare conductors with a wire brush.
  6. Remove conductor sleeve from connector. Discard sleeve for 1/0 – 2/0 AWG (if discarded go to step 9).
  7. Cut off the port sleeve at the step indicated on the sleeve. Make sure to cut straight across the end of the appropriately-sized step.
  8. Reinsert the conductor sleeve into the conductor port.
  9. Remove the set screw access plug and loosen the set screw to allow conductor insertion.
  10. For easier assembly lubricate the exterior of conductor insulation with the included dielectric silicone grease.
  11. Insert the conductor until the 2-1/4″ reference mark is even with the end of the port and the conductor hits the back of the connector.
  12. Tighten the pressure screws to the recommended torque below.
  13. Replace set screw access plug.

ISPB 2/0 SERIES

WIRE RANGE

(MCM/AWG)

| MAX TORQUE (IN./LB)
---|---

10 – #14| 35

8| 75

4 – #6| 120

1 – #3| 120

2/0 – 1/0 AWG| 120

©2022 NSI Industries
POLARIS_EDGE_INSTRUCTION_SHEETS_0422
nsiindustries.com 800.321.5847