iSMACONTROLLI SFAR-S-6TI Modbus I-O Module Instruction Manual

June 9, 2024
iSMACONTROLLI

iSMACONTROLLI SFAR-S-6TI Modbus I-O Module

SPECIFICATION

Power supply Voltage 10-38 V DC; 10-28 V AC
Power consumption 2,4 W @ 24 V DC 3 V A @ 24 V AC
Temperature inputs 6x Resistive or thermocouple configurable, resolution

0,1°C
Digital outputs| 2xTransistor output max 55 V DC, max 500 mA
Galvanic isolation| Max 1500 Vrms
Interface| RS485, up to 128 devices on the bus
Baudrate| From 2400 to 115200 bps
Ingress protection| IP40 – for indoor installation
Temperature| Operating -10°C – +50°C; Storage -40°C – +85°C
Relative humidity| 5 to 95% RH (without condensation)
Connectors| Max 2.5 mm2
Dimension| 119,1 mm x 101 mm x 22,6 mm
Mounting| DIN rail mounting (DIN EN 50022)
Housing material| Plastic, self-extinguishing PC/ABS

TOP PANEL

TEMPERATURE INPUTS

COMMUNICATION POWER SUPPLY

POWER SUPPLY

WARNING

  • Note, an incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has been correctly wired before turning the power ON.
  • Before wiring, or removing/mounting the product, be sure to turn the power OFF. Failure to do so might cause electric shock.
  • Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
  • Do not disassemble the product. Doing so might cause electric shock or faulty operation.
  • Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere etc.). Failure to do so might cause fire or faulty operation.
  • Firmly tighten the wires to the terminal. Insufficient tightening of the wires to the terminal might cause fire.

TERMINALS OF THE DEVICE

  Modbus Dec Hex Register Name Access Description
  30001 0 0x00 Version/Type Read Version and Type of the device
  30002 1 0x01 Switches Read Switches state
  40003 2 0x02 Baud rate Read & Write RS485 baud rate
  40004 3 0x03 Stop Bits & Data Bits Read & Write No of Stop bits & Data

Bits
 | 40005| 4| 0x04| Parity| Read & Write| Parity bit
 | 40006| 5| 0x05| Response Delay| Read & Write| Response delay in ms
 | 40007| 6| 0x06| Modbus Mode| Read & Write| Modbus Mode (ASCII or RTU)
 | 40010| 9| 0x09| Analog filtering| Read & Write| Configuration analog filtering
 | 40033| 32| 0x20| Received packets LSR (Least Significant Reg.)| Read & Write| No. of received packets
 | 40034| 33| 0x21| Received packets MSR (Most Significant Reg.)| ****

Read & Write

 | 40035| 34| 0x22| Incorrect packets LSR| Read & Write| ****

No of received packets with error

 | 40036| 35| 0x23| Incorrect packets MSR| Read & Write
 | 40037| 36| 0x24| Sent packets LSR| Read & Write| ****

No of sent packets

 | 40038| 37| 0x25| Sent packets MSR| Read & Write
 | ****

30051

| ****

50

| ****

0x32

| ****

Inputs

| ****

Read

| Connected sensors

Bit in high state → sensor is connected

 | 40052| 51| 0x33| Outputs| Read & Write| Alarms state bit 6 and 7 alarm outputs
 | 30053| 52| 0x34| Temperature 1| Read| Temperature or measured analog in mV·10 for voltage to 2048 mV in mV·100 for voltage to 256 mV in °C·10 for temperature

in Ω for resistance

 | 30054| 53| 0x35| Temperature 2| Read
 | 30055| 54| 0x36| Temperature 3| Read
 | 30056| 55| 0x37| Temperature 4| Read
 | 30057| 56| 0x38| Temperature 5| Read
 | 30058| 57| 0x39| Temperature 6| Read
 | ****

30059

| ****

58

| ****

0x3A

| ****

Alarm temperature 1

| ****

Read

| Alarm temperature for alarm output 1
 | ****

30060

| ****

59

| ****

0x3B

| ****

Alarm temperature 2

| ****

Read

| Alarm temperature for alarm output 2
 | 30061| 60| 0x3C| Junction temperature| Read| Module junction temperature
 | 30062| 61| 0x3D| Measurement current| Read| Measurement current
 | 40063| 62| 0x3E| MAX alarm level 1| Read & Write| ****


If the temperature exceeds this value the corresponding alarm flag is set

 | 40064| 63| 0x3F| MAX alarm level 2| Read & Write
 | 40065| 64| 0x40| MAX alarm level 3| Read & Write
 | 40066| 65| 0x41| MAX alarm level 4| Read & Write
 | 40067| 66| 0x42| MAX alarm level 5| Read & Write
40068| 67| 0x43| MAX alarm level 6| Read & Write|
40069| 68| 0x44| MIN alarm level 1| Read & Write| ****



If the temperature is below this value corresponding alarm flag is set

40070| 69| 0x45| MIN alarm level 2| Read & Write
40071| 70| 0x46| MIN alarm level 3| Read & Write
40072| 71| 0x47| MIN alarm level 4| Read & Write
40073| 72| 0x48| MIN alarm level 5| Read & Write
40074| 73| 0x49| MIN alarm level 6| Read & Write
40075| 74| 0x4A| Alarm settings 1| Read & Write| Alarm settings
**** 0 – alarm due to the current temperature
1 – Remember the value of the alarm, until reset by the master via Modbus
40076| 75| 0x4B| Alarm settings 2| Read & Write
40077| 76| 0x4C| Alarm settings 3| Read & Write
40078| 77| 0x4D| Alarm settings 4| Read & Write
40079| 78| 0x4E| Alarm settings 5| Read & Write
40080| 79| 0x4F| Alarm settings 6| Read & Write
40081| 80| 0x50| Constant junction| Read & Write| Value of junction temperature
40082| 81| 0x51| Junction temperature| Read & Write| Junction temperature offset
40083| 82| 0x52| Input 1 settings| Read & Write| Analog input mode:


0 – input disabled

1 – voltage to 2048 mV

2 – voltage to 256 mV 3 – J thermocouple

4 – K thermocouple 5 – T thermocouple 6 – N thermocouple 7 – S thermocouple

40084| 83| 0x53| Input 2 settings| Read & Write
40085| 84| 0x54| Input 3 settings| Read & Write
40086| 85| 0x55| Input 4 settings| Read & Write
40087| 86| 0x56| Input 5 settings| Read & Write
40088| 87| 0x57| Input 6 settings| Read & Write
40089| 88| 0x58| Output 1 settings| Read & Write| Alarm output settings 0 – output is set by PLC

+1 – temperature from input 1

+2 – temperature from input 2

+4 – temperature from input 3
+8 – temperature from input 4
+16 – temperature from input 5
+32 – temperature from input 6
+256 – Output is set if value is greater than Alarm Value (register 40091 or 40092) („cooling”)

+512 – Output is set if value is less than Alarm Value ( register 40091 or 40092) („heating”)

+1024 – The lowest value from selected inputs

+2048 – The greatest value from selected inputs

(if not select either of the two above options than is used average value of selected inputs)

40090| 89| 0x59| Output 2 settings| Read & Write
40091| 90| 0x5A| Alarm Value 1| Read & Write| Alarm value for outputs
40092| 91| 0x5B| Alarm Value 2| Read & Write
40093| 92| 0x5C| Alarm hysteresis 1| Read & Write| The hysteresis value for alarm outputs
40094| 93| 0x5D| Alarm hysteresis 2| Read & Write
40095| 94| 0x5E| Input resistance 1| Read & Write| ****




Lead wire resistance for each input

40096| 95| 0x5F| Input resistance 2| Read & Write
40097| 96| 0x60| Input resistance 3| Read & Write
40098| 97| 0x61| Input resistance 4| Read & Write
40099| 98| 0x62| Input resistance 5| Read & Write
40100| 99| 0x63| Input resistance 6| Read & Write
| | | | | | | |

INSTALLATION GUIDELINE

Please read the instruction before use or operating the device. In case of any questions after reading this document, please contact the iSMA CONTROLLI Support Team
([email protected]).

  • Before wiring or removing/mounting the product, make sure to turn the power off. Failure to do so might cause an electric shock.
  • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on.
  • Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock.
  • Do not disassemble the product. Doing so might cause an electric shock or faulty operation
  • Use the product only within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might cause a fire or faulty operation.
  • Avoid installing the product in close proximity to high-power electrical devices and cables, inductive loads, and switching devices. Proximity of such objects may cause an uncontrolled interference, resulting in an instable operation of the product.
  • Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can cause interferences in monitored and control signals.
  • It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for devices compared to AC/AC transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from other transformers and loads.
  • Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges.
  • Avoid powering the product and its controlled/monitored devices, especially high power and inductive loads, from a single power source. Powering devices from a single power source causes a risk of introducing disturbances from the loads to the control devices.
  • If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects, which are dangerous for devices.
  • Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external communication. It is recommended to use galvanic separators.
  • To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads.
  • Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena.
  • Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Electrical installation of this product must be done in accordance with national wiring codes and conform to local regulations.

iSMA CONTROLLI S.p.A. – Via Carlo Levi 52, 16010 Sant’Olcese (GE) – Italy | [email protected]
www.ismacontrolli.com
Installation Guideline| 1
st Issue rev. 1 | 05/2022

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

iSMACONTROLLI User Manuals

Related Manuals