COMMSCOPE UNP-6A-DM-1U-24 Distribution Module Panel Instruction Manual
- June 9, 2024
- CommScope
Table of Contents
UNP-6A-DM-1U-24 Distribution Module Panel
Instruction Sheet
General
The CommScope® distribution panels (DM) are available in a 24- or 48-port,
straight, angled or recessed angled configuration.
The panel consists of a rack mounted base unit, rear cable management
hardware, and labels for port numbering. Each panel mounts in a 19-inch
(483mm) equipment rack with universal hole spacing.
Ordering information is listed below:
Material ID | Part No. | Description |
---|---|---|
760162800 | UNP-6A-DM-1U-24 | Uniprise Distribution Module Panel, Cat 6A, UTP, |
1U, 24 port
760162818| UNP-6A-DM-2U-48| Uniprise Distribution Module Panel, Cat 6A, UTP,
2U, 48 port
760162826| UNPA-6A-DM -1U-24| Uniprise Angled Distribution Module Panel, Cat
6A, UTP, 1U, 24 port
760162834| UNPA-6A-DM -2U-48| Uniprise Angled Distribution Module Panel, Cat
6A, UTP, 2U, 48 port
760180000| CPP-5E-DM-1U-24| CommScope Distribution Module Panel, Cat 5E, UTP,
1U, 24 port
760180018| CPP-5E-DM-2U-48| CommScope Distribution Module Panel, Cat 5E, UTP,
2U, 48 port
760180026| CPPA-5E-DM-1U-24| CommScope Angled Distribution Module Panel, Cat
5E, UTP, 1U, 24 port
760180034| CPPA-5E-DM-2U-48| CommScope Angled Distribution Module Panel, Cat
5E, UTP, 2U, 48 port
760180042| UNP-6-DM-1U-24| Uniprise Distribution Module Panel, Cat 6, UTP, 1U,
24 port
760180059| UNP-6-DM-2U-48| Uniprise Distribution Module Panel, Cat 6, UTP, 2U,
48 port
760180067| UNPA-6-DM-1U-24| Uniprise Angled Distribution Module Panel, Cat 6,
UTP, 1U, 24 port
760180075| UNPA-6-DM-2U-48| Uniprise Angled Distribution Module Panel, Cat 6,
UTP, 2U, 48 port
760237022| CPPR-5E-DM-1U-24| CommScope Recessed Angled Distribution Module
Panel, Cat 5E, UTP, 1U, 24 Port
760237023| CPPR-5E-DM-2U-48| CommScope Recessed Angled Distribution Module
Panel, Cat 5E, UTP, 2U, 48 Port
760237024| NPP-6-DM-1U-24| NETCONNECT Distribution Module Panel, Cat 6, UTP,
1U, 24 port
760237025| NPP-6-DM-2U-48| NETCONNECT Distribution Module Panel, Cat 6, UTP,
2U, 48 port
760237026| NPPA-6-DM-1U-24| NETCONNECT Angled Distribution Module Panel, Cat
6, UTP, 1U, 24 port
760237027| NPPA-6-DM-2U-48| NETCONNECT Angled Distribution Module Panel, Cat
6, UTP, 2U, 48 port
760237028| NPPR-6-DM-1U-24| NETCONNECT Recessed Angle Distribution Module
Panel, Cat 6, UTP, 1U, 24 Port
760237029| NPPR-6-DM-2U-48| NETCONNECT Recessed Angle Distribution Module
Panel, Cat 6, UTP, 2U, 48 Port
760237030| UNPR-6-DM-1U-24| Uniprise Recessed Angled Distribution Module
Panel, Cat 6, UTP, 1U, 24 Port
760237031| UNPR-6-DM-2U-48| Uniprise Recessed Angled Distribution Module
Panel, Cat 6, UTP, 2U, 48 Port
760237032| NPP-6A-DM-1U-24| NETCONNECT Distribution Module Panel, Cat 6A, UTP,
1U, 24 port
760237033| NPP-6A-DM-2U-48| NETCONNECT Distribution Module Panel, Cat 6A, UTP,
2U, 48 port
---|---|---
760237034| NPPA-6A-DM-1U-24| NETCONNECT Angled Distribution Module Panel, Cat
6A, UTP, 1U, 24 port
760237035| NPPA-6A-DM-2U-48| NETCONNECT Angled Distribution Module Panel, Cat
6A, UTP, 2U, 48 port
760237036| NPPR-6A-DM-1U-24| NETCONNECT Recessed Angled Distribution Module
Panel, Cat 6A, UTP, 1U, 24 Port
760237037| NPPR-6A-DM-2U-48| NETCONNECT Recessed Angled Distribution Module
Panel, Cat 6A, UTP, 2U, 48 Port
760237038| UNPR-6A-DM-1U-24| Uniprise Recessed Angled Distribution Module
Panel, Cat 6A, UTP, 1U, 24 Port
760237039| UNPR-6A-DM-2U-48| Uniprise Recessed Angled Distribution Module
Panel, Cat 6A, UTP, 2U, 48 Port
Note: sample product images shown below.
How to Contact Us
- To find out more about CommScope® products, visit us on the web at www.commscope.com/
- For technical assistance:
– Within the United States, contact your local account representative or technical support at 1-800-344-0223. Outside the United States, contact your local account representative or PartnerPRO™ Network Partner.
– Within the United States, report any missing/damaged parts or any other issues to CommScope Customer Claims at 1-866-539-2795 or email to claims@commscope.com. Outside the United States, contact your local account representative or PartnerPRO Network Partner.
Tools Required
- Phillips head screwdriver
- Cable jacket scoring tool
- D-914 punch tool with M110 blade.
Specifications
Wire Termination
Wire Size:
22-24 AWG (0.64 – 0.51 mm) Solid Copper
22-24 AWG (0.64 – 0.51 mm) Seven Stranded Copper
Insulation Size:
0.042 inch maximum DOD
Insulation Types:
Polyethylene, Polypropylene, and FEP
IDC Reterminations:
20 minimum
Modular Jack Mating Cycles:
750 minimum
Environmental Data
Temperature Range:
-40°F (-40°C) to 158°F (70°C) (Storage)
14°F (-10°C) to 140°F (60°C) (Operational)
Humidity:
95% Noncondensing
Parts List
Verify parts against parts list below:
Quantity | Description |
---|---|
24-Port Flat Panel | 48-Port Flat Panel |
48-Port Ang Panel | 24-Port R-Ang Panel |
R-Ang Panel*
1| ―| ―| ―| ―| ―| 24-port flat panel
―| 1| ―| ―| ―| ―| 48-port flat panel
―| ―| 1| ―| ―| ―| 24-port angled panel
―| ―| ―| 1| ―| ―| 48-port angled panel
―| ―| ―| ―| 1| ―| 24-port recessed angled panel
―| ―| ―| ―| ―| 1| 48-port recessed angled panel
4| 4| 4| 4| 4| 4| P12-24 x ½” mounting screws
1| 2| 1| 2| 1| 2| Label holder kit
1| 2| 1| 2| 1| 2| Cable management bar
4| 8| 4| 8| 4| 8| Hook-and-loop straps
Important Safety Instructions
WARNING –
When using this product, the following basic safety precautions should be
followed to reduce the risk of fire, electric shock, and injury to persons:
- Never install communications wiring in wet locations unless it is designed for wet locations.
- Never install this product during a lightning storm. There is a remote risk of electric shock.
- Never touch uninsulated communication wiring or terminals unless the communication circuit has been disconnected at the network interface.
- Caution: All wiring that connects to this equipment must meet applicable local and national building codes and network wiring standards for communication cable.
- NPP Panels do not include 12-24 mounting screws.
Step 1 – Mount Panel to Rack
1. Mount panel to rack.
Step 2 – Terminate Conductors on Rear of Panel
Note: The module comes with a T568B wiring designation label installed. If T568A wiring is desired, first remove the “B” type label, change accordingly. If the module comes with a combined T568 A&B wiring designation label installed, choose T568A wiring or T568B wiring according to label designation.
- Prepare cable for termination. Terminate conductors on the IDC terminals per the wiring diagram shown above and utilizing the provided termination manager.
- See pages 7 and 8 for correct procedure on using the termination manager.
Step 3 – Assemble and Install Rear Cable Manager
- Once cables have been terminated, attach cable bar to rear of panel. For 48-port panels, two cable bars are provided. Insert four hook-and-loop straps to cable bar.
- Lay cables evenly in bends of cable bar and secure using the hook-and-loop straps provided.
Step 4 – Attaching Information Labels
- Enter information on the white information labels provided in label holder kits. Snap holders into panel modules and insert labels into label holders as shown in figure 1.
- To print a designation label, go to http://www.commscope.com/Resources/Labeling-Templates and scroll down to Panels and select the proper label template.
Note: Labeling website has two options for printing labels; letter size and A4 size.
Patch Panel Termination Manager Instructions
The termination managers provide pair positioning, control, and strain relief
features to the rear termination area of the panel. See Figure 1. Instructions
for using the termination manager are listed below.
Not applicable for Cat5e panels
Feed Pairs into Termination Manager (Figure 2)
-
Trim jacket back at least 3 inches (76mm) to expose twisted pairs.
-
Without crossing over or rearranging pairs out of the jacket, position pairs in-line per pair colors below:
T568B Wiring Application (Shown)
Blue, Brown, Orange, Green
T568A Wiring Application
Blue, Brown, Green, Orange -
Insert pairs through 4 holes on top surface of termination manager, one pair per hole, as shown.
-
Continue to feed pairs through termination manager until resistance is encountered at the jacket. This will usually be about 1/4 inch (6mm) from the jacket.
Fold Pairs into Slots (Figure 3)
-
Fold each pair over into adjoining slots on bottom end of termination manager. Conductor colors must be arranged in the slots as listed below:
T568B Wiring Application (Shown)
BL/OR Pairs – Blue/Orange conductors on top
BR/GR Pairs – both White conductors on top
T568A Wiring Application
BL/GR Pairs – Blue/Green conductors on top
BR/OR Pairs – both White conductors on top
Important: Add twist as needed to align pairs with slots. Never remove twist for any pair. Do not allow pairs to untwist inside termination manager or inside cable jacket. -
Ensure that both conductors of each pair are in slots completely without being pinched over bottom end surface.
Snap Termination Manager onto Rear Housing (Figure 4)
-
Snap assembled termination manager onto rear housing with pair colors in proper position. Push on using the termination manager housing, not by pushing with the cable. (Ensure that both lock tabs on manager fully seat into rear housing).
-
After termination manager is snapped onto rear housing, untwist individual pairs fully and line up correct color conductor and white conductor with the label on the rear housing.
Seat Wires into IDC Terminal Slots (Figure 5)
-
Grasping each untwisted pair, push the conductors down into IDC terminal slots to seat them before punching down. Seat down into slots as far as possible. (It may be easier to use needle nose pliers to perform this task).
-
Using the D-914 punch tool with M110 blade on HI impact setting, punch down conductors making sure the tool is straight and that conductors fully engage in the IDC terminals. Stagger the punch-down tool up and down, so that it stays in alignment with the staggered terminal slots.
Recommendations to Aid Assembly
- The termination manager should be snapped onto the rear housing immediately after the pairs have been fed and folded over into the slots. All termination managers should be installed on the panel before proceeding to seat and punch down conductors.
- Flex cables down for easier access, then seat and punch down the entire top row of the panel.
- Flex cables up for easier access, then seat and punch down the entire bottom row.
ADDENDUM:
25 pr Cable Termination if Required
Table A. 25-Pair Cable Terminations (B-Wiring Application)
IDC No.| 1| 2| 3| 4| 5| 6
1| W/BL| W/GY| R/BR| BK/G| Y/O| V/BL
2| BL/W| GY/W| BR/R| G/BK| O/Y| BL/V
3| W/O| R/BL| R/GY| BK/BR| Y/G| V/O
4| O/W| BL/R| GY/R| BR/BK| G/Y| O/V
5| W/G| R/O| BK/BL| BK/GY| Y/BR| V/G
6| G/W| O/R| BL/BK| GY/BK| BR/Y| G/V
7| W/BR| R/G| BK/O| Y/BL| Y/GY| V/BR
8| BR/W| G/R| O/BK| BL/Y| GY/Y| BR/V
Note: Pair 25 is used for spare pair.| |
Table B. 25-Pair Cable Terminations (A-Wiring Application)
IDC No.| 1| 2| 3| 4| 5| 6
1| W/BL| W/GY| R/BR| BK/G| Y/O| V/BL
2| BL/W| GY/W| BR/R| G/BK| O/Y| BL/V
3| W/G| R/O| BK/BL| BK/GY| Y/BR| V/G
4| G/W| O/R| BL/BK| GY/BK| BR/Y| G/V
5| W/O| R/BL| R/GY| BK/BR| Y/G| V/O
6| O/W| BL/R| GY/R| BR/BK| G/Y| O/V
7| W/BR| R/G| BK/O| Y/BL| Y/GY| V/BR
8| BR/W| G/R| O/BK| BL/Y| GY/Y| BR/V
Note: Pair 25 is used for spare pair.| |
WIRE COLOR| ABBREVIATION
---|---
BLUE| BL
WHITE| W
GREEN| G
BROWN| BR
ORANGE| O
RED| R
GRAY| GY
BLACK| BK
YELLOW| Y
VIOLET| V
860584457
Instruction Sheet
www.commscope.com
For RoHS Inquiries: CommScope Inc.
Corke Abbey, Bray Co. Dublin, Ireland
Attn: Legal Department
This product is covered by one or more U.S.
patents or their foreign equivalents. For patents, see
www.commscope.com/ProductPatent/ProductPatent.aspx
© 2016 CommScope, Inc. All rights reserved
References
- CommScope | now meets next
- CommScope | now meets next
- Label Templates for CommScope Structured Cabling Products
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>