Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler Instructions

June 9, 2024
Ferroli

PEGASUS F3 N 2S Floor Standing Gas Boiler InstructionsFerroli PEGASUS F3
N 2S Floor Standing Gas Boiler INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE
PEGASUS F3 N 2S
119 2S1136 2S1153 2S1170 2S1187 2S1221 2S1255 2S1289 2S

GENERAL WARNINGS

  • Carefully read and follow the instructions contained in this instruction booklet.
  • After boiler installation, inform the user regarding its operation and give him this manual, which is an integral and essential part of the product and must be kept with care for future reference.
  • Installation and maintenance must be carried out by professionally qualified personnel, in compliance with the current regulations and according to the manufacturer’s instructions. Do not carry out any operation on the sealed control parts.
  • Incorrect installation or inadequate maintenance can result in damage or injury. The Manufacturer declines any liability for damage due to errors in installation and use, or failure to follow the instructions.
  • Before carrying out any cleaning or maintenance operation, disconnect the unit from the electrical power supply using the switch and/or the special cut-off devices.
  • In case of a fault and/or poor operation, deactivate the unit and do not try to repair it or directly intervene. Contact professionally qualified personnel. Any repair/replacement of the products must only be carried out by qualified personnel using original replacement parts. Failure to comply with the above could affect the safety of the unit.
  • This unit must only be used for its intended purpose. Any other use is deemed improper and therefore hazardous.
  • The packing materials are potentially hazardous and must not be left within the reach of children.
  • The unit must not be used by people (including children) with limited physical, sensory or mental abilities or without experience and knowledge of it, unless instructed or supervised in its use by someone responsible for their safety.
  • The unit and its accessories must be appropriately disposed of, in compliance with the current regulations.
  • The images given in this manual are a simplified representation of the product. In this representation there may be slight and insignificant differences with respect to the product supplied.

**** THE CE MARKING CERTIFIES THAT THE PRODUCTS MEET THE ESSENTIAL REQUIREMENTS OF THE RELEVANT DIRECTIVES IN FORCE.
THE DECLARATION OF CONFORMITY MAY BE REQUESTED FROM THE MANUFACTURER.

INSTALLATION

2.1 Introduction Dear Customer,
Thank you for choosing PEGASUS F3 N 2S, a floor-standing boiler FERROLI featuring advanced design, cutting-edge technology, high reliability and quality construction. Please read this manual carefully and keep it for future reference. PEGASUS F3 N 2S is a high-efficiency heat generator for central heating, using natural gas or liquefied gas and regulated by an advanced electronic control system. The boiler shell consists of cast-iron elements whose particular shape ensures high exchange efficiency in all operating conditions, and an open-flue burner equipped with electronic ignition and ionisation flame control. The boiler also has an automatic boiler air vent valve, a 2-stage control thermostat and a safety thermostat. Thanks to the electronic ignition and flame control system, unit operation is for the most part automatic. The user only has to set the system temperature by means of the control thermostat.
2.2 Control panel
To access the control panel, lift the front door.

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control
panel

Key

  1. Arrangement for thermostatic controller
  2. Boiler pressure/temperature gauge
  3. Manual reset safety thermostat cover
  4. Cap
  5. Flame controller reset button with shutdown indicator
  6. 2-stage boiler control thermostat
  7. 0 – 1 – TEST switch

2.3 Lighting and turning off Lighting

  • Open the gas cock ahead of the boiler.
  • Turn on or insert any switch or plug ahead of the boiler.
  • Turn the boiler switch “7” to 1 (fig. 1).
  • Turn the knob “6” to the required temperature and that of a possible room thermostat to the required temperature value. The burner will light and the boiler begins to  unction automatically, controlled by its adjustment and safety devices.
  • If the boiler is equipped with an electronic thermostatic controller fitted in position 1 of fig. 1, the user must also take into account the manufacturer’s instructions.

If the burners do not light and the button-shutdown indicator 5 comes on after correctly carrying out the lighting procedures, wait about 15 seconds and then press the above-mentioned button. The flame controller reset in this way will then repeat the lighting cycle. If the burners do not light after several attempts, consult the faults section
In case of a power failure while the boiler is working, the burners will go out and relight automatically when the power is restored.

Turning off
Close the gas cock ahead of the boiler, turn knob “7” to 0 and disconnect the power.
To avoid damage caused by freezing during long idle periods in winter, it is advisable to drain all water from the boiler, DHW circuit and system; or add a suitable antifreeze  o the heating system.
The boiler switch “7” has 3 positions “0-1-TEST”; the first two have the on- off function, the third (unstable) must only be used for service and maintenance purposes.
2.4 Adjustments
System temperature adjustment
Turn the knob 6 of fig. 1 clockwise to increase the heating water temperature, or anticlockwise to decrease it. The temperature can be varied from a minimum of 30°C to a maximum of 90°C. However, it is advisable not to operate the boiler below 45°C.
Room temperature adjustment (with optional room thermostat)
Using the room thermostat, set the temperature required in the rooms. By room thermostat command, the boiler lights and brings the system water to the temperature set by boiler control thermostat 6 of fig. 1. The generator goes off when the required temperature in the rooms is reached. If the room thermostat is not installed the boiler will keep the system at the temperature set by the boiler control thermostat.
Water system pressure adjustment
The filling pressure with system cold, read on the boiler water gauge detail 2 of fig. 1, must be approx. 1.0 bar. If, during operation, the system pressure falls (due to the evaporation of gases dissolved in the water) to values below the minimum described above, the user must bring it to the initial value by operating the filling cock. At the end of the operation always close the filling cock.
2.5 Faults
Given below are the faults that can be caused by simple user-solvable problems.

Symbol Faults Cure
Boiler shutdown by the flame controller Check if the gas cocks ahead of

the boiler and on the meter are open.
Press the illuminated indicator-button.
In case of repeated boiler shutdowns, contact the nearest service centre.
| Boiler shutdown due to insufficient system pressure (only if a pressure switch is installed in the system)| Fill the system to 1-1.5 bar cold by means of the system filling cock.
Close the cock after use.
| Boiler shutdown due to water overtemperature| Unscrew the safety thermostat cover and press the button below. In case of repeated shutdowns, contact the nearest service centre.

Before calling the after-sales service, check that the problem is not due to no gas or power.
INSTALLATION
3.1 General Instructions
This unit must only be used for its intended purpose. This unit is designed to heat water to a temperature below boiling point at atmospheric pressure and must be connected to a heating system and/or a water supply system for domestic use, compatible with its performance, characteristics and its heating capacity. Any other use is considered improper. THE BOILER MUST ONLY BE INSTALLED BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, ANY LOCAL REGULATIONS AND THE RULES OF PROPER WORKMANSHIP.
The Manufacturer declines any liability for damage or injury caused by incorrect installation.
3.2 Place of installation
This unit is an “open chamber” type and can only be installed and operated in permanently ventilated rooms. An insufficient flow of combustion air to the boiler will affect its normal operation and fume evacuation. Also, the fumes forming in these conditions (oxides) are extremely harmful to the health if dispersed in the domestic environment. Therefore the place of installation must be free of dust, flammable materials or objects or corrosive gases. The room must be dry and not subject to freezing. When positioning the boiler, leave sufficient space around it for normal maintenance activities.
3.3 Plumbing connections Instructions
The heating capacity of the unit must be previously established by calculating the building’s heat requirement according to the current regulations. For proper operation and long life of the boiler, the plumbing system must be adequate and complete with all accessories that guarantee regular operation and running. If the delivery and return pipes follow a path where air pockets could form in certain places, it is advisable to install vent valves at these points. Also, install a discharge device at the lowest point in the system to allow its complete emptying. If the boiler is installed at a lower level than the system, it is advisable to provide a flowstop valve to prevent the natural circulation of system water. The temperature drop between the delivery manifold and the return to the boiler should not exceed 20°C.
Do not use the water system pipes to earth electrical appliances.
Before installation, carefully wash all the pipes of the system to remove any residuals or impurities that could affect proper operation of the unit.
Carry out the relevant connections as indicated in fig. 10.
It is advisable to install on-off valves between the boiler and heating system allowing the boiler to be isolated from the system if necessary.
Make the boiler connection in such a way that its internal pipes are free of stress.
Water system characteristics
In the presence of water harder than 25° Fr, it is advisable to use suitably treated water, in order to avoid possible scaling in the boiler caused by hard water, or corrosion produced by aggressive water. Due to its low thermal conductivity, scaling even just a few mm thick causes significant overheating of the boiler walls with consequent serious problems. Water treatment is indispensable in case of very large systems (containing large amounts of water) or with frequent introduction of replenishing water in the system. If partial or total emptying of the system becomes necessary in these cases, it is advisable to refill with treated water.
Filling boiler and system
The filling pressure with system cold system must be approx. 1 bar. If, during operation, the system pressure falls (due to the evaporation of gases dissolved in the water) to val- ues below the minimum described above, the user must bring it to the initial value. For correct operation of the boiler, when hot, its pressure must be approx. 1.5-2 bar.
3.4 Gas connection
Before carrying out the connection, make sure the unit is arranged for the type of fuel available and carefully clean all the system gas pipes to remove any residues that could affect proper boiler operation. The gas must be connected to the relevant connection (see fig. 10) in conformity with the current standards, with a rigid metal pipe or with a continuous flexible s/steel tube, installing a gas cock between the system and boiler. Make sure all the gas connections are tight.
The capacity of the gas meter must be sufficient for the simultaneous use of all equipment connected to it. The diameter of the gas pipe leaving the boiler does not determine the diameter of the pipe between the unit and the meter; it must be chosen according to its length and pressure losses, in conformity with the current regulations.
Do not use the gas pipes to earth electrical appliances.
3.5 Electrical connections Connection to the power supply
The boiler must be connected to a single-phase, 230 Volt-50 Hz electric line.
The unit’s electrical safety is guaranteed only when it is correctly connected to an efficient earthing system in conformity with the current safety regulations. Have the efficiency and suitability of the earthing system checked by professionally qualified personnel; the Manufacturer declines any liability for damage caused by failure to earth the system. Also make sure the electrical system is adequate for the maximum power absorbed by the unit, as specified on the boiler dataplate, in particular ensuring that the section of the system’s cables is suitable for the input.
The boiler is prewired and supplied with a connector located inside the control panel, arranged for connection to an electronic thermostatic controller (see wiring diagrams in sec. 5.5). It is also equipped with a three-core cable for connection to the electric line. The connections to the power supply must be made with a permanent connection and equipped with a double-pole switch with contact gap of at least 3 mm, interposing fuses of max. 3A between the boiler and line. It is important to respect the polarities (LINE: brown wire / NEUTRAL: blue wire / EARTH : yellow/green wire) when making the connections to the electric line.
Accessing the electrical terminal block and components inside the control panel
To access the electrical components inside the control panel, follow the sequence in fig. 2. The layout of the terminals for the various connections is given in the wiring diagrams in the technical data section.

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
1

Key
A Undo the 2 self-tapping screws securing the boiler cover.
B Lift by pressing upwards and remove the cover held to the sides of the boiler by pins.
C Undo and remove the two screws and the two plates holding the control panel.
D Turn the control panel forwards.
Any additional sensitive elements of the system’s control and safety devices, temperature probe, pressure switch, thermostat bulb, etc., must be located on the delivery
pipe within 40 cm of the boiler casing rear wall (see fig. 3).
Key
A System delivery
B System return
C 40 cm max.

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
2

3.6 Connection to the flue
The flue connection pipe diameter must not be less than that of the connection on the anti-backflow device. Starting from the anti-backflow device it must have a vertical  ection at least 50 cm long. Comply with the current regulations regarding installation and sizes of the flues and connection pipe. The diameters of the anti-backflow device collars are given in the table of fig. 10.

SERVICE AND MAINTENANCE

4.1 Adjustments
All adjustment and conversion operations must be carried out by Qualified Personnel.
The manufacturer declines any liability for damage or injury caused by unqualified and unauthorised people tampering with the unit.
Burner gas pressure adjustment
The boilers PEGASUS F3 N 2S are arranged to run on natural or liquefied gas. The pressure setting and test are performed in the factory. However, at first lighting, as there may be supply pressure variations, check and if necessary adjust the pressure at the nozzles, respecting the values given in the technical data table in sec.
5.3. Pressure adjustment operations must be carried out with the boiler working, using the pressure regulator on the 2-stage gas valves (see fig. 4)
Preliminary operations:

  1. Light the boiler and turn the control thermostat knob to minimum.
  2. Connect a pressure gauge to the pressure point on the gas manifold pipe of the burner assembly (see part 14 of fig. 11).
  3. Remove the protection cap of the pressure regulator 4 of fig. 4.

Minimum power (1st stage) adjustment

  1. Turn the control thermostat knob slowly clockwise to the 1st click; the gas valve will thus be supplied only on connections A and B (see fig. 4).
  2. Turn the screw 6 of fig. 4, checking that the pressure matches the values given in the technical data table in sec. 5.3.

Maximum power (2nd stage) adjustment

  1. Turn the control thermostat knob to maximum; the gas valve will now be supplied only on connections A, B and C (see fig. 4).
  2. Turn the screw 5 of fig. 4, checking that the pressure matches the values given in the technical data table in sec. 5.3.

The adjustment operations must be performed uniformly on the pressure regulators of all the valves.
The gas pressures measured at the burner gas manifold must be read at least 30 seconds after making the adjustments, i.e. when the flame has stabilised. On completing the adjustment operations, turn the burner on and off 2 – 3 times with the control thermostat and check that the pressure values are those just set; otherwise, it is necessary to make another adjustment to bring the pressures to the correct values.
Gas conversion
The unit can work with Natural gas (G20-G25) or liquefied gas (G30-G31) and is factoryset for use with one of the two gases, as clearly shown on the packing and dataplate. Whenever the unit has to be used with a different gas, a conversion kit will be required, proceeding as follows. From natural to liquefied gas

  1. Replace the nozzles at the main burner and pilot burner, fitting the nozzles specified in the technical data table in sec. 5.3.
  2. Remove the small cap 3 (fig. 4) from the gas valve, screw the ignition “STEP” regulator 2 (contained in the conversion kit) onto the valve and refit the cap 3 on the regulator.
  3. Adjust the burner gas pressures for minimum and maximum power as described in the previous section, setting the values given in the technical data table of section sec. 5.3.
  4. Operations 2 and 3 must be performed on all the valves.
  5. Apply the sticker contained in the conversion kit, near the dataplate as proof of the conversion.

From liquefied to natural gas
Carry out the same operations described above, making sure to remove the ignition “STEP” regulator 2 of fig. 4 of the gas valve; the cap 3 of fig. 4 must be fitted directly on the valve.

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
3

Key of main components

  1. Pressure point upstream
  2. Ignition “STEP” regulator for liquefied gas
  3. Plug
  4. Protection cap
  5. Pressure adjustment screw for max. power
  6. Pressure adjustment screw for min. power (1st stage)
  7. O-ring
  8. Decrease
  9. Increase
    V Honeywell valve VR 4601 CB

Key of electrical connections
A + B = Connections fed for min. power (1st stage)
A + B + C = Connections fed for max. power (2nd stage)
4.2 Commissioning
Commissioning must be carried out by Qualified Personnel.
The following operations and checks must be carried out at first lighting, and after all maintenance that involved disconnecting from the systems or work on safety devices or parts of the boiler.
Before lighting the boiler

  • Open any shutoff valves between the boiler and the system.
  • Check the tightness of the gas system, proceeding with caution and using soapy water to check for any leaks in connections.
  • Fill the water system and make sure all air contained in the boiler and the system has been vented by opening the air valve on the boiler and any vent valves in the system.
  • Make sure there are no water leaks in the system or boiler.
  • Make sure the electrical system is properly connected.
  • Make sure the unit is connected to an efficient earthing system.
  • Make sure the pressure and gas flow values are those required for heating.
  • Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler.

Boiler lighting

  • Open the gas cock ahead of the boiler.
  • Vent the air from the pipe ahead of the gas valve.
  • Turn on or insert any switch or plug ahead of the boiler.
  • Turn the boiler switch (pos. 7 – fig. 1) to position 1.
  • Turn the knob 6 (fig. 1) to a value above 50°C and that of the room thermostat (if present) to the required temperature value. The burner will light and the boiler be- gins to function automatically, controlled by its adjustment and safety devices.

If, after correctly carrying out the lighting procedure, the burners do not light and the button-indicator comes on, wait about 15 seconds then press the abovementioned button. The reset controller will repeat the lighting cycle. If the burners do not light after the second attempt, refer to the section sec. 4.4.
The boiler switch 7 has 3 positions “0-1-TEST”; the first two have the on-off function, the third (unstable) must only be used for service and maintenance purposes.
In case of a power failure while the boiler is working, the burners will go out and relight automatically when the power is restored.

Checks during operation

  • Make sure the fuel circuit and water systems are tight.
  • Check the efficiency of the flue and fume ducts while the boiler is working.
  • Make sure the water is circulating properly between the boiler and the system.
  • Check correct lighting of the boiler, by turning it on and off several times using the room thermostat or boiler thermostat.
  • Make sure the fuel consumption indicated on the meter matches that given in the technical data table in cap. 5.

Turning off
To temporarily turn the boiler off, just turn the boiler switch 7 (fig. 1) to 0.
To turn the boiler off for a prolonged period:

  • Turn the knob of the boiler switch 7 (fig. 1) to 0;
  • Close the gas cock ahead of the boiler;
  • Disconnect the power to the unit;

To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all water from the boiler and the system; or add a suitable antifreeze to the heating system
4.3 Maintenance\
THE FOLLOWING OPERATIONS MUST ONLY BE CARRIED OUT BY QUALIFIED PERSONNEL.
Seasonal inspection of the boiler and flue

It is advisable to carry out the following checks at least once a year:

  • The control and safety devices (gas valve, thermostats, etc.) must function correctly.
  • The fume ducts must be free of obstructions and leaks.
  • The gas and water systems must be tight.
  • The burner and boiler shell must be clean. Follow the instructions in the next section.
  • The electrodes must be free of deposits and properly positioned (see fig. 8).
  • The water pressure in the system when cold must be approx. 1 bar; otherwise bring it to that value.
  • The expansion tank, if present, must be filled.
  • The gas delivery and pressure must correspond to that given in the technical data table (see sec. 5.3).
  • The circulating pumps must not be blocked.

Safety devices
The boiler PEGASUS F3 N 2S is equipped with devices that guarantee safety in case of operation faults.
Temperature limiter (safety thermostat) with manual reset
This device prevents the water temperature in the system from exceeding boiling point.
The maximum cut-in temperature is 110°C.
Automatic reset of the temperature limiter can only occur on cooling of the boiler (the temperature must drop by at least 10°C) and identification and elimination of the problem that caused the shutdown. To reset the temperature limiter, unscrew the cover 3 of fig. 1 and press the button below.
Opening the front casing
To open the boiler front panel, see the sequence in fig. 5.

Before carrying out any operation inside the boiler, disconnect the power and close the gas cock upstream.

Combustion analysis
A fume sampling point has been included in the upper part of the anti-backflow device inside the boiler (see fig. 6).
To take the sample:

  1. Remove the top panel of the boiler
  2. Remove the insulation covering the anti-backflow device
  3. Open the fume sampling point;
  4. Insert the probe;
  5. Adjust the boiler temperature to maximum.
  6. Wait 10-15 minutes for the boiler to stabilise*
  7. Take the measurement.

Analyses made with a non-stabilised boiler can cause measurement errors.

Burner assembly removal and cleaning
To remove the burner assembly:

  • Disconnect the power and turn off the gas ahead of the boiler.
  • Undo the two screws securing the electronic flame controller (detail B – fig. 7) to the gas valve (detail A – fig. 7) and remove the controller.
  • Undo the screws fixing the connectors (F) to the gas valves and remove the connectors.
  • Disconnect the ignition and ionisation cables (E) from the electrode assembly.
  • Undo the nuts fixing the gas supply pipe ahead of the gas valves (detail C – fig. 7).
  • Undo the two nuts fixing the combustion chamber door to the cast iron elements of the boiler (detail D – fig. 7).
  • Remove the burner assembly and combustion chamber door.

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
6

Pilot burner assembly

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
7

  1. Combustion chamber door
  2. Inspection door
  3. Pilot burner
  4. Ignition electrode
  5. Detection electrode
  6. Pilot nozzle
  7. High voltage cable
  8. Gas supply pipe

Cleaning the boiler and flue
For proper cleaning of the boiler (see fig. 9):

  • Turn off the gas ahead of the unit and disconnect the power
  • Remove the front panel of the boiler (fig. 5).
  • Lift the casing cover by pressing upwards.
  • Remove the insulation 5 covering the anti-backflow device.
  • Remove the smoke chamber closing plate.
  • Remove the burner assembly (see next section).
  • Clean from the top downwards, using a flue brush. The same operation can be carried out from the bottom upwards.
  • Clean the fume exhaust ducts between the cast iron elements of the boiler shell with a vacuum cleaner.
  • Carefully refit all the previously removed parts and check the tightness of the gas circuit and the combustion ducts.
  • During cleaning operations be careful not to damage the fume thermostat bulb fitted in the back of the smoke chamber.

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
8

  1. Casing cover
  2. Smoke chamber closing plate
  3. Flue brush
  4. Combustion analysis plug
  5. Insulation

4.4 Troubleshooting

Fault Qn

After several lighting attempts . the electronic controller shuts down the boiler.| Clean the pilot burner nozzles with compressed air.
Check the regular gas flow to the boiler and that the air has been eliminated from the pipes.
Make sure the electrodes are correctly positioned and free of deposits (see fig. 8).
Make sure the boiler is connected to an efficient earth connection.
Check the connections to the ignition and ionisation electrodes.
The electrodes are not discharging in the ignition phase.| Make sure the electrodes are correctly positioned and free of deposits (see fig. 8).
Control thermostat adjusted too low
Check the power supply.
Check the connections to the ignition and ionisation electrodes.
Check the connections to the electronic flame controller.
Make sure the LINE -NEUTRAL are not inverted and that the earth contacts are efficient.
Check the inlet gas pressure and any open gas pressure switches.
Reset the safety thermostat.
Make sure the room thermostat is dosed.
The burner bums poorly: flames too high. too low or too yellow| Gas valve fitter dirty.
Check the gas supply pressure.
Gas nozzles dirty.
Make sure the boiler is not dirty.
Make sure the ventilation in the room where the unit is located is sufficient for proper combustion.
Smell of unburnt gas| Make sure the boiler is dean.
Check the flue draught
Make sure gas consumption is not excessive.
The boiler works but the tempera- Lure fails to increase| Check correct operation of the 2-stage control thermostat.
Make sure the gas valve 2nd stage operator (max. power) is fed.
Make sure gas consumption S not less than that provided for.
Make sure the boiler is perfectly clean.
Make sure the boiler is adequate for the system.
Make sure the heating pump is not blocked.
Temperature of the water to system too high or too low| Check correct operation of the 2-stage control thermostat.
Make sure the heating pump is not blocked.
Make sure the characteristics of the circulating pump are adequate for the system.
Explosion at burner. Ignition delays| Make sure the gas pressure is sufficient and that the boiler casing is not dirty.
The control thermostat switches back on with too great a tempera- ture difference| Make sure the bulb is properly inserted in the sheath.
Check correct operation of the 2-stage thermostat
The boiler produces condensation water| Make sure the boiler is not operating at too low temperatures (below 50°C).
Make sure gas consumption is regular.
Check the efficiency of the flue.
The boiler goes out for no apparent reason| Safety thermostat activation due to an ovedemperature.

TECHNICAL DATA AND CHARACTERISTICS

5.1 Dimensions and connections

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
8

A Version PEGASUS F3 N 119 – 136 2S
B Version PEGASUS F3 N 153 ÷ 289 2S

Type and model| A| B| C| D| E| F| al heating return| a2 heating delivery| a3 Gas inlet
---|---|---|---|---|---|---|---|---|---
PEGASUS F3 N 119 2S| 930| 133| 220| 50| 42| 1050| 2″| 2″| 1″
PEGASUS F3 N 136 2S| 1020| 148| 250| 53| 45| 1050| 2″| 2″| 1″
PEGASUS F3 N 153 2S| 1100| 148| 250| 58| 43| 1050| 2″| 2″| 1″ 1/2
PEGASUS F3 N 170 2S| 1190| 173| 300| 60| 46| 1050| 2″| 2″| 1″ 1/2
PEGASUS F3 N 187 2S| 1270| 173| 300| 58| 44| 1050| 2″| 2″| 1″ 1/2
PEGASUS F3 N 221 2S| 1440| 173| 300| 57| 45| 1050| 2″| 2″| 1″ 1/2
PEGASUS F3 N 255 2S| 1610| 198| 350| 62| 46| 1100| 2″| 2″| 1″ 1/2
PEGASUS F3 N 289 2S| 1780| 198| 350| 66| 49| 1100| 2″| 2″| 1″ 1/2

5.2 General view and main components

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
10

A Version PEGASUS F3 N 119 – 136 2S
B Version PEGASUS F3 N 153 ÷ 289 2S
Key

  1. “0 – 1 – TEST” switch
  2. 2-stage control thermostat
  3. Electronic controller reset button
  4. Cap
  5. thermohydrometer
  6. Cap
  7. Safety thermostat
  8. Arrangement for fitting an electronic controller
  9. Fume point on fume chamber
  10. Gas pressure switch
  11. Pilot burner complete with electrodes
  12. Gas manifold
  13. Pressure point
  14. Drain cock
  15. Electronic flame controller
  16. Gas valve
  17. 2nd stage operator

5.3 Technical data table

11308 119 136 153 170
Powers Pmax Pmin Pmax PmIn
Pmax PmIn
Heating Capacity (Net Heat Vakie – Hi) kW 131 77 149

110
Useful Heating Power| kW| 119| 71| 136| 82| 153| 92| 170| 102
Gas supply| Pmax| Pmln| Pmax| Pmln| Pmax| Pmln| Pmax| Pmln
Pilot nozzle G20| mm| 1 x 0.40| 1 x 0.40| 1 x 0.40| 1 x 0.40
Pilot nozzle G31| mm| 1 x 0.24| 1 x 024| 1 x 0.24| 1 x 0.24
Main nozzles G20| mm| 7 x 3.40| 8 x 3.40| 9 x 3.40| 10 x 3.40
Supply pressure 620| mbar| 20| 20| 20| 20
Pressure at burner G20| mbar| 13.| 5.| 13.| 5.| 13.| 5.| 13.| 5.
Delivery 620| rii3/h| 14.| 8.| 16.| 9.| 18.| 11.| 20.| 12.
Main nozzles 631| mm| 7 x 2.15| 8 x 2.15| 9 x 2.15| 10 x 2.15
Supply pressure G31| mbar| 37| 37| 37| 37
Pressure at burner G31| mbar| 36| 11.| 36| 11.| 36| 11.| 36| 11.
Delivery G31| kg/h| 10.| 6.0| 12.| 7.| 13.| 8.| 15.| 9.
Heating| | | |
Max. working tempera- tore| °C| 100| 100| 100| 100
Max. working pressure in heating| | 6| 6| 6| 6
No. elements| | 8| 9| 10| 11
Min. working pressure in heating| | 0.4| 0.4| 0.4| 0.4
No. burner trains| | 7| 8| 9| 10
Boiler water content| litres| 38| 42| 46| 50
Weight| | | |
Weight with packing| kg| 470| 530| 575| 625
Electrical power supply| | | |
Max. electrical input| W| 32| 32| 60| 60
Power voltagelfreguency| V/ft| 230/50| 230150| 230/50| 230/50
Electrical protection rat- ing| IP| XOD| XOD| XOD| XOD
irons| L ir| 221| 255e| |
---|---|---|---|---|---
Powers| Pmax| Pmin| Pmax| Pmin| Pmax| Pmin| Pmax| Pmin
Heating Capacity (Net Heat Value – Hi)| | 206| 122| 243| 144| 280| 166| 317| 188
Useful Heating Capacity| kW| 187| 112| 221| 133| 255| 153| 289| 173
Gas supply| Pmax| Pmin| Pmax| Pmin| Pmax| Pmin| Pmax| Pmin
Pilot nouJe G20| mm| 1 x 0.40| 1 x 0.40| 1 x 0.40| 1 x 0.40
Pilot nozzle G31| mm| 1 x 0.24| 1 x 0.24| 1 x 0.24| 1 x 024
Main nozzles G20| mm| 11 x 3.40| 13 x 3.40| 15 x 3.40| 17 x 3.40
Supply pressure G20| mbar| 20| 20| 20| 20
Pressure at burner G20| mbar| 13.| 5.| 13.| 5.| 13.| 5.| 13.| 5.
Delivery 620| m3nh| 22.| 13.| 26.| 15.| 30.| 18.| 34.| 20.
Main nozzles 631| mm| 11 x2.15| 13 x 2.15| 15 x 2.15| 17×215
Supply pressure G31| mbar| 37| 37| 37| 37
Pressure at burner G31| mbar| 36| 11.| 36| 11.| 36| 11.| 36| 11.
Delivery 631| kgb| 16.| 10.| 19.0| 11.| 22.| 13.| 25.| 15.
Heating| | | |
Max. working tempera- tore| ‘t| 100| 100| 100| 100
Max. working pressure in heating| b| 6| 6| 6| 6
No. elements| | 12| 14| 16| 18
MM. working pressure in heating| b| 0.4| 0.4| 0.4| 0.4
No. burner trains| | 11| 13| 15| 17
Boiler water content| litres| 54| 62| 70| 78
Weight| | | |
Weight with pacidng| kg| 665| 760| 875| 945
Electrical power supply| | | |
Max. electrical input| W| 32| 32| 60| 60
Power voltage/frequency| V/Hz| 230/50| 230/50| 230/50| 230/50
Electrical protection rat- ing| P| XOD| XOD| XOD| X00

5.4 Diagrams Pressure loss

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
11

Key
A Pressure losses m H²O column
B Delivery m ³/h
5.5 Wiring diagrams
Key – wiring diagrams
24 – Ignition electrode
32 – Heating circulating pump (not supplied)
44 – Gas valve
49 – Safety thermostat
72 – Room thermostat (not supplied)
82 – Detection electrode
83 – Electronic controller
98 – Switch
116 – Gas pressure switch
129 – Reset button with indicator light
159 – Test button
167 – 2nd stage gas valve
170 – 1st stage control thermostat
171 – 2nd stage control thermostat
Electrical connection diagram model 119 – 136

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
12

Main wiring diagram model 119 – 136

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
13

Electrical connection diagram model 153 ÷ 289
Key – wiring diagrams
24 – Ignition electrode
32 – Heating circulating pump (not supplied)
44 – Gas valve
49 – Safety thermostat
72 – Room thermostat (not supplied)
82 – Detection electrode
83 – Electronic controller
98 – Switch
116 – Gas pressure switch
129 – Reset button with indicator light
159 – Test button
167 – 2nd stage gas valve
170 – 1st stage control thermostat
171 – 2nd stage control thermostat
Electrical connection diagram model 153 ÷ 289

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
14

Main wiring diagram model 153 ÷ 289

Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler - Control panel
15

cod. 3540T624 – Rev. 02 – 11/2018Ferroli PEGASUS F3 N 2S Floor Standing
Gas Boiler - Bar cod. 3540T624 – Rev. 0 -/2018

Documents / Resources

| Ferroli PEGASUS F3 N 2S Floor Standing Gas Boiler [pdf] Instructions
PEGASUS F3 N 2S Floor Standing Gas Boiler, PEGASUS F3 N 2S, Floor Standing Gas Boiler, Standing Gas Boiler, Gas Boiler
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Ferroli User Manuals

Related Manuals