BEKA BA3400 Series Pageant Plug-in Digital Input Modules Instructions
- June 9, 2024
- BEKA
Table of Contents
Instructions for BA3400 series
Pageant plug-in
Digital Input modules Issue 2
16th November 2022
BA3400 Series Pageant Plug-in Digital Input Modules
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire, SG5 2DA, UK Tel: +44(0)1462 438301 e-mail: sales@beka.co.uk web: www.beka.co.uk
INTRODUCTION
The BA3400 series plug-in DI (Digital Input) modules are part of the BEKA Pageant Display system. Two models are available:
BA3401 | 8 contact inputs |
---|---|
BA3402 | 8 NAMUR 2-wire inputs |
Both models have IECEx, ATEX and UKCA intrinsic safety apparatus
certification. The DI modules plug into any of the seven module sockets at the
rear of the BA3101 Pageant Operator Display. Power for the module is provided
by the BA3101 Operator Display which determines the modules response speed. If
required multiple DI modules may be plugged into an Operator Display.
Fig 1 shows a BA3400 DI plug-in module with its features identified.
Each of the eight inputs is a separate intrinsically safe circuit but they are
not isolated from each other. Inputs should therefore only be connected to
isolated sensors and wiring such as reed relays, switch contacts and proximity
detectors. The BA3402 can power and monitor the status of 2-wire NAMUR
compliant sensors, such as proximity detectors. It may also be used to monitor
switch status in noisy environments.
In addition to their normal function, inputs 7 and 8 may be used for the
decoding a quadrature signal from a plant position sensor or a BEKA BA490
rotary encoder.
INTRINSIC SAFETY CERTIFICATION
Notified Body CML B.V. and UK Approved Body Eurofins CML have issued the BA3400 series plug-in DI modules with the following apparatus certificates:
IECEx | IECEx CML 21.0004X |
---|---|
ATEX | CML 21ATEX2110X |
UKCA | CML 21UKEX2111X |
The ATEX certificate has been used to confirm compliance with the European
ATEXr Directive for Group II, Category 1GD equipment, similarly the UKCA
certificate has been used to confirm compliance with UK statutory
requirements. All BA3400 series DI modules carry both the CE and UKCA marks,
subject to local codes of practice, they may be installed in any of the
European Economic Area (EEA) member countries and in the UK. ATEX certificates
are also acceptable for installations in some non EU countries.
These instructions describe IECEx, ATEX and UKCA installations which conform
with IEC / EN 60079-14 Electrical installations design, selection and
erection. When designing systems the local code of practice should be
consulted.
Plug-in BA3400 series Pageant DI Modules are CE marked to show compliance with
the European Explosive Atmospheres Directive 2014/34/EU and the European EMC
Directive 2014/30/EU.
The modules are also UKCA marked to show compliance with UK statutory
requirements Equipment and Protective Systems Intended for Use in Potentially
Explosive Atmospheres Regulations UKSI 2016:1107 (as amended) and with the
Electromagnetic Compatibility Regulations UKSI 2016:1091 (as amended).
2.1 Zones, gas groups and T rating
All of the BA3400 series DI certificates specify the same certification codes:
BA3401 | BA3402 |
---|---|
Ex ia IIC T4 Ga | Ex ia IIC T4 Ga |
Ex ia IIIC T135°C Da* | Ex ia IIIC T195°C Da* |
-40°C ≤ Ta ≤ 65°C | -40°C ≤ Ta ≤ 65°C |
- Dust certification requires the Pageant Operator Panel and the BA3400 series DI module to have a minimum additional IP54 rear protection.
2.2 Special conditions for safe use
i. Under certain extreme circumstances, the nonmetallic parts incorporated in the enclosure of this equipment may generate an ignition-capable level of electrostatic charge. Therefore, the equipment shall not be installed in a location where the external conditions are conducive to the build-up of electrostatic charge on such surfaces. In addition, the equipment shall only be cleaned with a damp cloth.
ii. In installations requiring EPL Da, Db, or Dc, the equipment shall be mounted to an enclosure which provides a minimum degree of protection of IP5X and which meets the requirements of EN60079-0 Clause 8.4 (material composition requirements for metallic enclosures for Group III) and/or EN60079-0 Clause 7.4.3 (Avoidance of a build up of electrostatic charge for Group III) as appropriate. All cable entries into the equipment shall be made via cable glands which provided a minimum degree of protection of IP5X.
iii. The BA3400 series shall only be used as part of a BEKA Pageant System.
2.3 Certification label information
The certification information label is fitted to the side of the BA3400 series plug-in DI module. It shows the model number, certification information, BEKA associates address and year of manufacture together with the serial number.
INSTALLATION
The BA3400 series plug-in DI module should be fitted into one of the seven
sockets at the rear of a BA3101 Pageant Operator Panel as shown in Fig 2.
For a hazardous area installation the plug-in DI module must be manufactured
by BEKA and have certification that specifies that it shall be used as part of
a BEKA Pageant
system.
3.1 Power consumption
The intrinsic safety certification of the BA3400 series plugin modules permits
any combination to be installed in a Pageant BA3101 display but there are
power limitations.
The percentage of the total available power that these modules consumes is:
BA3401 | 8 contact inputs | 4% |
---|---|---|
BA3402 | 8 NAMUR 2-wire inputs | 40% |
The sum of the percentage power consumption’s of all the plug-in modules installed in a BA3101 display must not exceed 100%. 3.2 BA3400 series plug-in DI module Installation
- The BA3400 series DI module may be fitted before or after the Operator Panel is installed. The Operator Panel should not be powered when the module is fitted.
- Carefully insert the DI module into the selected slot at the rear of the BA3101 Pageant Operator Panel. When correctly positioned secure the module by tightening the two captive module fixing screws.
- Connect field wiring to each of the eight pairs of removable input terminals shown in Fig 3. Each input is a separate intrinsically safe circuit and field wiring should comply with segregation requirements specified in IEC/EN 60079-14. If a multicore cable is used for the inputs, it should have Type A or B construction as specified in Clause 16.2.2.7 of IEC/ EN 60079-14 Wiring should be supported to avoid damaging the module’s terminals.
INPUTS
Both models have eight inputs which are not isolated from each other and
should therefore only be connected to isolated sensors. The BA3401 should be
used for contact
and open collector inputs and the BA3402 for NAMUR compliant 2-wire sensors
and for contact and open collector inputs in noisy environments.
4.1 BA3401 inputs
Each of the eight inputs has the following electrical specification allowing
it to sense the status of a wide range of switch contacts and sensors with
open collector outputs.
Sensing voltage | 3.3V |
---|---|
Sensing Current | 33µA |
Switching threshold | |
Closed | < 25kW |
Open | >35kW |
Frequency | Inputs polled 10 times per second by BA3101 Operator Panel. |
The intrinsic safety parameters for
each input are not restrictive as for intrinsic safety purposes the output
current Io is considered to be zero.
Therefore the maximum inductance that may be connected Lo is not specified,
the cable length between the BA3401 input terminals and the sensor is only
limited by the permitted capacitance Co which is extremely large.
Ui = 0
Uo = 4.94V
Io = 0
Po = 0
Co = 100µF for IIC
Any mechanically or magnetically activated switch contact located in the same
hazardous area as the BA3401 may be directly connected to any of the eight
input channels providing the switch and associated wiring can withstand a 500V
insulation test to earth. Most magnetically activated reed relays comply with
these requirements. Most certified intrinsically safe sensors with an open
collector output can also be connected to any of the eight input channels,
providing the sensor output is compatible with the sensing voltage and
current.
4.1.1 BA3401 quadrature input
Input channels 7 and 8 may be used together for decoding a quadrature signal
from a plant position sensor or a BEKA BA490 rotary encoder. Fig 5 shows the
required connections.
Fig 5 Connections for sensor with a quadrature output
Unlike most quadrature inputs which produce one incrementing or decrementing input pulse for each A + B cycle, the BA3401 produces four as shown in Fig 6 which results in increased resolution.
Sensing voltage | 3.3V |
---|---|
Sensing Current | 33µA |
Switching threshold | |
Closed | < 25kW |
Open | >35kW |
Frequency | 1kHz max |
Inputs polled 10 times per second by BA3101 Operator Panel.
The intrinsic safety parameters for the quadrature input are the same as those
for a single input shown in 4.1 and are again not restrictive.
The quadrature sensor and associated wiring should be able to withstand a 500V
rms insulation test to earth.
4.2 BA3402 inputs
Each of the eight inputs has the following electrical specification allowing
it to sense the status of a wide range of 2-wire NAMUR compliant sensors such
as proximity detectors. The BA3402 may also be used for monitoring the status
of switch contacts and sensors with open collector outputs in high noise
environments.
Sensing voltage| 8.2V|
---|---|---
Switching threshold| Lower| Upper
Proximity detector| 1.2mA| 2.1mA
Contact| 2.6kW| 5.5kW
Frequency| Inputs polled 10 times per second by BA3101 Operator Panel.|
The intrinsic safety parameters for each input are shown below.
Ui = 0
Uo = 8.8V
Io = 7.4mA
Po = 16mW
Co = 5.5µF for IIC
Lo = 556mH for IIC
Almost any certified intrinsically safe 2-wire NAMUR compliant sensor located
in the same hazardous area as the BA3402 may be directly connected to any of
the eight input channels. The Ci and Li of the sensor, plus the cable
capacitance and inductance, should be less than Co and Lo of the BA3402 input
.
The sensor and wiring should be able to withstand a 500V rms insulation test
to earth.Because the BA3402 has higher noise
immunity than the BA3401, it should be used in preference to the BA3401 for
switch contact monitoring in noisy environments. A switch contact located in
the same hazardous area as the BA3402 may be connected to any of the eight
input channels providing the switch and associated wiring can withstand a 500V
insulation test to earth. Most certified intrinsically safe sensors with an
open collector output can also be connected to any of the inputs, providing
the sensor output is compatible with the BA3402 sensing voltage and 500V
isolation is maintained.
4.2.1 BA3402 quadrature input
Input channels 7 and 8 may be used together for decoding a quadrature signal
generated by a certified sensor with a quadrature output, or from two separate
sensors having a
90º phase difference. Connections and waveforms are as shown in Figs 8 and
9.Unlike most quadrature inputs which produce one
incrementing or decrementing input pulse for each A + B cycle, the BA3402
produces four as shown in Fig 9 which results in increased resolution.
Sensing voltage| 8.2V|
---|---|---
Switching threshold| Lower| Upper
Proximity detector| 1.2mA| 2.1mA
Contact| 2.6kW| 5.5kW
Frequency| 1kHz max
Inputs polled 10 times per second by BA3101 Operator Panel.|
The intrinsic safety parameters for the quadrature input are the same as those
for a single input shown in 4.2.
The quadrature sensor and associated wiring should be able to withstand a 500V
rms insulation test to earth.
MAINTENANCE
BA3400 series DI input module should be regularly inspected to ensure that it
has not been damaged. The frequency of inspection depends upon environmental
conditions.
No attempt should be made to repair a faulty BA3400 series plug-in DI module.
Suspect modules should be returned to BEKA associates or your local BEKA
agent.
GUARANTEE
BA3400 series DI modules which fail within the guarantee period should be returned to BEKA associates or your local BEKA agent. It is helpful if a brief description of the fault symptoms is provided.
CUSTOMER COMMENTS
BEKA associates are always pleased to receive comments from customers about our products and services. All communications are acknowledged and whenever possible, suggestions are implemented.
All associated manuals, certificates, and datasheets can be downloaded from https://www.beka.co.uk/qr-ba3100
associates
Old Charlton Rd, Hitchin,
Hertfordshire, SG5 2DA, UK
Tel: +44(0)1462 438301
e-mail: sales@beka.co.uk
web: www.beka.co.uk
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>