NOVUS NP640 Relative Pressure Transmitter Instruction Manual
- June 9, 2024
- Novus
Table of Contents
NP640
RELATIVE PRESSURE TRANSMITTER
INSTRUCTIONS MANUAL
V1.0x I
PRESENTATION
NP640 positive relative pressure transmitter are robust and reliable devices
suitable for industrial applications. Its great differential lies in the fact
that it is possible to set its operating range easily and quickly.
With the aid of software, you have access to various information about the
transmitter and can define the most suitable configuration for your process.
PRECAUTION
Before operating the transmitter, you should carefully read the specifications
and instructions for use. In case of damage caused by incorrect operation or
misuse, the arranty becomes null and void.
The installation must be carried out by a specialized professional.
The power supply to the electronic instruments must come from a proper
instrumentation network.
UNPACKING
After unpacking, besides the transmitter, you should find:
- An installation and operation guide.
- A sealed electrical connector.
- A screw to attach the connector to the transmitter.
IDENTIFICATION
The identification label is attached to the body of the transmitter. On this
label, you will find information that allows you to recognize the device.
The figure below shows the identification label and details its information:
SPECIFICATIONS
Reference Conditions:
Environment 23 °C ± 3 °C, 24 V supply, 250 Ω load. Vertical position (pressure
connection down). Atmospheric pressure: 1015 ± 30 mbar.
Measure Type:
≤ 10 bar: Positive relative pressure.
≥ 16 bar: Sealed relative pressure with 1 bar reference pressure.
*Maximum Range (Max. Range) ():**
Measurement Ranges | Over Pressure | Burst Pressure |
---|---|---|
0.1 MPa (1 bar / 14.50 psi) | times the value of the maximum measurement range | |
measurement range | 5 times the upper value of the |
0.4 MPa (4 bar / 58.02 psi)
1 MPa (10 bar / 145.04 psi)
1.6 MPa (16 bar/ 232.06 psi)
2.5 MPa (25 bar / 362.59 psi)
4 MPa (40 bar / 580.15 psi)| 4 value toe upper times of the measurement range
6 MPa (60 bar / 870.20 psi)
10 MPa (100 bar / 1450.38 psi)
16 MPa (160 bar / 2320.60 psi)
25 MPa (250 bar / 3625.94 psi)| 1.5 times the value of the maximum measurement
range| 3 times the upper value of the measurement range
40 MPa (400 bar / 5801.51 psi)
Table 1 – Maximum measurement ranges
(*) Information available on the product identification label.
Rangeability:
3:1, set by software.
Measurement Accuracy:
< ±0.25 % of the maximum range (Max. Range)
Including linearity, hysteresis, and repeatability under reference conditions.
Attention: For ranges with sealed relative measurement, errors proportional to
the ambient pressure may occur when the altitude is different from sea level.
You can easily compensate for these errors by using the Zero Correction
function.
Long-term Stability:
< ± 0.3 % of the maximum range / year
Durability:
10 million cycles.
Thermal Maximum Deviation:
< ±0.05 % of the maximum range / °C
Including zero deviations and span.
Mounting Position Influence:
< 0.001% of the maximum range / °C
Resolution:
< 0.02 % of the maximum range.
Output Signal (Output):
Electric current, 4-20 mA, 2 wires.
Meets NAMUR NE-43 recommendation.
Maximum current: < 21.5 mA.
Power Supply (Power):
11 to 33 Vdc
Internal protection against reversal polarity of voltage supply.
Maximum Load (RL):
RL = (Vcc – 11) / 20 mA (Ω)
Where: Vcc = Voltage supply
Protection Degree:
IP65
Electrical Connection:
Connector for Type A valves (DIN EN 175301-803), IP65.
Conductor 1.5 mm² (max.) and cables between 6 and 8 mm in diameter.
Operating Temperature:
-20 to 70 °C / -4 to 158 °F
Medium Temperature:
-20 to 100 °C / -4 to 212 °F
Storage Temperature:
-40 to 100 °C / -40 to 212 °F
Dynamic Response:
< 30 ms
Process Connection (Thread):
¼ NPT; ½ NPT; ½ BSP, G ¼ (*)
Sensor Features:
Polysilicon Piezoresistive (silicone oil filled)
Transmitter Metal Housing:
Stainless 316
Wetted parts:
Sensor, stainless steel 316
Metal Connection, stainless steel 316
Compatibility: Any gas or liquid compatible with the constituent materials of the wetted parts.
Certification: CE, UKCA
ELECTRICAL CONNECTIONS
For troubleshooting, visit our FAQ at www.novusautomation.com.
Installation Recommendations
- Input signal conductors should run through the plant separately from output and supply conductors. If possible, in grounded conduits.
- The electronic instruments power supply must come from a proper instrumentation network.
- It is mandatory the use of RC FILTERS (electrical noise suppressors) in contactor coils, solenoids, etc.
- To improve the stability, immunity, and safety of the measurement, it is recommended to use the system grounding.
CONFIGURATION
To use the device in its factory configuration, no intervention is necessary.
It can be installed immediately.
To configure it, use the Transmitter Configuration Kit. This kit includes the
TxConfig-II software, distributed free of charge on NOVUS website, and the
TxConfig-USB-DIN43650 interface, which can be purchased in our distribution
and reseller network.
To install the TxConfig-II software, run the setup file
TxConfigIISetup.exe and follow the installer
instructions.
The TxConfig interface must be connected to the transmitter, as shown in the
figure below. The interface provides the power supply necessary for the
transmitter configuration operation.
SOFTWARE CONFIGURATION
When you run the TxConfig-II software, it will automatically recognize the transmitter and will display the following fields:
-
General Information:
This field contains data that identifies the transmitter. For consultation, this information should be submitted to the manufacturer. -
Unit:
Definition of the pressure unit adopted in the measurement range definition fields. -
Measurement Range:
Definition of the measurement range adopted by the transmitter.
Lower Limit: Target pressure value for 4 mA current.
Upper Limit: Target pressure value for 20 mA current.
Minimum Range: It is not possible to set a span lower than the
Minimum Range value indicated below in this same field. -
Sensor Failure: Establishes the behavior of the current output when the transmitter malfunctions:
Minimum: Output current goes to < 4 mA.
Maximum: Output current goes to > 20 mA. -
Zero Offset: When no pressure is applied, corrects for small deviations in the transmitter output current.
-
Send Configuration: Sends the configuration made. Once sent, the configuration will be immediately adopted by the transmitter.
-
Read Configuration: Reads the transmitter setup. The screen will display the current setting, which you can change.
DIMENSIONS
THREAD | A (mm) | B (mm) | WEIGHT (g) |
---|---|---|---|
NPT 1/4 | 16. | 63. | 135 |
NPT 1/2 | 20.0 | 67. | 166 |
BSP 1/2 | 14.0 | 61.0 | 145 |
G 1/4 | 14.0 | 61.0 | 129 |
(**) Previous versions (2020) have other measurements.