KRON Mult-K Grafic Multifunction and Consumption Energy Meter Installation Guide

June 8, 2024
KRON

Mult-K Grafic Multifunction and Consumption Energy Meter
Installation Guide

Mult-K Grafic Multifunction and Consumption Energy Meter

Knowing the Product

KRON Mult-K Grafic Multifunction and Consumption Energy Meter - fig
1

Mult-K Grafic
LCD Display
Navigation keys
Side locks
Power Supply Input
Voltage Input
Current Input
Ethernet Output*

Installing the Product

Accomodate the meter on the panel cutout and fasten it using the side locks Ⓓ. Panel’s cutout dimensions must be 92x92mm KRON Mult-K Grafic Multifunction
and Consumption Energy Meter - fig 2

Power Supply Connection

Power Supply signal must be applied to the Ⓔ terminal block. Cabling must be connected in accordance to the power supply option present in the meter.

Selectable AC Voltage (220 or 120 Vac)

Working Range: 80 to 120%
220Vac| 120Vac
KRON Mult-K Grafic Multifunction and Consumption Energy Meter - fig
3| KRON Mult-K Grafic
Multifunction and Consumption Energy Meter - fig 4
Universal Power Supply| DC Power Supply
Working Range:
85 to 265 Vac / 100 to 37SVdc| Working Range
24, 48Vdc: 80 to 120%12Vdc: 90 to 120%
KRON Mult-K Grafic Multifunction and Consumption Energy Meter - fig
5| KRON Mult-K Grafic
Multifunction and Consumption Energy Meter - fig 6

ATTENTION
Pay extreme attention to the type of auxiliary power supply of your meter.
Incorrect cabling connection or applying a voltage signal above the specified limits can damage it severely.

Voltage Input Connections

Connect phases and neutral references to the Ⓕ terminal block, using the order described below:

Terminal Description Signal do be Connected
4 – N Neutral
3 – Va Phase ‘R’
2 – Vb Phase ‘S’
1 – Vc Phase ‘T’

Measurement Range: 20 to 500Vac Ph-Ph 11,54 to 288,67 Vac Ph-N

Current Input Connections

Connect phase references to the Ⓖ terminal block, using the order described below:

Terminal Description Signal to be Connected
10 – °Ia CT’s S1 – Phase ‘R’
9 – Ia CT’s S2 – Phase ‘R’
8 – °Ib CT’s S1 – Phase ‘S’
7 – Ib CT’s S2 – Phase ‘S’
6 – °Ic CT’s S1 – Phase ‘T’
5 – Ic CT’s S2 – Phase ‘T’

Measurement Range: 20mA to 5Aac (Continuous Overload: up to 7.5Aac)

Accessing Operation Modes

Mult-K Grafic’s Man-Machine Interface is composed of an LCD display and three navigations keys – F1, F2 and F3. The navigation keys can assume diverse functions, which are always presented in the lower navigation bar. To access the intended function/command, the user must press the related key. The lower navigation bar will fade after ten seconds of no interaction with the analyzer.
Instantaneous Measurements: Initial and main mode of the analyzer, which allows access to other modes and the checking of V, A, W, VAr, VA, PF, Hz and THD values. In this mode, use the << and >> keys to navigate through the measurement parameters.
Energy Measurements: checking of kWh+, kWh-, kVArh+ and kVArh values. To access it, with the analyzer in the main mode, press any key. Then, press repeatedly the MODO key until the ENERGIA message appears on the ENERGIA right side. After that, press key.
KRON Mult-K Grafic Multifunction and Consumption Energy Meter - fig
9 Configurations : configuration of constants for PT and CT, connection diagrams, integration time (demand), communication, power quality parameters, and reset commands (energies, demands and voltage measurement campaigns). To access it, with the analyzer in the main mode, press any key.

Configurations mode

The following commands will be available when Configurations mode is accessed:
EDITAR: Editing of the currently selected parameter.
PROX. : Navigates through the pages of the configurations mode.
ALTERA : Confirms the changing of the highlighted parameter.
VOLTAR : Sends the analyzer back to the prior screen.
DEC : Decrements the active digit.
INC : Increments the active digit.
> >  Navigates through the available options of a selected menu.
SAIR :Returns to the main mode, leaving the configurations mode.
Below, menu descriptions and default settings of Mult-K Grafic:

Page Parameter Description Default
1 TP
TC Potential Transformer Ratio

Example: PT — 440/220V, PT ratio = 0002.00
Current Transformer Ratio
Example: CT –1000/5A, CT ratio = 0200.00| 0001.00
0001.00
2| KE
TI.| KE (Pulse constant)
Constant that determines the pulse rate of the related output, in Wh. This parameter needs to be configured only when the analyzer has this feature and its value must be always a TP x TC.
Connection Diagram
Definition of the connection diagram that will be used by the meter as a reference for parameter calculations, according to the measured circuit (Star, Delta,single-phase, two-phase, etc).| 0 Wh
0
(Star — 3Ph+N)
3| If| Integration time for demand calculation| 15
4| Endereco
Velocidade
Formato| MODBUS Address’
Transmission speed (baud rate) Data Format (parity and stop bits)
Forums equipped withEthernet output, this is the Logue potion Much will be present when accessing this par. For this pareictlar cost the address must be Sweet ‘1’.
Default in configuration: 10.0.0.1. default subnet mask: 255.0.00| 254
9600bps
8N2
5| Idioma
Cor LCD
Contraste| MMI language
Display color mode (normal or reverse) Display Contrast| Port.
Normal
50%
6| Memoria
Relogio
Custom| Mass memory configurations, including data recording interval and parameters to be recorded.
Internal Clock Adjustment
Configuration of custom screens. Up to three custom screens can be defined, using three distinct patterns (with 1, 3 or 6 parameters each).| Disabled (IA = 0)
Brazil (UTC-3)
Disabled
7| Reset
Senha
Ed. Senha| Resets energies and demands values.
Activates/Deactives password confirmation for accessing the Configurations mode.
Editing of password for accessing configurations mode.| Disabled
00021
8| Backlight| Display mode (normal or economical)| Econo

Connection Diagram Example – TL-00       KRON Mult-K Grafic
Multifunction and Consumption Energy Meter - fig 10

Connection Diagrams (CD – TL configuration) KRON Mult-K Grafic
Multifunction and Consumption Energy Meter - fig 11

FAQ – Frequently Asked Questions

a. The Mult-K Grafic doesn’t turn on
Check if the connection to the terminal block Ⓔ was made as stated in step ❸ and also if the voltage magnitude applied is within the working range for meter´s power supply.
b. Measurement values seem incorrect
Check if voltage and current connections are corresponding to each other, i.e., each meter’s channel with the same reference indication – Example: (Va, Ia – Ia) – must receive signals from the same phase, as stated in steps ❹ and ❺. Also check if the polarity of CTs is correct (Correct Installing, Primary side: (LINE) P1 – P2 (LOAD)| Secondary side, S1 connected to Ix S2 connected to Ix).
THIS IS A QUICK USER GUIDE, WITH ESSENTIAL INFO FOR CONFIGURING AND INITIAL OPERATION OF THE METER. FURTHER DETAILS CAN BE CHECKED IN THE PRODUCT’S USER MANUAL, ALSO AVAILABLE IN KRON’S WEBSITE: www.kron.com.br.