KRON MEDIDORES iKron 03 Energy Multifunction Meter Installation Guide

June 9, 2024
KRON MEDIDORES

KRON MEDIDORES iKron 03 Energy Multifunction Meter

Quick Installation Guide

Knowing the Product

KRON MEDIDORES iKron 03 Energy Multifunction Meter 1

| iKron 03| | Power Supply

Input

---|---|---|---

| LED display Three rows for

parameter checking (measurements and

configurations)

|

|

Voltage Input

| Indicative LEDs Type of parameter

currently showed in the display

|

|

Current Input

| Navigation keys| | Pulse Output
| Indicative LEDs

Multiplicative factors (k and M)

| |

RS-485 Output

| Side locks| |

Installing the product
Accommodate the meter on the panel cutout and fasten it using the side locks Ⓕ. Panel’s cutout dimensions must be 92x92mm.

KRON MEDIDORES iKron 03 Energy Multifunction Meter 2

Power Supply Connection
Power Supply signal must be applied to the Ⓖ terminal block. Ikron-03’s power supply working range is 85…265Vac / 100…350Vdc (universal source).

Universal Power Supply

85…265Vac / 100…350Vdc (without polarity)
KRON MEDIDORES iKron 03 Energy Multifunction Meter 3

ATTENTION
Pay extreme attention to the type of auxiliary power supply of your meter.
Incorrect cabling connection or applying a voltage signal above the specified limits can damage it severely.

Voltage Input Connections
Connect phases and neutral references to the Ⓗ inputs, using the order described below:

Terminal Description Signal to be Connected
18 – Va ‘Phase’ R
17 – Vb ‘Phase’ S
16 – Vc ‘Phase’ T
15 – N Neutro

Measurement Range: 20 to 500Vac Ph-Ph

11,54 to 288,67 Vac Ph-N

Current Input Connections
Connect phase references to the Ⓘ inputs, using the order described below:

Terminal Description Signal to be Connected
23 – Ia* CT’s S1 – Phase ‘R’
24 – Ia CT’s S2 – Phase ‘R’
21 – Ib* CT’s S1 – Phase ‘S’
22 – Ib CT’s S2 – Phase ‘S’
19 – Ic* CT’s S1 – Phase ‘T’
20 – Ic CT’s S2 – Phase ‘T’

Measurement Range: 20mA to 5Aac (Continuous Overload: up to 6Aac)

Accessing Operation Modes
Instantaneous Measurements: checking of V, A, W, VAr, VA, PF and Hz values. To access this mode, press the MENU key until the Inst message appears in the display. To navigate through menus use RIGHT or LEFT ERROW keys.

KRON MEDIDORES iKron 03 Energy Multifunction Meter 4

Energy Measurements: checking of kWh+, kWh-, kVArh+, kVArh-, kW and kVA values. To access this mode, press the MENU key until the Ener message appears in the display. To navigate through menus use RIGHT or LEFT ERROW keys.

KRON MEDIDORES iKron 03 Energy Multifunction Meter 5

Function (Configurations): configuration of constants for PT and CT, connection diagrams, integration time (demand), communication parameters and reset command (energies and demands). To access this mode, hold the MENU key for three seconds.

KRON MEDIDORES iKron 03 Energy Multifunction Meter 6

Configuring the Product
The first step is to access Function mode, by holding the MENU until the message FunC appears in L1. Then, to navigate through menus use RIGHT or LEFT ERROW keys. To enter a specific menu, use the key.

KRON MEDIDORES iKron 03 Energy Multifunction Meter 7

PT Configuration: Definition of Potential Transformer ratio.
Example: 440/220V, PT= 0002.00.
Use key to navigate through the digits and RIGHT or LEFT ERROW to increment or decrement the value of the active digit. If no PT is used, PT ratio must be 0001.00

KRON MEDIDORES iKron 03 Energy Multifunction Meter 8

CT Configuration: Definition of Current Transformer ratio.
Example: 500/5A, CT = 0100.00.
Use key to navigate through the digits and RIGHT or LEFT ERROW to increment or decrement the value of the active digit. If no CT is used, CT ratio must be 0001.00

KRON MEDIDORES iKron 03 Energy Multifunction Meter 9

CD Configuration: Definition of Connection Diagram, according to the circuit measured.
Use key to navigate through the
digits and RIGHT or LEFT ERROW to increment or decrement the value of the active digit. Please refer to the “Connection Diagrams” table for checking the available CD options.
To confirm a configured value, press until all digits stop flashing, only the LEDs ‘k’ and ‘M’ will be blinking in this situation.

KRON MEDIDORES iKron 03 Energy Multifunction Meter 10

Connection Diagram Example: CD-00

KRON MEDIDORES iKron 03 Energy Multifunction Meter 11

Connection Diagrams (CD – TL configuration)

KRON MEDIDORES iKron 03 Energy Multifunction Meter 12

FAQ – Frequently Asked Questions

  1. The iKron 03 doesn’t turn on
    Check if the connection to the terminal block Ⓖ was made as stated in step ❸ and also if the voltage magnitude applied is within the working range for meter´s power supply.

  2. Measurement values seem incorrect
    Check if voltage and current connections are corresponding to each other, i.e., each meter’s channel with the same reference indication – Example: (Va, Ia – Ia) – must receive signals from the same phase, as stated in steps ❹ and ❺. Also check if the polarity of CTs is correct (Correct Installing, Primary side: (LINE) P1  P2 (LOAD)| Secondary side, S1 connected to Ix S2 connected to Ix). Also verify if PT,CT and CD configurations are correct.

  3. Which parameter should be read to check energy consumption?
    To read energy consumption info, the user must verify the Positive Active Energy parameter (EA). This parameter is the first that appears when Energy Measurements mode is accessed. “EA” is a cumulative value, so, to obtain the energy consumption during a period of time, a prior reading must be subtracted from the current value.

THIS IS A QUICK USER GUIDE, WITH ESSENTIAL INFO FOR CONFIGURING AND INITIAL OPERATION OF THE METER. FURTHER DETAILS CAN BE CHECKED IN THE PRODUCT’S USER MANUAL, ALSO AVAILABLE IN KRON’S WEBSITE: www.kron.com.br