Drayton 2290B Programmable Room Thermostat Installation Guide

June 8, 2024
Drayton

Drayton-logo

Drayton 2290B Programmable Room Thermostat

Installation Guide

Before Installation
If you do not have the knowledge to install the thermostat safely then you must arrange for a competent electrician to install it for you. Wiring must conform to the current IEE regulations. Prior to commencing the installation, you must ensure the mains supply is switched off.

  1. Remove the front cover by releasing the 2 screws at the bottom. Mounting holes and electrical connections are found underneath the hinged black cover(Fig 1).
  2. Fix back plate directly onto the wall using suitable wall plugs and screws or mount it over the existing wall box (Fig 2).
  3. Complete the wiring according to the connection suggestions shown in (Fig 3). For the Basic boiler, Combi boiler and Basic boiler with zone valve applications Digistat with battery or mains supply are suitable. For Electric Heat applications use Digistat with mains supply only.
  4. Close the black hinged terminal cover and replace the front cover by locating the two latches at the top then fasten the 2 screws at the bottom (Fig 4).
  5. Remove the battery cover by sliding the battery cover at the bottom downwards (Fig 5).
  6. Install the 2AA batteries provided (Fig 6).Drayton-2290B-Programmable-Room-Thermostat-fig5
  7. Replace the battery cover(Fig 7).Drayton-2290B-Programmable-Room-Thermostat-fig6
  8. The Digistat is now installed and will automatically start to control the room temperature.

INSTALLER OPTIONS

To make changes to the default InstallerOptions shown below, enter the Installer Options menu by pressing the settings button for 3 seconds. This allows access to the User Menu 01, the Advanced User Settings Menu 02, the Installer Settings 03, and Service Interval Settings 04. Use the + and – buttons to scroll to Installer Options and press to select. You can exit the menu by pressing until you have returned to the home screen. In the Installer Options menu (Fig 8), scroll through the options using the + and – buttons and press O to select. Scroll through the different settings using the + and – buttons and press O to select and save. (Fig 9 shows Option 02 OFF).Drayton-
2290B-Programmable-Room-Thermostat-fig7

  • (Option 01) Partial Sight Assistant
    When enabled, audible tones indicate when the setpoint is more than, less than or equal to the current room temperature when a user manually adjusts the setpoint using the + button: Setpoint > room temperature -single high tone per 0.5°C increase Setpoint = room temperature – double tone Setpoint < room temperature -single low tone per 0.5°C decrease

  • (Option 02) Frost Protection
    The Digistat will switch on the heating ifthe temperature falls to 5°C and maintains a temperature of 7°C even when in OFF mode.

  • (Option 03) Minimum Setpoint Limit
    Change minimum setpoint temperature. After any changes to setpoint limits, all setpoints in AUTO, MANUAL, BOOST and HOLIDAY modes will be modified to conform accordingly.Drayton-2290B-Programmable-Room-Thermostat-
fig8

  • (Option 04) Maximum Setpoint Limit
    Change maximum setpoint temperature. After any changes to setpoint limits, all setpoints in AUTO, MANUAL, BOOST and HOLIDAY modes will be modified to conform accordingly.

  • (Option 05) Optimum Start
    When enabled, this uses current ambient temperature, the next scheduled setpoint and heat gain data captured by the device to adjust the thermostat setpoint early, so the ambient temperature is at the required level when the next event starts.

  • Delayed Start
    When enabled, this uses current ambient temperature, current event setpoint and heating characteristics of the environment to delay implementation of the setpoint if the ambient temperature is already close to it, therefore saving energy.

  • (Option 06) Valve Protection Time
    In some hydronic heating systems it may be required to protect the valve by operating it for a given time. When enabled, this maintenance feature ensures that each relay output is operated for at least one (1) minute each week.

  • (Option 07) Sensor Fault Function
    In the event of a sensorfault, central heating output is reduced to 30%by turning heating ON for 3 minutes, then OFF for 7 minutes.

  • (Option 08) Application Type
    Select the central heating system energy type.

  • (Option 09) System Capability
    Select the flow capability of the heating system.

  • (Option 13) Installer Settings Lock
    When enabled, installers can lock the installer settings menu until a 3 digit code is entered. If the code is forgotten while device is locked, please call the Technical Helpline.

  • (Option 20) Reset
    (Service Interval settings are NOT reset) Reset the Digistat to its original factory settings.

Service IntervalOptions continued on reverse.

  • (Si Option 01) Si Status
    Enable or disable Service Interval Mode.

  • (Si Option 02) Si Type
    Select effect imposed on the heating when service is due.

  • (Si Option 03) Service Due Date
    Set date when next service is due.

  • (Si Option 04) Warning
    Select no. of days before the service due date.

  • (Si Option 05) Service Due Alarm
    Enable or disable the audible service due alarm.

  • (Si Option 06) Si Boost
    Enable or disable the Service Boost feature (5 boosts).

  • (Si Option 07) Password Reset
    Change the 4 digit PIN. If you forget your Si password, please call the Technical Helpline.

Technical Data

Power supply 2x AA 1.5V alkaline batteries
Switch type & rating 3(1)A at 230V/50Hz
Min. recommended current SPDT (voltage free contacts) 10mA@24VAC

(inductive)
Ambient temperature| Operating: 0°C to +40°C Storage: -20°C to 65°C
Ambient humidity (non condensing)|

20% to 80%, 90% non-condensing

Temperature range| 5°C to 30°C
Rated impulse voltage| 4KV
Ball pressure test| 75°C
Disconnection means| 1B
Automatic action| 100,000 cycles
Operating Frequency| 2402-2480 MHz
Max RF Power transmitted|

+10dBm

Pollution situation| Degree 2
Protection level| IP30
Wiring|

comply with IEE wiring regulations

Energy Class| IV = 2%
Relevant EC Directives:

Standards:

| 2014/53/EU (RED)

2011/65/EU (RoHS)

2012/19/EU (WEEE)

EN 60730-1

EN 60730-2-7

EN 60730-2-9

ESTI EN 300 328

ESTI EN 301 489

EN IEC 63000

User Guide

The Drayton Digistat thermostat is a universal thermostat with 24-hour, 5-2-day or 7-day program types and up to 8 time/ temperature events per day and can also be used as a simple room thermostat.

Clock Setting

Your Digistat is fitted with a “real-time clock”, which is pre-set a the factory; you will not have to alter the time settings. A special feature of this real-time clock is it will automatically change over during the GMT/BST summer/winter change-over, removing the need to manually alter the clock at these times.

General Operation
Programmable thermostats do not have “On” and “Off”times like traditional timers. They offer temperature control both day and night and you simply select which temperatures you require at each point in the day. With the unit in “Auto Mode”(the calendar icon is visible at the bottom of the screen) the temperature can be changed for a short time by using the + and – buttons. Changing the temperature in this way will keep the Digistat set to your new temperature until the next pre-programmed event (at which time it will revert to the programmed temperature). The temperature is set, and the unit will revert to showing the room temperature again. The indicator will show on the screen ifthe unit is calling for heat.

Programming the Digistat
Your Digistat comes with the following settings pre-programmed for your convenience and is suitable for those working out of the house during a typical 9-5 pattern. When the 5-2day program type is selected the pre-set temperatures will be different Mon-Fri and Sat-Sun, as per the tables below:

Pre-set Program 1 (24h, 5-2day weekdays, or 7day):

Event| 1| 2| 3| 4| **(5)*| (6)| (7)| (8)**
---|---|---|---|---|---|---|---|---
Time

Temperature

| 06:30

20°C

| 08:30

16°C

| 16:30

21°C

| 22:30

OFF

|  |  |  |
Pre-set Program 1 (5-2day weekend):
Event| 1| 2| 3| 4| **(5)*| (6)| (7)| (8)**
Time

Temperature

| 07:00

20°C

| 09:00

18°C

| 16:00

21°C

| 23:00

OFF

|  |  |  |

To add these additionaltime periods manually (max. 8 per day) please referto the steps to the right. The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by Schneider Electric is under license. Other trademarks and trade names are those of their respective owners.

What is a programmable room thermostat?

…an explanation for householders

A programmable room thermostat is both a programmer and a room thermostat. A programmer allows you to set ‘On’ and ‘Off ’time periods to suit your own lifestyle. A room thermostat works by sensing the air temperature, switching the heating when the air temperature falls belowthe thermostat setting, and switching it off once this set temperature has been reached. So, a programmable room thermostat lets you choose what times you want the heating to be on, and what temperature it should reach while it is on. It will allow you to select different temperatures in your home at different times of the day (and days of the week) to meet your particular needs. Turning a programmable room thermostat to a higher setting will not make the room heat up any faster. How quickly the room heats up depends on the design ofthe heating system, for example, the size of boiler and radiators. Neither does the setting affect how quickly the room cools down. Turning a programmable room thermostat to a lower setting will result in the room being controlled at a lower temperature, and saves energy. The way to set and use your programmable room thermostat is to find the lowest temperature settings that you are comfortable with at the different times you have chosen, and then leave it alone to do its job. The best way to do this is to set low each day until you are comfortable with the temperatures.You won’t have to adjust the thermostat further. Any adjustments above these settings will waste energy and cost you more money.

If your heating system is a boiler with radiators, there will usually be only one programmable room thermostat to control the whole house.But you can have different temperatures in individual rooms by installing thermostatic radiator valves (TRVs) on individual radiators. If you don’t have TRVs, you should choose a temperature that is reasonable for the whole house. If you do have TRVs, you canchoose a slightly higher setting to make sure that even the coldest room is comfortable, then prevent any overheating in other rooms by adjusting the TRVs. The time on the programmer must be correct. Some types have to be adjusted in spring and autumn at the changes between Greenwich Mean Time and British Summer Time.

You may be able to temporarily adjust the heating program, for example, ‘Override, ‘Advance’ or ‘Boost. These are explained in the manufacturer’sinstructions. Programmable room thermostats need a free flow of air to sense the temperature, so they must not be covered by curtains or blocked by furniture. Nearby electric fires, televisions, and wall or table lamps may prevent the thermostat from working properly.

Setting up Times/Temperatures on the Digistat

  1. With the product operating as normal in Auto Mode, press once Use and-to select the day or set of days you want to adjust the times and temperatures for. Press O to confirm.
  2. The time on the display will now be flashing as shown, use +and – to adjust the first-period start time. Press O to confirm.
  3. Once the time has been set the temperature on the display will now be flashing, use + and – to adjust the temperature for the first time period. Press O to confirm.
  4. Move to the next time and temperature periods and adjust as needed, confirming the changes by pressing O. Then the schedule will be saved by pressing when the word SAvE is flashing.
  5. In Pre-set Program 1you will have 4 time periods available, to add more (max. 8 per day) press + when you see the SAVE option on-screen and time period 5 at the bottom of the screen, to scroll to the Add option. Press O to add the time period then adjust the time and temperature as required.
  6. To exit press go back until you return to the home screen.

To change from Automatic to Manual mode use the settings button to access the theUser01 menu. From here select Mode and use the up and down buttons to select Auto or Man. Confirm with the O button and use the back button to exit.

All done!
You have completed the quick start and the unit is now set correctly to follow your required timings. For further user information surrounding the thermostat and the app control please use the website where you can download full user instructions.

401 Southway Drive Schneider Electric Industries SAS
Plymouth 35 rue Joseph Monier
PL6 6QT F-92500 Rueil-Malmaison
United Kingdom France

Technical Helpline Tel: 0333 6000 622
Website: www.draytoncontrols.co.uk
Email: customer.care@draytoncontrols.co.uk

Hereby, Schneider Electric Controls UK Ltd, declares that Digistat 2290B
is in complia nce with Direc tive 2014/53/EU.
The declaration of conformity may be consulted at
www.draytoncontrols.co.uk

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Drayton User Manuals

Related Manuals