Aeotec MultiSensor 7 ZWA024-A Manual

June 8, 2024
Aeotec

Table of Contents

Aeotec

MultiSensor 7

SKU: ZWA024-A

Quickstart

This is a
secure
Alarm Sensor
for
.

Please make sure the internal battery is fully charged.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

Aeotec MultiSensor 7 is aZ-Wave smart sensor. The corner of your room just got 6 times smarter. Its a motion sensor and its also so much more. Installing this 1 piece of Z-Wave technology is the same as installing 6 pieces of Z-Wave technology. Your home control network will immediately understand motion, temperature, humidity,light, Ultraviolet and Vibration readings wherever MultiSensor 6 is installed. Those intelligent readings will equate to intelligent automation. And intelligent automation will give you the perfect smart home.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| Lifeline. Device Reset Locally: When factory reset.Notification Report:See Notification Chapter for more information.Sensor Binary Report:See Param5 for more information.Sensor Multilevel Report:When sensors above over limit or below under limit.Battery Report:See Param101.Indicator Report:Issued when the indicator light changed
---|---|---
2| 5| Basic Set Command will be sent to the associated device when motion trigger or untrigger. The basic set value is determined by Param11, Param12. See Param13 for more information.
3| 5| Basic Set:When the temperature change value is over or under the threshold set by Param16. Scale is determined by Param64.
4| 5| Basic Set:When the temperature change value is under or over the threshold set by Param17. Scale is determined by Param64.
5| 5| Basic Set:When the current humidity is over or under the threshold set by Param14
6| 5| Basic Set:When the current humidity is under or over the threshold set by Param15
7| 5| Basic Set:When the current light/lux is over or under the threshold set by Param18
8| 5| Basic Set:When the current light/lux is under or over the threshold set by Param19.
9| 5| Basic Set:When the current UV is over or under the threshold set by Param20
10| 5| Basic Set:When the current UV is under or over the threshold set by Param21
11| 5| Sensor Multilevel Report:When sensors above over limit or below under limit.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Beaming Enable/Disable

Used to enable/disable beaming.If set to 1, FLiR commands will be supported. But the device must be re-included into the network to activate it.0 – disable1 – enable
Size: 1 Byte, Default Value: 1

SettingDescription

0 Disable
1 – 0 Enable

Parameter 10: Power Status

This value is Readonly. Used to report the power status (USB or Battery powered)0 – When battery powered, the device will act as RSS.1 – When USB cable insert, the device will act as LSS.The device must be re-included in the network to change the role type.
Size: 1 Byte, Default Value: 0

SettingDescription

0 When battery powered, the device will act as RSS.
1 – 0 When USB cable insert, the device will act as LSS.

Parameter 101: Automatic Report Checklist 1

Checklist 1 for automatic timed report. When the corresponding item is selected, it will be checked when timeout setting by Param111. 1 – Battery16 – UV32 – Temperature64 – Humidity128 – Lux
Size: 1 Byte, Default Value: 241

SettingDescription

1 – 0 Battery
16 – 0 UV
32 – 0 Temperature
64 – 0 Humidity
128 – 0 Lux

Parameter 102: Automatic Report Checklist 2

Checklist 2 for automatic timed report. When the corresponding item is selected, it will be checked when timeout setting by Param112.1 – Battery16 – 32 – Temperature64 – Humidity128 – Lux
Size: 1 Byte, Default Value: 0

SettingDescription

1 – 0 Battery
16 – 0 UV. Other value descriptions, please see above description box of this

parameter.

Parameter 103: Automatic Report Checklist 3

Checklist 3 for automatic timed report. When the corresponding item is selected, it will be checked when timeout setting by Param113. 1 – Battery16 – UV32 – Temperature64 – Humidity128 – Lux
Size: 1 Byte, Default Value: 0

SettingDescription

1 – 0| Battery. Other value descriptions, please see above description box of this parameter.
---|---

Parameter 11: Motion Group Control(Group2)

_Set control of other devices on group2 based on motion trigger.0 – Send BASIC_SET (0xFF) when motion is triggered to associated deviceSend BASIC_SET (0x00) when motion is untriggered to associated device1 – Send BASIC_SET (0x00) when motion is triggeredSend BASIC_SET (0xFF) when motion is untriggered2 – Send BASIC_SET (0xFF) when motion is triggered, Nothing when motion untriggered.3 – Send BASIC_SET (0x00) when motion is triggered, Nothing when motion untriggered.4 – Send BASIC_SET (0x00) when motion is untriggered, Nothing when motion triggered.5 – Send BASIC_SET (0xFF) when motion is untriggered, Nothing when motion triggered.6 – Send BASIC_SET (value is configured by parameter 12) when motion is triggered to associated devices.Send BASICSET (value is configured by parameter 12) when motion is untriggered.
Size: 1 Byte, Default Value: 0

SettingDescription

0| Send BASIC_SET (0xFF) when motion is triggered to associated device Send BASIC_SET (0x00) when motion is untriggered to associated device
---|---
1 – 0| Send BASIC_SET (0x00) when motion is triggered Send BASIC_SET (0xFF) when motion is untriggered
2 – 0| Send BASIC_SET (0xFF) when motion is triggered, Nothing when motion untriggered.
3 – 0| Send BASIC_SET (0x00) when motion is triggered, Nothing when motion untriggered.
4 – 0| Send BASIC_SET (0x00) when motion is untriggered, Nothing when motion triggered.
5 – 0| Send BASIC_SET (0xFF) when motion is untriggered, Nothing when motion triggered.
6 – 0| Send BASIC_SET (value is configured by parameter 12) when motion is triggered to associated devices. Send BASIC_SET (value is configured by parameter 12) when motion is untriggered.

Parameter 111: Automatic Checklist 1 Interval Time

Interval time set in seconds to check the checklist1s items. Multilevel Sensor Report will be sent when timeout.
Size: 2 Byte, Default Value: 3600

SettingDescription

30 – 65535 Interval time set in seconds

Parameter 112: Automatic Checklist 2 Interval Time

Interval time set in seconds to check the checklist2s items. Multilevel Sensor Report will be sent when timeout.
Size: 2 Byte, Default Value: 3600

SettingDescription

30 – 65535 Interval time set in seconds

Parameter 113: Automatic Checklist 3 Interval Time

Interval time set in seconds to check the checklist3s items. Multilevel Sensor Report will be sent when timeout.
Size: 2 Byte, Default Value: 3600

SettingDescription

30 – 65535 Interval time set in seconds

Parameter 12: Motion Group Value Setting

_Set Basic Set value for Group2. The MSB will act as the basic set value when motion trigger. The LSB will act as the basic set value when motion untrigger. E.g. value=0x0A00, then BASIC_SET(0x0A) will be sent when motion trigger, BASICSET(0x00) will be sent when motion untrigger.
Size: 2 Byte, Default Value: 65280

SettingDescription

0 – 65535 Set Basic Set value for Group2.

Parameter 13: Motion Group Control Requirement

_Set threshold of Light/Lux when devices associated in group2 should be triggered by motion. Associated device only receive BASICSET command when light
Size: 2 Byte, Default Value: 30000

SettingDescription

0 – 30000 Set threshold of Light/Lux

Parameter 14: Over Humidity Group Threshold (Group5)

_Set threshold of humidity. If measured humidity >= (this value), send BASIC_SET (0xFF) to associated devices through group5. If measured humidity < (this value) send BASICSET (0x00) to associated devices through group5.
Size: 1 Byte, Default Value: 60

SettingDescription

0 – 100 Set threshold of humidity.

Parameter 15: Under Humidity Group Threshold (Group6)

_Set threshold of humidity. If measure humidity(this value) send BASICSET (0x00) to associated devices through group6.
Size: 1 Byte, Default Value: 40

SettingDescription

0 – 100 Set threshold of humidity.

Parameter 16: Over Heat Group Threshold (Group3)

_Set threshold of temperature. Designed to control Air Conditioners or temperature controllers ON or OFF. If measuredtemperature >= (this value, Scale is determined by Param64) send BASIC_SET (0xFF) to associated devices. If measured temperature<(this value) send BASICSET (0x00) to associated devices. E.g. Value 239 means 23.9 C. Value 750 means 75.0 F.
Size: 2 Byte, Default Value: 239

SettingDescription

-400 – 850 Set threshold of temperature

Parameter 17: Under Heat Group Threshold (Group4)

_Set threshold of temperature. Designed to control Air Conditioners or temperature controllers ON or OFF. If measured temperature(this value) send BASICSET (0x00) to associated devices. E.g. Value 155 means 15.5 C. Value 600 means 60.0 F.
Size: 2 Byte, Default Value: 155

SettingDescription

-400 – 850 Set threshold of temperature

Parameter 18: Over Light Group Threshold (Group7)

_Set threshold of Light/Lux. If measured light/lux >= (this value) send BASIC_SET (0xFF) to associated devices. If measured light/lux < (this value) send BASICSET (0x00) to associated devices.
Size: 2 Byte, Default Value: 2000

SettingDescription

0 – 30000 Set threshold of Light/Lux.

Parameter 19: Under Light Group Threshold (Group8)

_Set threshold of Light/Lux. If measured light/lux(this value) send BASICSET (0x00) to associated devices.
Size: 2 Byte, Default Value: 100

SettingDescription

0 – 30000 Set threshold of Light/Lux.

Parameter 2: Motion Retrigger Time

Presence re-detection time set in second to allow motion sensor to reset timeout of motion sensor. In this time, the motion sensor can not be triggered again. If this value reach zero, the timeout configuration value set by Param3 will be reset. This setting value must always be less than timeout configuration.0 – disable1~3600 – timeout set in seconds
Size: 2 Byte, Default Value: 30

SettingDescription

30 – 3600 timeout set in seconds

Parameter 20: Over UV Group Threshold (Group9)

_Set threshold of UV. If measured UV >= (this value) send BASIC_SET (0xFF) to associated devices. If measured UV < (this value) send BASICSET (0x00) to associated devices.
Size: 1 Byte, Default Value: 8

SettingDescription

0 Set threshold of UV.

Parameter 201: Temperature Offset Value

Can add or minus this setting value to calibrate temperature when checked. Scale is defined by Param64. e.g. Value 15 means 1.5C or 1.5F.
Size: 2 Byte, Default Value: 0

SettingDescription

-200 – 200 Temperature Offset Value

Parameter 202: Humidity Offset Value

Can add or minus this setting value to calibrate humidity when checked. Unit: %.
Size: 1 Byte, Default Value: 0

SettingDescription

-100 – 100 Humidity Offset Value

Parameter 203: Lux Offset Value

Can add or minus this setting value to calibrate Lux when checked.
Size: 2 Byte, Default Value: 0

SettingDescription

-10000 – 10000 Lux Offset Value

Parameter 204: UV Offset Value

Can add or minus this setting value to calibrate UV when checked.
Size: 1 Byte, Default Value: 0

SettingDescription

-10 – 10 Offset Value range -10-10.

Parameter 21: Under UV Group Threshold (Group10)

_Set threshold of UV. If measured UV(this value) send BASICSET (0x00 to associated devices.)
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 11 Set threshold of UV.

Parameter 3: Motion Untrigger Time

Timeout configuration set in second for motion sensor to send no trigger status.
Size: 2 Byte, Default Value: 240

SettingDescription

30 – 3600 timeout set in seconds

Parameter 39: Low Battery Threshold

Configure low battery report threshold, sends low battery report via notification and battery report when battery level drops under setting. Unit %.
Size: 1 Byte, Default Value: 50

SettingDescription

10 – 90 Configure low battery report threshold

Parameter 4: Motion Sensitivity

Set the sensitivity of motion sensor.0 – disable1- minimum sensitivity11 – maximum sensitivity
Size: 1 Byte, Default Value: 11

SettingDescription

0 Disable
1 – 11 sensitivity range

Parameter 40: Threshold Check Enable/Disable

Enable/Disable threshold reporting, check time can be adjusted by Param45.0 – disable all threshold reports1 – enable all threshold reports
Size: 1 Byte, Default Value: 0

SettingDescription

0 disable all threshold reports
1 – 0 enable all threshold reports

Parameter 41: Temperature Threshold

Threshold = (Value * 0.1) Scale is determined by Param64. 0 = disable.
Size: 1 Byte, Default Value: 10

SettingDescription

0 – 255| Threshold = (Value * 0.1) Scale is determined by Param64. 0 = disable.
---|---

Parameter 42: Humidity Threshold

Humidity range = 1% to 50%, 0 = disable.
Size: 1 Byte, Default Value: 5

SettingDescription

0 – 50 Humidity range = 1% to 50%, 0 = disable.

Parameter 43: Lux Threshold

0 = disable
Size: 2 Byte, Default Value: 250

SettingDescription

0 – 10000 Lux Threshold

Parameter 44: UV Threshold

0 = disable
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 11 UV Threshold

Parameter 45: Threshold Check Time

Set threshold check time in seconds if threshold is enable via Param40.1~65535 – When USB powered60~65535 – When Battery powered
Size: 2 Byte, Default Value: 240

SettingDescription

1 – 65535 Set threshold check time in seconds

Parameter 46: Low Temperature Report

Eable/Disable alarm report for low temperature(
Size: 1 Byte, Default Value: 1

SettingDescription

0 Disable
1 – 0 Enable

Parameter 48: Sensor Limit Control

This value is bit mask. Used to enable/disable measurement reports for various sensors that is more than the upper limit value or less than the lower limit value.1 – Temperature upper level2 – Humidity upper level4 – Lux upper level8 – UV upper level16 – Temperature lower level32 – Humidity lower level64 – Lux lower level128 – UV lower level
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disable
1 – 0 Temperature upper level
2 – 0 Humidity upper level

Parameter 49: Temperature Upper Limit

Set upper limit level for temperature set in scale of 0.1. Scale is determined by Param64. If (Current measurement) > (Upper Limit), then report sensor.
Size: 2 Byte, Default Value: 280

SettingDescription

-400 – 1000 Set upper limit level for temperature

Parameter 5: Motion Report Type

Set which command class will be sent when motion sensor is triggered or detriggered.0 – Sends Notification Report1 – Sends Sensor Binary Report2 – Sends Notification and Sensor Binary Report
Size: 1 Byte, Default Value: 2

SettingDescription

0 Sends Notification Report
1 – 0 Sends Sensor Binary Report
2 – 0 Sends Notification and Sensor Binary Report

Parameter 50: Temperature Lower Limit

Set lower limit level for temperature set in scale of 0.1. Scale is determined by Param64. If (Current Measurement) < (Lower limit), then report sensor.
Size: 2 Byte, Default Value: 0

SettingDescription

-400 – 1000 Set lower limit level for temperature

Parameter 51: Temperature Recover Limit

Temperature recover limit set in scale of 0.1. Scale is determined by Param64. If (Current measurement) = (lower limit + recover limit), then temperature report.
Size: 1 Byte, Default Value: 20

SettingDescription

1 – 255 Temperature recover limit set in scale of 0.1.

Parameter 52: Humidity Upper Limit

Set humidity upper limit level.
Size: 1 Byte, Default Value: 60

SettingDescription

0 – 100 Set humidity upper limit level.

Parameter 53: Humidity Lower Limit

Set humidity lower limit level
Size: 1 Byte, Default Value: 40

SettingDescription

0 – 100 Set humidity lower limit level

Parameter 54: Humidity Recover Limit

Set humidity recover limit level. Refer to Param 51.
Size: 1 Byte, Default Value: 5

SettingDescription

1 – 50 Set humidity recover limit level

Parameter 55: Lux Upper Limit

Set lux upper limit level.
Size: 2 Byte, Default Value: 1000

SettingDescription

0 – 30000 Set lux upper limit level.

Parameter 56: Lux Lower Limit

Set lux lower limit level.
Size: 2 Byte, Default Value: 100

SettingDescription

0 – 30000 Set lux lower limit level.

Parameter 58: UV Upper Limit

Set UV upper limit level.
Size: 1 Byte, Default Value: 8

SettingDescription

1 – 11 Set UV upper limit level.

Parameter 59: UV Lower Limit

Set UV lower limit level.
Size: 1 Byte, Default Value: 4

SettingDescription

1 – 11 Set UV lower limit level.

Parameter 6: Vibration Sensor Enable/Disable

Used to enable/disable vibration sensor.0 – disable vibration1~254 – timeout set in minutes to reset vibration status255 – timeout set in minutes to reset vibration status
Size: 1 Byte, Default Value: 255

SettingDescription

0 disable vibration
1 – 254 timeout set in minutes to reset vibration status
255 timeout set in minutes to reset vibration status

Parameter 60: UV Recover Limit

Set UV recover limit level. Refer to Param 51.
Size: 1 Byte, Default Value: 1

SettingDescription

1 – 5 Set UV recover limit level.

Parameter 61: Out-of-limit State

This is read only and bit mask. Out of the limit state of sensors.Bit Mask:0 – within limit1 – out of limitValue:1 – Temperature upper level2 – Humidity upper level4 – Lux upper level8 – UV upper level16 – Temperature lower level32 – Humidity lower level64 – Lux lower level128 – UV lower level
Size: 1 Byte, Default Value: 0

SettingDescription

0 within limit
1 – 0 Temperature upper level
2 – 0 Humidity upper level
4 – 0 Lux upper level

Parameter 64: Temperature Scale

Set the scale for temperature when reports.0 – Celsius1 – Fahrenheit
Size: 1 Byte, Default Value: 0

SettingDescription

0 Celsius
1 – 0 Fahrenheit

Parameter 67: Lux Recover Limit

Set lux recover limit level. Refer to Param 51.
Size: 1 Byte, Default Value: 100

SettingDescription

1 – 255 Set lux recover limit level.

Parameter 7: Vibration Intensity Reports

Used to enable/disable vibration intensity reports. If set to 1, vibration intensity will be sent to gateway when triggered. If set to 0, do not report.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disable
1 – 0 Enable

Parameter 81: LED Activity

Allow user to enable/disable LED activity of specific reports sent by sensor. Button press indicator is not affected by this.0 – disable1 – enable
Size: 1 Byte, Default Value: 1

SettingDescription

0 disable
1 – 0 enable

Parameter 82: Motion Sensor Report Indicator

If LED is enabled by Param81, allow user to change the report color of motion sensor.0 – Disabled1 – Red2 – Blue3 – Green4 – Pink5 – Cyan6 – Purple7 – Orange8 – Yellow9 – White
Size: 1 Byte, Default Value: 3

SettingDescription

0 Disable
1 – 0 Red
2 – 0 Blue
3 – 0 Green
4 – 0 Pink
5 – 0 Cyan
6 – 0 Purple
7 – 0 Orange
8 – 0 Yellow
9 – 0 White

Parameter 83: Temperature Sensor Report Indicator

If LED is enabled by Param81, allow user to change the report color of temperature sensor.0 – Disabled1 – Red2 – Blue3 – Green4 – Pink5 – Cyan6 – Purple7 – Orange8 – Yellow9 – White
Size: 1 Byte, Default Value: 0

SettingDescription

0| Disable. Other value descriptions, please see above description box of this parameter.
---|---

Parameter 84: Humidity Sensor Report Indicator

If LED is enabled by Param81, allow user to change the report color of humidity sensor.0 – Disabled1 – Red2 – Blue3 – Green4 – Pink5 – Cyan6 – Purple7 – Orange8 – Yellow9 – White
Size: 1 Byte, Default Value: 0

SettingDescription

0| Disable. Other value descriptions, please see above description box of this parameter.
---|---

Parameter 85: Lux Sensor Report Indicator

If LED is enabled by Param81, allow user to change the report color of Lux sensor.0 – Disabled1 – Red2 – Blue3 – Green4 – Pink5 – Cyan6 – Purple7 – Orange8 – Yellow9 – White
Size: 1 Byte, Default Value: 0

SettingDescription

0| Disable. Other value descriptions, please see above description box of this parameter.
---|---

Parameter 86: UV Sensor Report Indicator

If LED is enabled by Param81, allow user to change the report color of UV sensor.0 – Disabled1 – Red2 – Blue3 – Green4 – Pink5 – Cyan6 – Purple7 – Orange8 – Yellow9 – White
Size: 1 Byte, Default Value: 0

SettingDescription

0| Disable. Other value descriptions, please see above description box of this parameter.
---|---

Parameter 87: Vibration Sensor Report Indicator

If LED is enabled by Param81, allow user to change the report color of vibration sensor.0 – Disabled1 – Red2 – Blue3 – Green4 – Pink5 – Cyan6 – Purple7 – Orange8 – Yellow9 – White
Size: 1 Byte, Default Value: 2

SettingDescription

0| Disable. Other value descriptions, please see above description box of this parameter.
---|---

Parameter 88: Battery Report Indicator

If LED is enabled by Param81, allow user to change the report color of battery.0 – Disabled1 – Red2 – Blue3 – Green4 – Pink5 – Cyan6 – Purple7 – Orange8 – Yellow9 – White
Size: 1 Byte, Default Value: 0

SettingDescription

0| Disable. Other value descriptions, please see above description box of this parameter.
---|---

Parameter 89: Wakeup Report Indicator

If LED is enabled by Param81, allow user to change the report color of wakeup.0 – Disabled1 – Red2 – Blue3 – Green4 – Pink5 – Cyan6 – Purple7 – Orange8 – Yellow9 – White
Size: 1 Byte, Default Value: 8

SettingDescription

0| Disable. Other value descriptions, please see above description box of this parameter.
---|---

Parameter 9: Wakeup CC Timeout

Timeout set in seconds after Wakeup CC is send out before go to sleep. If wakeup no more information received, return to sleep mode immediately.
Size: 1 Byte, Default Value: 15

SettingDescription

0 – 255 Timeout set in seconds

Parameter 90: Communication Indicator

If LED is enabled by Param81, allow user to change indicator color when receiving communication from gateway or other devices.0 – Disabled1 – Red2 – Blue3 – Green4 – Pink5 – Cyan6 – Purple7 – Orange8 – Yellow9 – White
Size: 1 Byte, Default Value: 0

SettingDescription

0| Disable. Other value descriptions, please see above description box of this parameter.
---|---

Technical Data

Hardware Platform ZGM130
Device Type Notification Sensor
Network Operation Always On Slave
Firmware Version HW: 1 FW: 1.01
Z-Wave Version 7.12.2
Certification ID ZC12-21080291
Z-Wave Product Id 0x0371.0x0102.0x0018
Color White
Firmware Updatable Updatable by Consumer by RF
Security V2 S2_UNAUTHENTICATED ,S2_AUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Application Status
  • Association Grp Info V3
  • Association V2
  • Battery
  • Configuration V4
  • Device Reset Locally
  • Firmware Update Md V5
  • Indicator V3
  • Manufacturer Specific V2
  • Multi Channel Association V3
  • Notification V8
  • Powerlevel
  • Security
  • Security 2
  • Sensor Binary V2
  • Sensor Multilevel V11
  • Supervision
  • Transport Service V2
  • Version V3
  • Wake Up V2
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Aeotec User Manuals

Related Manuals