Ring Retrofit Alarm Kit 4AW1SZ-0EN0 Manual

June 8, 2024
Ring

Ring

Ring Retrofit Alarm Kit

SKU: 4AW1SZ-0EN0

Quickstart

This is a
secure
Alarm Sensor
for
.

Please make sure the internal battery is fully charged.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

Ring Retrofit Alarm Kit is a Wired-to-wireless bridge that connects to your existing hardwired contact sensors and transmits open/close events wirelessly to Ring Alarm. Connect up to 8 wired contact sensor zones to the device. Set up and configure the device using the Ring app. After installation and setup, monitor and receive notifications when doors and windows with wired sensors connected to Retrofit Alarm Kit open and close. The Ring Alarm Base Station is required to enable Retrofit Alarm Kit features and functions. Once setup, wired sensors connected to Retrofit Alarm Kit can be monitored just like other Ring Alarm sensors in the system.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 1| Group one is a lifeline group who will receive unsolicited messages relating to case tamper notifications, battery level notifications, Wake-Up notifications, and Device Reset Notifications.
---|---|---
2| 1| Group two is intended to be used with multi-channel association for a controller to subscribe to contact switch open/close notifications sent encapsulated from each of the eight endpoints one for each contact switch. Each endpoint must be enabled by putting the controllers node ID into the devices Association Group 2 with either an Association Set encapsulated with Multi-Channel Encapsulation OR a Multi-Channel Association Set encapsulated with Multi-Channel Encapsulation.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Heartbeats

Number of seconds between periodic battery reports. (Heartbeats)
Size: 2 Byte, Default Value: 4200

SettingDescription

255 – 4200 Number of seconds between periodic battery reports. (Heartbeats)

Parameter 2: One-Time Wakeup Notification

One-Time Wakeup Notification. (In addition to normal Wakeup Notification)
Size: 2 Byte, Default Value: 0

SettingDescription

1 – 3600| One-Time Wakeup Notification. (In addition to normal Wakeup Notification)
---|---

Parameter 3: Application Level Retries

Number of Application Level Retries after a failed transmission defined as either not ACKed or Supervision Report not returned when encapsulated.
Size: 1 Byte, Default Value: 5

SettingDescription

1 – 15| Number of Application Level Retries after a failed transmission defined as either not ACKed or Supervision Report not returned when encapsulated.
---|---

Parameter 4: seconds to sleep

The minimum number of seconds to sleep between application level retries.
Size: 1 Byte, Default Value: 6

SettingDescription

1 – 60| The minimum number of seconds to sleep between application level retries.
---|---

Parameter 5: Application Retry Multiplier

_Application Retry Multiplier. The number of seconds between a current application retry is the count of retries multiplied by this number in seconds

  • a small random delay._
    Size: 1 Byte, Default Value: 1

SettingDescription

1 – 5| Application Retry Multiplier. The number of seconds between a current application retry is the count of retries multiplied by this number in seconds

  • a small random delay.
    ---|---

Parameter 6: wait for a Supervisory Report

The number of milliseconds to wait for a Supervisory Report in response to a Supervisory encapsulated Get.
Size: 2 Byte, Default Value: 1500

SettingDescription

500 – 5000| The number of milliseconds to wait for a Supervisory Report in response to a Supervisory encapsulated Get.
---|---

Technical Data

Hardware Platform ZM5101
Device Type Notification Sensor
Network Operation Reporting Sleeping Slave
Firmware Version HW: 1 FW: 1.00:01.00
Z-Wave Version 6.81.03
Certification ID ZC10-19116787
Z-Wave Product Id 0x0346.0x0B01.0x0101
Color White
Security V2 S2_UNAUTHENTICATED ,S2_AUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Basic V2
  • Battery
  • Configuration
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Multi Channel Association V3
  • Multi Channel V4
  • Notification V8
  • Powerlevel
  • Security 2
  • Supervision
  • Transport Service V2
  • Version V3
  • Wake Up V2
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals