myTEM SmartHome Radio Socket CH MTSOC-100CH-WL Manual

June 8, 2024
myTEM SmartHome

myTEM SmartHome

Radio Socket CH

SKU: MTSOC-100CH-WL

Quickstart

This is a
secure
On/Off Power Switch
for
CEPT (Europe)
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
Inclusion (Add)To include (Add) the device to a Z-Wave network, press the button four times in quick succession. When the device is in Add mode, the LED flashes green. When finished, the new status is:Add:The LED lights up briefly in greenRemove:The LED lights up briefly in red

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The myTEM Radio Socket is a universal, Z-Wave compatible switch/adapter for loads up to 2300 watts (type J, CH). The power and energy consumption of the connected device is measured. In addition, a temperature and humidity sensor is integrated. These values are reported to the central controller and can be used to control other functions.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Remark: It is recommended to use the primary controller of the previous network unless it is no longer available or damaged.To start the Remove process press the button four times in quick succession. The LED flashes red and then the new status is:Add: The LED lights up briefly in greenRemove: The LED lights up briefly in red

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Inclusion (Add)To include (Add) the device to a Z-Wave network, press the button four times in quick succession. When the device is in Add mode, the LED flashes green. When finished, the new status is:Add:The LED lights up briefly in greenRemove:The LED lights up briefly in red

Exclusion

Exclusion (Remove)To exclude (Remove) the device from a Z-Wave network, press the button four times in quick succession. When the device is in Add mode, the LED flashes green. When finished, the new status is:Add:The LED lights up briefly in greenRemove:The LED lights up briefly in red

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| Z-Wave Plus Lifeline a) Notification Report: System, Heartbeat b) Notification Report: Power Management Power has been applied c) Meter Report: Single electric meter, Kilowatt d) Meter Report: Single electric meter,Kilowatt hours e) Multilevel Sensor Report: Air temperature, Celsius f) Multilevel Sensor Report: Humidity, Percentage value g) Binary Switch ReportFurther information and how to trigger the events are under Description in the manual
---|---|---

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Heartbeat Rate

If the Notification System Heartbeat is on, a Notification Report System Heartbeat is sent periodically every 60 minutes (default value).
Size: 2 Byte, Default Value: 60

SettingDescription

1 – 1440 Heartbeat rate [min]

Parameter 10: Send Interval Humidity

If the humidity value does not change, the Multilevel Sensor Report with the actual humidity is sent after the Send Interval Humidity.
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 120 Send interval humidity [min]

Parameter 11: Minimum Delta Humidity Send

Whenever the measured humidity has changed by the Minimum Delta Humidity Send value since the last value sent, the actual humidity is sent by a Multilevel Sensor Report.
Size: 2 Byte, Default Value: 10

SettingDescription

10 – 1000 Minimum delta humidity [0.1 %]

Parameter 2: Main Voltage

The Main Voltage is used – together with the Phase Shift parameter and the messured current – to calculate the actual power of the output and the cumulated energy.
Size: 2 Byte, Default Value: 230

SettingDescription

80 – 280 Main voltage [V]

Parameter 3: Phase Shift – Cosines (Phi)

The Phase Shift is used – together with the Main Voltage parameter and the messured current – to calculate the actual power of the output and the cumulated energy.
Size: 2 Byte, Default Value: 100

SettingDescription

0 – 100 Phase shift [0.01%]

Parameter 4: Send Interval Power

If the power value of the output does not change, the Meter Report for the actual power is sent after the Send Interval Power.
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 120 Send interval power [min]

Parameter 5: Minimum Delta Power Send

Whenever the calculated power has changed by the Minimum Delta Power Send value since the last value sent, the actual power is sent by a Meter Report.
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Minimum delta power [%]

Parameter 7: Minimum delta energy send

Whenever the cumulated energy has changed by the Minimum Delta Energy send value since the last value sent, the cumulated energy is sent by a Meter Report.
Size: 2 Byte, Default Value: 2000

SettingDescription

1 – 50000 Minimum delta energy [0.001 kWh]

Parameter 8: Send Interval Temperature

If the temperature value does not change, the Multilevel Sensor Report with the actual temperature is sent after the Send Interval Temperature
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 120 Send interval energy [min]
1 – 120 Send interval temperature [min]

Parameter 9: Minimum Delta Temperature Send

Whenever the measured temperature has changed by the Minimum Delta Temperature Send value since the last value sent, the actual temperature is sent by Multilevel Sensor Report.
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Minimum delta temperature [0.1 K]

Technical Data

Hardware Platform ZM5101
Device Type On/Off Power Switch
Network Operation Always On Slave
Firmware Version HW: 1 FW: 1.00
Z-Wave Version 6.71.03
Certification ID ZC10-19056523
Z-Wave Product Id 0x034E.0x0001.0x0004
Supported Meter Type Electric Energy
Electric Load Type ELV (Electronic)IncandescentInductive (e.g. Motor)
Sensors Air TemperatureHumidity
Supported Notification Types Power ManagementSystem
Firmware Updatable Updatable by Consumer by RF
Security V2 S2_UNAUTHENTICATED ,S2_AUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Application Status
  • Association Grp Info V3
  • Association V2
  • Basic V2
  • Configuration V4
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Meter V4
  • Notification V8
  • Powerlevel
  • Security 2
  • Sensor Multilevel V11
  • Supervision
  • Switch Binary
  • Transport Service V2
  • Version V3
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

myTEM SmartHome User Manuals

Related Manuals