myTEM SmartHome Radio Switch Dual MTSWI-100-WL Manual

June 8, 2024
myTEM SmartHome

myTEM SmartHome

Radio Switch Dual

SKU: MTSWI-100-WL

Quickstart

This is a
secure
On/Off Power Switch
for
CEPT (Europe)
.

To run this device please connect it to your mains power supply.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The myTEM Radio Switch Dual is a universal, Z-Wave compatible wall or ceiling switch (ON/OFF) and is used to control two electrical devices (e.g. roller shutters, window blinds, lamps, fans, etc.). The power and energy con-sumption of the connected devices are measured.Two additional digital inputs and the programmable be-havior to the wireless commands allow flexible use in the house. At the same time, the device also serves as a Z-Wave repeater to improve range and stability of the Z-Wave network.The device is intended for installation in a flush-mounted box, e.g. behind light switches or sockets.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| Z-Wave Plus LifelineSystem / Heartbeat; sent periodically (see Configuration Parameter Heartbeat)Power Mangement / Power has been applied; sent after Powerup and ResetMeter / Kilowatt; sent periodically and when values changes (see configuration parameter Send Interval Power and Minimum Delta Power Send)Meter / Kilowatt hours; sent periodically and when values changes (see configuration parameter Send Interval Energy and Minimum Delta Energy Send)
---|---|---
2| 5| Binary Switch Report; sent when the output 1 changes state
3| 5| Binary Switch Report; sent when the output 2 changes state
4| 5| Binary Sensor Report; sent when the input 1 changes state
5| 5| Binary Sensor Report; sent when the input 2 changes state

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Heartbeat rate

If the notification System Heartbeat is on, a notification report System Heartbeat is sent periodically every 60 minutes (default value).
Size: 2 Byte, Default Value: 60

SettingDescription

1 – 1440 Heartbeat rate [min]

Parameter 10: Send Interval Power Output 2

Period with which the power of output 2 is sent by a Meter Report.
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 120 Interval power [min]

Parameter 11: Minimum Delta Power Send Output 2

When the power of output 2 changes this anount the energy value is sent by a Meter Report.
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Minimum delta power [%]

Parameter 2: Main Voltage

Together with the mesured current and the Phase shift configuration parameter the Main Voltage confirguation parameter is used to calculate the power of the oututs.
Size: 2 Byte, Default Value: 230

SettingDescription

20 – 280 Main voltage [V]

Parameter 3: Phase shift – cosines (phi)

Together with the mesured current and the Main Voltage configuration parameter the Phase shift configruation parameter is used to calculate the power of the oututs.
Size: 2 Byte, Default Value: 100

SettingDescription

0 – 100 Phase shift [0.01]

Parameter 4: Send Interval Energy Output 1

Period with which the energy of output 1 is sent by a Meter Report.
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 120 Interval energy [min]

Parameter 5: Minimum Delta Energy Send Output 1

When the energy of output 1 changes this anount the energy value is sent by a Meter Report.
Size: 2 Byte, Default Value: 2000

SettingDescription

1 – 50000 Minimum delta energy [0.001 kWh]

Parameter 6: Send Interval Power Output 1

Period with which the power of output 1 is sent by a Meter Report.
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 120 Interval power [min]

Parameter 7: Minimum Delta Power Send Output 1

When the power of output 1 changes this anount the energy value is sent by a Meter Report.
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Minimum dleta power [%]

Parameter 8: Send Interval Energy Output 2

Period with which the energy of output 2 is sent by a Meter Report.
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 120 Interval energy [min]

Parameter 9: Minimum Delta Energy Output 2

When the energy of output 2 changes this anount the energy value is sent by a Meter Report.
Size: 2 Byte, Default Value: 2000

SettingDescription

1 – 50000 Minimum delta energy [0.001 kWh]

Technical Data

Hardware Platform ZM5101
Device Type On/Off Power Switch
Network Operation Always On Slave
Firmware Version HW: 1 FW: 1.00
Z-Wave Version 6.71.03
Certification ID ZC10-19086712
Z-Wave Product Id 0x034E.0x0001.0x0007
Loads Controlled 2
Firmware Updatable Updatable by Consumer by RF
Supported Notification Types Power ManagementSystem
Supported Meter Type Electric Energy
Electric Load Type ELV (Electronic)IncandescentInductive (e.g. Motor)
Security V2 S2_UNAUTHENTICATED ,S2_AUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Application Status
  • Association Grp Info V3
  • Association V2
  • Basic
  • Configuration V4
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Meter V5
  • Multi Channel Association V3
  • Multi Channel V4
  • Notification V8
  • Powerlevel
  • Security 2
  • Sensor Binary
  • Supervision
  • Switch Binary V2
  • Transport Service V2
  • Version V3
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals