myTEM SmartHome Radio I/O Modul MTIOM-100-WL Manual

June 8, 2024
myTEM SmartHome

Table of Contents

myTEM SmartHome

Radio I/O Modul

SKU: MTIOM-100-WL

Quickstart

This is a
secure
Binary Switch
for
.

To run this device please connect it to your mains power supply.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The Radio IO Modul MTIOM-100-WL is a universal, Z-Wave compatible module from myTEM for extending your smart home system with additional inputs and outputs. It is a Z-Wave device of the type Binary Switch for the use in Europe / Switzerland.Main use is for:- Switching of lights- Switching of single-phase fan motors- Switching of electric blinds or similar shading devices- Operation by means of buttons, sensors via the central serverFunctions:- Supply voltage 24 VDC10%- Communication via Z-Wave mesh network- 6 digital inputs 24 VDC (DI1DI6) for e.g. external switches- 24 VDC power supply, 100 mA, for the digital inputs DI1DI6 (VDIout)- 4 analog inputs (AI1AI4), which can be used for 0-10 VDC or NTC-, PTC- or PT1000 sensors. Analog inputs can also be used as digital inputs 24 VDC.- 6 digital outputs with potential-free, relay 8 A, 250 VAC- Manual positions of the outputs via DIP switch for easy commissioning- The device is installed in a control cabinet, mounted on a 35 mm DIN rail

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| (Lifeline group) Root: Notification Report System::Heartbeat triggered periodically, Notification Report Power Management::Power has bin applied triggered upon start-up, Device Reset Locally triggered upon set to factory default.EP7 – EP12: Notification Report System::Digital input open triggered when digital input 1 – 6 resp. change from 24V applied to open, Notification Report System::Digital input high state triggered when digital input 1 – 6 resp. change from open to 24V applied.EP13 – EP17: Multilevel Sensor Report triggered periodically or on value change of analog input 1 – 4 resp.EP13 – EP17: Multilevel Sensor Supported Report triggered when type of analog input 1 – 4 resp. is changed by configuration parameter.
---|---|---

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Heartbeat rate [min]

see manual
Size: 2 Byte, Default Value: 60

SettingDescription

1 – 1440 Value tells at what interval [min] Heartbeat will be sent

Parameter 10: DI 5 send enable

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Notifications for DI 5 are disabled
1 Binary Sensor Report for DI 5 is enabled
2 Central Scene Report for DI 5 is enabled

Parameter 11: DI 5 send interval [min]

see manual
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1200| Value tells at what interval [0.1min] notification for DI 5 will we sent
---|---

Parameter 12: DI 6 send enable

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Notifications for DI 6 are disabled
1 Binary Sensor Report for DI 6 is enabled
2 Central Scene Report for DI 6 is enabled

Parameter 13: DI 6 send interval [min]

see manual
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1200| Value tells at what interval [0.1min] notification for DI 6 will we sent
---|---

Parameter 14: AI 1 send enable

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Sending AI 1 values disabled
1 Sending AI 1 values enabled

Parameter 15: AI 1 sensor select

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Configure AI 1 for NTC 5k Ohm thermistor
1 Configure AI 1 for NTC 10k Ohm thermistor
2 Configure AI 1 for PTC 1k Ohm thermistor
3 Configure AI 1 for PT1000 thermistor
4 Configure AI 1 for 0 – 10V sensor
5 Configure AI 1 for digital input

Parameter 16: AI 1 send interval [min]

see manual
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1200| Value tells at what interval [0.1min] sensor values for AI 1 will be sent
---|---

Parameter 17: AI 1 send delta temp [K]

see manual
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Value tells at whattemperature difference [0.1K]for AI 1 will be sent

Parameter 18: AI 1 send delta volt [V]

see manual
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Value tells at whatvoltage difference [0.1V]for AI 1 will be sent

Parameter 19: AI 2 send enable

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Sending AI 2 values disabled
1 Sending AI 2 values enabled

Parameter 2: DI 1 send enable

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Notifications for DI 1 are disabled
1 Binary Sensor Report for DI 1 is enabled
2 Central Scene Report for DI 1 is enabled

Parameter 20: AI 2 sensor select

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Configure AI 2 for NTC 5k Ohm thermistor
1 Configure AI 2 for NTC 10k Ohm thermistor
2 Configure AI 2 for PTC 1k Ohm thermistor
3 Configure AI 2 for PT1000 thermistor
4 Configure AI 2 for 0 – 10V sensor
5 Configure AI 2 for digital input

Parameter 21: AI 2 send interval[min]

see manual
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1200| Value tells at what interval [0.1min] sensor values for AI 2 will be sent
---|---

Parameter 22: AI 2 send delta temp [K]

see manual
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Value tells at whattemperature difference [0.1K]for AI 2 will be sent

Parameter 23: AI 2 send delta volt [V]

see manual
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Value tells at whatvoltage difference [0.1V]for AI 2 will be sent

Parameter 24: AI 3 send enable

seemanual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Sending AI 3 values disabled
1 Sending AI 3 values enabled

Parameter 25: AI 3 sensor select

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Configure AI 3 for NTC 5k Ohm thermistor
1 Configure AI 3 for NTC 10k Ohm thermistor
2 Configure AI 3 for PTC 1k Ohm thermistor
3 Configure AI 3 for PT1000 thermistor
4 Configure AI 3 for 0 – 10V sensor
5 Configure AI 3 for digital input

Parameter 26: AI 3 send interval[min]

see manual
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1200| Value tells at what interval [0.1min] sensor values for AI 3 will be sent
---|---

Parameter 27: AI 3 send delta temp [K]

see manual
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Value tells at whattemperature difference [0.1K]for AI 3 will be sent

Parameter 28: AI 3 send delta volt [V]

see manual
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Value tells at whatvoltage difference [0.1V]for AI 3 will be sent

Parameter 29: AI 4 send enable

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Sending AI 4 values disabled
1 Sending AI 4 values enabled

Parameter 3: DI 1 send interval [min]

see manual
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1200| Value tells at what interval [0.1min] notification for DI 1 will we sent
---|---

Parameter 30: AI 4 sensor select

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Configure AI 4 for NTC 5k Ohm thermistor
1 Configure AI 4 for NTC 10k Ohm thermistor
2 Configure AI 4 for PTC 1k Ohm thermistor
3 Configure AI 4 for PT1000 thermistor
4 Configure AI 4 for 0 – 10V sensor
5 Configure AI 4 for digital input

Parameter 31: AI 4 send interval [min]

see manual
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1200| Value tells at what interval [0.1min] sensor values for AI 4 will be sent
---|---

Parameter 32: AI 4 send delta temp [K]

see manual
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Value tells at whattemperature difference [0.1K]for AI 4 will be sent

Parameter 33: AI 4 send delta volt [V]

see manual
Size: 2 Byte, Default Value: 5

SettingDescription

1 – 100 Value tells at whatvoltage difference [0.1V]for AI 4 will be sent

Parameter 4: DI 2 send enable

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Notifications for DI 2 are disabled
1 Binary Sensor Report for DI 2 is enabled
2 Central Scene Report for DI 2 is enabled

Parameter 5: DI 2 send interval [min]

see manual
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1200| Value tells at what interval [0.1min] notification for DI 2 will we sent
---|---

Parameter 6: DI 3 send enable

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Notifications for DI 3 are disabled
1 Binary Sensor Report for DI 3 is enabled
2 Central Scene Report for DI 3 is enabled

Parameter 7: DI 3 send interval[min]

see manual
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1200| Value tells at what interval [0.1min] notification for DI 3 will we sent
---|---

Parameter 8: DI 4 send enable

see manual
Size: 2 Byte, Default Value: 0

SettingDescription

0 Notifications for DI 4 are disabled
1 Binary Sensor Report for DI 4 is enabled
2 Central Scene Report for DI 4 is enabled

Parameter 9: DI 4 send interval [min]

see manual
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1200| Value tells at what interval [0.1min] notification for DI 4 will we sent
---|---

Technical Data

Hardware Platform ZGM130
Device Type Binary Switch
Network Operation Always On Slave
Firmware Version HW: 0 FW: 1.00:00.07
Z-Wave Version 7.13.2
Certification ID ZC12-21020178
Z-Wave Product Id 0x034E.0x0001.0x000A
Loads Controlled 6
Z-Wave Scene Type Central Scene
Electric Load Type
Security V2 S2_UNAUTHENTICATED ,S2_AUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info V3
  • Association V2
  • Basic V2
  • Configuration V4
  • Device Reset Locally
  • Firmware Update Md V5
  • Indicator V3
  • Manufacturer Specific V2
  • Multi Channel Association V3
  • Multi Channel V4
  • Notification V8
  • Powerlevel
  • Security 2
  • Sensor Multilevel V11
  • Supervision
  • Switch Binary V2
  • Transport Service V2
  • Version V3
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals