Simon S100 Rocker iO for Dimmer 10002020-13X Manual

June 8, 2024
Simon

Simon

S100 Rocker iO for Dimmer

SKU: 10002020-13X

Quickstart

This is a ****

Light Dimmer
for
CEPT (Europe)
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
When the pushbutton is released after a press of (2sec<T<10sec) the device will send a NIF to include from Z-Wave network or perform an association with other Z-Wave device.Central LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.This process does not perform a default reset of configurations.Main LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

Simon iO Dimmer is ready to operate with Z-Wave controllers and configured to be managed by Simon100 IO APP using the HUB plug IO for getting a better user experience. Sending the Blind Up/Down or setting a specific position.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

When the pushbutton is released after a press of (30sec<T) the device will perform a factory default values operation, excluding it from network and reset the configuration parameters.Main LED will perform 1 Blink with 5 sec.Please use this procedure only when the network primary controller is missing or otherwise inoperable.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

When the pushbutton is released after a press of (2sec<T<10sec) the device will send a NIF to include from Z-Wave network or perform an association with other Z-Wave device.Central LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.This process does not perform a default reset of configurations.Main LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.

Exclusion

When the pushbutton is released after a press of (2sec<T<10sec) the device will send a NIF to exclude from Z-Wave network or perform an association with other Z-Wave device.Main LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.This process does not perform a default reset of configurations.Main LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1 3 Z-Wave Plus Lifeline
2 20 ctrl.CC Basic, Basic Report, Value 0x00 – 0x63 Report Dimming vaule

after 2 seconds of last dimming change.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Association LED

Activates the Central LED. Configuration Used by Masters iO in order to identify the devices associated to their Group2 during manual association process.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Turns the LED OFF
1 – 255 Turns the LED ON

Parameter 10: Delay ON

Time that Dimmer delays the activation of the load after it receives an ON request.This value must be set in hexadecimal format, and can accept these values:0 – > ON Delay is 0.0×01…0x7F –> Delay ON is from 1 to 127 seconds. (1 second resolution)0x80…0xfE–> Delay ON is from 1 to 127 seconds. (1 minute resolution)
Size: 1 Byte, Default Value: 0

SettingDescription

0 ON Delay is 0 seconds
1 – 127 ON Delay is set in seconds from 1 to 127 seconds
128 – 254 ON Delay is set in minutes from 1 to 127 minutes

Parameter 11: Activation Time

Time that Dimmer activates of the load after it turns the load ON.This value must be set in hexadecimal format, and can accept these values:0 – > Activation Time is 0.0×01…0x7F –> Activation Time is from 1 to 127 seconds. (1 second resolution)0x80…0xfE–> Activation Time is from 1 to 127 seconds. (1 minute resolution)
Size: 1 Byte, Default Value: 0

SettingDescription

0 Activation Time is 0 seconds
1 – 127 Activation Time is set in seconds from 1 to 127 seconds
128 – 154 Activation Time is set in minutes from 1 to 127 minutes

Parameter 12: Behavior of LED in Repose

Sets the Left and Right Leds to 20% in order to find the device and the touch areas at night.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Left and Right LEDs OFF
1 – 255 Left and Right LEDs ON at 20percent

Parameter 13: Lock Input

Locks the local control of the sunblind. This configuration does not modifies the control via Z-Wave.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Local action enabled
1 – 255 Local action locked

Parameter 15: Reset Default

Write only parameter used to restore configurations or perform a completely restore default.
Size: 2 Byte, Default Value: 0

SettingDescription

17170 Configuration values are restored
39015 Factory reset.

Parameter 16: Delay OFF

Time that Dimmer delays the deactivation of the load after it receives an OFF request.This value must be set in hexadecimal format, and can accept these values:0 – > Delay OFF is 0.0×01…0x7F –> Delay OFF is from 1 to 127 seconds. (1 second resolution)0x80…0xfE–> Delay OFF is from 1 to 127 seconds. (1 minute resolution)
Size: 1 Byte, Default Value: 0

SettingDescription

0 OFF Delay is 0 seconds
1 – 127 OFF Delay
128 – 254 OFF Delay is set in minutes from 1 to 127 minutes

Parameter 19: Press Action

Defines the action to be performed when key is pressed.
Size: 1 Byte, Default Value: 5

SettingDescription

0 When short press, the device toggles the load. The Slider does not work.
1 When short press, the device turns ON the load. The Slider does not work.
2 When short press, the device turns OFF the load. The Slider does not works.
4 When short press, the device turns ON the load. When hold press from

2seconds to 10seconds device turns OFF the load. The Slider does not works with this configuration, the device will not send the Node Info neither Show the LEDs feedback with this press action. The Slider does not work.
5| When short press, the device toggles the load. The Slider dims the load when it is ON.

Parameter 20: Identify

Write only value that performs a fast blink on Central LED during 5 seconds in order to identify the device when it is installed in a multiple frame.
Size: 1 Byte, Default Value: 0

SettingDescription

1 – 255 Central LED performs a fast blink

Parameter 21: Load State

Read only 2 Byte configuration parameter used to read the dimmer state.Byte 0 is used to know the load state ON or OFF.0 Dimmer is OFF.1 Dimmer is ON.Byte 1 is used to Know the last active dimming percentage.
Size: 2 Byte, Default Value: 0

SettingDescription

1 – 99 Load is OFF and las timming value is from 1% to 99%
256 – 355 Load is ON Dimmed at 1% to 99%

Parameter 23: Calibration Required

Read only configuration used to know is device needs to be calibrated in order to work properly.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Device is calibrated
255 Calibration must be performed

Parameter 27: Lock Hold Press

Locks the major part of Hold press effects in order to avoid undesired callibrations, Z-Wave changes or restores Default.0xFF Hold Press from 2sec to 20 sec does not performs a Node infoHold Press of 10 to 15 does not performs a automatic callibrationHold press of 15 to 30 does not changes the sunblind or awing reportsHold press of 30sec restores configuration except Lock Hold Press, and sends a Node info in order to add or remove from Z-Wave Network
Size: 1 Byte, Default Value: 0

SettingDescription

0 Hold Press is available
1 – 255 Hold Press from 2sec to 20 sec does not performs a Node info,Hold

Press of 10 to 15 does not performs a automatic callibration,Hold press of 15 to 30 does not changes the sunblind or awing changes, Hold press of 30sec restores configuration except Lock Hold Press, and sends a Node info in order to add or remove from Z-Wave Network

Parameter 4: Set Time

Sets the u0022Set Timeu0022 that will take the Dimmer to go from 0% to 100%This value must be set in hexadecimal format, and can accept these values:0 – > Set Time is 0.0×01…0x7F –> Set Time is from 1 to 127 seconds. (1 second resolution)0x80…0xfE–> Set Time is from 1 to 127 seconds. (1 minute resolution)
Size: 1 Byte, Default Value: 0

SettingDescription

0 Sets Time is 0
1 – 127 Set Time is set in seconds from 1 to 127 minutes
128 – 254 Set Time is set in minutes from 1 to 127 minutes

Parameter 5: Fade Time

Sets the u0022Fade Timeu0022 that will take the Dimmer to go from 100% to 0%This value must be set in hexadecimal format, and can accept these values:0 – > Fade Time is 0.0×01…0x7F –> Fade Time is from 1 to 127 seconds. (1 second resolution)0x80…0xfE–> Fade Time is from 1 to 127 seconds. (1 minute resolution)
Size: 1 Byte, Default Value: 0

SettingDescription

0 Fade Time is 0 seconds
1 – 127 Fade Time is set in seconds from 1 to 127 seconds
128 – 254 Fade Time is set in minutes from 1 to 127 minutes

Parameter 6: Min Dimming %

Relative adjust used to set the minimum regulation value. This adjust is done in reference to internal values, accepted dimming values will always be from 1 to 0x63.Minimum Value must be < than Maximum Value.
Size: 1 Byte, Default Value: 1

SettingDescription

1 – 98 minimum internal dimming value

Parameter 7: Max Dimming %

Relative adjust used to set the maximum regulation value. This adjust is done in reference to internal values, accepted dimming values will always be from 1 to 0x63.Maximum Value must be > then Minimum Value.
Size: 1 Byte, Default Value: 100

SettingDescription

2 – 99 maximum internal dimming value

Parameter 9: Callibration

Write only configuration used to request the automatic adjust of UP and DOWN times.
Size: 1 Byte, Default Value: 0

SettingDescription

255 Sunblind starts its callibration process

Technical Data

Hardware Platform ZM5202
Device Type Light Dimmer Switch
Network Operation Always On Slave
Firmware Version HW: 1 FW: 4.24:78.59:70.48
Z-Wave Version 6.51.07
Certification ID ZC10-18026010
Z-Wave Product Id 0x0267.0x0007.0x0000
Neutral Wire Required ok
Supported Meter Type Electric Energy
Electric Load Type Dimmable ELV (Magnetic)Dimmable LEDDimmable MLV

(Magnetic)Incandescent
Firmware Updatable| Updatable by Professional/Technician
Frequency| XXfrequency
Maximum transmission power| XXantenna

Supported Command Classes

  • Association Grp Info V3
  • Association V2
  • Basic
  • Configuration V2
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Meter V4
  • Powerlevel
  • Switch Multilevel V3
  • Version V2
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals