LEVITON IS-C1048 6 Inch and 8 Inch Gravity Cylinder Remote Emergency Backup Instruction Manual
- June 8, 2024
- Leviton
Table of Contents
- IMPORTANT SAFETY INSTRUCTIONS
- MOUNTING BRACKET
- ELECTRICAL CONNECTIONS
- MOUNTING CYLINDER TO MOUNTING BRACKET
- FASTEN SET SCREWS
- Remote Driver Housing Installation
- REPLACING OPTICS/INSTALLING ACCESSORIES:
- WIRING & DIMMING COMPATIBILITY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
IS-C1048 6 Inch and 8 Inch Gravity Cylinder
Remote Emergency Backup
Instruction Manual
WARNING
Risk of electrical shock. Disconnect power before servicing or installing
luminaire.
WARNING
Risk of injury or damage. Luminaire will fail if not installed properly.
Follow installation instructions.
WARNING
Risk of injury. Wear safety glasses and gloves during installation and
servicing.
Allow ample time to cool before handling.
IMPORTANT SAFETY INSTRUCTIONS
- Read all installation instructions before installing. It is important to save these instructions.
- Only install and connect LED module with power disconnected at the circuit breaker. Hot plugging, or connecting the module with power on, could damage the LEDs and is not covered by warranty.
- Observe and follow all label information and instructions regarding dry, damp and wet location listings, proper Intense LED module, warnings of installation near combustible materials and/or insulation.
- Be sure to connect ground wire to prevent electric shock or other potential hazards.
- The product must be installed in a manner consistent with the intended use and in compliance with the national electrical codes and local codes by a person familiar with the construction and operation of the product and the hazards involved.
- WARNING: Use only Intense Lighting trims listed for use with this fixture. Use of trims other than those listed by Intense Lighting is a violation of N.E.C 110-3(B) and voids all warranties.
MOUNTING BRACKET
- Attach universal mounting bracket to junction box using hardware supplied with junction box.
ELECTRICAL CONNECTIONS
- Make electrical connections through center hole of universal mounting bracket.
- Connect ground wire from mounting bracket to green (ground) supply wire and ground wire from fixture, black wire from cylinder to black (hot) supply wire and white wire from cylinder to white (neutral) supply wire. Use UL listed connectors or wire nuts (by others) to make the connections. Connect dimming wires if applicable, see page 3.
![LEVITON IS-C1048 6 Inch and 8 Inch Gravity Cylinder Remote Emergency Backup
- Figure 2](https://manuals.plus/wp-content/uploads/2023/01/LEVITON-IS-C1048-6 -Inch-and-8-Inch-Gravity-Cylinder-Remote-Emergency-Backup-Figure-2.jpg)
MOUNTING CYLINDER TO MOUNTING BRACKET
- Lift cylinder up and over mounting bracket. Align the arrows on the mounting bracket with the notches on the wall mount.
![LEVITON IS-C1048 6 Inch and 8 Inch Gravity Cylinder Remote Emergency Backup
- Figure 3](https://manuals.plus/wp-content/uploads/2023/01/LEVITON-IS-C1048-6 -Inch-and-8-Inch-Gravity-Cylinder-Remote-Emergency-Backup-Figure-3.jpg)
FASTEN SET SCREWS
- Attach the M3 set screws under the wall mount with the hex key tool (do not overtighten).
![LEVITON IS-C1048 6 Inch and 8 Inch Gravity Cylinder Remote Emergency Backup
- Figure 4](https://manuals.plus/wp-content/uploads/2023/01/LEVITON-IS-C1048-6 -Inch-and-8-Inch-Gravity-Cylinder-Remote-Emergency-Backup-Figure-4.jpg)
Installation Instructions
6” & 8” Gravity Cylinder Remote Emergency Backup – Wall Mounted
Remote Driver Housing Installation
REMOTE BOX INSTALLATION
- Attach remote box at two 1/4” holes on 6 inch centers with frame in installation hardware (supplied by others)
- Remove cover plate
- Remove required knockouts and run conduit to junction box fixture is attached to (**maximum 50 feet length from fixture”)
- Run connecting wires for LED driver class 2 by local and national electrical regulations, minimum 18 AWG wire and at maximum 50 feet length
- Make electrical connections (see wiring diagram at the end of this document)
- Reinstall cover plate with supplied 8-32 hardware, insure wires are clear of box edges not pinched or damaged when cover is screwed down
![LEVITON IS-C1048 6 Inch and 8 Inch Gravity Cylinder Remote Emergency Backup
- Figure 5](https://manuals.plus/wp-content/uploads/2023/01/LEVITON-IS-C1048-6 -Inch-and-8-Inch-Gravity-Cylinder-Remote-Emergency-Backup-Figure-5.jpg)
REPLACING OPTICS/INSTALLING ACCESSORIES:
- Remove trim, then remove optic holder from cylinder.
- Remove retaining ring that secures optic, then remove optic.
- Install accessory in optic holder and/or insert new optic.
- Secure retaining ring and replace optic holder then trim.
WIRING & DIMMING COMPATIBILITY
For use with all Intense Lighting product with supported dimming options.
Please check configuration of product for correct dimming protocol.
Phase Dimming or Lutron® LTEA2W Hi-Lume 2-Wire
- 120V Only
- Forward 1% / Reverse 5%
COMPATIBLE DIMMERS
Product | Part Number(s) | Type |
---|---|---|
Leviton | IPEO4 | Reverse |
Leviton | IP106-111 | Forward |
Leviton | 6633-P | Forward |
Lutron | DVELV300P | Reverse |
Lutron | DVCL-153P | Forward |
Lutron | SHOP | Forward |
Cooper | DLCO3P | Forward |
Cooper | DAMP | Forward |
0-10V Dimming
- 120V or 277V
- Dims down to 1% or 0.1% light output
- Consult dimming manufacturer for installation instructions and power packs
![LEVITON IS-C1048 6 Inch and 8 Inch Gravity Cylinder Remote Emergency Backup
- Figure 8](https://manuals.plus/wp-content/uploads/2023/01/LEVITON-IS-C1048-6 -Inch-and-8-Inch-Gravity-Cylinder-Remote-Emergency-Backup-Figure-8.jpg)
COMPATIBLE DIMMERS
Manufacturer+B294 | Part Number(s) |
---|---|
HUNT | PS-010-IV-120V, PS-010-WH-120V, PS-010-3W-IV-120, PS-010-3W-WH-120V, |
PS-010-IV-277V, PS-010-WH-277V, PS-010-3W-IV-277V, PS-010-3W-WH-277V,
FD-010: PS-IFC-010-IV, PS-IFC-010-WH-120/277V, FD-010: PS-IFC-010-3W-IV,
PS-IFC-010-3W-WH-120/277V, FD-010-120V, FD-010-277V
Leviton| Leviton Centura Fluorescent Control System, IllumaTech™ IP7 Series,
DPSPE-212
Lightolier| ZP600FAM120, MP1500FAM120, V2000FAMU
Lithonia| LEQ BC, LEQ LVBC, SLD LVBC, SQ1DC
Lutron| DVTV, NTFTV
Synergy| ISD BC 120/277
Lutron® LDE1 Hi-Lume EcoSystem
- 120V or 277V
- Dims down to 1%
- Consult dimming manufacturer for installation instructions
![LEVITON IS-C1048 6 Inch and 8 Inch Gravity Cylinder Remote Emergency Backup
- Figure 9](https://manuals.plus/wp-content/uploads/2023/01/LEVITON-IS-C1048-6 -Inch-and-8-Inch-Gravity-Cylinder-Remote-Emergency-Backup-Figure-9.jpg)
COMPATIBLE DIMMERS
Product | Part Number(s) |
---|---|
Ec o S y s t em | C S -1L-W M, C S -2L-W M, C S -1L-CM, C S -2L-CM, EcoSystem |
ESN, Grafik Eye QS with EcoSystem, Quantum
For use with all Intense Lighting product with supported dimming options.
Please check configuration of product for correct dimming protocol.
DMX512 RDM (Cylinders without RJ45)
- 120V or 277V
- Dims Down to 0.1% Light Output
- RDM Channel Programmable
![LEVITON IS-C1048 6 Inch and 8 Inch Gravity Cylinder Remote Emergency Backup
- Figure 10](https://manuals.plus/wp-content/uploads/2023/01/LEVITON- IS-C1048-6-Inch-and-8-Inch-Gravity-Cylinder-Remote-Emergency-Backup- Figure-10.jpg)
DALI
- 120V or 277V
- Dims down to 0.1%
INTENSE LIGHTING | 3340 E La Palma Ave, Anaheim, CA 92806 |
tel 714 630-9877 | fax 714 630-9883
For Intense Lighting’s limited product warranty, go to
www.intenselighting.com. For a printed copy
of the warranty, you may call 800 961-5321.
© 2022 Intense Lighting, LLC. All rights reserved. Note: This document is
subject to change without notice.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>