NOVUS TxIsoBlock-HRT Configurable Head Mount Temperature Transmitter Instruction Manual
- June 8, 2024
- Novus
Table of Contents
TxIsoBlock-HRT
TEMPERATURE TRANSMITTER – OPERATING MANUAL – V1.1x B
INTRODUCTION
The TxIsoBlock-HRT is a configurable head mount temperature transmitter widely
required in various industrial processes. Its universal input can be
configured to read RTDs, thermocouples and mV signals.
It converts the input signal into a 4-20 mA linear output proportional to the
configured range. The TxIsoBlock-HRT uses the HART® communication protocol
over the 4-20 mA output current loop.
The input and output are electrically isolated, enhancing their performance
and user and system safety.
SPECIFICATIONS
Sensor input: User defined. The supported sensors are listed in Table 1,
along with their maximum ranges.
Thermocouples: Types J, K, R, S, T, N, E and B, according to IEC 60584
(ITS-90).
Impedance >> 1 MΩ Pt100: Excitation 0.15 mA, α= 0.00385, according IEC
60751 (ITS-90).
For 2-wire sensors, tie terminals 3 and 4 together. Pt1000:
Excitation 0.20 mA, α= 0.00385, according IEC 60751 (ITS-90).
For 2-wire sensors, tie terminals 3 and 4 together.
NTC R25°C: 10 kΩ ±1 %, B25/85 = 3435.
Voltage: 0 to 50 mVdc. Impedance >> 1 MΩ.
Sensor Type| Maximum Measurement Range| Minimum
Retransmission Range
---|---|---
Thermocouple K| -150 to 1370 °C
(-238 to 2498 °F)| 50 °C
(90 °F)
Thermocouple J| -100 to 760 °C
(-148 to 1400 °F)| 50 °C
(90 °F)
Thermocouple R| -50 to 1760 °C
(-58 to 3200 °F)
| 200 °C
(360 °F)
Thermocouple S| -50 to 1760 °C
(-58 to 3200 °F)| 200 °C
(360 °F)
Thermocouple T| -160 to 400 °C
(-256 to 752 °F)| 50 °C
(90 °F)
Thermocouple N| -270 to 1300 °C
(-454 to 2372 °F)| 50 °C
(90 °F)
Thermocouple E| -90 to 720 °C
(-130 to 1328 °F)| 50 °C
(90 °F)
Thermocouple B| 500 to 1820 °C
(932 to 3308 °F)| 200 °C
(360 °F)
Pt100| -200 to 650 °C
(-328 to 1202 °F)| 30 °C
(54 °F)
Pt1000| -200 to 650 °C
(-328 to 1202 °F)| 30 °C
(54 °F)
NTC| -30 to 120 °C
(-22 to 248 °F)| 10 °C
(18 °F)
Voltage| 0 to 50 mV| 3 mV
Table 1 – Sensors accepted by the transmitter
Switch-on delay: < 10 s with damping filter set to factory setting.
The accuracy is only guaranteed after 15 min. Terms of reference for
accuracy: Ambient: 25 °C (77 °F); voltage: 24 Vdc, load: 250 Ω.
Stabilization time of 15 minutes after any setting is required. Temperature
effect: NTC: < 0.11 % FS / 25 °C (45 °F)
Other sensors: < 0.05 % FS / 25 °C (45 °F) (FS = Full Scale).
Response time: Typical 6 s with factory damping filter. This is the maximum
time between a temperature step being applied in the input and the output
reaching 90 % of the corresponding value. HART protocol version: 7.
RTD cable resistance effect: 0.005 °C (0.009 °F) / Ω.
Maximum allowable cable resistance for RTD: 25 Ω.
Accuracy: Calibration error in relation to sensor measuring range (Full
Scale).
Sensor Type | CURRENT LOOP | HART |
---|---|---|
Typical Accuracy | Minimum Accuracy | Typical |
Accuracy | Minimum Accuracy |
Pt100 (-200 to 650 °C)
(-328 to 1202 °F)| 0.08 %| 0.15 %| 0.05 %| 0.15 %
Pt1000 (-200 to 650 °C)
(-328 to 1202 °F)| 0.07 %| 0.15 %| 0.04 %| 0.15 %
K, J, R, S, T, N, E, B| 0.07 % ( )| 0.15 % ( )| 0.04 % ( )|
0.15 % ( )
mV| 0.07 %| 0.15 %| 0.04 %| 0.15 %
NTC| 0.20 °C| 0.45 °C| 0.15 °C| 0.45 °C
(0.36 °F)| (0.81 °F)| (0.27 °F)| (0.81 °F)
Table 2 – Accuracy of input types
*() Add Cold Junction compensation: < ± 1 °C (1.8°F).
Power supply influence: < 0.005 % / V (percentage of the full measure
range).
Output (4-20 mA): 4-20 mA current, 2-wired; linear and proportional to
the configured range.
Output resolution (4-20 mA): 0.25 µA.
Power supply: 8.5 to 36 Vdc (output 4-20 mA).
Maximum load (RL): RL (max.) = (Vdc – 8.5) / 0.0215 [Ω] Where: Vdc =
Power supply voltage (8.5 to 36 Vdc)
Operating temperature: -40 to 85 °C (-40 to 185 °F).
Humidity: 0 to 90% RH.
It presents electrical isolation between input and output of 1.5 kVrms.
Internal protection against reverse polarity of the supply voltage.
Cold Junction compensation for thermocouples.
Connection wire cross section: 0.14 to 1.5 mm².
Screw Tightening: 0.8 Nm.
Housing: Polyamide.
Standards and Certifications:** NAMUR NE-43 standard and CE and HART®
certifications.
CONFIGURATION
When the transmitter is used with the factory setting, no further action is
required and the transmitter is ready to be installed.
Changes to the configuration are possible through the TxConfig II software,
provided free of charge.
The TxConfig II configuration software allows the device configuration.
A TxConfig-HRT interface is required to allow the communication between a
computer and the device. The Txconfig II configuration software is
continuously updated and new versions can be downloaded at no charge from the
manufacturer’s website. To install, execute the
TxConfigIISetup.exe file and follow the instructions.
The interface connects the transmitter to the computer, as shown in Fig. 1:
SOFTWARE CONFIGURATION
The fields in the screen mean:
-
General Information: This field shows information that identifying the transmitter. This information should be sent to the manufacturer in an eventual request for technical assistance.
-
Sensor: Select the type of sensor to be used. See Table 1.
-
Unit: Select the temperature unit to °C (Celsius) or °F (Fahrenheit).
-
Range: Sets de measurement range of the transmitter.
Lowest Limit: Equivalent temperature for a current of 4 mA.
Highest Limit: Equivalent temperature for a current of 20 mA.
Sensor Range: The values chosen cannot exceed the Range of Sensor shown in this field. See Table 1 of this manual.
Minimum Range: It is not possible to establish a range with a span less than the Minimum Range value indicated below in this field. See Table 1 of this manual. -
HART Information:
Tag: Field with a brief identification of the device (up to 8 characters).
Descriptor: Descriptor used by the master for registering (up to 16 characters).
Message: Message used by the master for registering (up to 32 characters). -
Sensor Failure: It establishes the output behavior, when the transmitter indicates a failure, as recommended NAMUR NE 43:
Minimum: Output current goes to <= 3.6 mA (down-scale), typically used for refrigeration.
Maximum: Output current goes to >= 21.5 mA (up-scale), typically used for heating. -
Zero Offset: It corrects small deviations presented in the transmitter output, for example, when the sensor is replaced.
-
Filter: Damping filter.
The damping filter changes the response time of the transmitter in order to smooth the variations in the output. The value set in the filter indicates the time interval at which the PV will reach 63% of its final value.
The factory setting is 1.0 s and can be changed from 0 s to 32 s. In a case with variation from 0 ° C to 100 ° C, considering the factory configuration and after 1.0 s, the PV value will be 63 °C.
With zero value in the filter, the function is disabled. -
Enable write protection: When activated, the configuration setting is not allowed.
-
Send Configuration: It applies the new setup. Once sent, the setup will be immediately adopted by the transmitter.
-
Read Configuration: Reads the current setup in the transmitter connected. The screen now presents the current setup that may be changed by the user.
-
Polling Address: Dynamic (i.e., configurable) address that allows devices to be quickly identified on a network.
-
Enable Current Loop: When disabled, the current remains at 4 mA.
FACTORY SETTING
- Sensor: Pt100 3-wire, range 0 to 100 °C
- Maximum output for sensor failure
- 0 °C zero correction
- Unit: °C
- Filter: 1.0 s
- Address: 0
- Current Loop: Enabled
**** It is possible to configure the device via third-party software and with
the help of an FSK modem to perform HART® communication.
An EDD (Electronic Device Descriptor) file is available, which can be used
with compatible systems and allows access to the settings and supervise the
transmitter.
To put the devices on the same network (or put them in multidrop mode), they
must have different polling addresses and the current loop must be disabled.
MECHANICAL INSTALLATION
The TxIsoBlock-HRT transmitter is suitable to be installed in heads.
Vibrations, moisture and extreme temperatures, electro-magnetic interference,
high voltage and other interferences can permanently damage the unit and could
cause error in the measured value.
DIMENSIONS
ELECTRICAL INSTALLATION
- Polyamide housing to the terminals.
- Section of the cable used: 0.14 to 1.5 mm².
- Recommended torque in the terminal: 0.8 Nm.
RECOMMENDATIONS FOR INSTALLATION
- Conductors of small electrical signals must be distant from activation or high-tension/current conductors, preferably passing through grounded conduits.
- A specific electrical power supply network should be provided for instruments use only.
- In controlling and monitoring applications, possible consequences of any system failure must be considered in advance.
- RC filters (47 Ω and 100nF, serial) in inductor charges (contactors, solenoids, etc.) are recommended.
ELECTRICAL CONNECTIONS
The figures next show the electrical connections required. The terminals 3, 4,
5 and 6 are dedicated to the sensor connection.
LOAD represents the 4-20 mA current measuring device (indicator, controller,
recorder, etc.).
Pt100 / Pt1000 2-WIRE
Note: When used the Pt100 / Pt1000 2-wire, the terminals 3 and 4 must be
interconnected, according to the figure below.
To use the Pt100 / Pt1000 2-wire, you must configure the Pt100/ Pt1000 3-wire
option in TxConfig II.
The Pt100 / Pt1000 wire length should be less than 30 cm to maintain the
measurement error within specifications (electrical resistance).
Pt100 / Pt1000 3-WIRE
Pt100 / Pt1000 4-WIRE
Pt100 / Pt1000 3 and 4-wire: The use of wires with same length and gauge is
recommended for a better resistance compensation. The transmitter compensates
up to 25 Ω per wire.
THERMOCOUPLE
voltage (0-50 mV)
NTC
OUTPUT (4-20 mA)
OPERATION
The transmitter is factory calibrated with standardized sensors, not requiring
any adjustment by the user.
Small corrections can be accomplished through the TxConfig II software (in
units of temperature).
The user may choose the sensor and the range that best fits its application.
The range chosen must not exceed the maximum measuring range defined for the
sensor and must not be less than the minimum range for the sensor.
It is important to note that the accuracy of the transmitter refers to the
maximum range of the sensor used, regardless of the actual range. Example:
- The sensor Pt100 has a max. range of -200 to 650 °C and total accuracy de 0.08 %.
- Thus, we can have an absolute error up to 0.68 °C (0.08% of 850 °C).
- This error is possible in a wide range as the maximum (-200 to 650 ° C) or in a narrower range, set by the user as (example) 0 to 100 ° C.
WARRANTY