tuya Three-Phase WiFi Meter with 60A Electricity Meter Instructions
- June 9, 2024
- Tuya
Table of Contents
Three-Phase WiFi Meter with 60A Electricity Meter
Instructions
Three-Phase WiFi Meter with 60A Electricity Meter
DTS238-7 ZN/S three phase din rail type multi-function watt hour meter(D3703)
The meter is used in three phase four wire power grid. The meter is designed
to measure AC active energy and variable parameter. All of its functions
comply with the relative
technical requirement for class 1 three phase watt hour meter in IEC61036 and
its data communication rules obey the requirement of DL/T645 or MODBUS-RTU. It
is a long life meter with the advantage of high stability, high over load
capability, low power loss and small volume.
Basic Function
★LCD display with backlight
★Bi-directional total active energy measurement, reverse active/ energy
measure in the total active/reactive energy
★ The meter also display real voltage, real current, real power, real power
factor, real frequency, import active energy, export active energy
★Keypad for LCD display step by step
★Pulse LED indicates working of meter, Pulse output with optical coupling
isolation
★Loss phase indication in LCD
★Energy data can store in memory chip more than 15 years after power off
★RS485 communication port, MODBUS-RTU protocol
★35mm din rail installation
Optional Function
★reset energy function(the reset energy kWh display is dependent with the
total energy display, this reset will not affect the total energy)
DTS238-7 ZN/S three phase din rail type multi-function watt hour meter(D3703)
Technical Data
Rate voltage| DTS238-7 ZN/S three phase four wire 3×127/220V,
3×120/208V, 3×220/380V, 3×230/400V, 3×240/415V
---|---
DSS238-7 ZN/S three phase three wire(two phase three wire) 2×120/208V,
2×127/220, 3x220V, 3x380V, 3X100V
Working voltage range| 0.8~1.2Un
Rate Current| 5A/CT, 1.5(6)A, 5(60)A, 10(100)A, or other as required
Frequency| 50Hz or 60Hz
Connection mode| CT type or Direct type
Display| LCD
Accuracy class| 1.0
Power consumption| <0.5W/5VA /each phase
Start current| 0.004Ib
Impulse Voltage| 6kV 1.2μs waveform
Over current withstand| 30Imax for 0.01s
IP grade| IP20
Constant| 400~6400 imp/kWh
Pulse output| Passive pulse, pulse width is 80±5 ms
Communication port| RS485 port, baud rate 1200~9600 bps, default is 9600bps,
address 1~247, None parity, stop bits 1, data bits 8.
Executive standard| DIN 43880, IEC62053-21, IEC62052-11, MODBUS-RTU
Work temperature| -30℃~70℃
Outline dimension LXMXH| 125x88x73mm
Weight| Approx 0.7kg
Accuracy
Voltage | 0.5% |
---|---|
Current | 0.5% |
Power Factor | 1% |
Active power | ±1% |
Reactive Power | ±2% |
Active Energy (kWh) | Class 1.0 |
Environment
Operating temperature | -25℃~55℃ |
---|---|
Storage temperature | -40℃~80℃ |
DTS238-7 ZN/S three phase din rail type multi-function watt hour meter(D3703)
Reference temperature | 23℃±2℃ |
---|---|
Relative humidity | 0 to 95%, non-condensing |
Altitude | Up to 2500m |
Warm up time | 10s |
Mechanical Environment | M1 |
Electromagnetic Environment | E2 |
Degree of pollution | 2 |
Wire connection
-
three phase four wire direct connection
-
three phase four wire through current transformer connection
-
three phase three wire direct connection
-
three phase three wire through current transformer connection
DTS238-7 ZN/S three phase din rail type multi-function watt hour meter(D3703)
Terminal function
Outline dimension
Noting : other voltage , current are also available . Other function also can be special design as customer requirement