Introduction

EPS Box-TP integrates two contactors which provides simple connection for users. It is compatible with equipment with back-up function. Configured with EPS Box, customers just need to connect 3 wires between inverter and EPS Box. It can simplify the operation and improve security.

Overview:

Product overview

Product overview

Object Description
1 LOAD
2 EPS
3 ON-GRID

Wiring Diagram

Note:the following is the wiring diagram of EPS BOX TP. It is necessary to connect the ON-GRID side of EPS BOX TP to the power grid, connect the EPS port to the EPS port of the energy storage machine, and connect the LOAD port to the load at home. The function of TP is to select the power of the load port from the GRID or the EPS port of the energy storage machine.

Note: According to Australian safety requirements, the neutral cables of the on-grid side and backup side must be connected together.Otherwise, the backup function will not work. This diagram is an example for an application that neutral connects with the PE in a distribution box. For countries such as Australia, New Zealand, South Africa, etc, please follow local wiring regulations.

Wiring Diagram

This diagram is an example for an application in which neutral is separated from the PE in the distribution box.

For countries such as China, Germany, the Czech Republic, Italy, etc, please follow local wiring regulations.Need internal or external eps box, connect PE and the off-grid N line.

Wiring Diagram

Preparation

Package Contents
Before installation, make sure that nothing inside the package is damaged. The following items should be inside the package.

  • **A.

**

  • **B.

**

  • **C.

**

  • **D.

**

  • **E.

**

Number Items Quantity
A Expansion Screws 4
B Expansion Tubes 4
C Cushion Blocks 4
D Self-Tapping Screws 4
E AC Connectors 3

Tools
Before you start, get the following tools ready.

  • Diagonal Pilar

  • Screwdriver
    Tools

  • Rubber Hammer

  • 6 Driller

  • Marker Pen

Mounting

Step 1: Install the four cushion blocks on EPS Box -TP with self-tapping screws.
Mounting Instruction

Step 2: Use EPS Box -TP with cushion blocks as a template to mark the four holes’ position on the wall with marker pen.
Mounting Instruction
Mounting Instruction

Step 3: Drill holes with (‘) 6 driller carefully, make sure the holes are deep enough for installing. Install the expansion tubes through cushion blocks into the holes and tighten them.
Mounting Instruction

Step 4: Install the expansion screws with screwdriver to fix the EPS Box- TP.
Mounting Instruction

Wiring Connection

Step 1: Grid String Connection
EPS Box-TP is designed for three-phase grid. Per voltage range is 220/230/240V; frequency is 50/60Hz. Other technical requests should comply with the requirement of the local public grid.

Model(kw) 5.0 6.0 8.0 10.0 12.0
Cable (ON-GRID) 6.0mm2 6.0mm2 6.0mm2 6.0mm2 6.0mm2
Cable (EPS) 4.0mm2 4.0mm2 4.0mm2 4.0mm2 4.0mm2
Micro-Breaker 32A 32A 32A 32A 32A

Step 2: Grid Wiring

  • Check the grid voltage and compare with the permitted voltage range (refer to technical data).
  • Disconnect the circuit-breaker from all the phases and secure against re-connection.
  • Trim the wires:
    • Trim all the wires to 52.5mm and the PE wire to 55mm.
    • Use the crimping pliers to trim 12mm of insulation from all wire ends as below.
      Wiraing Conection

Note: Please refer to local cable type and color for actual installation.

A. EPS Wiring

  •  Set the parts on the cable.
    EPS wiring

  • Crimp wires, screw twisting torque 0.8+/-0.1N-m.
    EPS wiring

  • Push Housing into Body.
    EPS wiring

  • Put the sealing body and yarn trapper into the main body, screw the lock nut into the main body, and the torque is (2.5 + / – 0.5N-m).
    EPS wiring

  • Insert the male end into the female end. For the rotation direction of the lock, please refer to the LOCK mark on the assembly.
    EPS wiring

B. ON-GRID/LOAD Wiring

  • Separate the ON-GRID plug into three parts as below.

    • Hold middle part of the female insert, rotate the back shell to loosen it, detach it from female inset.
    • Remove the cable nut (with rubber insert) from the back shell.
      LOAD Wiring
  • Slide the cable nut and then Install the back shell onto the cable.
    LOAD Wiring

  • Push the threaded sleeve into the socket, tighten up the cap on the terminal.
    LOAD Wiring

  • Remove the ON-GRID connector: Press the bayonet out of the slot with a small screwdriver or the unlock tool and pull it out, or unscrew the threaded sleeve, then pull it out.
    LOAD Wiring

Overview of EPS Box-TP

Overview Of EPS Box-TP

Technical Parameters

Model EPS Box-TP

Grid
Max. AC Input Current (A)| 32
Rated AC Voltage (V)| 220/380, 230/400, 3L/N/PE
Rated AC Frequency (Hz)| 50/60
EPS
Max. EPS Input Current (A)| 25
Rated EPS Voltage (V)| 220/380, 230/400, 3L/N/PE
Rated EPS Frequency (Hz)| 50/60
Load

Rated Output Current (A), On Grid Mode| On Grid Mode 32
Rated Output Current (A), EPS Mode| EPS Mode 32
Rated Grid Voltage (V| 220/380, 230/400, 3L/N/PE
Rated Grid Frequency (Hz)| 50/60
General Data
Cooling Concept| Natural
Operating Temperature Range (°C)| -25~+50
Demensions (WHD)(mm)| 340223170
Net Weight (Kg)| 2.8
Ingress Protection| IP65

Customer Support

The copyright of this manual belongs to FOXESS CO., LTD. Any corporation or individual should not plagiarize, partially or fully copy (including software, etc.), and no reproduction or distribution of it in any form or by any means is permitted. All rights reserved.

FOXESS CO., LTD.
Add: No.939, Jinhai Third Road, New Airport Industry Area,
Longwan District, Wenzhou, Zhejiang, China
Tel: 0510- 68092998
WWW.FOX-ESS.COM

FOX Logo

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals