GREE 3VIR09HP230V1BO Single Zone Mini-Split Heat Pump Instruction Manual

June 9, 2024
Gree

GREE 3VIR09HP230V1BO Single Zone Mini-Split Heat Pump

GREE-3VIR09HP230V1BO-Single-Zone-Mini-Split-Heat-Pump-
product

Single-Zone, Heat Pump System

MODELS:

  • 3VIR09HP230V1BO
  • 3VIR12HP230V1BO
  • 3VIR18HP230V1BO
  • 3VIR24HP230V1BO

Thank you for choosing our product. Please read this Installation & Owner’s Manual carefully before operation and retain it for future reference. If you lose this Manual, please contact your local distributor or visit www.greecomcomfort.com/resources now to download and file the electronic version.

Explanation of Symbols

  • WARNING: This symbol indicates the possibility of death or serious injury.
  • CAUTION: This symbol indicates the possibility of injury or damage to property.
  • NOTICE: Indicates important but not hazard-related information, used to indicate risk of property damage.

Exception Clauses
Manufacturer will bear no responsibilities when personal injury or property loss is caused by the following reasons.

  1. Damage the product due to improper use or misuse of the product;
  2. Altering, changing, maintaining or using the product with other equipment without following the recommendations in the manufacturer’s instruction manual;
  3. After verification, the product defect is directly caused by corrosive gas;
  4. After verification, the defects are due to improper operation or handling during the transportation of the product;
  5. Operating, repairing or maintaining the unit without following the instruction manual or related regulations.
  6. After verification, the problem or dispute is caused by the quality or performance of parts and components produced by other manufacturers;
  7. The damage is caused by natural disasters, a hazardous environment or force majeure.

If you need to install, move or maintain this air conditioner, please use a licensed HVAC dealer to avoid serious damage or personal injury or death. When refrigerant leaks or requires discharging during installation, maintenance, or disassembly, it should be handled by certified professionals in compliance with local laws and regulations. This equipment is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the equipment by a person responsible for their safety. Children should be supervised to ensure that they do not play with the equipment.

Safety precautions

WARNING

Installation

  • Installation or maintenance must be performed by qualified professionals.
  • The equipment shall be installed in accordance with local and national wiring codes.
  • All wiring, circuit breakers, and disconnects must be to code.
  • All wiring of indoor and outdoor units should be connected by licensed professionals.
  • Disconnect the power supply before proceeding with any work related to electricity and safety.
  • All power and control wiring must conform to the air conditioner’s specifications and local codes. An unstable power supply or incorrect wiring may result in electrical shock, fire hazard, or unit malfunction.
  • Grounding of units must comply with the National Electrical Code and local codes.
  • Air Conditioner should be properly grounded. The incorrect grounding may cause electrical shock.
  • Do not connect power before finishing installa-tion.
  • To prevent malfunctions, install a properly sized circuit breaker.
  • An all-pole disconnect switch having a contact separation of at least 3mm in all poles should be installed in the fixed wiring.
  • The circuit breaker must be properly sized to the unit specifications and code to prevent an electrical overload or short circuit.

CAUTION

Installation

  • Instructions for the installation and use of this product are provided by the manufacturer.
  • Select a location which is out of reach for children and far away from animals or plants. If unavoidable, please install a fence for safety.
  • The indoor unit should be installed close to an outside wall.
  • Wire to code (see submittals).
  • Power and control wiring from the outdoor unit to the indoor unit must be continuous.
  • A circuit breaker must be installed in the line.
  • The yellow-green wire is the ground wire it cannot be used for any other purpose.
  • This air conditioner is first-class electric equipment. It must be properly grounded to code. Improper grounding could cause an electrical shock.
  • The refrigerant circuit temperature will be hot, keep the interconnecting wire away from all copper tubing.

WARNING

Operation and Maintenance
  • This equipment can be used by children aged 8 years and above and persons with reduced physical, sensory, or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning the use of the equipment in a safe way and understand the hazards involved.
  • Children shall not play with the equipment.
  • Cleaning and user main-tenance shall not be made by children without supervision.
  • If the supply wiring is damaged, it must be replaced by a licensed HVAC technician or another licensed electrical professional.
  • Connect the air conditioner to a dedicated circuit breaker.
  • Disconnect the power supply when cleaning the air conditioner, to avoid an electrical shock.
  • To avoid electrical shock, do not wash the equipment with water.
  • To avoid electrical shock or unit malfunction do not spray water on the indoor unit.
  • Do not repair the air conditioner by yourself. Doing so may cause electrical shock or damage. Contact a licensed HVAC contractor.
  • To avoid injury, do not touch the fins when removing the filter.
  • Do not extend fingers or objects into the air inlet or air outlet. It may cause personal injury or damage.
  • To avoid damaging the remote controller, do not spill water on it.
  • To avoid damage when drying the air filter, do not use a flame or hair dryer.
  • Do not block air outlets or air inlets. It may cause the unit to malfunction.
  • Do not step on or put heavy objects on the top panel of the outdoor unit. It may damage the unit or cause personal injury.
  • If any of the following occur, turn off the air conditioner and disconnect power immediately and contact the dealer or a qualified professional for service.
    • The wiring is overheating or damaged.
    • Abnormal sounds during operation.
    • Circuit breaker trips off frequently.
    • A burning smell coming from the air conditioner.
    • Indoor unit is leaking.

Parts name

Outdoor Unit

NOTE
The actual product may be different from the above graphics, please refer to the actual product.

Installation notice

Safety precautions for installing and relocating the unit

To ensure safety, please be mindful of the following precautions.

WARNING

  • When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the specified refrigerant. Any presence of air or other foreign substance in the refrigerant circuit will cause system pressure rise or compressor rupture, resulting in injury.
  • When installing or moving this unit, do not charge the refrigerant which does not comply with that on the nameplate or unqualified refrigerant. Otherwise, it may cause abnormal operation, wrong action, mechanical malfunction or even serious safety accidents.
  • When refrigerant needs to be recovered during relocating or repairing the unit, be sure that the unit is running in cooling mode. Then, fully close the valve at the high-pressure side (liquid valve). About 30-40 seconds later, fully close the valve at the low-pressure side (gas valve), immediately stop the unit and disconnect the power. Please note that the time for refrigerant recovery should not exceed 1 minute. If refrigerant recovery takes too much time, air may be sucked in and cause pressure rise or compressor rupture, resulting in injury.
  • During refrigerant recovery, make sure that the liquid valve and gas valve is fully closed and power is disconnected before detachi-ng the connection pipe. If the compressor starts running when the stop valve is open and the connection pipe is not yet connected, air will be sucked in and cause pressure rise or compressor rupture, resulting in injury.
  • When installing the unit, make sure that the connection pipe is securely connected before the compressor starts running. If the compressor starts running when the stop valve is open and the connection pipe is not yet connected, air will be sucked in and cause pressure rise or compressor rupture, resulting in injury.
  • Prohibit installing the unit at a place where there may be leaked corrosive gas or flammable gas. aked gas around the unit, it may cause an explosion and other accidents.
  • Do not use extension cords for electrical connections. If the electric wire is not long enough, please contact a local service center authorized and ask for a proper electric wire. Poor connections may lead to electric shock or fire.
  • Use the specified types of wires for electrical connections between the indoor and outdoor units. Firmly clamp the wires so that their terminals receive no external stresses. Electric wires with insufficient capacity, wrong wire connections and insecure wire terminals may cause electric shock or fire.
Tools for installation
  1. Level meter
  2. Screwdriver
  3. Impact drill
  4. Drill head
  5. Pipe expander
  6. Torque wrench
  7. Open-end wrench
  8. Pipe cutter
  9. Leak detector
  10. Vacuum pump
  11. Pressure meter
  12. Universal meter
  13. Inner hexagon spanner
  14. Measuring tape

NOTICE

  • Please contact the local agent for installation.
  • Don’t use unqualified power cold.
Selection of installation location

Basic requirement
Installing the unit in the following places may cause malfunction. If it is unavoidable, please consult the local dealer:

  1. The place with strong heat sources, vapors, flammable or explosive gas, or volatile objects spread in the air.
  2. The place with high-frequency devices (such as welding machines, and medical equipment).
  3. The place is near a coastal area.
  4. The place with oil or fumes in the air.
  5. The place with sulfurated gas.
  6. Other places with special circumstances.
  7. The equipment shall not be installed in the laundry.
  8. It’s not allowed to be installed on an unstable or motive base structure (such as a truck) or in a corrosive environment (such as a chemical factory).

Outdoor unit

  1. Select a location where the noise and outflow of air emitted by the outdoor unit will not affect the neighborhood.
  2. The location should be well-ventilated and dry, in which the outdoor unit won’t be exposed directly to sunlight or strong wind.
  3. The location should be able to withstand the weight of the outdoor unit.
  4. Make sure that the installation follows the requirement of the installation dimension diagram.
  5. Select a location that is out of reach for children and far away from animals or plants. If it is unavoidable, please add the fence for safety purposes.
Safety precaution
  1. Must follow the electric safety regulations when installing the unit.
  2. According to the local safety regulations, use a qualified power supply circuit and air switch.
  3. Make sure the power supply matches the requirement of the air conditioner. Unstable power supply or incorrect wiring or malfunction. Please install proper power supply cables before using the air conditioner.
  4. Properly connect the live wire, neutral wire, and grounding wire of the power socket.
  5. Be sure to cut off the power supply before proceeding with any work related to electricity and safety.
  6. Do not put through the power before finishing the installation.
  7. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
  8. The temperature of the refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
  9. The equipment shall be installed in accordance with national wiring regulations.

Grounding requirement

  1. The air conditioner is the first class electric equipment. It must be properly grounded with a specialized grounding device by a professional. Please make sure it is always grounded effectively, otherwise, it may cause an electric shock.
  2. The yellow-green wire in air conditioner is a grounding wire, which can’t be used for other purposes.
  3. The grounding resistance should comply with national electric safety regulations.
  4. The equipment must be positioned so that the disconnect is accessible.
  5. An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in the fixed wiring.

Installation of the outdoor unit

Step 1:

Fix the support of the outdoor unit (select it according to the actual installation situation)

  1. Select the installation location according to the house structure.
  2. Fix the support of the outdoor unit on the selected location with expansion screws.

NOTICE

  • Take sufficient protective measures when installing the outdoor unit.
  • Make sure the support can withstand at least four times the unit weight.
  • The outdoor unit should be installed at least 1-1/4 in above the floor in order to install the drain joint.(for the model with a heating tube, the installation height should be no less than 8 in.)
  • For the unit with a cooling capacity of 9000 – 12000 Btu, 6 expansion screws are needed; for the unit with a cooling capacity of 24000~30000 Btu, 8 expansion screws are needed; for the unit with a cooling capacity of 36000+ Btu 10 expansion screws are needed.

Step 2:

Install drain joint (only for some models)

  1. Connect the outdoor drain joint to the hole on the chassis, as shown in the picture below.
  2. Connect the drain hose to the drain vent.

NOTICE

  • As for the shape of the drainage joint, please refer to the current product. Do not install the drainage joint in the severe cold area. Otherwise,it will be frosted and then cause malfunction.

Step 3:

Fix outdoor unit

  1. Place the outdoor unit on the support.
  2. Fix the foot holes of the outdoor unit with bolts.

Step 4:

Connect indoor and outdoor pipes

  1. Remove the screw on the right handle of the outdoor unit and then remove the handle.
  2. Remove the screw cap of the valve and aim the pipe joint at the bellmouth of the pipe.
  3. Pretighten the union nut with hand.
  4. Tighten the union nut with torque wrench by referring to the sheet below.
Hex nut diameter Tightening torque(N .m)
1/4” 15~20
3/8” 30~40
1/2” 45~55
5/8” 60~65
3/4” 70~75

Step 5:

Connect outdoor electric wire

  1. Remove the wire clip; connect the power con-nection wire and signal control wire (only for cooling and heating unit) to the wiring terminal according to the color; fix them with screws.GREE-3VIR09HP230V1BO-Single-Zone-Mini-Split-Heat-Pump-fig- \(10\) NOTICE
    • The wiring board is for reference only, please refer to the actual one.
  2. Fix the power connection wire and signal control wire with a wire clip (only for the cooling and heating unit).

NOTICE

  • After tightening the screw, pull the power cord slightly to check if it is firm.
  • Never cut the power connection wire to prolong or shorten the distance.

Step 6: Pipe Neatly

  1. The pipes should be placed along the wall, bent reasonably, and hidden possibly. Min. semidiam enter of bending the pipe is 4 in.
  2. If the outdoor unit is higher than the wall hole, you must set a U-shaped curve in the pipe before the pipe goes into the room, in order to prevent rain from getting into the room.GREE-3VIR09HP230V1BO-Single-Zone-Mini-Split-Heat-Pump-fig- \(11\)

NOTICE

  • The through-wall height of the drain hose should not be higher than the outlet pipe hole of indoor unit.
  • The water outlet can’t be placed in water in order to drain smoothly.
  • Slant the drain hose slightly downwards. The drain hose can’t be curved, raised and fluctuant, etc.

Test and operation

Use vacuum pump
  1. Remove the valve caps on the liquid valve and gas valve and the nut of the refrigerant charging vent.
  2. Connect the charging hose of gauges to the refrigerant charging vent of gas valve and then connect the other charging hose to the vacuum pump.
  3. Open the gauges completely and operate for 10-15 min to check if the pressure gauge remains in -15 psi.
  4. Close the vacuum pump and maintain this status for 1-2min to check if the pressure of the gauge remains in -15 psi. If the pressure de- creases, there may be a leak.
  5. Remove the gauges, and open the valve core of the liquid valve and gas valve completely with the inner hexagon spanner.
  6. Tighten the screw caps of valves and refrigerant charging vent.
  7. Reinstall the handle.

Leak detection

  1. With a leak detector:
    • Check if there is a leak.
  2. With soap water:
    • If a leak detector is not available, please use soapy water for leak detection. Apply soap water at the suspected position and keep the soap water for more than 3min. If there are air bubbles coming out of this position, there’s a leak.
Check after installation

●   Check according to the following requirement after finishing the installation.

Items to be checked| Possible malfunction
Has the unit been installed firmly?| The unit may drop, shake or emit noise.
Have you done the refri- gerant leak test?| It may cause insufficient cooling(heating) capacity.
Is heat insulation of pipe- line sufficient?| It may cause condensation and water dripping.
Is water drained well?| It may cause condensation and water dripping.
Is the voltage of power supply according to the voltage marked on the nameplate?| It may cause malfunction or damage the parts.
Is electric wiring and pip- eline installed correctly?| It may cause malfunction or damage the parts.
Is the unit grounded securely?| It may cause electric leakage.
Does the power cord fol- low the specification?| It may cause malfunction or damage the parts.
Is there any obstruction in the air inlet and outlet?| It may cause insufficient cooling(heating) capacity.
The dust and sundries caused during installation are removed?| It may cause malfunction or damage the parts.
The gas valve and liquid valve of connection pipe are open completely?| It may cause insufficient cooling (heating) capacity.
Is the inlet and outlet of the piping hole been covered?| It may cause insufficient cooling (heating) capacity or waste electricity.

Test operation

  1. Preparation of test operation
    • The client approves the air conditioner.
    • Specify the important notes for the air conditioner to the client.
  2. Method of test operation
    • Put through the power, and press the ON/OFF button on the remote controller to start the operation.
    • Press the MODE button to select AUTO, COOL, DRY, FAN, and HEAT to check whether the operation is normal or not.
    • If the ambient temperature is lower than 16°C(61°F), the air conditioner can’t start cooling.

Configuration of the connection pipe

  1. The standard length of the connection pipe: 5m, 7.5m, 8m.
  2. Min. length of the connection pipe is 3m.
  3. Max. length of the connection pipe is shown as below.

Max. length of the connection pipe


Cooling capacity

| Max. length of connection pipe(ft)
---|---
9000Btu/h (2637W)| 50
12000Btu/h (3516W)| 66
18000Btu/h (5274W)| 82
24000Btu/h (7032W)| 82

  1. Additional refrigerant oil and refrigerant charging are required after prolonging the connection pipe.
    • After the length of the connection pipe is prolonged for 10m at the basis of standard length, you should add 5 ml of refrigerant oil for each additional 5m of connection pipe.
    • The calculation method of additional refrigerant charging amount(on the basis of liquid pipe): Additional refrigerant charging amount = prolonged length of liquid pipe × additional refrigerant charging amount per meter
    • Based on the length of the standard pipe, add refrigerant according to the requirement as shown in the table. The additional refrigerant charging amount per meter is different according to the diameter of the liquid pipe. See the following sheet.

The additional refrigerant charging amount for R410A

Piping size Outdoor unit throttle
Liquid pipe Gas pipe

htg (oz/ft)

1/4”| 3/8” or 1/2”|  | .215
1/4” or 3/8”| 5/8” or 3/4”|  | .54
1/2”| 3/4” or 7/8”|  | 1.29
5/8”| 1” or 1 1/4”|  | 1.29
3/4”| |  | 2.7
7/8”|
|  | 3.76

Pipe expanding method

NOTICE
Improper pipe expansion is the main cause of refrigerant leaks. Please expand the pipe according to the following steps:

A: Cut the pipe

  • Confirm the pipe length according to the distance between the indoor unit and the outdoor unit.
  • Cut the required pipe with a pipe cutter.

B: Remove the burrs

  • Remove the burrs with shaper and prevent the burrs from getting into the pipe.

C: Put on a suitable insulating pipe

D: Put on the union nut

  • Remove the union nut on the indoor connection pipe and outdoor valve; install the union nut on the pipe.

E: Expand the port

  • Expand the port with an expander.

NOTICE

  • “A” is different according to the diameter, please refer to the sheet below:
Outer diameter (mm) A(mm)
Max Min
Φ6 – 6.35(1/4″) 1.3
Φ9 – 9.52(3/8″) 1.6
Φ12-12.7(1/2″) 1.8
Φ15.8-16(5/8″) 2.4

F: Inspection

  • Check the quality of expanding port. If there is any blemish, expand the port again according to the steps above.

Working temperature range

  • 3VIR09HP230V1AO, 3VIR12HP230V1AO
  • 3VIR18HP230V1AO, 3VIR24HP230V1AO
  Indoor side DB/WB(°C /°F) Outdoor side DB/WB(°C /°F)
Maximum 26.7/19.4 50/24
cooling (80/67) (122/75)
Maximum 26.7/-(80/-) 30/18
heating (86/65)

NOTE
The operating temperature range (outdoor temper-ature) for cooling is -29°C(-20°F)~50°C(122°F); for heating is -30°C(-22°F)~30°C(86°F).

3VIR09HP115V1AO,3VIR12HP115V1AO

NOTE

  • The operating temperature range (outdoor temper-ature) for cooling is -25°C(-13°F)~50°C(122°F); for heating is -30°C(-22°F)~30°C(86°F).

LIMITED WARRANTY STATEMENT

FOR WARRANTY SERVICE OR REPAIR:
Contact your installing contractor. You may find the installer’s name on the equipment or in your Owner’s packet. Complete product registration below and keep on file for future reference. Warranty registration: Register your unit(s) on www.greecomfort.com, follow links to “Warranty Registration”

PRODUCT REGISTRATION

  • Model No.
  • Serial No.
  • Date of Installation
  • Owner Name
  • Address of Installation
  • Installing Contractor
  • Address
  • Phone No. / E-mail

GREE distributor (hereinafter “Company”) warrants this product against failure due to defects in materials or workmanship under normal use and maintenance as follows. All warranty periods begin on the date of original installation. If the date cannot be verified, the warranty period begins one hundred twenty (120) days from the date of manufacture. If a part fails due to a defect during the applicable warranty period, Company will provide a new or remanufactured part, at Company’s option, to replace the failed defective part at no charge for the part. This limited warranty is subject to all provisions, conditions, limitations, and exclusions listed below.

  • A warranty period of Five (5) years on all parts to the original registered end user.

  • A warranty period of 90 days on the remote control is provided with the original unit.

  • A warranty period of 1 yr on all parts to the original registered commercial end user.
    The limited warranty applies only to systems that are properly installed by a state-certified or licensed HVAC contractor, under applicable local and state law in accordance with all applicable building codes and permits; GREE installation and operation instructions, and good trade practices.

  • Warranty applies only to products remaining in their original installation location.

  • Defective parts must be returned to the distributor through a registered servicing dealer for credit.

LIMITATIONS OF WARRANTIES:
ALL IMPLIED WARRANTIES AND/OR CONDITIONS (INCLUDING IMPLIED WARRANTIES OR CONDITIONS OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR USE OR PURPOSE) ARE LIMITED TO THE DURATION OF THIS LIMITED WARRANTY, SOME STATES OR PROVINCES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY OR CONDITION LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE EXPRESS WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON, WHATSOEVER.

THIS WARRANTY DOES NOT COVER:

  1. Labor or other costs incurred for diagnosing, repairing, removing, installing, shipping, servicing or handling of either defective parts, or replacement parts, or new units.
  2. Product cleaning is required prior to warranty service and repair.
  3. Normal maintenance as outlined in the installation and servicing instructions or Owner’s Manual, including filter cleaning and/or replacement and lubrication.
  4. Failure, damage, or repairs due to faulty installation, misapplication, abuse, improper servicing, unauthorized alteration or improper operation.
  5. Failure to start due to voltage conditions, blown fuses, open circuit breakers, or damages due to the inadequacy or interruption of electrical service.
  6. Failure or damage due to floods, winds, fires, lightning, accidents, corrosive environments (rust, etc.) or other conditions beyond the control of the Company.
  7. Failure or damage of coils or piping due to corrosion on installations within one (1) miles of sea coast or corrosive body.
  8. Parts not supplied or designated by Company, or damages resulting from their use.
  9. Products installed outside the 48 contiguous United States, except the District of Columbia and Hawaii.
  10. Electricity or fuel costs, or increases in electricity or fuel costs from any reason whatsoever, including additional or unusual use of supplemental electric heat. 11. Any cost to replace, refill or dispose of refrigerant, including the cost of refrigerant.
  11. Shipping damage or damage as a result of transporting the unit.
  12. Accessories such as condensate pumps, line sets, and so forth are not covered.
  13. Any special, indirect, or consequential property or commercial damage of any nature whatsoever. Some states or provinces do not allow the exclusion of incidental or consequential damages, so the above limitation may not apply to you.
  14. Consumable components, such as air filters, are not covered under the parts warranty.

This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. In jurisdictions where warranty benefits conditioned on registration are prohibited by law, registration is not required, and the STANDARD warranty period shown above will apply.

U.S. CONTACT INFORMATION TRADEWINDS, LLC
E-mail: info@twclimate.com
Contractor Support: 888-850-7928 | Mon- Fri 8 AM – 5 PM EDT

GREECOMFORT.COM.

CAT NO: GREE_VIREO GEN3_B0_INSTALL_12282022.