WFCO WF-8700-AD Series Power Station User Manual
- June 4, 2024
- WFCO
Table of Contents
- WFCO WF-8700-AD Series Power Station
- REVERSE BATTERY PROTECTION
- WF-8700-AD Series Power Center Safety Features
- OPERATIONAL FEATURES
- Troubleshooting the WF-8700-AD Series Power Center
- GENERAL COMPLIANCE INFORMATION
- INSTALLATION INSTRUCTIONS
- CONSUMER LIMITED WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
WFCO WF-8700-AD Series Power Station
GENERAL INFORMATION
WF-8700-AD Series Power Center Safety Features
REVERSE BATTERY PROTECTION
The WF-8700-AD Series Power Centers will charge the 12-volt House battery if installed. A battery DOES NOT have to be installed for WF-8700-AD Series Power Center converter operation. When a battery is installed, a reverse polarity fuse protects the converter circuitry. The fuse is located along the bottom of the row of fuses. Refer to Figure 1 on page four. This feature prevents permanent damage to the converter from a battery connected into the circuit backwards. In addition to protecting the converter section, the reverse polarity fuse is the main connection between the converter and the DC fuse board.
The fuse values and quantity vary depending on which WF-8700-AD Series Power Center you have. Refer to the table and drawing below.
- WF-8725-AD – 30A (1)
- WF-8735-AD – 40A (1)
- WF-8740-AD – 30A (2)
BLOWN FUSE INDICATORS ON DC FUSE BOARD
The DC Fuse Board has individual blown fuse indicators as standard equipment.
The WF-8725-AD has four DC circuits (three Branch and one Battery). The
WF-8735-AD and WF-8740-AD have six DC circuits (Five Branch and one Battery).
Each of the circuits contain a red LED to indicate a blown fuse. If one of the
circuits draws more current than the rating of the fuse, the fuse will blow.
When this occurs, the red LED for that circuit will illuminate. NOTE: The fuse
board employs surface mount LEDs which are barely visible to the naked eye.
Replace the blown fuse with a known good fuse of the same rating. NOTE: If the
replacement fuse blows again, check that circuit for a short or overload
condition .
AUTOMATIC COOLING FAN
The cooling fan in the WF-8700-AD Series Power Center is incremental and is
controlled by the current drawn out of the converter to the applied load. The
on-board microprocessor increases fan speed as the total load increases and
decreases fan speed as the load decreases. Unlike traditional temperature-
controlled fans, the load-controlled fan provides better component cooling by
avoiding temperature spikes which can lead to premature component failure.
OVER-TEMPERATURE PROTECTION
If the internal temperature of the converter exceeds a critical point, it will
shut down. This protects the unit from excessive heat that may damage
sensitive components. The unit will restart once the temperature inside has
dropped.
ELECTRONIC CURRENT LIMITING
If the output current exceeds the maximum rating for the WF-8700-AD Series
Power Center converter, the output current will remain constant, but the
output voltage will begin to drop. If this occurs, the unit will recover once
loads are reduced .
SHORT-CIRCUIT PROTECTION
Should a short-circuit occur in the RV, the WF-8700-AD Series Power Center
converter will drop the voltage output to zero volts. If the short-circuit
condition is removed and no other fault conditions are detected, the converter
will resume normal operation. However, short-circuit conditions are dangerous,
and an RV will require inspection by a qualified service technician.
CIRCUIT PROTECTION
WF-8700-AD Series Power Center Fuses and Breakers
WF-8700-AD Series Power Center Safety Features
DC FUSES (12 VOLTS)
The DC fuse boards have spaces the Branch, Battery and Reverse Polarity fuses
as described above. Should any of fuse’s blow, the Branch Circuit fuses, and
the Reverse Battery Protection fuses should be replaced with ATC or ATO
automotive type fuses such as:
- Littelfuse type 257
- Bussmann type ATC
AC CIRCUIT BREAKERS (120/240 VOLTS)
The AC Breaker side of the WF-8700-AD Series Power Center is located on the
left side of the enclosure. The WF-8700-AD Series Power Center accepts
standard residential breakers. The WF-8725-AD has spaces for a 30 Amp Main and
up to 3 Branch breakers when using duplex breakers. The WF-8735-AD and
WF-8740-AD have spaces for a 30 Amp Main and up to 5 Branch breakers when
using duplex breakers. A list of factories tested, and approved breakers
follows. The breakers may be purchased at most big-box department stores and
home centers.
UL-LISTED MAIN CIRCUIT BREAKERS, RATED FOR 120V, MAXIMUM 30A
The following breakers have been factory tested and approved for use as 30 Amp
Main breakers in the WF-8700-AD Series Power Center:
Manufacturer | Model/Cat. No./Type |
---|---|
Cutler Hammer | Type BR and C |
Thomas Betts | Type TB or TBBD |
ITE/Siemens | Type QP or QT |
Square D | Type HOM or HOMT |
Murray | Type MP-T or MH-T |
General Electric | Type THQL, THQP |
UL-LISTED BRANCH CIRCUIT BREAKERS, RATED FOR 120V, MAXIMUM 20A
The following breakers have been factory tested and approved for use as Branch
breakers in the WF-8700-AD Series Power Center:
Manufacturer | Model/Cat. No./Type |
---|---|
Cutler Hammer | Type BR and C, Type BRD, BD and A |
Thomas Betts | Type TB or TBBD |
ITE/Siemens | Type QP or QT |
Square D | Type HOM or HOMT |
Murray | Type MP-T or MH-T |
General Electric | Type THQL, THQP |
When replacing any of the installed circuit breakers, the replacement should
be of the same manufacturer, type designation, and equal interrupting rating,
not to exceed 30A.
The “Short-Circuit-Current” rating for the breaker should be 10,000 Amps.
Breaker Filler Plates: Model #FP-01 or FP-01B (Black)
OPERATIONAL FEATURES
AUTO-DETECT
This product includes the exclusive “Auto-detect” feature for the charging of
batteries .With this new technology, the power converter will evaluate the
charging cycle of a battery, determine the type of battery being used, and
then choose the appropriate charging program(profile) to provide for the best
performance and maintenance of that battery.
Because of the differences of Lead Acid, AGM and Lithium type batteries, a
system that provides a charge to the battery or batteries must be able to
accommodate the different charging requirements .With the use of the “Auto-
detect” product, the charging requirement is able to be “detected” and is then
automatically set for the type of battery being used. For standard Lead Acid
and AGM ≠batteries, WFCO power converters still use the Three-Stage Smart
Charging to effectively maximize battery life by monitoring through the
different phases of the charge cycle .On the other hand, Lithium batteries
will prefer the use of only two stages when charging, and therefore the power
converter will charge using the WFCO Two-Stage Smart Charging system.
LEAD ACID & AGM THREE-STAGE SMART CHARGING
In order to maximize battery life for lead acid and AGM, it is best to charge
batteries slowly, keep them topped off with a trickle-charge when the RV is
not being used. The 3-Stage “smart” charger continuously measures the battery
voltage output and regulates the amount of charge using three modes of
operation: Absorption, Bulk and Float modes.
All WFCO power converters are automatic three-stage switching power supplies.
The converter senses which mode it needs to be in by checking the RV system
voltage.
ABSORPTION MODE
The converter normally provides a constant target output voltage of 13.6 VDC
(nominal) to power all the branch circuits. However, it is current limited,
and if the output (load) current reaches its maximum, the output voltage will
drop as necessary to hold the converter’s maximum output current level (the
Amperage rating) without exceeding it.
BULK MODE
If the output current reaches its maximum (normally caused by a discharged
battery), this will cause the converter to go into Bulk Mode, which means the
target output voltage will change to 14.4 VDC and a timer will start. Although
the converter is outputting 14.4 VDC, you will not be able to read that on a
voltmeter due to the voltage-current relationship. From the paragraph above,
as load current increases, output voltage decreases. The actual output voltage
will not rise until the load current is reduced, which happens naturally as
the battery charges or if 12 VDC appliances are turned off.
Bulk Mode will be maintained until the current draw drops to approximately
five Amps, or until the timer reaches four hours (whichever happens first).
Then the target output voltage is changed back to 13.6 VDC for Absorption
Mode. Lights that are powered from the output may change brightness slightly
at that time.
FLOAT MODE
The third mode of charging is what is called the “float” charge .This mode is
designed to provide a “trickle charge” to the battery after the system
observes no significant variations in current draw over a long period of time
. When in “float” mode, the voltage will reduce from 13.6V to 13.2V and supply
the “trickle charge” which helps to preserve the life of the battery while
keeping it charged and ready for use. A change in DC current will cause the
converter to exit the mode and return to the Absorption mode and then to Bulk
mode if required. NOTE: For a detailed explanation of the charging modes,
please refer to our publication “Theory of Operation”, document #AD-TD-0001-0.
LITHIUM TWO-STAGE SMART CHARGING
The two-stage “smart” charger continuously measures the battery voltage output
and regulates the amount of charge using two modes of operation: Bulk and
Absorption mode.
2-STAGE CONVERTER VOLTAGE OUTPUT MODES
Understanding output voltages of a two-stage converter.
BULK MODE
This mode is designed with two purposes in mind. First, to quickly restore the
energy back into the battery. Second, to ensure the lithium cells inside the
battery remain balanced. This is accomplished by boosting the output voltage
to 14.6 VDC and allowing the maximum current to flow as required by the loads.
The bulk mode stage could last anywhere from one to four hours based on the
battery and load current which is being used. For a full battery, the bulk
stage has a minimum time requirement of one hour, which allows the lithium
cells inside the battery the time required to “balance”.
For an empty battery, the bulk stage has a maximum time requirement of four hours. If your application requires longer than four hours (such as a larger battery bank > 200 Ahr), a simple cycling of power will reset the timers. As the energy is restored into the battery, the DC system voltage will climb and the current from the converter will decrease. If the total amperage draw from the converter reaches a preset point (within the one-to-four-hour timer), the converter is designed to drop out of bulk mode.
ABSORPTION MODE
This mode is designed with one purpose in mind. This purpose is to provide a
safe operating voltage for all loads in the RV. This is accomplished by
reducing (from bulk mode) the output voltage to 13.6 VDC and remaining at this
voltage until the power is cycled to the converter. The absorption mode stage
is the default or normal mode of operation, which has no timer associated with
it. In this mode output of 13.6 VDC is provided to the DC circuits in the RV.
This voltage has a long-term history as the acceptable voltage for all loads
in the RV, and should not place undue stress (nor reduce the longevity) of the
lights and appliances in the RV. This is not to say that all loads will have
an issue with a constant higher voltage; however, some loads may have an
issue. Please refer to the individual manufacturer’s specifications for the
acceptable operating voltage range of the connected load.
Troubleshooting the WF-8700-AD Series Power Center
Refer to the Troubleshooting Guide for the WF-8700-AD Series Power Center (Figure 5) below.
CHECKING CONVERTER OUTPUT VOLTAGE
Before checking the WF-8700-AD Series Power Center output voltage, disconnect
the battery cables at the battery. Make sure the converter is plugged into an
AC source (105-130 VAC). Check the converter output voltage at the battery
with a voltmeter. Place the meter probes on the disconnected battery cables;
place the Positive (red) meter probe on the + Positive battery wire and place
the Negative (black) meter probe on the – Negative wire on the battery cable.
Be sure you have good connections at the cables. If the voltage reads
13.6-14.4V, the converter is functioning properly.
If the converter output voltage at the battery reads 0.0 VDC, or if the
battery is not charging, check for an open inline fuse in the battery wire
circuit. One may have been installed by the RV manufacturer. Also check for
loose wiring connections. NOTE: The battery circuit (Red wire) should have the
following fuse installed:
- WF-8725-AD – Circuit #4 – 30 A
- WF-8735-AD – Circuit #6 – 30 A
- WF-8740-AD – Circuit #6 – 30 A
CHECKING FOR REVERSE BATTERY HOOKUP (REVERSE POLARITY FUSES)
If there is no DC output coming from the WF-8700-AD Series Power Center
converter section, first check the reverse polarity fuse(s) on the fuse board.
Then, visually inspect the fuses for any breaks in the fuse element. If no
breaks are found, use a continuity tester to check for continuity. If the
reverse polarity fuses are blown, it means the RV battery was accidentally
connected in reverse, either at the battery or at the converter. Investigate
the connections and reconnect the cables properly. Replace the fuse with the
same type and Amperage rating as the original.
IMPORTANT: These fuses protect the converter from damage if the RV battery is
accidentally connected in reverse. A reversed battery connection, even if for
only a second, will cause these fuses to blow.
If the above checks have been made but the converter output still reads 0.0
VDC, the converter
is not functioning properly. Contact the Arterra Distribution Power PROs at 1
877-294-8997. Before placing the call,
please have available the WF-8700 Series Power Center model number from the
front panel label and the 14-digit serial number from the bar code tag located
on the fan panel.
The fan panel is accessible after the door assembly has been removed.
AC REVERSE POLARITY (AUDIBLE ALARM)
This power center is equipped with an AC REVERSE POLARITY PROTECTION
feature. Should the incoming AC neutral wire and lead wire be connected
backwards at the power center, an alarm located in the power center enclosure
will sound .This alarm will continue to sound until the AC wires are connected
correctly.
Should it be determined that the converter section of the WF-8700-AD Series
Power Center is defective, and the unit is under warranty, the entire unit
will need to be returned. The converter section is not user serviceable.
When preparing the unit for return, remove the AC breakers. Label and
disconnect each wire
as they are removed from the breakers and Ground and Neutral bars. The DC
wires protruding from the back of the WF-8700-AD Series Power Center have been
connected to the DC circuits in your RV by the RV manufacturer. In a similar
fashion, label and disconnect these wires. Follow the packaging instructions
in your warranty claim packet.
GENERAL COMPLIANCE INFORMATION
Agency Listings
UL
The WF-8700-AD Series Power Centers are UL-Listed, and cUL-Listed (Canadian).
FCC COMPLIANCE CLASS B
NOTE: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy, and if not
installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his
own expense.
INSTALLATION INSTRUCTIONS
Installing the WF-8700-AD Series Power Center
MOUNTING THE ENCLOSURE
The WF-8700-AD Series enclosure should be mounted in an accessible area such
as a wall or in the side of a cabinet. The front of the enclosure should not
be obstructed to allow free air flow for the cooling fan. The enclosures will
slide into rough openings as follows:
- WF-8725-AD – 10 7/16” W x 6 1/8” H x 3 ¾” D
- WF-8735P and WF-8740P – 10 3/8” W x 6 7/8” H x 4 5/16” D
After wiring is completed, the enclosure fastens to the wall or cabinet using four wood screws not supplied).
WIRING THE AC BREAKERS
Make sure no AC power is coming into the RV from either the Shore Power cord
or an on-board generator. Determine the proper size breakers for the loads the
WF-8700-AD Series Power Center will be powering. You can use either single or
duplex breakers or a combination of both. We recommend that all the breakers
used be of the same brand. A total of four breakers can be mounted in the
WF-8725-AD when using duplex breakers: one Main breaker and up to three Branch
breakers. A total of six breakers can be mounted in the WF-8735-AD and 8740-AD
when using duplex breakers: one Main and up to five Branch breakers. Refer to
the tables on pages five and six for a selection of approved breakers. The
Main breaker should be 30 Amp and is to be installed in the left-most
position. See the wiring diagrams below. A hold down clip is provided to keep
the breaker securely in place .
The 30 Amp power cord is routed through the large knockout in the back of the wiring compartment and secured with a Romex clamp. The Black (Hot) wire is connected to the 30 Amp Main breaker as shown. The White (Neutral) wire is connected to the Neutral Terminal bar at the bottom of the wiring compartment. The Green (Ground) wire is connected to the Ground Terminal bar also located at the bottom of the compartment. Route the Romex leads for the Branch circuits through the Strain Reliefs in the back of the wiring compartment. In a similar fashion, connect the black wire to the Branch breaker and the white and green wires to the appropriate Terminal bar. The Black power wire for converter power on the WF-8735-AD and WF-8740-AD has a pigtail connection. The metal pin is inserted in the Branch breaker designated for converter power. The end with the wire nut can be used to power another circuit if necessary. If not used, leave the wire nut installed and push the wire to the side. Make sure all terminals are torqued to the specifications listed on the back of the door assembly.
WIRING THE DC FUSE BOARD
Make sure the house battery is disconnected before beginning the DC wiring.
Determine what DC loads are to be connected to the fuse board and what
position they will occupy. All four circuits on the WF-8725-AD Power Center
have up to 20 Amp ATO or ATC fuses installed. On the WF-8735-AD and WF-8740-AD
Power Centers, circuits F5 and F6 can be used for slide-outs or other higher
current loads and can have a maximum 30 Amp ATO or ATC fuse installed. The
remaining four circuits are general purpose and can have up to 20 Amp ATO or
ATC fuses installed. Make sure the fuses are seated properly.
All models have wire lead connections. Strip approximately 1/4” of insulation
from the wires and attach to the appropriate connected load using a wire nut
or other approved method. Make sure the connectors are tightly secured.
Connect the heavy wire (Red) coming from the battery to the Red 10AWG wire
coming from the back of the enclosure.
As a last step, install a separate bus bar in a location behind the converter.
Connect the 10AWG White wire coming from the back of the enclosure to this bus
bar. Connect the battery negative wire to this bus bar along with all the
negative DC load wires. Also, run a wire from the bus bar to chassis ground.
CONSUMER LIMITED WARRANTY
For WFCO Electronic Products
WFCO extends, to the original owner, a Two-Year Limited Product Warranty. This
warranty is
in effect from the date of original purchase for a period of two years. This
limited warranty is extended specifically for and is limited to Recreational
Vehicle application and is only valid within the continental United States,
Alaska, Hawaii and the Provinces of Canada. WFCO warrants, to the owner, that
its products are free from defects in material and workmanship under normal
use and service based on its intended use and function. This warranty is
limited to the repair or replacement, at WFCO’s discretion, of any defective
parts or defective assembly. Any implied warranties of merchantability or
fitness for intended use are limited in duration unless applicable State Law
provides otherwise. You may have other rights as specified by each individual
state.
EXCLUSIONS AND LIMITATIONS
The OEM warranty specifically does not apply to the following:
- Any WFCO product that has been repaired or altered by an unauthorized person.
- Any damage caused by misuse, faulty installation, testing, negligence, accident or any WFCO product installed in a commercial vehicle.
- Any WFCO product, whose serial number has been defaced, altered or removed.
- Any WFCO product, whose installation has not been in accordance with the WFCO written instructions.
- Any consequential damages arising from the loss of use of the product including but not limited to inconvenience, loss of service, loss of revenue, loss or damage to personal property, cost of all services performed in removing or replacing the WFCO product. Specifications are subject to change without notice or obligation.
- Any WFCO Electronics products sold through unauthorized Internet sources (Example: eBay) will be excluded from all warranty coverage offered by Arterra Distribution / WFCO.
CONSUMER WARRANTY CLAIM PROCEDURE
Upon determination and validation by an authorized OEM dealer that a WFCO
product has a defect, a Return Goods Authorization (RGA) number will be
required before the product can be returned. The RGA number can be requested
by completing the Warranty Information Fax Sheet and appropriate
Troubleshooting Form found at wfcoelectronics.com. Once these forms have been
completed, email the forms along with Proof of Purchase to
warranty@wfcoelectronics.com or fax the three
documents to the Warranty Department at
574-294-8698 .After receipt of the
forms, an RGA number will be issued. This number shall appear on all
correspondence with warranty service. Upon validation of the warranty, WFCO
shall replace the product with a like product. The RGA number shall be placed
on the outside of the carton used to return the product for ease of
identification. Do not mark directly on the product. The product must be
packaged properly to avoid further product damage which could cause a non-
warrantable condition.
WARRANTY ASSISTANCE
The consumer may contact the selling Dealer or OEM for warranty assistance.
The consumer may also contact Arterra Distribution, exclusive distributor to
WFCO Products at:
574-294-8997 or Fax
574-294-8698.
ARTERRA DISTRIBUTION
877-294-8997
wfcoelectronics.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>