TECH EU-401N PWM Solar For Collectors User Manual
- June 2, 2024
- TECH
Table of Contents
PWM Solar For Collectors
User Manual
Safety
Before using the device for the first time the user should read the following
regulations carefully. Not Obeying the rules included in this manual may lead
to personal injuries or controller damage. The user’s manual should be stored
in a safe place for further reference. In order to avoid accidents and errors
it should be ensured that every person using the device has familiarized
themselves with the principle cooperation as well as security functions of the
controller. If the device is to be sold or put in a different place, make sure
that the user’s manual is there with the device so that any potential user has
accesso essential information about the device.
The manufacturer does not accept responsibility for any injuries or damage
resulting from negligence;therefore, users are obliged to take the necessary
safety measures listed in this manual to protect their lives and property.
**WARNING**
- High voltage! Make sure the regulator is disconnected from the mains before performing any activities involving the power supply (plugging cables, installing the device etc.).
- The device should be installed by a qualified electrician.
- Before starting the controller, the user should measure earthing resistance of the electric motors as well as the insulation resistance of the cables.
- The regulator should not be operated by children.
NOTE
- The device may be damaged if struck by a lightning. Make sure the plug is disconnected from the power supply during storm.
- Any use other than specified by the manufacturer is forbidden.
- Before and during the heating season, the controller should be checked for condition of its cables. The user should also check if the controller is properly mounted and clean it if dusty or dirty.
Care for the natural environment is our priority. Being aware of the fact that
we manufacture electronic devices obligates us to dispose of used elements and
electronic equipment in a manner which is safe for nature. As a result, the
company has received a registry number assigned by the Main Inspector of
Environmental Protection. The symbol of a crossed out rubbish bin on a product
means that the product must not be thrown out to ordinary waste bins. By
segregating waste intended for recycling, we help protect the natural
environment. It is the user’s responsibility to transfer waste electrical and
electronic equipment to the selected collection point for recycling of waste
generated from electronic and electrical equipment.
II. Use
EU-401N temperature regulator is intended for controlling solar collector
systems in various configurations. The device controls the collector pumps (or
both the pump and the valve) on the basis of solar batteries temperature and
the accumulation tank temperature (two tanks). Optionally, it is possible to
connect an additional device: circulating pump, electric heater or to send a
signal to CH boiler in order to initialise the fire-up process.
Controlling the circulating pump and sending a fire-up signal to the CH boiler
may be done directly from the controller. An additional signal relay is
necessary in order to control the heater. The controller offers PWM pump
control option enabling the user to adjust its rotational speed.
Principle of operation
Example control panel
Use buttons to navigate through the menu. Press MENU to enter the menu or confirm the settings. Use PLUS and MINUS buttons to switch between menu options. Press MENU to confirm your choice. In order to return to the main screen view (or higher level menu), press EXIT button. Follow the procedure to adjust the settings.
User menu
III.a) Home page
During standard operation of the controller, the graphic display shows the
main page. Apart from the selected scheme, the display also shows:
– operation mode (or type of alarm),
– current time,
– collector temperature
– current temperature of the heat tank
– temperature of all additional sensors depending on selected configuration
On the right-hand side of the screen you may see the following icons:
Active operation mode icon| Icon of active additional device
(peripherals)
---|---
| Automatic operation mode| | Circulating pump
| Collector defrost mode| | Pellet boiler fire-up (voltagefree signal)
| Holiday mode| | Heater
| Collector overheating (alarm mode)| | Anti-legionella
| Sensor damage (alarm mode)| |
If one of the sensors is damaged, an additional icon will be flashing in the
place of the damaged sensor temperature. The icon indicates which sensor was
disconnected or damaged. Additionally, the pump icon will be displayed on the
system scheme (if the pump is working/rotating) or/and the valve icon will
appear (with an indication of current circulation direction).
III.b) Main menu – block diagram
Due to multiple functions fulfilled by the controller, the menu is divided
into Main menu and Service menu.
The main menu includes basic controller options such as operation mode, time
and date settings, language version etc. It is illustrated by the following
block diagram.
* The
parameter is available only when an additional device (heater) is connected.
III.c) Operation mode
This function enables the user to select the operation mode.
Automatic operation.
In automatic operation mode the pump is active when the minimum difference
between collector and tank temperature is reached (the temperature difference
at which the pump is enabled is defined as Solar pump activation delta in:
SERVICE MENU>Pumps>Solar pump activation delta).
The pump remains active until the pre-set temperature is reached (to define
the pre-set temperature go to SERVICE MENU>Accumulation tank>Pre-set
temperature) or until the difference between collector and tank temperature
reaches solar pump deactivation delta : SERVICE MENU>Pumps>Solar pump
deactivation delta (in this case the pump will be activated again when the
collector temperature exceeds the tank temperature by the value of solar pump
activation delta). When the pump is disabled after the pre-set temperature is
reached, it will be activated again when the temperature drops below the pre-
set value by the tank hysteresis value (the hysteresis may be defined in
SERVICE MENU>Accumulation tank>Tank hysteresis).
Collector defrosting
This function enables the user to activate the collector pump manually in
order to cause the snow deposited on the solar collector to melt. After this
function has been activated, the mode is active for a user-defined period of
time. After this time automatic operation is resumed. To set the defrosting
time go to: SERVICE MENU > Solar collector > Defrosting time. The function may
be deactivated manually, to shorten its operation time, by selecting a
different operation mode.
Holiday mode
After this mode has been activated, the pump is active when one of the
following conditions has been fulfilled: Collector temperature reaches the
overheating temperature aloe (SERVICE MENU> Solar collector> Overheating
temperature) minus the value of Holiday delta parameter (SERVICE MENU>Solar
collector>Holiday delta). When this condition is fulfilled, the pump is
activated in order to cool the collector down. The pump is disabled when the
temperature drops by 5°C. Collector temperature is lower than the tank
temperature – the pump is activated in order to cool the tank down. It remains
active until the temperatures of the tank and the collector are equal.
Anti-legionella
This function is active only when an additional device is connected (one of
the Peripherals in the Service menu must be selected). Thermal disinfection
involves raising the temperature of water in the tank to the required
disinfection temperature, read from the upper sensor of the tank (in the case
of using an optional sensor, the user should make sure that it measures the
temperature of water in the upper part of the tank, as it is the priority
sensor for this function). Disinfection aims to eradicate Legionella
pneumophila – bacteria which lower the cell-mediated immunity. The bacteria
often multiplies in hot water reservoirs (optimum temperature: 35°C). After
this function has been activated, the water tank is heated until the
predefined temperature is reached (SERVICE MENU > Peripherals > Heater > Anti-
legionella > Antilegionella temperature). The temperature is maintained for
the whole disinfection time (SERVICE MENU > Peripherals > Heater > Anti-
legionella > Anti-legionella time). Next, the standard operation mode is
restored. Disinfection temperature needs to be reached within a pre-defined
period of time from its activation (SERVICE MENU > Peripherals > Heater >
Anti-legionella > Maximum anti-legionella time). Otherwise, the function will
be automatically deactivated.
Manual mode
This function enables the user to check the system devices manually (using
MENU button) by switching
ON/OFF:
– the solar pump,
– the second solar pump or the switching valve,
– peripherals – additional devices ( voltage-free contact e.g. for firing up
the pellet boiler).
III.d) Clock
This function is used to set current time
III.e) Date
This submenu enables the user to set current date. Time and date settings are
essential for energy counting function to operate correctly.
III.f) Ethernet module
NOTE This type of control is available only after purchasing and
connecting an additional controlling module ST-505 which is not included in
the standard controller set. Internet module is a device enabling the user
remote control of the solar heating system via the Internet at emodul.eu. The
user controls the status of all heating system devices on the home computer
screen and the operation of each device is presented in the form of animation.
Apart from the possibility to view the temperature of every sensor, the user
can change the pre-set temperature of the tank etc. The installation process
is intuitive. Connect the module and go to the main controller menu to
activate the Internet module (Menu>>Ethernet module>>ON). Once Registration
option has been selected, the device generates a code which must be entered on
the website
NOTE
The code is valid for 60 minutes. If the user fails to register on the website
within this time, a new code must be generated.
Internet module parameters such as IP address, IP mask, gate address etc. may
be set manually or by selecting DHCP option.
III.g) GSM module
NOTE This type of control is available only after purchasing and
connecting an additional controlling module ST-65 which is not included in the
standard controller set. GSM module is an optional device which, cooperating
with the controller, enables the user remote control of the CH boiler
operation via a mobile phone. The user is sent an SMS every time an alarm
occurs. Moreover, after sending a certain text message, the user receives
feedback on the current temperature of all the sensors. The ST-65 module may
operate independently of the collector controller. It has two additional
inputs with temperature sensors, one contact input to be used in any
configuration (detecting closing/opening of contacts) and one controlled
output (e.g. a possibility of connecting an additional contractor to control
any electric circuit) When any of the temperature sensors reaches the pre-set
maximum or minimum temperature, the module automatically sends an SMS message
with such information.A similar procedure is used in the case of opening or
closing of the contact input, which may be used as a simple means of property
protection.
III.h) Statistics
This submenu enables the user to monitor current operating status of the
controller:
III.h.1) Gains
This parameter enables the user to check how much energy was gained in
different time periods: daily, weekly, monthly, annually and temporary.
NOTE Statistics provide only approximate data to illustrate roughly the
energy gain.
IV. Collector overheats
This submenu shows a list of collector overheats (instances of too high
temperature detected by the collector sensor). The user may view:
– date of the overheat incident
– time
– duration
– reading from collector sensor
V. Power failures
This submenu shows a list of power failures registered by the controller. The
user may view:
– date
– time
– duration
V.a) Backlight
This parameter is used to adjust the screen brightness. The screen brightness
changes after a few seconds of inactivity.
V.b) Display contrast
This parameter is used to adjust the display contrast.
V.c) Language
This option is used to select the language version of the controller menu.
V.d) Information
Once this option has been selected, the display shows the controller
manufacturer’s logo and current software version.
V.e) Factory settings
This function is used to restore factory settings saved previously in the
service menu.
IV. Service menu
In order to enter the service menu, select SERVICE MENU, enter the code using
plus and minus: 0112 and confirm by pressing MENU. In order to return to the
main screen view (leave the service menu), press EXIT a few times or wait
about 30 seconds ( the controller will leave the service menu automatically).
A block diagram of the service menu is presented below.
IV.a) Accumulation tank
This menu enables the user to adjust all the parameters related to the tank
(heat accumulator).
IV.a.1.) Pre-set temperature
This function is used to adjust the pre-set tank temperature. After reaching
this temperature the collector pump is deactivated.
IV.a.2) Maximum temperature of tank 1
Using this option, the user may declare the maximum acceptable safe
temperature value which the tank can reach in case of collector overheat.
If the collector reaches its alarm temperature (overheat), the pump is
activated automatically in order to cool down the heated collector, regardless
of the pre-set temperature. The pump operates until the tank maximum
temperature is reached or until the collector temperature drops by the value
of the alarm hysteresis (see: SERVICE MENU > Solar collector> Alarm
hysteresis).
IV.a.3) Minimum temperature of tank
1 Using this parameter, the user may declare the minimum acceptable
temperature value which the tank can reach. Below this temperature the pump is
not activated in collector defrosting mode.
IV.a.4) Tank hysteresis
Using this function, the user declares the tank hysteresis value. If the tank
reaches the pre-set temperature and the pump is deactivated, it will be
activated again after the tank temperature drops below the pre-set value by
the value of this hysteresis.
IV.a.5) Cooling to pre-set temperature
When the collector reaches the overheat temperature, the pump is activated in
emergency mode to cool it down. In this case, the heat is transferred to the
tank until the maximum temperature is reached. To prevent the accumulation of
too hot water in the tank, Cooling to pre-set temperature function should be
activated. Once activated, when the collector temperature drops below the
temperature of the tank, the pump is activated in order to cool down the tank
until it reaches the pre-set temperature.
IV.a.6) Holiday delta
This function is active only in Holiday mode. This parameter determines how
many °C before reaching the collector overheat temperature the pump is
activated in order to cool it down. The pump is deactivated after the
collector temperature drops by at least 5°C.
IV.b) Solar collector
These parameters enable the user to configure solar collector operation.
IV.b.1) Overheat temperature It is acceptable alarm temperature of the solar
collector at which the pump is forced to activate in order to cool down the
solar panels. The discharge of warm water will take place regardless of the
tank preset temperature. The pump will operate until the tank temperature
drops below the alarm temperature by alarm hysteresis value (Service Settings
Solar collector > Alarm hysteresis) or until the tank reaches the maximum acceptable temperature (Service settings > Accumulation tank > Maximum temperature).
IV.b.2) Minimum heating temperature
It is the collector threshold temperature. If the collector temperature is higher and starts to drop, the controller disables the pump when the minimum heating temperature is reached. When the collector temperature is below this threshold and starts to increase, the pump is activated when the minimum heating temperature plus hysteresis ( 3°C ) is reached. The threshold heating temperature is not active in the emergency mode, manual mode or collector defrosting.
Tech IV.b.3) Antifreezes temperature Due to the different freezing temperatures of the liquid in the solar installation anti-freeze temperature was introduced. This parameter determines the minimum safe temperature at which glycol liquid does not freeze (temperature measured at the collector). In case of a significant drop in the collector temperature (to the value of anti-freeze temperature), the pump is activated and operates continuously until the collector reaches safe temperature. The setting range of this parameter is within -50: +10°C.
IV.b.4) Alarm hysteresis
Using this function the user sets the value of the collector alarm hysteresis. If the tank reaches the alarm temperature (Overheat temperature) and the pump is activated, it will be deactivated again when the collector temperature drops below the maximum temperature by alarm hysteresis value.
IV.b.5) Defrosting time
Using this function the user determines for how long the pump is enabled once collector defrosting function has been activated. IV.c) Pumps IV.c.1) Pump revolutions – regulated or constant Using this function the user defines the mode of the pump operation: constant revolutions, when the pump operates at all times at full power (when enabled) or regulated revolutions. In the case of regulated revolutions, the user should adjust several additional parameters (see below).
IV.c.2) Maximum collector temperature Using this setting the user declares the value of the collector maximum alarm temperature at which the pump may be damaged. This temperature should be adjusted according to the collector technical specification. Due to the phenomenon of glycol “gelation” at high temperatures and the risk of damaging the solar pump, the pump is deactivated after reaching the maximum alarm temperature (the controller switches to Collector overheat mode.).
IV.c.3) Sola r pump deactivation delta This function determines the difference between the collector temperature and the tank temperature at which the pump is deactivated (so as not to cool down the tank). IV.c.4) Solar pump activation delta This function determines the difference between the collector temperature and the tank temperature at which the pump is enabled (this is the pump activation threshold).
IV.c.5) Gear coefficient
This parameter is available only if regulated revolutions option is selected. When the conditions for the pump activation are met, it is initially activated at minimum speed (solar pump work minimum). Then the pump speed increases according to this coefficient which determines the difference (°C) between the collector temperature and the tank temperature at which the pump speeds up by 10%. The gear coefficient applies only to the pump operating revolutions, namely the value of revolutions within the limits of the solar pump work minimum (0% for the gear coefficient) as well as the solar pump work maximum (100% for the gear coefficient). The greater the difference between the collector temperature and the tank temperature, the higher the pump speed.
EU – 401N User’s manual v 1.1.3
Example:
If the gear coefficient value is 3, each 3°C difference between the tank temperature and the collector temperature results in 10% increase in pump speed. The table below contains examples of the coefficient values and its results.
**| Gear coefficient 3| Gear coefficient 4| Gear coefficient
5| Gear coefficient 6| Pump revolutions| working
---|---|---|---|---|---|---
****Δ value (collector temp. – tank temp.)| Δ3| Δ4| Δ5| Δ6|
10%|
** Δ6| Δ8| Δ10| Δ12| 20%|
** Δ9| Δ12| Δ15| Δ18| 30%|
Δ12| Δ16| Δ20| Δ24| 40%|
Δ15| Δ20| Δ25| Δ30| 50%**|
IV.c.6) Solar pump work minimum
This parameter is available only if regulated revolutions option is selected.
Using this setting the user should define the pump minimum initial speed.
IV.c.7) Solar pump work maximum
This parameter is available only if regulated revolutions option is selected.
Using this setting the user should define the pump maximum operating speed
(%).
IV.c.8) Installation sampling
This function enables the user to activate or deactivate circulation sampling,
aimed at updating the temperature reading, by activating the collector pump
for a short period of time (when standard conditions of pump activation are
not met). Sampling forces short-time activation of the pump after the
collector temperature increase of at least 3°C.
IV.c.9) Control revolutions
-
Increase
It concerns PWM pump whose speed increases when the signal increases. -
Decrease
It concerns PWM pump whose speed decreases when the signal increases.
IV.d) Peripherals
The user may connect and configure the settings of an additional device. If
there is no additional device, the user should select NONE (deactivate).
Additional devices to choose from and examples of connections supporting all
available installation schemes are presented below. In the case of schemes 12
and 14 it is not possible to connect an additional device – the function is
unavailable.
IV.c.10) Circulating pump
Once this device is selected, the user should adjust operation time and pause
time of the pump during its activity. Next, the user should define the hours
of pump operation using From hour and Through hour functions. Entering the
same times (from – through) will result in the device being active throughout
the whole day.
IV.c.11) PLT (pellet) boiler fire-up
This option is used to set the voltage-free signal to fire up the pellet
boiler. The user defines activation delta – the difference between the pre-set
tank temperature and the current tank temperature at which the controller
sends a signal to fire up the boiler. Next, the user selects the time period
throughout which this function will be active (with the use of from hour and
through hour parameters).
IV.c.12) Heater
The heater is used to electrically heat the tank. The principle of operation
is similar to that in the previous case but the heater should be connected by
means of an additional contactor. The user defines the activation delta (the
difference between the pre-set tank pre-temperature and current tank
temperature) below which the controller activates the heater. Next, the user
selects the time period in which the electric heating function will be active
(using from hour and through hour parameters).
IV.c.13) Contact (in)compatible with pump
This setting determines the operation of the voltage-free contact. If the
option Contact compatible with pump is selected, the voltage-free contact will
always close when the pump operates (the additional device will be enabled).
Otherwise (when the icon is deselected), the contact will open at each
activation of the solar pump.
IV.c.14) Cooling down with DHW pump
This function is active beyond the time period, which means all the time.
Sensor 4 is required for it to operate correctly (it should be installed in
the external DHW tank). This function will not operate in the installation
scheme which uses all the sensors. The tank sensor is also necessary for it to
operate (in the case of two sensors in the tank – the top sensor). If the
conditions listed above are met, the peripheral device will be activated
(contact closing) when:
➔ the tank temperature during its growth exceeds its maximum temperature
reduced by cooling activation delta and operates until the temperature drops
below the tank maximum temperature reduced by cooling deactivation delta (both
parameters may be adjusted in the menu).
➔ the temperature in the tank is higher than the DHW temperature. A constant
hysteresis of 3°C is used here.
IV.e) Energy counting
The following parameters need to be configured to achieve more accurate energy
measurement.
IV.c.15) Number of collectors
On the basis of the number of collectors the controller calculates how much
heat has been produced by the solar installation (energy gain).
IV.e.2) Flow
The user should specify the amount of glycol that flows through the pump
during one minute.
IV.e.3) Type of medium
The user chooses the agent used: ethylene glycol, propylene glycol or water.
IV.e.4) Glycol solution
The user specifies glycol concentration in water (given in percent.
IV.e.5) Calibration
This function allows the user to calibrate the temperature difference between
the sensors. The temperature is measured in the place where the temperature
sensor is installed. Deviations may occur in the flow and temperature
measurement at the tank return. The manufacturer does not recommend changing
this setting.
IV.f) Alarm sound
This function enables the user to activate/deactivate the sound signal after
an alarm occurs.
IV.g) Factory settings
The controller is pre-configured for operation. However, the settings should
be customized to the user’s needs. Return to factory settings is possible at
any time. Once the factory settings option is activated, all customized
settings of the solar installation controller (saved in the user’s menu) are
lost and replaced with the manufacturer’s settings. Then, the parameters may
be customized anew. Return to factory settings results in activating the
default installation scheme.
IV.h) Edit service code
It is possible to edit service menu code. Go to this submenu, enter the code
and confirm the settings.
Protections
In order to ensure safe and failure-free operation, the controller is equipped
with a range of protections.
-
Sensor protection.
If one of the sensors is damaged, an acoustic signal is activated and the following symbol will appear on the right hand side of the display. An additional icon informing the user which sensor is disconnected or damaged will flash in the place of its temperature. In order to deactivate the alarm signal in case of error, press EXIT button. -
Protection against collector overheating.
If the maximum (alarm) temperature is reached, the regulator switches to the so-called collector overheat mode and the display shows a corresponding symbol . The pump is enabled in order to cool down the collector until the maximum tank temperature is reached or until the collector temperature drops by the value of the alarm hysteresis (see: SERVICE MENU > Solar Collector> Alarm Hysteresis) In the case of two tanks, both of them are used to cool down the overheated collector (at the same time or one by one, depending on the operation algorithm setting). -
Heat tank protection.
In the event of collector overheating, each tank may be heated to no more than the pre-set maximum safe temperature. After reaching this temperature, the pump of a given tank is disabled (in system configuration with two tanks and a valve, the circulation is switched to the second tank). -
Fuse.
The regulator is equipped with a WT 3.15A tube fuse-link protecting the network.
WARNING
Higher amperage fuse should not be used as it may lead to controller damage.
Software update
NOTE
Software update shall be conducted only by a qualified fitter. After the
software has been updated, it is not possible to restore previous settings.
In order to install new software, the controller must be unplugged from the
power supply. Next, insert the flash drive with the new software into the USB
port. Connect the controllers to the power supply holding MENU button at the
same time until a single sound signal is heard. It indicates that the software
updating process has started.
Maintenance
Before and during the heating season, EU-401N controller should be checked for condition of its cables. The user should also check if the controller is properly mounted and clean it if dusty or dirty.
Power supply | 230V ±10% / 50Hz |
---|---|
Power consumption | 4W |
Collector sensor thermal resistance | -30÷180˚C |
Tray sensor thermal resistance | -30÷99˚C |
Pump 1 max. output load | 0,5A |
Pump 2/Valve max. output load | 0,5A |
Additional output 1 max. output load | 1A |
Fuse | 3,15A |
VII. How to install the device
CAUTION:
The controller should be installed by a qualified electrician! Make sure that
the plug is disconnected from the power supply at that time.
NOTE
The cable connecting the temperature sensor should be put in a protective tube
and it should not be exposed to weather conditions. The cable connection of
the solar controller should be durable, made under shelter and well
insulated. Metal parts of the sensor and the collector system should be
earthed.
Pictorial diagram – collectors
*Pictorial diagram – it cannot replace CH installation project. Its aim is to present how the controller may be expanded. This heating installation diagram does not include protective elements which are necessary to ensure correct installation.
PWM pump connection scheme:
EU DECLARATION OF CONFORMITY
Hereby, we declare under our sole responsibility that EU-401N PWM manufactured
by TECH STEROWNIKI, head-quartered in Wieprz Biała Droga 31, 34-122 Wieprz, is
compliant with Directive 2014/35/EU of the European Parliament and of the
Council of 26 February 2014 on the harmonisation of the laws of Member States
relating to the making available on the market of electrical equipment
designed for use within certain voltage limits (EU OJ L 96, of 29.03.2014, p.
357), Directive 2014/30/EU of the European Parliament and of the Council of 26
February 2014 on the harmonisation of the laws of Member States relating to
electromagnetic compatibility (EU OJ L 96 of 29.03.2014, p.79), Directive
2009/125/EC establishing a framework for the setting of ecodesign requirements
for energy-related products as well as the regulation by the MINISTRY OF
ENTREPRENEURSHIP AND TECHNOLOGY of 24 June 2019 amending the regulation
concerning the essential requirements as regards the restriction of the use of
certain hazardous substances in electrical and electronic equipment,
implementing provisions of Directive (EU) 2017/2102 of the European Parliament
and of the Council of 15 November 2017 amending Directive 2011/65/EU on the
restriction of the use of certain hazardous substances in electrical and
electronic equipment (OJ L 305, 21.11.2017, p. 8).
For compliance assessment, harmonized standards were used:
PN-EN IEC 60730-2-9:2019-06, PN-EN 60730-1:2016-10.
Wieprz, 08.04.2022
Central headquarters:
ul. Biafa Droga 31, 34-122 Wieprz
Service: ul. Skotnica 120, 32-652 Bulowice
phone: +48 33 075 93 80
e-mail: serwis@techsterowniki.pl
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>