Window Master WUF 110 Motor-Interface 230V Instructions

June 3, 2024
Window Master

Window Master WUF 110 Motor-Interface 230V

Window-Master-WUF-110-Motor-Interface-230V-PRODUCT

Important information

  • Only genuine 24 V WindowMaster operators should be connected.
  • WUF 110 is a class II product and must be connected according to the rules for its class.
  • The WUF 110 must not be covered (maximum casing temperature: 45°C). Should not be exposed directly to the sun
  • For indoor use only.
  • The surface should be cleaned with a soft damp cloth using a small amount of household cleaner diluted in water.
  • The motor interface is to be installed by a certified electrician according to the current electrical regulations.
  • Before installation and removal of motor interface WUF 110 disconnect from the mains supply. Ensure that the motor interface cannot be connected unintentionally.
  • Never put a hand or the like out of the window before the system is disconnected form supply voltage.
  • The packaging can be disposed of together with ordinary household waste.
  • In case of damaged power cable, the product is to be discarded.
  • Electrical products must be disposed of in conformity with national regulations for electronic waste and not with usual household waste.
  • In case of technical problems, please contact WindowMaster, see telephone list below.

Installation instructions for WUF 110 motor interface
Read installation instructions carefully before proceeding and keep for future reference.Window-Master-WUF-110-Motor-Interface-230V-
FIG-1

Description

The motor interface is used for WindowMaster window operators as well as installation in the surface mounting system SystemLine. WUF 110 permits 230 V AC operation with WindowMaster 24 V DC operators.

  • Fitting and connection: The motor interface is fitted into the window profile next to the WindowMaster operators. The operator is connected using the double pole plug. The 2 meter long 3-core cable is connected to the mains supply through a switch for control.
  • Primary mains supply: 230 V AC, 50/60 Hz, 50 VA.
  • Nominal output voltage: ±24 V DC / 0.8 A / operating time max. 2 min. per 5 min. (40%).
  • IP value: IP 44.