L8000117 Emergency Lighting
User Guide
Inverter Application Guide
Safety Precautions
Safety Warnings and Instructions for Design-In and Manufacturing
- Do not use damaged or defective contacts or housings.
- Do not service the inverter when mains voltage is connected; this includes connecting or disconnecting the luminaire.
- Do not use damaged products.
- Cap off all unused wires to prevent accidental contact with the luminaire, inverter housing, or other conductive surface.
- The luminaire manufacturer is responsible for its own luminaire design and must comply with all relevant safety standards.
- Design-in support is available to answer other safety concerns not mentioned here; Please contact your Bodine sales representative for more information.
- Bodine emergency lighting inverters are intended for built-in use and should not be exposed to the elements such as snow, rain, ice, and other types of moisture. Exposure can lead to corrosion of the inverter housing and should be avoided. It is the installer’s responsibility to prevent exposure. Bodine emergency lighting inverters are specified for UL damp and dry locations only. These emergency lighting inverters must be installed in accordance with national and local electrical codes.
- Avoid touching live parts
- Do not use inverters with damaged wiring
- Disconnect AC power and inverter connector before servicing
Applications
Emergency Lighting Inverter Applications
Bodine emergency lighting inverters allow selected normal LED luminaires to be
converted into code-required emergency light sources.
Depending on your application requirements, here are a variety of inverters at
different power ratings. These range from as low as 10 watts all the way up to
400 watts. The 10W inverter is considered unit equipment and can even be
installed inside the luminaire.
This design-in guide (DIG) can be a useful resource to help with selecting the
best
Bodine emergency lighting inverter for your application.
Specification sheets and installation instructions for our inverter products
are also available on our website
(www.bodine.com/inverter).
Product specifications and proper installation requirements are also provided
here.
Product Naming Convention:
- ELI = Emergency Lighting Inverter
- S = Sinusoidal Output
- 185 or other number = Maximum Output Power
- 2HR = Extended runtime of 2 Hours, only on extended runtime products
- Final Name: ELI-S-185 2Hr
| Technical support (Mon-Fri, 8AM-5PM CST)
888-263-4738, Option 2
Or email us at BodineTech@Signify.com
---|---
| If questions arise during installation, Bodine provides free technical
support during normal business hours (Mon.- Fri. 8 AM – 5 PM CST).
| For a more in-depth review of a particular application, completely
confidential design-in services are available free of charge. Contact your
local Bodine sales representative for more information.
Battery Installation
Battery Installation and Connections
Most Bodine emergency lighting inverters use maintenance-free sealed lead
acid (SLA) batteries. Since these batteries use SLA chemistry, they must be
charged immediately upon installation and within eight (8) months of the
batteries’ manufacturer’s date code.
This date code is in the form of MMDDY. Thus, a date code of 12191 means the
battery was manufactured on December 19, 2021 and must be charged within eight
(8) months of this date. If your battery has an earlier date code, check the
float voltage. If it is less than 12VDC, it should be replaced.
Another concern is battery discharge when the unit is not in use (not
charging). If AC power will not be present to the inverter for extended
periods, the battery cable connection to the inverter’s printed circuit board
should be disconnected to prevent damage to the battery due to deep discharge.
Refer to your product’s installation instructions for more detailed
information concerning this and overall product wiring.
Ilustration 4
Battery Wiring Connections
Attach the battery wires as shown in the illustration.
This is a typical installation for the ELI-S-100. See your product’s specific
instruction sheet for installation instructions.
External Connections and Wiring
Typical connections to the normal AC LED driver and LED load are shown
below.
The switched AC power source to the inverter can also be used to connect
normal non-emergency luminaires on the same circuit.
The unswitched hot connection is used for battery charging and for sensing the
AC line to determine when inverter/emergency operation from the battery should
initiate.
The dimming connections are for feed-throughs to the emergency luminaires and
for power control during emergency operation to adjust the luminaires to the
proper output power.
For internal connections (screw terminal inside inverter), you will require a
Phillips-head screwdriver.
Note: not all inverters have an inverter connector. See your specific product’s installation instruction sheet for information
Dimming
Auto-Dimming
One of the premier features of Bodine emergency lighting inverters is Auto-
dimming. The auto-dimming function is available on the ELI-S-10, ELI-S-100,
and ELI-S-250. In this mode, the installer can connect a large number of
luminaires to the inverter for emergency backup. (ELI-S-10 is the exception,
which is only intended to be used with a single luminaire.)
When AC power connects to the inverter, the inverter begins powering up its
connected load at approximately a 10% dimming level (about 1VDC dimming
control output signal) and gradually increases the dimming signal until the
inverter output is at full power.
All auto-dimming inverters come with a maximum connected load power rating. If
too many luminaires are connected to the inverter, even at 10% dimming levels,
the inverter will not operate properly until the load is reduced to the
inverter’s output ratings. Improper operation is typically indicated by the
inverter attempting to operate the load every five seconds (approximately)
and then shutting off.
In the example below, fifteen 40W fixtures are connected to the ELI-S-250
inverter (250 VA), dimmed to 40% automatically, providing 16W to each fixture.
15 multiplied by 16W equals 240 VA, thus the ELI-S-250 is effectively able to
power all fixtures at 16W.
The ELI-S-100 also offers manual dimming using preset dip switches. See
product instructions for more information.
Non-Dimmable Emergency Lighting System
Dimmable Emergency Lighting System
Inverter Operation
Emergency Lighting Inverter Operation
Once you have installed your inverter per the instructions, AC power is
applied to the inverter and the inverter connector is closed or switch SW1
OUTPUT ENABLE is in the ON position (only on ELI-S-250 and ELI-S-185 2HR, see
figure below). You can now check for proper load operation in normal and
emergency modes if battery is sufficiently charged.
In normal mode, the luminaires connected to the inverter should operate as
they normally do. The local switching means and/or 0-10VDC dimming should
control these luminaires. When emergency mode is activated, either by
depressing the test switch or turning off the circuit breaker feeding the
inverter and luminaires, the inverter- connected luminaires should operate at
their normal output power levels (if the total connected load is less than the
inverter’s output power rating) or at lower output power levels as set by the
auto-dimming circuit or the manual dip-switch settings.
If this is the first test of the inverter, this is a good opportunity to
ensure light levels meet LSC (NFPA 101 Life Safety Code) requirements. As with
any emergency lighting
device, it should be tested for 30 seconds once every 30 days, and for 90
minutes once every year. This is code-required testing necessary to ensure
your emergency lighting system is operational and adequate for egress
purposes.
Electromagnetic Compatibility/CEC (Title 20)
Electromagnetic Compatibility
Most Bodine emergency lighting inverters are designed to meet EMC requirements
set forth in FCC Title 47 Part 15 Class A regulation.
Compliance to this standard means our products are suitable for commercial and
industrial applications.
See FCC Title 47 CFR Part 15 for details regarding performance requirements in
the FCC regulation. Check your product’s individual spec sheet to determine if
it meets these EMC requirements.
CEC Compliance (Title 20)
Most Bodine emergency lighting inverters are designed to meet battery charger
requirements per CEC Title 20. Compliance to this standard means our products
are suitable for commercial and industrial use in California.
A complete list of registered products can be found at
cacertappliances.energy.ca.gov/Pages/ApplianceSearch.aspx
using the search tool and entering “Signify” under the company tab.
Product spec sheets and labels with the BC (Battery Charger logo, shown below,
demonstrate they comply with CEC Title 20 requirements. Check your product’s
individual spec sheet or label to determine if it meets these requirements.
Electrical/Thermal Specifications
Electrical Specifications
Bodine emergency lighting inverters provide a nearly sinusoidal output voltage
to the load in the event of an AC power outage. In addition to this sinusoidal
voltage specification, these inverters also provide the following output
regulation:
Output voltage regulated to ±10% for both 120VAC and 277VAC. Output frequency
regulated to ±5% for 60 Hz.
Thermal Specifications
The inverter ambient temperature ranges are listed below. If the installation
environment requires a higher surge rating than provided, extra surge
protection may be required.
This protection will be necessary on the unstitched hot connection (AC normal
mains).
Other Features
All Bodine emergency lighting inverters are UL listed to UL 924 and CSA C22.2
No. 141 for use in the U.S. and Canada except for the ELI-S-400, which is ETL
Listed to these standards.
They are also provided with a charging indicator light/test-switch that can be
used for quick testing of the inverter operation in emergency mode.
These inverters are for indoor or damp location use. They are not for use in
wet or hazardous locations.
Inverter | Ambient Temperature Range |
---|---|
ELI-S-10 | 0-50°C |
ELI-S-20 | 0-50°C, 20W Output; 0-45°C, 25W Output |
ELI-S-100 | 0-40°C |
ELI-S-185 2Hr | 20-30°C |
ELI-S-250 | 20-30°C |
ELI-S-400 | 20-30°C |
Power and Apparent Power/Mechanical Mounting
Considerations in Lighting Design
Power vs. Apparent Power in an Inverter
The power rating of an inverter assumes a load with unity, or 100% power
factor (resistive load). Thus, an ELI-S-100 would provide a theoretical 100W
to a purely resistive load.
Most connected lighting loads do not have a unity power factor, even those
with high efficiency LED drivers. There are often conditions where the
lighting load power factor and efficiency do not reach 0.9, or 90%. When an
LED driver is dimmed, for example, its loading characteristics change and its
power factor and efficiency then reduce. The type of dimming (linear or
logarithmic) can affect the power factor and efficiency as well. Understanding
the rating of the inverter product is therefore critical.
For our inverter products, the “power” rating of the inverter provides for a
load unity power factor. If the load’s power factor is lower than unity (which
it likely is), then the power provided by the inverter is apparent power with
a unit of volt-amps (VA).
Using the ELI-S-100 again as an example, if the load’s power factor is 0.9
(leading or lagging), the total apparent power would be 100VA with only 90W of
real power being delivered to the load.
This must be a consideration in the lighting design as it could reduce the
number of total luminaires connected to the inverter.
Mechanical Mounting of Inverter
As with many higher power inverters, their enclosures and contents are much
heavier than typical unit equipment. For example, the ELI-S-400 weighs nearly
100 lbs.
A mounting shelf capable of supporting the weight of the inverter is
necessary. Steps should be taken to ensure the inverter is securely mounted
and adequately supported.
Mounting hardware is not provided with the inverter. There are fastener
keyhole knockouts, as shown to the right, on the back of the inverter
enclosure to permit securing of the enclosure to a rigid surface like a
cinderblock wall using appropriately rated lag screws and concrete anchors.
Note that the information provided in this document is subject to change.
The recommendations and other advice contained in this document are provided
solely for informational purposes for internal evaluation by the user of this
document. Signify does not make and hereby expressly disclaims any warranties
or assurances whatsoever as to the accuracy, completeness, reliability,
content and/or quality of any recommendations and other advice contained in
this document, whether express or implied including, without limitation, any
warranties of satisfactory quality, fitness for a particular purpose or non-
infringement. Signify has not investigated, and is under no obligation or duty
to investigate, whether the recommendations and other advice contained in
this document are, or may be, in conflict with existing patents or any other
intellectual property rights. The recommendations and other advice contained
herein are provided by Signify on an “as is” basis, at the user’s sole risk
and expense. This document is not an official testing certificate and cannot
be used or construed as a document authorizing or otherwise supporting an
official release of a luminaire. The user of this document remains at all
times liable and responsible for any and all required testing and approbation
prior to the manufacture and sale of any luminaire.
Specifically mentioned products, materials and/or tools from third parties are
only indicative and reference to these products, materials and/or tools does
not necessarily mean they are endorsed by Signify. Signify gives no
warranties regarding these and assumes no legal liability or responsibility
for any loss or damage resulting from the use of the information thereto
given here.
© 2022 Signify Holding. All rights reserved. The information provided herein
is subject to change, without notice. Signify does not give any representation
or warranty as to the accuracy or completeness of the information included
herein and shall not be liable for any action in reliance thereon. The
information presented in this document is not intended as any commercial
offer and does not form part of any quotation or contract, unless otherwise
agreed by Signify.
PBo-2103BR Inverter Design in Guide brochure 08/22 page 11 of 11
Signify North America Corporation
400 Crossing Blvd, Suite 600
Bridgewater, NJ 08807
Telephone: 855-486-2216
Signify Canada Ltd.
281 Hillmount Road,
Markham, ON, Canada L6C 2S3
Telephone: 800-668-9008
All trademarks are owned by Signify Holding or their respective owners.