niko 353-650321 Presence Detector for Flush Mounting Box Instruction Manual

June 4, 2024
niko

niko 353-650321 Presence Detector for Flush Mounting Box Instruction Manual

Installation

Installation
Installation

Dimensions

Dimensions

Wiring

230 V – OFF

Wiring

App settings

| | |
---|---|---|---
Factory settings| Switch ON/OFF| 500 lux|

15 min

Inductions


LED behaviour

Green LED continuous on|

| Connection OK|
---|---|---|---
Green LED breathing|

| Connection OK, overrule ON|
Green LED flashing|

| Warming up| Wait
Red LED continuous on|

| Error|

More info –>

Red LED breathing|

| Warning
Blue LED flashing|

| Walk test active

Specifications

  • Article number: 353-650321
  • Configuration: DALI-2 master
  • Input voltage: 230 Vac ± 10 %, 50 Hz
  • Maximum power consumption: 0.3 W
  • Short circuit behaviour shutdown trigger: voltage below 12 V, exceeding 1.3 s
  • Short circuit behaviour restart period: every 14 s until success
  • Detector output: DALI Broadcast/DALI Adressable
  • Maximum voltage on the DALI bus: 15 Vdc
  • Maximum supply current: 250 mA
  • Maximum guaranteed current on the DALI bus: 100 mA
  • Maximum startup time DALI: < 1200 ms
  • Maximum PIR detection startup time: 70 s
  • Maximum number of control gear on the DALI bus: 64
  • Number of dimmable zones:  3
  • Light intensity range: 20 – 2000 lux, ∞
  • Switch-off delay: pulse, 20 s – 120 min, ∞
  • Detection angle: 360°
  • Detection range (PIR): ø 12 m from a height of 3 m
  • Ambient temperature: -25 – +40 °C
  • Mounting method: flush-mounting box
  • Mounting height: 2 – 3.5 m
  • Colour: white (RAL 9010)
  • Dimensions visible (HxWxD): 100 x 100 x 9.5 mm
  • Dimensions (HxWxD): 100 x 100 x 44.5 mm
  • Wire capacity: 1.5/2.5 mm²
  • Protection degree: IP20
  • Impact resistance: IK02
  • Modification of settings: app (iOS/Android) and 2-way Bluetooth® communication
  • Maximum range Bluetooth® (free field, depending on the device): 50 m
  • Operating frequency: 2.4 GHz
  • Maximum radio frequency power: -2 dBm
  • Halogen-free: yes
  • Marking: CE

Detection area

Detection area

Troubleshooting

Problem

| Possible cause|

Proposed solution

---|---|---
Load does not turn on| The wiring is not correct| Check the wiring scheme
 | The ambient light is too strong| Check the response value luminosity and raise the value if necessary
Load does not turn off| The switch-off delay is too long| Check the switch-off delay and shorten the delay if necessary
 | The detector receives false triggers| Check for any objects that may cause false triggering and remove them from the detection range or lower the sensitivity
App cannot connect to the detector| Bluetooth® has been disabled on your mobile device| Enable Bluetooth® on your mobile device

Support & contact

EN +32 3 778 90 80 support@niko.eu

NL België: +32 3 778 90 80 support.be@niko.eu
Nederland: +31 880 15 96 10 support.nl@niko.eu

FR Belgique: +32 3 778 90 80 support.be@niko.eu
France: +33 820 20 66 25 support.fr@niko.eu
Suisse: +41 44 878 22 22 support.ch@niko.eu

DE Deutschland: +49 7623 96697-0 support.de@niko.eu
Schweiz: +41 44 878 22 22 support.ch@niko.eu
Österreich: +43 1 7965514 support.at@niko.eu
Belgien: +32 3 778 90 80 support.be@niko.eu

DK +45 74 42 47 26 support.dk@niko.eu
SE +46 8 410 200 15 support.se@niko.eu
NO +47 66 77 57 50 support.no@niko.eu
IT +41 44 878 22 22 support.ch@niko.eu
PL +48 509 378 373 support.pl@niko.eu
SK +421 2 63 825 155 support.sk@niko.eu

nv Niko sa
Industriepark West 40
9100 Sint-Niklaas, Belgium
www.niko.eu

Niko prepares its manuals with the greatest care and strives to make them as complete, correct and up to date as possible. Nevertheless, some deficiencies may subsist. Niko cannot be held responsible for this, other than within the legal limits. Please inform us of any deficiencies in the manuals by contacting Niko customer services at support@niko.eu