PowerWalker VFI 1000 CRM LCD Uninterruptible Power Supply System User Manual
- June 4, 2024
- PowerWalker
Table of Contents
PowerWalker VFI 1000 CRM LCD Uninterruptible Power Supply System
Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully
Transportation
- Please transport the UPS system only in the original package to protect against shock and impact.
Preparation
- Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
- Do not install the UPS system near water or in moist environments.
- Do not install the UPS system where it would be exposed to direct sunlight or near heater.
- Do not block ventilation holes in the UPS housing.
Installation
- Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
- Place cables in such a way that no one can step on or trip over them.
- Do not connect domestic appliances such as hair dryers to UPS output sockets.
- The UPS can be operated by any individuals with no previous experience.
- Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
- Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
- Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
- When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA.
Operation
-
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads. -
The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is
-
not connected to the building wiring outlet.
-
In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
-
Prevent no fluids or other foreign objects from inside of the UPS system.
Maintenance, service and faults
- The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
- Caution – risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
- Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
- Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
- Caution – r isk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
- Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:
- remove wristwatches, rings and other metal objects
- use only tools with insulated grips and handles.
- When changing batteries, install the same number and same type of batteries.
- Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
- Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
- Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
- Do not dismantle the UPS system.
Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing
inside the package is damaged. Please keep the original package in a safe
place for future use.
NOTE: There are two different types of online UPS: standard and long-run
models. Please refer to the following model table.
Model | Type | Model | Type |
---|---|---|---|
PowerWalker VFI 1000 CRM LCD | Standard model | PowerWalker VFI 1000 CRS LCD |
Long-run
model w/o batteries
PowerWalker VFI 2000 CRM LCD| PowerWalker VFI 2000 CRS LCD
PowerWalker VFI 3000 CRM LCD| PowerWalker VFI 3000 CRS LCD
Rear panel view
- AC input
- Input circuit breaker
- USB communication port
- RS-232 communication port
- SNMP intelligent slot (option)
- External battery connection
- Output receptacles
- Output terminal
1-3K Setup the UPS
Step 1: External battery connection
This UPS is not including batteries. Please connect external batteries as
below chart.
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid
using extension
cords. The power cord is supplied in the UPS package.
Step 3: UPS output connection
- For socket-type outputs, simply connect devices to the outlets.
- For terminal-type input or outputs, please follow below steps for the wiring configuration:
- Remove the small cover of the terminal block
- Suggest using AWG14 or 2.1mm2 power cords for 3KVA model.
- Upon completion of the wiring configuration, please check whether the wires are securely affixed.
- Put the small cover back to the rear panel.
Step 4: Communication connection Communication port:
To allow for unattended UPS shutdown/start-up and status monitoring, connect
the communication cable one end to the USB/RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400
card. When installing either SNMP or AS400 card in the UPS, it will provide
advanced communication and monitoring options.
PS. USB port and RS-232 port can’t work at the same time.
Step 5: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the
UPS.
Note: The battery charges fully during the first five hours of normal
operation. Do not expect full battery run capability during this initial
charge period.
Step 6: Install software
For optimal computer system protection, install UPS monitoring software to
fully configure UPS shutdown. You may insert provided CD into CD-ROM to
install the monitoring software. If not, please follow steps below to download
and install monitoring software from the internet:
-
Go to the website
http://www.powerwalker.com/index.php?lang=&page=viewpower -
Click ViewPower software icon and then choose your required OS to download the software.
-
Follow the on-screen instructions to install the software.
-
When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.
Tower Installation
The UPS can be also installed in vertical position. The LCD can be rotated by 90 degrees.
Operations
Button operation
Button | Function |
---|
ON/Mute Button
| Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.
Mute the alarm: When the UPS is on battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system. But it’s not applied to the situations when warnings or errors occur.
Up key: Press this button to display previous selection in UPS setting mode.
Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or converter mode.
OFF/Enter Button
| Turn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button.
Confirm selection key: Press this button to confirm selection in UPS setting mode.
Select Button
| Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, battery voltage, output voltage and output frequency. It will return back to default display when pausing for 10 seconds.
Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby mode or bypass mode.
Down key: Press this button to display next selection in UPS setting mode.
ON/Mute + Select Button
| Switch to bypass mode: When the main power is normal, press ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS will enter to
bypass mode. This action will be ineffective when the input voltage is out of acceptable range.
LCD Panel
Audible Alarm
Description | Buzzer status | Muted |
---|---|---|
Battery Mode | Sounding every 4 seconds | **** |
Yes
Low Battery| Sounding every second
Overload| Sounding twice every second
Fault| Continuously sounding
Bypass Mode| Sounding every 10 seconds
LCD display wordings index UPS Setting
There are three parameters to set up the UPS.
Parameter 1: It’s for program alternatives. Refer to below table.
Parameter 2 and parameter 3 are the setting options or values for each
program.
Output voltage setting
Interface | Setting |
---|
| Parameter 3: Output voltage
For 200/208/220/230/240 VAC models, you may choose the following output voltage:
200: presents output voltage is 200Vac 208: presents output voltage is 208Vac 220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
For 100/110/150/120/127 VAC models, you may choose the following output voltage:
100: presents output voltage is 100Vac
| 110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac (Default)
127: presents output voltage is 127Vac
---|---
Frequency Converter enable/disable
Interface | Setting |
---|---|
Parameter 2 & 3: Enable or disable converter mode. You may choose the |
following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable(Default)
Output frequency setting
Interface | Setting |
---|---|
**** | Parameter 2 & 3: Output frequency setting. You may set the initial |
frequency on battery mode: BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following output frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
ECO enable/disable
Interface | Setting |
---|---|
Parameter 3: Enable or disable ECO function. You may choose the |
following two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
ECO voltage range setting
Interface | Setting |
---|
| Parameter 2 & 3: Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from +7V to +24V of the nominal voltage. (Default: +12V)
For 100/110/115/120/127 VAC models, the setting range in parameter 3 is from +3V to +12V of the nominal voltage. (Default: +6V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from -7V to -24V of the nominal voltage. (Default: -12V)
For 100/110/115/120/127 VAC models, the setting voltage
in parameter 3 is from -3V to -12V of the nominal voltage. (Default: -6V) |
---|
Bypass enable/disable when UPS is off
Interface | Setting |
---|---|
Parameter 3: Enable or disable Bypass function. You may choose the |
following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
Bypass voltage range setting
Interface | Setting |
---|
| Parameter 2 & 3: Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from 230Vac to 264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
115-132: setting the high voltage point in parameter 3 from 115Vac to 132Vac(Default: 132Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from 170Vac to 220Vac. (Default: 170Vac)
For 100/110/115/120/127 VAC models:
95-110: setting the low voltage point in parameter 3 from 95Vac to 110Vac. (Default: 95Vac)
Autonomy limitation setting
Interface | Setting |
---|---|
**** | Parameter 3: Set up backup time on battery mode for general |
outlets.
0-999: setting the backup time in minutes from 0-999 for general outlets on battery mode.
0: When setting as “0”, the backup time will be only 10 seconds.
999: When setting as “999”, the backup time setting will be disabled. (Default)
00: Exit setting
Operating Mode Description
Faults Reference Code
Fault event | Fault code | Icon | Fault event | Fault code | Icon |
---|---|---|---|---|---|
Bus start fail | 01 | x | Inverter output short | 14 | **** |
Bus over | 02 | x | Battery voltage too high | 27 | **** |
Bus under | 03 | x | Battery voltage too low | 28 | **** |
Bus unbalance | 04 | x | Over Temperature | 41 | x |
Inverter soft start fails | 11 | x | Overload | 43 | **** |
Inverter voltage high | 12 | x | Charger failure | 45 | x |
Inverter voltage Low | 13 | x |
Warning indicator
Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom | Possible cause | Remedy |
---|---|---|
No indication and alarm even though the mains is normal. | The AC input power | |
is not connected well. | Check if input power cord firmly connected to the |
mains.
The AC input is connected to the UPS output.| Plug AC input power cord to AC
input correctly.
The icon flashing on LCD display and alarm is sounding every second.| The
external or internal battery is incorrectly connected.| Check if all batteries
are connected well.
Fault code is shown as 27 and the icon is lighting on LCD display and alarm is
continuously sounding.| Battery voltage is too high or the charger is fault.|
Contact your dealer.
Fault code is shown as 28 and the icon is lighting on LCD display and alarm
is continuously sounding.| Battery voltage is too low or the charger is
fault.| Contact your dealer.
The icon is flashing on LCD display and alarm is sounding twice every second.|
UPS is overload| Remove excess loads from UPS output.
UPS is overloaded. Devices connected to the UPS are
fed directly by the electrical network via the Bypass.
| Remove excess loads from UPS output.
After repetitive overloads, the UPS is locked in the Bypass mode. Connected
devices are fed directly by
the mains.
| Remove excess loads from UPS output first. Then shut down the UPS and
restart it.
Fault code is shown as 43 and The icon is lighting on LCD display and alarm is
continuously sounding.| The UPS shut down automatically because of overload at
the UPS output.| Remove excess loads from UPS output and restart it.
Fault code is shown as 14 and the icon is lighting on LCD display and alarm is
continuously sounding.| The UPS shut down automatically because short circuit
occurs on the UPS output.| Check output wiring and if connected devices are in
short circuit status.
Fault code is shown as 01, 02, 03, 04, 11, 12, 13 ,41 and 45 on LCD display
and alarm is continuously sounding.| A UPS internal fault has occurred. There
are two possible results:
1. The load is still supplied, but directly from AC power via bypass.
2. The load is no longer supplied by power.
| Contact your dealer
Symptom| Possible cause| Remedy
---|---|---
Battery backup time is shorter than nominal value| Batteries are not fully
charged| Charge the batteries for at least 5 hours and then check capacity. If
the problem still persists,
consult your dealer.
Batteries defect| Contact your dealer to replace the battery.
Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service
life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries
must be replaced. In this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a
cool, dry location. During storage, recharge the battery in accordance with
the following table:
Storage Temperature | Recharge Frequency | Charging Duration |
---|---|---|
-25°C – 40°C | Every 3 months | 1-2 hours |
40°C – 45°C | Every 2 months | 1-2 hours |
Specifications
MODEL
| PowerWalker
VFI 1000CRM LCD (L)
| PowerWalker
VFI 2000CRM LCD (L)
| PowerWalker
VFI 3000CRM LCD (L)
---|---|---|---
**CAPACITY*| 1000 VA / 800 W| 2000 VA / 1600 W| 3000 VA / 2400 W
INPUT**
Voltage Range
|
Low Line Transfer
| 85VAC/75VAC/65VAC/55VAC±5% or 160VAC/140VAC/120VAC/110VAC±5%
(Ambient Temp.<350C)
( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)
Low Line Comeback
| 95VAC/85VAC/75VAC/65VAC or 175VAC/155VAC/135VAC/125VAC ± 5 %
(Ambient Temp.<350C)
( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)
High Line Transfer| 145 VAC ± 5 % or 300 VAC ± 5 %
High Line Comeback| 140 VAC ± 5 % or 290 VAC ± 5 %
Frequency Range| 40Hz ~ 70 Hz
Phase| Single phase with ground
Power Factor| ≧ 0.99 @ nominal voltage (input voltage)
OUTPUT
Output voltage| 100/110/115/120/127VAC or 200/208/220/230/240VAC
AC Voltage Regulation| ±1% (Batt. Mode)
Frequency Range| 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range (Batt. Mode)| 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Overload
| Ambient Temp.<350C
105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal
110%~130%: UPS shuts down after 1minute at battery mode or transfer to bypass when the utility is normal
130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal
Current Crest Ratio| 3:1
Harmonic Distortion| ≦ 3 % THD (linear load); ≦ 6 % THD (non-linear load)
Transfer Time| AC Mode to Batt. Mode| Zero
Inverter to Bypass| 4 ms (Typical)
Waveform (Batt. Mode)| Pure Sinewave
EFFICIENCY
AC Mode| 88%| 89%| 90%
Battery Mode| 83%| 87%| 88%
BATTERY
Battery Type| 12 V / 9 AH| 12 V / 9 AH| 12 V / 9 AH
Numbers| 2| 4| 6
Recharge Time| 4 hours recover to 90% capacity (Typical)
Charging Current| 1.0 A (max.)
Charging Voltage| 27.4 VDC ± 1%| 54.7 VDC ±1%| 82.1 VDC ±1%
PHYSICAL
Dimension, D X W X H| 310 X 438 X 88 (mm)| 410 X 438 X 88 (mm)| 630 X 438 X 88
(mm)
Net Weight (kgs)| 12| 19| 29,3
ENVIRONMENT
Operation Humidity| 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level| Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232 or USB| Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux,
Unix and MAC
Optional SNMP| Power management from SNMP manager and web browser
The long-run model is only available in 200/208/220/230/240VAC systems.
Derate capacity to 80% of capacity in Frequency converter mode or when the
output voltage is adjusted to 100/200/208VAC.
Product specifications are subject to change without further notice
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>