LENNOX LD 024-074 Cold Weather Kit Instruction Manual
- June 4, 2024
- Lennox
Table of Contents
LENNOX LD 024-074 Cold Weather Kit
PACKAGED UNITS KITS AND ACCESSORIES
INSTALLATION INSTRUCTIONS FOR COLD WEATHER KIT USED ON LG/LD 024-074 GAS PACKAGED UNITS
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes. Line voltage is present at all components when the unit is not in operation on units with single‐pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
Installation
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
- Disconnect all power to unit and open compressor access panel.
- Install the heater and control assembly in the compressor compartment as shown in Figures 1 and 3. Secure with provided screws.
- Make harness and wire connections as shown in figure 2. Refer to figure 3 for component layout details.
- Route wires away from copper plumbing. Do not leave any wires on the base pan.
Shipping and Packing List
Package 1 of 1 contains:
- 1- Heater assembly
- 1- Control assembly
- 1- Wire harness
- 4- #10 Sheet metal screws
Application
The cold weather kit heats the compressor compartment to allow gas valve
operation during low outdoor temperatures. See table 1 for usage.
TABLE 1
Operation
When the ambient temperature drops below 20°F (-7°C), S61 closes. When the ambient temperature drops below -10°F (-23°C), S60 closes to energize K125 and bring on the HR6 heater. When the ambient temperature rises to 20°F (-7°C), S60 opens to de-energize the HR6 heater. When the ambient temperature drops below -20°F (-29°C), S59 opens to disable the GV1 gas valve. S59 closes to allow heating when the temperature rises to 10°F (-12°C).