iLOQ S10 ONLINE SYSTEM – PLANNING GUIDELINES

This document provides instructions, installation examples and connection diagrams for the iLOQ S10 Online system. The system consists of the iLOQ N100 Net Bridge and connected iLOQ bus devices. These instructions are for a single Net Bridge installation. The system can have several Net Bridges and the principles apply for every Net Bridge in the system.

BASIC PLANNING GUIDELINES
  •  iLOQ N100 Net Bridge works as a bus controller. It has one main bus. The bus can be divided into 6 branches. The branching must be done all the way up from the Net Bridge.
  • The maximum number of connected iLOQ bus devices depends on the chosen power supply, branch cable length and overall power consumption generated by iLOQ bus devices and cable losses.
  • Calculate overall bus power consumption by adding up the overall power consumptions from each branch:
    •  Check the (door) installation power consumption from Page 4 in order to get iLOQ bus device power consumption of a single installation.
    • Add up all power consumptions of the installations in a single branch in order to get cumulative iLOQ bus device power consumption.
    •  Check the overall branch specific power consumption including cable losses from Graph 1 on Page 2.
    •  Add up all the branch specific power consumptions and ensure that the overall power consumption does not exceed the available bus power, which depends on the chosen power supply (see Table 3).
  • It is possible to use double wiring for powering the bus to decrease cable losses, thus increasing the number of connected iLOQ bus devices (see Graph 2 on Page 3).
  • Place the Net Bridge as close to iLOQ bus devices as possible to minimize cable power losses. However, place the Net Bridge in a secure location such as a technical room.
  • Use the bus power for powering only iLOQ bus devices. DO NOT use bus power for powering any other devices, such as electric locks. However, the same DC power supply can be used for powering other external devices, such as electric locks, in addition to the Net Bridge. If this is the case, consider the number of wire pairs needed for other devices and branch the power all the way up from the DC power supply connectors, NOT from the Net Bridge connectors. Also ensure that the rated capacity of the power supply is sufficient to handle the additional load from external devices.
  •  If necessary, please contact your iLOQ representative for case-specific calculations and other cabling options.
  •  Do not use iLOQ system cables to transfer the bus data of other systems.
  •  Do not install iLOQ system cables in close proximity to high-interference sources like electric motors or fans.
iLOQ S10 ONLINE BUS SPECIFICATIONS

Table 1. Bus Layout (for a single iLOQ N100 Net Bridge)

Max. No. of Branches| Max. No. of Bus Devices| Max. Single Branch Length
6| 32| 300 m
Table 2. Cabling requirements

Cable Type| Min. for Single Wiring| Min. for Double Wiring
MHS / Cat 5 / Cat 6| 2 x 2 wires| 3 x 2 wires
Table 3. Max. Available Bus Power (depending on power supply)

PoE| PoE+| DC
10 W| 20 W| 30 W
Table 4. iLOQ Bus Device Power Consumption

iLOQ N102 Door Module| iLOQ N103

Key Reader / Hot Spot

| iLOQ N104 RFID Reader
1 W| 0.1 W| 1 W

iLOQ-S10-Online-System-1 iLOQ-S10-Online-
System-2 iLOQ-S10-Online-System-3 iLOQ-S10-Online-
System-4 iLOQ-S10-Online-System-5

NOTES

  •  iLOQ S10 Online lock cylinders
  •  If the lock cylinders are installed on nearby separate doors, both doors must have the same ground potential

iLOQ-S10-Online-System-6

NOTES

  •  iLOQ S10 Online lock cylinder
  • iLOQ N103 used as a combined key reader and a hot spot for controlling the electric lock
  • Consider the number of wires needed for other door equipment (e.g. door opener push button and electric lock powering) and add them to the door cable wiring
  •  The powering of the electric lock must be arranged separately. Do not use iLOQ bus power for powering the electric lock.

iLOQ-S10-Online-System-7

NOTES

  •  iLOQ S10 Online lock cylinder
  •  iLOQ N104 RFID Reader used for controlling the electric lock
  •  Consider the number of wires needed for other door equipment (e.g. door opener push button and electric lock powering) and add them to the door cable wiring
  • The powering of the electric lock must be arranged separately. Do not use iLOQ bus power for powering the electric lock.

iLOQ-S10-Online-System-8

NOTES

  •  iLOQ S10 Online lock cylinder
  • iLOQ N103 used as a key reader for controlling the electric lock
  •  Consider the number of wires needed for other door equipment (e.g. door opener push button and electric lock powering) and add them to the door cable wiring
  • The powering of the electric lock must be arranged separately. Do not use iLOQ bus power for powering the electric lock.

iLOQ-S10-Online-System-9

NOTES

  • It is strongly prohibited to use the main bus power (DC-, DC+) for any other purpose than what is described in this document (e.g. powering an electric lock is forbidden).

iLOQ-S10-Online-System-10

NOTES

  • It is strongly prohibited to use the main bus power (DC-, DC+) for any other purpose than what is described in this document (e.g. powering an electric lock is forbidden).

iLOQ-S10-Online-System-11