niko 353-600121 Presence Detector Instruction Manual

June 4, 2024
niko

Manual
Presence detector
353-600121

Presence detector P42MR, 230 V, master, 12-13 m, 360°, for flush-mounting box

Wiring

  230 V – OFF

  • remove if you want to use the contact as a dry contact (potential-free)

Dimensions

Installation

  230 V – OFF

App settings

  230 V – ON

LED behaviour

  230 V – ON

Green LED continuous on| | Connection OK|
---|---|---|---
Green LED breathing| | Connection OK, overrule ON|
Green LED flashing| | Warming up| Wait
Red LED continuous on| | Error|

More info –>

Red LED breathing| | Warning
Blue LED flashing| | Walk test active

Specifications

Article number  353-600121
Configuration 230 V Master
Input voltage 230 Vac ± 10 %, 50 Hz
Maximum power consumption 0.2 W
Relay contact NO (max. µ10 A), potential-free
Maximum load incandescent and halogen lamps (cosφ 2300 W
Maximum load fluorescent lamps (cosφ ≥ 0.5) 1200 VA
Maximum load economy lamps (CFLi) 350 W
Maximum load LED lamps 230 V 350 W
Maximum load LED driver 500 VA
Maximum load electronic transformer 500 VA
Maximum capacitive load 140 µF
Maximum switching current 165 A/20 ms or 800 A/200 µs
Light intensity range 20 – 2000 lux, ∞
Number of channels 1 channel
Maximum number of secondary detectors 10
Switch-off delay pulse, 15 s – 120 min, ∞
Hysteresis on light intensity 10%
Detection angle 360°
Detection range (PIR) Ø 12 m from a height of 3 m
Ambient temperature -25 – +40 °C
Mounting method flush-mounting box
Mounting height 2 – 3.5 m
Colour white (RAL 9010)
Dimensions visible (HxWxD) 100 x 100 x 9.5 mm
Dimensions (HxWxD) 100 x 100 x 44.5 mm
Wire capacity 1.5/2.5 mm²
Maximum range Bluetooth ® (free field, depending on the device) 50 m
Operating frequency 2.4 GHz
Maximum radio frequency power  -2 dBm
Protection degree IP20
Impact resistance IK02
Modification of settings app (iOS/Android) and 2-way Bluetooth® communication
Halogen-free yes
Marking CE

Detection area

Troubleshooting

Problem Possible cause Proposed solution
Load does not turn on The wiring is not correct Check the wiring scheme
The ambient light is too strong Check the response value luminosity and raise

the value if necessary
Load does not turn off| The switch-off delay is too long| Check the switch-off delay and shorten the delay if necessary
The detector receives false triggers| Check for any objects that may cause false triggering and remove them from the detection range or lower the sensitivity
App cannot connect to the detector| Bluetooth ®  has been disabled on your mobile device| Enable Bluetooth ®  on your mobile device

Support & contact

NV Niko sa Industriepark West 40 9100 Sint-Niklaas, Belgium
www.niko.eu

+32 3 778 90 80
support@niko.eu

Niko prepares its manuals with the greatest care and strives to make them as complete, correct and up to date as possible. Nevertheless, some deficiencies may subsist. Niko cannot be held responsible for this, other than within the legal limits. Please inform us of any deficiencies in the manuals by contacting Niko customer services at support@niko.eu.

PM353-600121R22203

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals