ASCO Stainless Steel Redundant Control System Installation Guide
- June 3, 2024
- ASCO
Table of Contents
- Introduction
- RCS Device Description
- Designing a Safety Instrumented Function using an ASCO RCS
- Installation and Commissioning
- RCS Block Diagram
- RCS Operation and Truth Tables
- RCS Maintenance
- Status of the document
- Appendix A – SIS Checklist
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Redundant Control System
I&M V_9535_DA
Safety Manual for Safety Integrated Systems
Introduction
This Safety Manual provides information necessary to design, install, verify and maintain a Safety Instrumented Function (SIF) utilizing an ASCO Redundant Control System, RCS. This manual provides necessary requirements for meeting the IEC 61508 or IEC 61511 functional safety standards.
1.1 Terms and Abbreviations
- Safety – Freedom from unacceptable risk of harm
- Functional Safety – The ability of a system to carry out the actions necessary to achieve or to maintain a defined safe state for the equipment / machinery / plant / apparatus under control of the system
- Basic Safety – The equipment must be designed and manufactured such that it protects against risk of damage to persons by electrical shock and other hazards and against resulting fire and explosion. The protection must be effective under all conditions of the nominal operation and under single fault condition
- Safety Assessment – The investigation to arrive at a judgment – based on evidence – of the safety achieved by safety-related systems
- Fail-Safe State – State where the solenoid valve is de-energized and spring is extended.
- Fail Safe Failure – Failure which causes the valve to go to the defined fail-safe state without a demand from the process.
- Fail Dangerous Failure – Failure that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state).
- Fail Dangerous Undetected – Failure that is dangerous and that is not being diagnosed by automatic stroke testing.
- Fail Dangerous Detected – Failure that is dangerous but is detected by automatic stroke testing.
- Fail Annunciation Undetected – Failure that does not cause a false trip or prevent the safety function but does cause loss of an automatic diagnostic and is not detected by another diagnostic.
- Fail Annunciation Detected – Failure that does not cause a false trip or prevent the safety function but does cause loss of an automatic diagnostic or false diagnostic indication.
- Fail No Effect – Failure of a component that is part of the safety function but has no effect on the safety function.
- Low demand Mode – Mode where the frequency of demands for operation made on a safety- related system is no greater than twice the proof test frequency.
1.2 Acronyms
- FMEDA – Failure Modes, Effects and Diagnostic Analysis
- HFT – Hardware Fault Tolerance
- MOC – Management of Change. These are specific procedures often done when performing any work activities in compliance with government regulatory authorities.
- MTTFS – Mean Time To Fail Spurious
- PFDavg – Average Probability of Failure on Demand
- SFF – Safe Failure Fraction, the fraction of the overall failure rate of a device that results in either a safe fault or a diagnosed unsafe fault.
- SIF – Safety Instrumented Function, a set of equipment intended to reduce the risk due to a specific hazard (a safety loop).
- SIL – Safety Integrity Level, discrete level (one out of a possible four) for specifying the safety integrity requirements of the safety functions to be allocated to the E/E/PE safety-related systems where Safety Integrity Level 4 has the highest level of safety integrity and Safety Integrity Level 1 has the lowest.
- SIS – Safety Instrumented System – Implementation of one or more Safety Instrumented Functions. An SIS is composed of any combination of sensor(s), logic solver(s), and final element(s).
1.3 Product Support
Product support can be obtained from:
ASCO Customer Support / Technical Support.
160 Park Ave.
Florham Park NJ 07932, USA
support@ascovalve.com
Tel. 800-524-1023 or
973-966-2000
Fax. 973-966-2628
1.4 Related Literature
- Hardware Documents: ASCO RCS Operation Guide # V9512, V9709, V9957, V9958, and V9959.
- Guidelines/References: Safety Integrity Level Selection – Systematic Methods Including Layer of Protection Analysis, ISBN 1-55617-777-1, ISA
- Control System Safety Evaluation and Reliability, 2nd Edition, ISBN 1-55617-638-8, ISA
- Safety Instrumented Systems Verification, Practical Probabilistic Calculations, ISBN 1-55617-909-9, ISA
1.5 Reference Standards
- Functional Safety
- IEC 61508: 2000 Functional safety of electrical/electronic/ programmable electronic safety-related systems
- ANSI/ISA 84.00.01-2004 (IEC 61511 Mod.) Functional Safety – Safety Instrumented Systems for the Process Industry Sector
RCS Device Description
The RCS is an electro-mechanical and pneumatic system consisting of a set of
two (2) or three (3) solenoid operated valves and possibly one (1)
pneumatically operated valve. The valves are interconnected to allow different
architectures for the control of pneumatically actuated block valves. It
provides diagnostic components to verify the state of the devices as well as
enabling online testing of the devices. These components are pressure or
proximity switches monitoring the pneumatic pressures at critical points of
the RCS assembly. In addition to the switches, an Automated Diagnostic Test,
ADT, can be implemented in a safety rated logic solver (not included). The ADT
provides the diagnostics necessary to achieve the safety ratings of the RCS.
Alternatively, the Diagnostic Test can be initiated manually. Manually
initiated tests are very effective. However, these tests cannot be considered
automatic diagnostics in the sense of IEC 61508/IEC 61511.
Depending on the protected process, the safety action of the block valve can
either be spring return open or spring return close. The spring forced block
valve actuator will receive air supply to move the block valve to the safe
state (NO) or the spring forced block valve actuator will be vented to move
the block valve to the safe state (NC). The
piston type actuator will receive air to one side and be vented on the
opposite side to move the block valve to the safe state (DA). To account for
these three action types, three different RCS versions are available for
safety applications:
- Normally Closed (NC)
- Normally Open (NO)
- Double Acting (DA)
The NC version is used to vent air from a spring-forced actuator if the
solenoids are de-energized, the NO version is used to supply air to a spring-
forced actuator if the solenoids are de-energized. Both versions differ only
in the air duct routing within the manifold that connects the valves and the
external ports.
The selection of the version has direct impact on the probability of failure
on demand of the entire safety instrumented function since the loss of
instrument air for a NO RCS will inhibit the safety action of the block valve
and decrease safety integrity.
The selection of the NO/NC version is based on the spring forced state of the
controlled actuator. Most safety applications will require that the vented
state (spring forced position) of the block valve actuator be the safe state;
however, exceptions may require the pressurized state (not spring forced
position) of the block valve actuator be the safe state. In this case,
additional requirements to ensure the integrity and availability of all energy
sources will be called for.
The Double Acting version is used with a piston type block actuator. The
“safe” state of the process valve must be determined. The Double Acting RCS
will control air to the side of the process valve actuating cylinder that will
drive the process valve to the “safe” state and vent the opposite side of the
process valve actuating cylinder in the same operation.
The RCS is available in a 1oo1 simplex, 1oo1 Hot Standby (HS), 2oo2 Normally
Open (NO) & Normally Closed (NC), 2oo2 Double Acting (DA) and 2oo3 Normally
Closed (NC) configuration. This manual covers the use of the RCS in all modes.
In this safety manual, the signals to the RCS are defined in de-energized-to-
safe configuration. In the case of a 2oo2 configuration, at least one of the
two solenoid operated valves in the RCS has to be energized to prevent the
block valve from moving to the safe state. In a 2oo3 configuration at least
two (2) solenoid operated valves in the RCS must be energized to prevent the
valve from moving to the safe state.
The switches have both normally open and normally closed contacts to provide
indication of valve state. Truth Tables contained in this manual provide
status of the normally open contacts during various states.
Designing a Safety Instrumented Function using an ASCO RCS
3.1 Safety Function
When de-energized, the ASCO RCS moves to its fail-safe position. Depending on
the version specified, Normally Closed (NC) or Normally Open (NO), the RCS
will supply air or vent air depending on the piping of the installation. The
Double Acting RCS, when de-energized, will supply air to one side of the
cylinder and vent the opposite side of the cylinder at the same time.
As defined in IEC 61508, the RCS is intended to be a part of the final element
subsystem and the achieved SIL level of the designed function must be verified
by the designer.
3.2 Environmental limits
The designer of a SIF must check that the product is rated for use within the
expected environmental limits.
Temperature: The RCS shall be mounted such that the internal temperature
within the enclosure does not exceed the specified temperature limits shown in
the unit’s I&M.
3.3 Application limits
The application limits of an ASCO RCS are specified in the user manual, I&M:
- I&M V9512: 1oo1 and 2oo2 Aluminum with Pressure Switches
- I&M V9709: 1oo1 and 2oo2 Stainless steel with Pressure Switches.
- I&M V9957: 2oo2 Aluminum with Proximity Switches
- I&M V9958: 2oo3 Aluminum without diagnostics.
- I&M V9959: 2oo3 Aluminum with Proximity Switches
It is especially important that the designer checks for material compatibility considering on-site chemical contaminants and air supply conditions. If the RCS is used outside of the application limits or with incompatible materials, the reliability data provided becomes invalid.
3.4 Design Verification
A detailed Failure Mode, Effects, and Diagnostics Analysis (FMEDA) report is
available from ASCO Valves, Inc. Refer to the appropriate FMEDA report for all
failure rates and the expected useful lifetime.
- 1oo1 Simplex, 1oo1 Hot Standby, 2oo2 with Pressure Switches (ASC 08-12-44)
- 1oo1 Simplex, 1oo1 Hot Standby, 2oo2 with Proximity Switches (ASC 15-04-065)
- 1oo1 Simplex, 1oo1 Hot Standby, 2oo2 with Stainless Steel construction (ASC 14-09-018)
- 2oo2, 2oo3 redundant with Pressure or Proximity switches (ASC 20-02-115)
The achieved Safety Integrity Level (SIL) of an entire Safety Instrumented
Function (SIF) design must be verified by the designer via a calculation of
PFDavg considering redundant architectures, proof test interval, proof test
effectiveness, any automatic diagnostics, average repair time and the specific
failure rates of all products included in the SIF. Each subsystem must be
checked to assure compliance with minimum hardware fault tolerance (HFT)
requirements. The Exida exSILentia® tool is recommended for this purpose as it
contains accurate models for the RCS and its failure rates.
When using an ASCO RCS in a redundant configuration, a common cause factor of
5% should be included in safety integrity calculations.
The failure rate data listed in the FMEDA report is only valid for the useful
lifetime of an ASCO Solenoid. The failure rates will increase sometime after
this time period. Reliability calculations based on the data listed in the
FMEDA report for mission times beyond the lifetime may yield results that are
too optimistic, i.e. the calculated Safety Integrity Level will not be
achieved.
3.5 SIL Capability
3.5.1 Systematic Integrity
This product has met manufacturer design process requirements for Safety
Integrity Level (SIL) 3. These are intended to achieve sufficient integrity
against systematic errors of design by the manufacturer. A Safety Instrumented
Function (SIF) designed with this product must not be used at a SIL level
higher than the statement without “prior use” justification by end user or
diverse technology redundancy in the design.
3.5.2 Random Integrity
The RCS is a Type A Device.
The failure rate data used for the FMEDA meets the exida criteria for Route 2H
(See FMEDA report Section 5.1). Therefore, the Redundant Control System can be
classified as a 2H device when the listed failure rates are used. When 2H data
is used for all of the devices in an element, then the element meets the
hardware architectural constraints up to SIL 2 at HFT=0 (or SIL 3 @ HFT=1) per
Route 2H. If Route 2H is not applicable for the entire final element, the
architectural constraints will need to be evaluated per Route 1H.
When the final element assembly consists of many components (RCS, quick
exhaust valve, actuator, isolation valve, etc.) the SIL must be verified for
the entire assembly using failure rates from all components. This analysis
must account for any hardware fault tolerance and architecture constraints.
3.5.3 Safety Parameters
For detailed failure rate information refer to the Failure Modes, Effects and
Diagnostic Analysis Report for the RCS.
3.6 Connection of the RCS to the SIS Logic-solver
The RCS is connected to the safety rated logic solver which is actively
performing the safety function as well as automatic diagnostics designed to
diagnose potentially dangerous failures within the RCS. The isolating valves
solenoid control power shall be supplied by the safety rated logic solver via
the safety function output. Connections must be made according to the
instructions supplied by the safety rated logic solver. The output rating of
the I/O module shall meet or exceed the electrical specifications of the valve
solenoid:
Table 1 – Solenoid Specifications
Table 1.1 – Solenoid Voltage DC) Specifications, Direct Cur ent oil Resistance @20-C. +-10%(Ohms)
Wattage| Voltage (DC)| Mn. Pull In (mA)| Drop Out (mA)| Coil Resistance @
20°C, +-10%
(Ohms)
1.4W| 12| 64| 14.| 102
24| 42| 7.0| 410
48| 21| 4.| 1640
120| 9| 2.| 10.000
Table 1.2 – Solenoid Specifications, Alternating Current
Wattage| Voltage (AC)| VA Holding| VA Inrush| Coil Resistance @ 20°C, +-10%
(Ohms)
---|---|---|---|---
10.1W| 120/60-110/50
230/50-240/50| 25| 50| 85
450
If the safety rated logic solver output module provides line-integrity testing
by pulse tests or other means, the impedance range applicable for this test
shall be within the RCS solenoid impedance.
If connected to a passive input module (a module that provides only the
switching but not the switching energy), the external power supply shall meet
all pertinent electrical safety requirements specified by the safety rated
logic solver (i.e. IEC 61010).
The input rating of the I/O module shall meet the electrical specifications of
the switches:
| Pressure Switch| Proximity Switch
---|---|---
Construction| Gold Contacts| Silver Contacts| Palladium
Silver| Palladium Silver
ElectricalRating| DC| 1AResistive@28VDC
0.5AInductive@28VDC| 5AResistive@28VDC
3AInductive@28VDC
0.5AResistive@125VDC| 3AResistive@24VDC
AC| 1A @125VAC| 5A @ 125VAC or 250VAC| 4A @120VAC
2A @240VAC
Table 2- Switch Specifications
NOTE: IEC 61508 requires de-rating, and the actual switch loads need to
be less than the listed specifications
If the safety rated logic solver input module requires line-end devices for
open wire / short circuit wire protection, these devices shall be mounted at
the terminal block of the RCS according to the logic-solver manufacturer’s
instructions
If the logic-solver input module provides line-integrity testing by pulse
tests or other means the impedance range applicable for this test shall be
within the RCS pressure switch impedance.
3.7General Requirements
- The system’s response time shall be less than process safety time. The RCS will switch between two states in less than 500 ms.
- All SIS components including the RCS must be operational before process start-up.
- The ADT shall be run at least once per month or ten times within the expected hazard demand interval, whichever comes first. The ADT may be run as often as desired and is recommended every 24 hours.
- The user shall verify that the RCS is suitable for use in safety applications by confirming that the RCS nameplate is properly marked.
- The programming used to implement the ADT shall not be modified without the accomplishment of an impact analysis by a competent safety engineer.
- Personnel performing maintenance and testing on the RCS shall be competent to do so.
- Results from the ADT manually initiated tests, and proof tests shall be recorded and reviewed periodically.
- The useful life of the RCS is discussed in the Failure Modes, Effects and Diagnostic Analysis Report for the RCS.
Installation and Commissioning
4.1 Installation
- The ASCO Solenoid valve must be installed per standard installation practices outlined in the Installation Manual.
- The environment must be checked to verify that environmental conditions do not exceed the ratings.
- The ASCO Solenoid must be accessible for physical inspection.
4.2 Physical Location and Placement
- The RCS shall be accessible with sufficient room for cabling and pneumatic connections and shall allow manual proof testing of the bypass function.
- Pneumatic piping to the block valve shall be kept as short and straight as possible to minimize the airflow restrictions and potential clogging of the exhaust line. Long or kinked pneumatic tubes may also increase the block valve closure time.
- The Breather/Vent valve shall be accessible and should be inspected for obstruction during manual proof testing.
- The RCS shall be mounted in a low vibration environment. If excessive vibration is expected, special precautions shall be taken to ensure the integrity of electrical and pneumatic connectors or the vibration should be reduced using appropriate damping mounts.
4.3 Electrical Connections
- The device requires external electrical connections. The energy for actuating the isolating valves is provided by the control signal lines. The RCS device is available in the following control signal configurations: 12 VDC, 24 VDC, 48VDC, 120 VDC, 120/60-110/50 VAC or 230/50-240/50 VAC.
- All wirings shall provide sufficient electrical isolation between adjacent signal lines and between signal lines and ground.
- Stranded 16 to 18 AWG (or equivalent gauge and flexibility) shall be used.
- It is recommended that conduit sealant be used to prevent condensation from entering the enclosure and, in Class 1 Div. 2 conditions will prevent hazardous gasses and vapors from migrating through the conduit to the control room or open ignition source.
- Wiring shall be according to the National Electrical Code (ANSI-NFPA 70) or other applicable local codes.
- The terminal clamps are designed for one wire only; DO NOT attempt to terminate multiple wires into one terminal.
- Strip the wires to the recommended length appropriate for the termination block.
- Ensure all wire strands are fully inserted into the terminal block and no shorts between adjacent wires on the terminal block are possible.
- Use care when running signal wiring near to, or crossing conduit or wiring that supplies power to motors, solenoids, lighting, horns, bells, etc. Sufficient electrical isolation and shielding against electromagnetic interference from items in the vicinity of the cable run shall be provided.
- AC power wiring should be run in a separate conduit from DC power. All power wiring to and from the RCS should be in a grounded conduit. Outdoor cable runs shall be protected against lightning strike.
- The RCS shall be connected to a high-quality instrument grade ground with #14 AWG or heavier wire. A grounding stud is provided on the inside and outside of the enclosure.
4.4 Pneumatic Connections
-
Recommended piping for the inlet and outlet pneumatic connections to the RCS is 1/2” stainless
steel or PVC tubing. The length of tubing between the RCS and the block valve shall be kept as shoras possible and free of kinks. -
Only dry instrument air filtered to 40-micron level or better shall be used.
-
The Process air pressure shall be:
o For 1oo1 and 2oo2 with Pressure Switches: 21 kPa – 1034 kPa (3 psi – 150 psi).
o For 1oo1, 2oo2 and 2oo3 with Proximity Switches: 0 kPa – 1034 kPa (0 psi – 150 psi) -
The Pilot air pressure should be 275 kPa – 1034 kPa (40 psi -150 psi).
-
The rocess air capacity shall be sufficient to move the pneumatically actuated bypass valve withinthe required time.
-
The RCS has a Cv of greater than 2.0.
RCS Block Diagram
5.11oo1HS, 2oo2 Normally Closed with Pressure Switches
Figure 1 shows the simplified block diagram of the 1oo1HS and 2oo2 devices in
Normally Closed configuration with Pressure switches. SOV1 and SOV2 are
solenoid operated valves; B/P 3 is a key-lock or lever controlled
pneumatically actuated valve, and PS1, PS2 and PS3 are pressure switches. The
bypass valve is used to apply
pneumatic supply directly through the bypass valve to the block valve actuator
forcing it to remain in the normal condition (not safe state, maintenance
override), while isolating and venting solenoid-operated valves 1 and 2 and
all three pressure switches.
SOV 1 AND SOV 2 IN DE-ENERGIZED STATE
B/P 3 BYPASS VALVE IN NORMAL STATE
PS 1, PS 2 AND PS 3 PRESSURE SWITCHES
NORMALLY OPEN CONTACTS IN CLOSED STATE
Figure 1 – RCS 1oo1HS, 2oo2 Normally Closed Configuration (Safe State) with
Pressure Switches
The airflow in Figure 1 is depicted in the safe state of the RCS. In this
state, both solenoids are de-energized resulting in the venting of air from
the block valve actuator, allowing the spring return actuator to move the
block valve to the safe state.
5.21oo1HS, 2oo2 Normally Open with Pressure Switches
Figure 2 shows the simplified block diagram of the 1oo1HS and 2oo2 devices in
Normally Open configuration with Pressure switches. SOV1 and SOV2 are solenoid
operated valves; B/P 3 is a key-lock or lever controlled pneumatically
actuated valve, and PS1, PS2 and PS3 are pressure switches. Both SOV1 and SOV2
must remain de-energized to allow the block valve to remain in the safe state
position. The bypass valve can be used to block the pneumatic supply directly
forcing it to be vented while isolating solenoid-operated valves 1 and 2 and
all three pressure switches.
SOV 1 AND SOV 2 IN DE-ENERGIZED STATE
B/P 3 BYPASS VALVE IN NORMAL STATE
PS 1, PS 2 PRESSURE SWITCHES NORMALLY OPEN CONTACTS IN OPEN STATE
PS 3 PRESSURE SWITCH NORMALLY OPEN CONTACT IN CLOSED STATE
Figure 2 – RCS 1oo1HS, 2oo2 Normally Open Configuration (Safe State) with
Pressure Switches
In Figure 2, The airflow is depicted in the safe state of the RCS. In this
state, both solenoids are de-energized resulting in the supply of air to the
block valve actuator, overcoming the spring return in the actuator to move the
block valve to the safe state.
5.31oo1HS, 2oo2 Normally Closed with Proximity Switches
Figure 3 shows the simplified block diagram of the 1oo1HS and 2oo2 devices in
Normally Closed configuration with proximity switches. SOV1 and SOV2 are
solenoid perated valves; B/P 3 is a key-lock or lever controlled
pneumatically actuated valve, and PS1, PS2 and PS3 are proximity switches. The
bypass valve is used to apply pneumatic supply directly through the bypass
valve to the block valve actuator forcing it to remain in the normal condition
(not safe state, maintenance override), while isolating and venting solenoid-
operated valves 1 and 2, changing the state of the proximity switches.
SOV 1 AND SOV 2 IN DE-ENERGIZED STATE
B/P 3 BYPASS VALVE IN NORMAL STATE
PS 1, PS 2 AND PS 3 PROXIMITY SWITCHES
NORMALLY OPEN CONTACTS IN CLOSED STATE
Figure 3 – RCS 1oo1HS, 2oo2 Normally Closed Configuration (Safe State) with
Proximity Switches
The airflow in Figure 3 is depicted in the safe state of the RCS. In this
state, both solenoids are de-energized resulting in the venting of air from
the block valve actuator, allowing the spring return actuator to move the
block valve to the safe state.
5.41oo1HS, 2oo2 Normally Open with Proximity Switches
Figure 4 shows the simplified block diagram of the 1oo1HS and 2oo2 devices in
Normally Open configuration with Proximity switches. SOV1 and SOV2 are
solenoid operated valves; B/P 3 is a key-lock or lever controlled
pneumatically actuated valve, and PS1, PS2 and PS3 are proximity switches.
Both SOV1 and SOV2 must remain de-energized to allow the block valve to remain
in the safe state position. The bypass valve can be used to block the
pneumatic supply directly forcing it to be vented while isolating solenoid-
operated valves 1 and 2 and all three proximity switches.
SOV 1 AND SOV 2 IN DE-ENERGIZED STATE
B/P 3 BYPASS VALVE IN NORMAL STATE
PS 1, PS 2 & PS 3 PROXIMITY SWITCH NORMALLY OPEN CONTACTS IN CLOSED STATE
Figure 4 – RCS 1oo1HS, 2oo2 Normally Open Configuration (Safe State) with
Proximity Switches
In Figure 4, The airflow is depicted in the safe state of the RCS. In this
state, both solenoids are de-energized resulting in the supply of air to the
block valve actuator, overcoming the spring return in the actuator to move the
block valve to the safe state
5.5 2oo2 Double Acting with Pressure Switches
Depending on the protected process, the safety action of the 2oo2 Double
Acting will direct the air supply to either side of the block actuator. Figure
6 shows the simplified block diagram of the device in the safe mode in the De-
energized to Trip (DTT) configuration and using proximity switched for
diagnostics.
SOV 1 AND SOV 2 IN DE-ENERGIZED STATE FC;
B/P 3 BYPASS VALVE IN NORMAL STATE
PS 1 PRESSURE SWITCH NORMALLY OPEN CONTACT IN OPEN STATE
PS 2 AND PS 3 PRESSURE SWITCHES NORMALLY OPEN CONTACTS IN CLOSED STATE
C1 TO INLET PRESSURE, C2 TO EXHAUST
Figure 5 – RCS 2oo2 Double Acting Configuration (Safe State) with Pressure
Switches
5.6 2oo2 Double Acting with Proximity Switches
Depen ding on the protected process, the safety action of the 2oo2 Double
Acting will direct the air supply to either side of the block actuator. Figure
6 shows the simplified block diagram of the device in the safe mode in the De-
energized to Trip (DTT) configuration and using proximity switched for
diagnostics.
SOV 1 AND SOV 2 IN DE-ENERGIZED STATE FC;
B/P 3 BYPASS VALVE IN NORMAL STATE
PS 1 PRESSURE SWITCH NORMALLY OPEN CONTACT IN OPEN STATE
PS 2 AND PS 3 PRESSURE SWITCHES NORMALLY OPEN CONTACTS IN CLOSED STATE
C1 TO INLET PRESSURE, C2 TO EXHAUST
Figure 5 – RCS 2oo2 Double Acting Configuration (Safe State) with Pressure
Switches
5.6 2oo2 Double Acting with Proximity Switches
Depending on the protected process, the safety action of the 2oo2 Double
Acting will direct the air supply to either side of the block actuator. Figure
6 shows the simplified block diagram of the device in the safe mode in the De-
energized to Trip (DTT) configuration and using proximity switched for
diagnostics.
SOV 1 AND SOV 2 IN DE-ENERGIZED STATE FC;
B/P 3 BYPASS VALVE IN NORMAL STATE
PS 1 PRESSURE SWITCH NORMALLY OPEN CONTACT IN OPEN STATE
PS 2 AND PS 3 PRESSURE SWITCHES NORMALLY OPEN CONTACTS IN CLOSED STATE
C1 TO INLET PRESSURE, C2 TO EXHAUST
Figure 6 – RCS 2oo2 with Proximity Switches, Double Acting Configuration (Safe
State)
5.7 2oo3 Normally Closed without Diagnostics
Figure 7 shows the simplified block diagram of the 2oo3 in Normally Closed
without diagnostics. SOV1, SOV2 and SOV3 are solenoid operated valves. This
version does not present a bypass valve to isolate and vent the solenoid-
operated valves 1, 2 and 3.
The airflow in Figure 7 is depicted in the safe state of the RCS. In this
state, the three (3) solenoids are deenergized resulting in the venting of air
from the block valve actuator, allowing the spring return actuator to move the
block valve to the safe state.
Figure 7 – RCS 2oo3 Normally Closed Configuration (Safe State) without
Diagnostics In this configuration, it is required to have at two (2) solenoids
energized to provide pneumatic supply and allow the pressure to overcome the
spring return actuator to move the block valve to the normal or degraded state
(not safe state).
5.82oo3 Normally Closed with Proximity Switches
Figure 8 shows the simplified block diagram of the 2oo3 in Normally Closed
with proximity switches. SOV1, SOV2 and SOV3 are solenoid operated valves; B/P
4 is a key-lock or lever controlled pneumatically actuated valve; and PS1, PS2
PS3 and PS4 are proximity switches. The bypass valve is used to apply
pneumatic supply directly through the bypass valve to the block valve actuator
forcing it to remain in the normal condition (not safe state, maintenance
override), while isolating and venting solenoid-operated valves 1, 2 and 3,
changing the state of the proximity switches. The airflow in Figure 8 is
depicted in the safe state of the RCS. In this state, the three (3) solenoids
are deenergized resulting in the venting of air from the block valve actuator,
allowing the spring return actuator to move the block valve to the safe state.
SOV 1, SOV 2 AND SOV 3 IN DE-ENERGIZED STATE
B/P 4 BYPASS VALVE IN NORMAL STATE
PS 1, PS 2, PS 3 AND PS 4 PROXIMITY SWITCHES
NORMALLY OPEN CONTACTS IN CLOSED STATE
Figure 8 – RCS 2oo3 with Proximity Switches, Normally Closed Configuration
(Safe State)
RCS Operation and Truth Tables
In the truth tables for all possible device states it can be noticed the following color code:
- Highlighted in light gray is the state when the RCS unit is in a legal mode (safe state) other than the standard running conditions.
- Dark gray indicates an illegal state.
6.11oo1HS Normally Closed
Figures 1 and 3 illustrates the pneumatic pathways for this configuration at
the safe state condition (safety action). In this condition, the RCS is
blocking the inlet air supply and venting the block valve actuator (normally
closed operation). This configuration is most commonly used in safety
applications since a loss of electrical or pneumatic energy will result in the
safe state of the block valve.
In the 1oo1HS, Normally Closed Mode, only one solenoid is on-line during
normal operation. A spurious failure of the online solenoid is indicated by
the pressure or proximity switch state associated with the on-line solenoid.
The response to the detected failure is to energize the second solenoid to
maintain air supply to the block valve, reducing the potential for spurious
trips.
The truth table for the 1oo1HS Normally Closed with Pressure Switches is
presented in Table 3.
State|
State Type
| Valve Position|
Valve Pressure Switch Normally Open
| Process/Outlet
---|---|---|---|---
SOV1| SOV2| Bypass Valve| PS 1| PS 2| PS 3
1| Degraded| Energized| Energized| Normal| Open (False)| PS2Open(False)|
Closed (True)| Air Supply
2| Safe| De-Energized| De-Energized| Normal| Closed (True)| Closed (True)|
Closed (True)| Vented
3| Normal| Ce-Energized| Energized|
Normal
| Closed (True)| Open (False)| Closed (True)| Air Supply
4| Normal| Energized| Ce-Energized|
Normal
| Open (False)| Closed (True)| Closed (True)| Air Supply
5| Maintenance
Bypass| De-Energized| De-Energized| Actuated| Open (False)| Open (False)|
Open(False)| Air Supply
6| Illegal| Energized| Energized| Actuated| Open (False)| Open (False)| Open
(False)| Air Supply
7| Illegal| De-Energized| Energized| Actuated| Open (False)| Open (False)|
Open (False)| Air Supply
8| Illegal| Energized| Ce-Energized| Actuated| Open (False)| Open (False)|
Open (False)| Air Supply
The truth table for the 1oo1HS Normally Closed with Proximity Switches is presented in Table 4.
State|
State Type
| Valve Position|
Valve Pressure Switch Normally Open
| Process/Outlet
---|---|---|---|---
SOV1| SOV2| Bypass Valve| PS 1| PS 2| PS 3
1| Degraded| Energized| Energized| Normal| Open (False)| PS2Open(False)|
Closed (True)| Air Supply
2| Safe| De-Energized| De-Energized| Normal| Closed (True)| Closed (True)|
Closed (True)| Vented
3| Normal| Ce-Energized| Energized| Normal| Closed (True)| Open (False)|
Closed (True)| Air Supply
4| Normal| Energized| Ce-Energized| Normal| Open (False)| Closed (True)|
Closed (True)| Air Supply
5| Maintenance
Bypass| De-Energized| De-Energized| Actuated| Closed(True)| Closed(True)|
Open(False)| Air Supply
6| Illegal| Energized| Energized| Actuated| Closed(True)| Closed(True)| Open
(False)| Air Supply
7| Illegal| De-Energized| Energized| Actuated| Closed(True)| Closed(True)|
Open (False)| Air Supply
8| Illegal| Energized| Ce-Energized| Actuated| Closed(True)| Closed(True)|
Open (False)| Air Supply
Table 4 – Truth Table for 1oo1HS Normally Closed with Proximity Switches –
De-Energized to trip
The normal operating state of the device is state number 3 (SOV1 de-energized
only) or state number 4 (SOV2 de-energized only). If the logic-solver responds
to a safety demand, it de-energizes SOV1 and SOV2 and causes the inlet air
supply to be blocked off and venting the block valve actuator. This in turn
will cause the block valve to move to the safe state. The safe state of the
RCS is therefore state 2.
6.2 1oo1HS Normally Open
Figures 2 and 4 illustrates the pneumatic pathways for this configuration
at the safe state condition (safety action). In this condition, the RCS is
supplying air to the block valve actuator, hence the expression normally open.
This configuration is characterized by supplying air to the block valve if the
solenoids are de-energized. To put the protected process into the safe state,
pneumatic energy is necessary. Therefore, this configuration should only be
used in rare cases such as when:
- the activation of the system is mitigating an existing hazard
- the unintentional or spurious activation of the system is a hazard itself
Examples of such applications are fire & gas systems, emergency cooling and
deluge systems, or flare control systems.
Additionally, restrictions to secure the integrity of the air supply may
apply:
- At least two independent air sources or an air storage device such as an accumulator shall be used. These sources must provide emergency air for a safe process shutdown, for a time span required by the application.
- Each air source must be provided with pressure integrity monitoring through a safety critical input read back into the safety rated logic solver. Any air supply failure shall lead to an alarm.
The truth table for 1oo1HS Normally Open using Pressure Switches is shown in Table 5.
State
| State Type|
Valve Position
|
Valve Pressure Switch Normally Open
|
Process/Outlet
---|---|---|---|---
SOV1
|
SOV2
|
Bypass Valve
|
PS 1
|
PS 2
|
PS 3
1| Degraded| Energized| Energized| Normal| Open (False)| PS2Open(False)|
Closed (True)| Vented
2| Safe| De-Energized| De-Energized| Normal| Open (False)| Closed (True)|
Closed (True)| Air Supply
3| Normal| Ce-Energized| Energized| Normal| Open (False)| Open (False)| Closed
(True)| Vented
4| Normal| Energized| De-Energized| Normal| Closed (True)| Closed (True)|
Closed (True)| Vented
5| Maintenance
Bypass| De-Energized| De-Energized| Actuated| Open (False)| Closed(True)|
Open(False)| Vented
6| Illegal| Energized| Energized| Actuated| Open (False)| Closed(True)| Open
(False)| Vented
7| Illegal| De-Energized| Energized| Actuated| Open (False)| Closed(True)|
Open (False)| Vented
8| Illegal| Energized| D-Energized| Actuated| Open (False)| Closed(True)| Open
(False)| Vented
Table 5 – Truth Table for 1oo1HS Normally Open with Pressure Switches – De-
Energized to trip
The truth table for 1oo1HS Normally Open using Proximity Switches is shown in
Table 6.
State
|
State Type
| Valve Position|
Valve Proximity Sensor/Switch Normally Open Contacts
| Process/Outlet
---|---|---|---|---
SOV1| SOV2| Bypass Valve| PS 1| PS 2|
PS 3
1| Degraded| Energized| Energized| Normal| Open (False)| PS2Open(False)|
Closed (True)| Air Supply
2| Safe| De-Energized| De-Energized| Normal| Closed (True)| Closed (True)|
Closed (True)| Vented
3| Normal| Ce-Energized| Energized| Normal| Closed (True)| Open (False)|
Closed (True)| Air Supply
4| Normal| Energized| De-Energized| Normal| Open (False)| Closed (True)|
Closed (True)| Air Supply
5| Maintenance
Bypass| De-Energized| De-Energized| Actuated| Closed(True)| Closed(True)|
Open(False)| Air Supply
6| Illegal| Energized| Energized| Actuated| Closed(True)| Closed(True)| Open
(False)| Air Supply
7| Illegal| De-Energized| Energized| Actuated| Closed(True)| Closed(True)|
Open (False)| Air Supply
8| Illegal| Energized| De-Energized| Actuated| Closed(True)| Closed(True)|
Open (False)| Air Supply
Table 6 – 1oo1HS Normally Open with Proximity Switches – De-Energized to
trip
The normal operating state of the device is state number 3 (SOV1 de-energized
only) or state number 4 (SOV2 de-energized only). If the logic-solver responds
to a safety demand, it de-energizes SOV1 resulting in the supply of air to the
block valve actuator, overcoming the spring return in the actuator. This in
turn will cause the block valve to move to the safe state. The safe state of
the RCS is therefore state 2.
6.3 2oo2 Normally Closed
Figures 1 and 3 illustrates the pneumatic pathways for this configuration at
the safe state condition (safety action). In this condition, the RCS is
blocking the inlet air supply and venting the block valve actuator (normally
closed operation). This configuration is most commonly used in safety
applications since a loss of electrical or pneumatic energy will result in the
safe state of the block valve. In the 2oo2 Normally Closed Mode, both
solenoids are on-line during normal operation. A spurious failure of
either solenoid is indicated by the pressure or proximity switch state
associated with that solenoid. The second solenoid will maintain air supply to
the block valve, reducing the potential for spurious trips.
The truth table for the 2oo2 Normally Closed with Pressure Switches is
shown in Table 7.
State
|
State Type
| Valve Position|
Valve Proximity Sensor/Switch Normally Open Contacts
|
Process/Outlet
---|---|---|---|---
SOV1
| SOV2| Bypass Valve| PS 1| PS 2|
PS 3
1| Normal| Energized| Energized| Normal| Open (False)| PS2Open(False)| Closed
(True)| Air Supply
2| Safe| De-Energized| De-Energized| Normal| Closed (True)| Closed (True)|
Closed (True)| Vented
3| Degraded| De-Energized| Energized| Normal| Closed (True)| Open (False)|
Closed (True)| Air Supply
4| Degraded| Energized| De-Energized| Normal| Open (False)| Closed (True)|
Closed (True)| Air Supply
5| Maintenance
Bypass| De-Energized| De-Energized| Actuated| Open (False)| Open (False)|
Open(False)| Air Supply
6| Illegal| Energized| Energized| Actuated| Open (False)| Open (False)| Open
(False)| Air Supply
7| Illegal| De-Energized| Energized| Actuated| Open (False)| Open (False)|
Open (False)| Air Supply
8| Illegal| Energized| De-Energized| Actuated| Open (False)| Open (False)|
Open (False)| Air Supply
Table 7 – Truth Table for 2oo2 Normally Closed with Pressure Switches – De-
Energized to trip
The truth table for the 2oo2 Normally Closed with Proximity Switches is
shown in Table 8.
State
|
State Type
| Valve Position|
Valve Proximity Sensor/Switch Normally Open Contacts
| Process/Outlet
---|---|---|---|---
SOV1| SOV2| Bypass Valve| PS 1| PS 2|
PS 3
1| Degraded| Energized| Energized| Normal| Open (False)| PS2Open(False)|
Closed (True)| Air Supply
2| Safe| De-Energized| De-Energized| Normal| Closed (True)| Closed (True)|
Closed (True)| Vented
3| Normal| Ce-Energized| Energized| Normal| Closed (True)| Open (False)|
Closed (True)| Air Supply
4| Normal| Energized| De-Energized| Normal| Open (False)| Closed (True)|
Closed (True)| Air Supply
5| Maintenance
Bypass| De-Energized| De-Energized| Actuated| Closed(True)| Closed(True)|
Open(False)| Air Supply
6| Illegal| Energized| Energized| Actuated| Closed(True)| Closed(True)| Open
(False)| Air Supply
7| Illegal| De-Energized| Energized| Actuated| Closed(True)| Closed(True)|
Open (False)| Air Supply
8| Illegal| Energized| De-Energized| Actuated| Closed(True)| Closed(True)|
Open (False)| Air Supply
Table 8 – Truth Table for 2oo2 Normally Closed with Proximity Switches –
De-Energized to trip
The normal operating state of the device is state number 1 (both SOV’s are
energized open). If the logic-solver responds to a safety demand, it de-
energizes both SOV1 and SOV2, and causes the inlet air supply to be blocked
off and venting the block valve actuator. This in turn will cause the block
valve to move to the safe state. The safe state of the RCS is therefore state
2.
6.4 2oo2 Normally Open
Figures 2 and 4 illustrates the pneumatic pathways for this configuration at
the safe state condition (safety action). In this condition, the RCS is
supplying air to the block valve actuator, hence the expression normally open.
This configuration is characterized by supplying air to the block valve if the
solenoids are de-energized. To put the protected process into the safe state,
pneumatic energy is necessary. Therefore, this configuration should only be
used in rare cases such as when:
- The activation of the system is mitigating an existing hazard
- The unintentional or spurious activation of the system is a hazard itself
Examples of such applications are fire & gas systems, emergency cooling and
deluge systems, or flare control systems.
Additionally, restrictions to secure the integrity of the air supply may
apply:
- At least two independent air sources or an air storage device such as an accumulator shall be used. These sources must provide emergency air for a safe process shutdown, for a time span required by the application.
- Each air source must be provided with pressure integrity monitoring through a safety critical input read back into the safety rated logic solver. Any air supply failure shall lead to an alarm.
The truth table for the 2oo2 Normally Open with Pressure Switches is shown in Table 9.
State
| State Type|
Valve Position
|
Valve Proximity Sensor/Switch Normally Open Contacts
|
Process/Outlet
---|---|---|---|---
SOV1
|
SOV2
|
Bypass Valve
|
PS 1
|
PS 2
|
PS 3
1| Normal| Energized| Energized| Normal| Closed (True)| Closed (True)| Closed
(True)| Vented
2| Safe| De-Energized| De-Energized| Normal| Open (False)| Open (False)|
Closed (True)| Air Supply
3| Degraded| Ce-Energized| Energized| Normal| Open (False)| Closed (True)|
Closed (True)| Vented
4| Degraded| Energized| De-Energized| Normal| Closed (True)| Open (False)|
Closed (True)| Vented
5| Maintenance Bypass| De-Energized| De-Energized| Actuated| Open (False)|
Open (False)| Open(False)| Vented
6| Illegal| Energized| Energized| Actuated| Open (False)| Open (False)| Open
(False)| Vented
7| Illegal| De-Energized| Energized| Actuated| Open (False)| Open (False)|
Open (False)| Vented
8| Illegal| Energized| D-Energized| Actuated| Open (False)| Open (False)| Open
(False)| Vented
Table 9 – Truth Table for 2oo2 Normally Open with Pressure Switches – De-
Energized to trip
The truth table for the 2oo2 Normally Open with Proximity Switches is shown in
Table 10.
State
| State Type|
Valve Position
|
Valve Proximity Sensor/Switch Normally Open Contacts
|
Process/Outlet
---|---|---|---|---
SOV1
|
SOV2
|
Bypass Valve
|
PS 1
|
PS 2
|
PS 3
1| Normal| Energized| Energized| Normal| Open (False)| Open (False)| Closed
(True)| Air Supply
2| Safe| De-Energized| De-Energized| Normal| Closed (True)| Closed (True)|
Closed (True)| Vented
3| Degraded| Ce-Energized| Energized| Normal| Closed (True)| Open (False)|
Closed (True)| Air Supply
4| Degraded| Energized| De-Energized| Normal| Open (False)| Closed (True)|
Closed (True)| Air Supply
5| Maintenance Bypass| De-Energized| De-Energized| Actuated| Closed (True)|
Closed (True)| Open(False)| Air Supply
6| Illegal| Energized| Energized| Actuated| Closed (True)| Closed (True)| Open
(False)| Air Supply
7| Illegal| De-Energized| Energized| Actuated| Closed (True)| Closed (True)|
Open (False)| Air Supply
8| Illegal| Energized| D-Energized| Actuated| Closed (True)| Closed (True)|
Open (False)| Air Supply
Table 10 – Truth Table for 2oo2 Normally Open with Proximity Switches – De-
Energized to trip
The normal operating state of the device is state number 1 (both SOV’s
energized open). If the logic solver responds to a safety demand, it de-
energizes both SOV1 and SOV2 resulting in the supply of air to the blockvalve
actuator, overcoming the spring return in the actuator. This in turn will
cause the block valve to move to the safe state. The safe state of the RCS is
therefore state 2.
6.5 2oo2 Double Acting
The Double Acting RCS must be used with a safe last state actuator valve
package.
Figures 5 and 6 illustrates the pneumatic pathways for this configuration at
the safe state condition (safety action). In this condition, the RCS is
supplying inlet air to C1 process and venting C2 process of the block valve
actuator In the 2oo2-Double Acting Mode, both solenoids are on-line during
normal operation. A spurious failure of either
solenoid is indicated by the pressure or proximity switch state associated
with that solenoid. When SOV1 or SOV2 is energized by itself, the pressure
across the block valve actuator is balanced. The block valve actuator does not
change states.
The truth table for the 2oo2 Double acting with Pressure Switches is shown in
Table 11:
State
| State Type|
Valve Position
|
Valve Proximity Sensor/Switch Normally Open Contacts
|
Process/Outlet
---|---|---|---|---
SOV1
|
SOV2
|
Bypass Valve
|
PS 1
|
PS 2
|
PS 3
1| Normal| Energized| Energized| Normal| Open (False)| Open (False)| Closed
(True)| C1vented
C2 Air Supply
2| Safe| De-Energized| De-Energized| Normal| Closed (True)| Closed (True)|
Closed (True)| C1vented
C2 Air Supply
3| Degraded| Ce-Energized| Energized| Normal| Closed (True)| Open (False)|
Closed (True)| C1vented
C2 Air Supply
4| Degraded| Energized| De-Energized| Normal| Open (False)| Closed (True)|
Closed (True)| C1vented
C2 Air Supply
5| Maintenance Bypass| De-Energized| De-Energized| Actuated| Closed (True)|
Closed (True)| Open(False)| C1vented
C2 Air Supply
6| Illegal| Energized| Energized| Actuated| Open (False)| Open (False)| Open
(False)| C1vented
C2 Air Supply
7| Illegal| De-Energized| Energized| Actuated| Open (False)| Open (False)|
Open (False)| C1vented
C2 Air Supply
8| Illegal| Energized| D-Energized| Actuated| Open (False)| Open (False)| Open
(False)| C1vented
C2 Air Supply
Table 11 – Truth Table for 2oo2 Double Acting with Pressure Switches
The truth table for the 2oo2 Double acting with Proximity Switches is shown in
Table 12:
State
| State Type|
Valve Position
|
Valve Proximity Sensor/Switch Normally Open Contacts
|
Process/Outlet
---|---|---|---|---
SOV1
|
SOV2
|
Bypass Valve
|
PS 1
|
PS 2
|
PS 3
1| Normal| Energized| Energized| Normal| Open (False)| Open (False)| Closed
(True)| C1vented
C2 Air Supply
2| Safe| De-Energized| De-Energized| Normal| Closed (True)| Closed (True)|
Closed (True)| C1vented
C2 Air Supply
3| Degraded| Ce-Energized| Energized| Normal| Closed (True)| Open (False)|
Closed (True)| C1vented
C2 Air Supply
4| Degraded| Energized| De-Energized| Normal| Open (False)| Closed (True)|
Closed (True)| C1vented
C2 Air Supply
5| Maintenance Bypass| De-Energized| De-Energized| Actuated| Closed (True)|
Closed (True)| Open(False)| C1vented
C2 Air Supply
6| Illegal| Energized| Energized| Actuated| Closed (True)| Closed (True)| Open
(False)| C1vented
C2 Air Supply
7| Illegal| De-Energized| Energized| Actuated| Closed (True)| Closed (True)|
Open (False)| C1vented
C2 Air Supply
8| Illegal| Energized| D-Energized| Actuated| Closed (True)| Closed (True)|
Open (False)| C1vented
C2 Air Supply
Table 12 – Truth Table for 2oo2 Double Acting with Proximity Switches
The normal operating state of the device is state number 1 (both SOV’s are
energized open). If the logic-solver responds to a safety demand, it de-
energizes both SOV1 and SOV2, and causes the inlet air supply to be directed
to C1 and vents C2 of the block valve actuator. This in turn will cause the
block valve to move to the safe state. The safe state of the RCS is therefore
state 2
6.6 2oo3 Normally Closed without Diagnostics
Figures 7 illustrates the pneumatic pathways for this configuration at the
safe state condition (safety action). In this condition, the RCS is blocking
the inlet air supply and venting the block valve actuator (normally closed
operation). This configuration is most commonly used in safety applications
since a loss of electrical or pneumatic energy will result in the safe state
of the block valve.
In the 2oo3 Normally Closed Mode, the three (3) solenoids are on-line during
normal operation. A spurious failure of only one (1) solenoid will not
generate a spurious trip of the block valve as the other two solenoids will
maintain air supply to the block valve, reducing the potential for spurious
trips.
However, when at least two (2) solenoids present a spurious failure the block
valve will be vented and move to the safe position.
The truth table for the 2oo3 Normally Closed without Diagnostics is shown in
Table 13.
State| State
Type| Valve Position| Process/Outlet
---|---|---|---
Sove 1| SOV 2| SOV 3
1| Normal| Energized| Energized| Energized| Vented
2| Safe| De-Energized| De-Energized| De-nergized| Air Supply
3| Degraded| De-Energized| Energized| Energized| Air Supply
4| Degraded| Energized| De-Energized| Energized| Vented
5| Degraded| Energized| Energized| De-nergized| Vented
6| Degraded| De-Energized| De-Energized| Energized| Vented
7| Degraded| De-Energized| Energized| De-nergized| Vented
8| Degraded| Energized| De-Energized| De-nergized| Vented
Table 13 – Truth Table for 2oo3 without Diagnostics – De-Energized to Trip
6.7 2oo3 Normally Closed with Proximity Switches
Figures 8 illustrates the pneumatic pathways for this configuration at the
safe state condition (safety action). In this condition, the RCS is blocking
the inlet air supply and venting the block valve actuator (normally closed
operation). This configuration is most commonly used in safety applications
since a loss of electrical or pneumatic energy will result in the safe state
of the block valve.
In the 2oo3 Normally Closed Mode, the three (3) solenoids are on-line during
normal operation. A spurious failure of only one (1) solenoid, indicated by
its respective proximity switch, will not generate a spurious trip of the
block valve as the other two solenoids will maintain air supply to the block
valve, reducing the potential for spurious trips. However, when at least two
(2) solenoids present a spurious failure the block valve will be vented and
move to the safe position. The truth table for the 2oo3 Normally Closed with
Proximity Switches is shown in Table 14.
Stele| StateType| Valve Position| Valve Proximity
Sensor/Switch Normally Open Contacts| Process/Outle
---|---|---|---|---
SOV 1| SOV 2| SOV 3| BypassValve| PS 1| PS 2|
PS 3| PS 4
1| Normal| Energized| Energized| Energized| Normal| Open(False)| Open(False)|
Open(False)| Closed(True)| Air Supply
2| Safe| De-nergized| De-nergized| De-nergized| Normal| Closed(True)|
Closed(True)| Closed(True)| Closed(True)| Vented
3| Degraded| De-nergized| Energized| Energized| Normal| Closed(True)|
Open(False)| Open(False)| Closed(True)| Air Supply
4| Degraded| Energized| De-nergized| Energized| Normal| Open(False)| Closed
(True)| Open(False)| Closed(True)| Air Supply
5| Degraded| Energized| Energized| De-nergized| Normal| Open(False)|
Open(False)| Closed(True)| Closed (True)| Air Supply
6| Degraded| De-nergized| De-nergized| Energized| Normal| Closed(True)|
Closed(True)| Open(False)| Closed(True)| Vented
7| Degraded| De-nergized| Energized| De-nergized| Normal| Closed(True)|
Open(False)| Closed(True)| Closed(True)| Vented
8| Degraded| Energized| De-nergized| De-nergized| Normal| Open(False)| Closed
(True)| Closed(True)| Closed(True)| Vented
9| De-nergized| De-nergized| De-nergized| De-nergized| Actuated| Closed
(True)| Closed (True)| Closed (True)| Open(False)| Air Supply
10| Illegal| Energized| Energized| Energized| Actuated| Closed(True)|
Closed(True)| Closed(True)| Open(False)| Air Supply
11| Illegal| De-nergized| Energized| Energized| Actuated| Closed(True)|
Closed(True)| Closed(True)| Open(False)| Air Supply
12| Illegal| Energized| De-nergized| Energized| Actuated| Closed(True)|
Closed(True)| Closed(True)| Open(False)| Air Supply
13| Illegal| Energized| Energized| De-nergized| Actuated| Closed(True)|
Closed(True)| Closed (True)| Open(False)| Air Supply
14| Illegal| De-nergized| De-nergized| Energized| Actuated| Closed(True)|
Closed(True)| Closed(True)| Open(False)| Air Supply
15| Illegal| De-nergized| Energized| De-nergized| Actuated| Closed(True)|
Closed(True)| Closed(True)| Open(False)| Air Supply
16| Illegal| Energized| De-nergized| De-nergized| Actuated| Closed(True)|
Closed(True)| Closed(True)| Open(False)| Air Supply
Table 14 – Truth Table for 2oo3 Normally Closed with Proximity Switches – De- Energized to Trip
RCS Maintenance
7.1 Operator Interface Options
The RCS is available with various interface and display options. These options
provide local indication anfeedback for plant personnel. There are several
constraints related to these options.
- Any operator interface shall be implemented in a manner that has a predictable effect on the RCS and does not interfere with its safety function.
- Field modifications shall not be made to the internal wiring or pneumatic connections of the RCS.
7.2 Automated Diagnostic Test (ADT)
The RCS architecture alone is not sufficient to achieve the required
diagnostic coverage for devices used in critical environments. The associated
pressure or proximity switches will have to be used by the safety rated logic
solver to:
- Verify the system transitions into the safe state if requested
- Detect illegal states of the system (refer to truth tables)
- Detect degraded state for the 1oo1HS configuration (refer to truth tables) or the degraded state for the 2oo2 and 2oo3 configuration (refer to truth tables)
- Detect the bypass (forced) state of the safety function (refer to truth tables).
In addition to the static detection of the system state and to enable the
logic-solver to verify correct system state transition, the sensor information
is used to implement a safety-critical test of the RCS function. These
diagnostics also allow implementing a hot-standby switchover to SOV2 if SOV1
fails safe, however this function is NOT a safety function since it only
reduces the spurious trip rate of the device.
For functional testing, the two (2) solenoids, in case of 2oo2 configuration,
or the three (3) for the 2oo3, are brought on-line. Each solenoid is then de-
energized individually with pressure or proximity switch confirmation of
successful changing of state. No bypassing is required for functional testing.
This means that the system is sequenced, from its normal operation, through
the states:
- 2oo2: 1 > 3 >1 > 4 > 1
- 2oo3D: 1 > 3 > 1 > 4 > 1 > 5 > 1
The correct assertion of these states is verified by reading the switch transition. The safe state can be achieved at any time during the function test by de-energizing the digital outputs on the safety rated logic solver. Refer to the relevant Truth table for the pressure and proximity switches for each of these states. The functional testing is performed to detect potential undetected dangerous component failure within the device such as:
- SOV1 stuck in energized position
- SOV2 stuck in energized position
- SOV3 stuck in energized position
- Pressure switch 1 stuck in open or closed position
- Pressure switch 2 stuck in open or closed position
- Proximity switch 1 stuck in open or closed position
- Proximity switch 2 stuck in open or closed position
- Proximity switch 3 stuck in open or closed position
- Open bypass valve in combination with a defective pressure switch 3
- Open bypass valve in combination with a defective proximity switch 4
A potentially dangerous state of the bypass valve is detectable through
pressure or proximity switch 3 (in 2oo2configurations) or proximity switch 4
(in 2oo3 configuration).
In 2oo2, an open bypass valve will cause a transition of pressure or proximity
switch 3 into a position disallowed in the normal state.
In 2oo3, an open bypass valve will cause a transition of proximity switch 4
into a position disallowed in thenormal state.
When in Bypass mode, the detection mechanism for the SOV’s will not provide
the actual electrical state of theSOV’s as no pressure is supplied to these
valves (refer to Truth tables for additional details).Since the position of
the bypass valve is safety critical, the valve can be secured with a key
switch. The key is removable in normal state (not bypassed) and should not be
left inserted during normal operation to prevent inadvertent overrides.Any
failure detected by the ADT shall be annunciated by the safety rated logic
solver.
7.2.1 State Verification Test
The correct state of all valves shall be verified and compared against the
commanded state. The state tables in Section 6 of this manual can be used as a
guide. This verification shall be performed periodically with a cycle time of
½ of the process safety time or less.
If any illegal states are detected, they shall be immediately annunciated.
These states are excluded by design and the root cause for these faults cannot
be determined or be contributed to a specific component. The RCS shall be
repaired within 72 hours.
7.2.2 Valve Diagnostic Test
The ability of the logic solver to actuate the RCS shall be tested. This test
shall sequence the SOV valves through the different states. The truth tables
presented in Section 6 represent the normal working conditions for the RCS
configurations
However, some critical functions of the RCS cannot be tested by the ADT. The
failure analysis of the device has determined that the following failure modes
will not be detected by the diagnostic test:
- Blockage or partial blockage of the line between the actuator and the RCS (NC).
- Blockage or partial blockage of the supply line between the pneumatic supply and the RCS (NO).
- Electrical shorts between a pressure or proximity sensor and the associated valve solenoid at the termination block (if common ground is used for both signals and in NO mode)
- Interruption of the Diagnostic Test
Items 1 and 2 are important since they entirely disable the actuating
function of the RCS and are instantaneously dangerous. These faults however
can be detected if a partial valve stroke test is implemented. Items 3 and 4
will not be instantaneously dangerous but will affect the diagnostic coverage
or may induce a dangerous state if a second fault occurs.
These failure modes shall be tested manually in an interval longer than the
diagnostic interval time, and often enough to reduce the probability of the
system to be in an undetected dangerous state. Manual test with longer test
intervals is commonly called proof test.|
Items 1-4 shall be tested during the proof test of the SIF.
The manual tests of items 1, 2 and 3 can be substituted by automated tests if
a partial stroke test of the block valve is implemented.The following tables
identify the defective valve / switch and the failure must be annunciated to
initiate repair.
NOTE: All “Failure Verification” states of PS1, PS2, PS3, and PS4 in
tables 15 through 21 are made with reference to the switch normally open
contacts.
2oo2 Configurations
State | Failure Verification | Defective Component |
---|---|---|
1 | PS1 closed | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
3 | PS1 open | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
4 | PS1 closed | PS1 defective or SOV1 defective |
PS2 open | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable |
Table 15 – 2oo2 (NC) with Pressure Switches – Defective Component Identification
State | Failure Verification | Defective Component |
---|---|---|
1 | PS1 closed | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
3 | PS1 open | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
4 | PS1 closed | PS1 defective or SOV1 defective |
PS2 open | PS2 defective or SOV2 defective | |
P53 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable |
Table 16 – 2oo2 (NC) with Proximity Switches – Defective Component Identification
State | Failure Verification | Defective Component |
---|---|---|
1 | PS1 open | PS1 defective or SOV1 defective |
PS2 open | PS2 defective or S0V2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
3 | PS1 closed | PS1 defective or SOV1 defective |
PS2 open | PS2 defective or S0V2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
4 | PS1 open | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable |
Table 17 – 2oo2 (NO) with Pressure Switches – Defective Component Identification
State | Failure Verification | Defective Component |
---|---|---|
1 | PS1 closed | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
3 | PS1 open | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
4 | PS1 closed | PS1 defective or SOV1 defective |
PS2 open | PS2 defective or S0V2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable |
Table18 – 2oo2 (NO) with Proximity Switches – Defective Component Identification
State | Failure Verification | Defective Component |
---|---|---|
1 | PS1 open | PS1 defective or SOV1 defective |
P52 closed | PS2 defective or 50V2 defective | |
PS3 open | P53 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
3 | PS1 closed | PS1 defective or SOV1 defective |
P52 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
4 | PS1 open | PS1 defective or SOV1 defective |
PS2 open | PS2 defective or 50V2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable |
Table 19 – 2oo2 (DA) with Pressure Switches – Defective Component Identification
State | Failure Verification | Defective Component |
---|---|---|
1 | PS1 closed | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
3 | PS1 open | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
4 | PS1 closed | PS1 defective or SOV1 defective |
PS2 open | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or bypass function active | |
More than one signal mismatched | Fault not localizable |
Table 20 – 2oo2 (DA) with Proximity Switches – Defective Component
Identification
2oo3 Configuration
State | Failure Verification | Defective Component |
---|---|---|
1 | PS1 closed | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 closed | PS3 defective or SOV3 defective | |
PS4 open | PS4 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
3 | PS1 open | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 closed | PS3 defective or SOV3 defective | |
PS4 open | PS4 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
4 | PS1 closed | P51 defective or SOV1 defective |
PS2 open | PS2 defective or SOV2 defective | |
PS3 closed | PS3 defective or SOV3 defective | |
PS4 open | PS4 defective or bypass function active | |
More than one signal mismatched | Fault not localizable | |
5 | PS1 closed | PS1 defective or SOV1 defective |
PS2 closed | PS2 defective or SOV2 defective | |
PS3 open | PS3 defective or 50V3 defective | |
PS4 open | PS4 defective or bypass function active | |
More than one signal mismatched | Fault not localizable |
Table 21 – 2oo3 Defective Component Identification
7.3 Manually Initiated Diagnostic Test
The manually initiated diagnostic test is identical to the ADT described in
7.2 except that instead of automatically initiating the diagnostic, operator
action is required by means of pushing a push button. The diagnostics that are
executed are identical, thus, the same outputs can be expected.
7.4 Proof Test without Automatic Testing
The objective of proof testing is to detect failures within an ASCO Solenoid
that are not detected by any automatic diagnostics of the system. Of main
concern are undetected failures that prevent the safety instrumented function
from performing its intended function.
The frequency of proof testing, or the proof test interval, is to be
determined in reliability calculations for the safety instrumented functions
for which an ASCO Solenoid is applied. The proof tests must be performed more
frequently, or as frequently as specified in the calculation in order to
maintain the required safety integrity of the safety instrumented function.
The following proof test procedure is recommended. Any failures that are
detected and that compromise functional safety should be reported to ASCO
Valves, Inc.
Step | Action |
---|---|
1. | Bypass the safety function and take appropriate action to avoid a false |
trip.
2.| Perform an Automated Diagnostic Test (ADT) to confirm the proper
functioning of the RCS.
3.| De-energize the RCS Solenoids to force the ActuatorNaive assembly to the
Fail-Safe state and confirm that the Safe State was achieved and within the
correct time.
Note:-This tests for all failures that could prevent the functioning of the
Control Valve as well as the rest of the final control element.
4.| Inspect the RCS for any leaks, visible damage or contamination
5.| Re-store the RCS to normal operation and confirm that the normal operating
state was achieved.
6.| Remove the bypass and otherwise restore normal operation.
Table 22 – Proof Test Procedure
This test will detect approximately 96% of possible DU failures without
ADT, 33% with ADT. The person(s) performing the proof test of an ASCO Solenoid
should be trained in SIS operations, including bypass procedures, solenoid
maintenance and company Management of Change procedures. No special tools are
required.
7.5 Proof Test with Automatic Partial Valve Stroke Testing
An automatic partial valve stroke testing scheme that performs a full stroke
of the isolation valves in the RCS and measures valve movement timing will
detect most potentially dangerous failure modes. It is recommended that a
physical inspection (Step 2 from Table 1) be performed on a periodic basis
with the time interval determined by plant conditions. A maximum inspection
interval of five years is recommended.
7.6 Repair and replacement
Repair procedures must be followed. Please refer to the appropriate I&M per
your specific construction:
- I&M V9512: 1oo1 and 2oo2 Aluminum with Pressure Switches
- I&M V9709: 1oo1 and 2oo2 Stainless steel with Pressure Switches.
- I&M V9957: 2oo2 Aluminum with Proximity Switches
- I&M V9958: 2oo3 without diagnostics.
- I&M V9959: 2oo3 Aluminum with Proximity Switches
7.7 ASCO Notification
Any failures that are detected and that compromise functional safety should be
reported to ASCO Valves, Inc. Please contact ASCO Technical Support.
Status of the document
8.1 Releases
Version: R3
Revision: DA
Version History: V0, R3, DA
Release status: ECN 314141 Released on 07/21
Appendix A – SIS Checklist
The following checklist may be used as a guide to employ the RCS device in a safety critical SIF compliant to IEC61508.
# | Activity | Result | Verified By | Date |
---|---|---|---|---|
Target Safety Integrity Level and PFDavg determined | ||||
Correct valve mode chosen (NO/NC/DA) | ||||
Design decision documented | ||||
Electrical compatibility and suitability verified | ||||
Pneumatic compatibility and suitability verified | ||||
SIS logic solver requirements for valve tests defined and documented | ||||
Line monitoring requirements for SIS logic solver connection determined | ||||
Routing of electric and pneumatic connections determined | ||||
SIS logic solver requirements for partial stroke tests defined | ||||
anddocumented | ||||
Design formally reviewed and suitability formally assessed | ||||
Implementation | ||||
Physical location appropriate | ||||
Electrical connections appropriate and according to applicable codes | ||||
Pneumatic connections appropriate and according to applicable codes | ||||
SIS logic solver line-end devices installed (if applicable) | ||||
SIS logic solver state verification test implemented | ||||
SIS logic solver valve actuation test implemented | ||||
Maintenance instructions for proof test released | ||||
Verification and test plan released | ||||
Implementation formally reviewed and suitability formally assessed | ||||
Verification and Testing | ||||
Electrical connections verified and tested | ||||
Pneumatic connection verified and tested | ||||
SIS logic solver line-end devices tested | ||||
SIS logic solver state verification test verified | ||||
SIS logic solver valve actuation test verified | ||||
Safety loop function verified | ||||
Safety loop timing measured | ||||
Bypass function tested | ||||
Verification and test results formally reviewed, and suitability formally | ||||
assessed | ||||
Maintenance | ||||
Tubing blockage / partial blockage tested | ||||
Enclosure vent inspected | ||||
Electrical connection inspected | ||||
Bypass function and pressure sensors tested |
Safety loop function tested
©ASCO, L.P. 160 Park Avenue, Florham Park, New Jersey 07932
www.emerson.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>