SIEMENS PXG3.W100-2 BACnet-IP Web Interface Instruction Manual
- June 3, 2024
- SIEMENS
Table of Contents
- PXG3.W100-2 BACnet-IP Web Interface
- Functions
- Application
- Type summary
- Product documentation
- Technical and mechanical design
- LED indicators and service pin
- Safety
- Technical data
- Function data
- Interfaces
- Conformity
- Connection terminals
- Dimensions
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Desigo™ Control Point
BACnet/IP Web interface
PXG3.W100-2, PXG3.W200-2 Instruction Manual
PXG3.W100-2 BACnet-IP Web Interface
Interface for web-based, graphical operation of BACnet automation stations using Desigo touch panels and devices with an HTML 5.0 web browser.
- Simultaneous access by various operator units
- Central administration of graphics and data for other operating views
- Offline engineering with ABT Site
- Upload and download configuration data over the IP interface
- 2-port Ethernet switch for low-cost cabling (10Base-T/100Base-Tx)
- LED indication for Ethernet link and activity
- Operating voltage AC 24 V or DC 24 V
- Plug-in screw terminal block for supply
- Mounting on DIN rail or on the wall
Functions
The device has a web server that processes data from various Desigo automation
stations and other devices based on BACnet IP to HTML5 web pages.
The following functions are available to operate and monitor a plant:
- Log-in and log-out
- User administration
- Customized graphics
- Alarm view to monitor and log alarms
- Alarm forwarding to e-mail recipient
- Graphics-based operation of time schedules
- Graphically displaying trend data
- Generic operation of all objects and properties of assigned devices
Application
The web interfaces PXG3.W100-2 and PXG3.W200-2 are the central points of access to operate the automation level and room automation. The central point of access permits simultaneous operation on various operator units and supports
- Connection of Desigo touch panels PXM30-1, PXM40-1 und PXM50-1
- Access via devices using a standard web browser with HTML5.
Type summary
Type | Order number | Description |
---|---|---|
PXG3.W100-2 | S55842-Z140 | BACnet/IP web interface with standard functionality |
PXG3.W200-2 | S55842-Z141 | BACnet/IP web interface with extended functionality |
Product documentation
Type of document | Document no. |
---|---|
Data sheet BACnet/IP Touch Panels PXM30.E / PXM40.E / PXM50.E | A6V11664137 |
Data sheet Touch Panel Clients PXM30-1 / PXM40-1 / PXM50-1 | A6V11664139 |
Desigo Control Point Basic documentation | A6V11666339 |
Desigo Touch-Panel Clients Commissioning | A6V11604303 |
Desigo Control Point Operating manual | A6V11211557 |
Desigo Control Point Engineering manual | A6V11604297 |
Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download
Technical and mechanical design
The device can be mounted on a standard rail or on the wall. The device can be mounted on a standard rail or on the wall.
-
Plastic housing
-
LEDs for communication and state
-
Service button
-
a2-port Ethernet switch with 2 LEDs per port
4 bNot supported -
Plug-in terminal blocks with screw terminals Power supply
-
Not supported
-
Not supported
-
Not supported
-
Slider for mounting on standard mounting rails
-
Eyelets for cable ties
-
Holes for wall mounting
-
Date / Series and Serial number
LED indicators and service pin
Activity| LED / Interface| Color| Activity|
Function
---|---|---|---|---
| Ethernet 1…2| Green| Continuously ON Continuously OFF Flashing| Link
active No connection Network traffic
Yellow| Continuously ON Continuously OFF| Link 100 Mbps Link 10 Mbps
| RUN| Green| Continuously ON Continuously OFF Flashing| Device
operational Device not operational Start-up or program halted
Red| Continuously OFF Continuously ON
Rapid flashing| OK
HW or SW fault – power off and on the device
Firmware or application missing/corrupted
| Blue| Continuously OFF| Function not supported
SVC| Red| Continuously OFF Flashing| OK Device is not configured
Flashing per wink command| Identification of the device after receipt of
winkcommand
COM1 / 2 TX| Yellow| Continuously OFF| Function not supported
COM1 / 2 RX| Yellow
| Service button| | Short press| Identification on the network
As per description:| Do the following to reset the device to factory state:
1.Power off the device.
2Power on the device.
3.Wait until all LEDs light up and turn off again, then press the Service
button.
4.Keep the Service button pressed until all LEDs light up, then release the
but- ton.
All LEDs turn off, the device restarts.
5.Wait until the device has fully started up– unconfigured (green RUN LED and
red SVC LED are flashing).
Notes
Safety
| CAUTION
---|---
National safety regulations Failure to comply with national safety regulations
may result in personal injury and propert
Mounting position and ambient temperature
The devices can be snapped onto standard rails or screwed onto a flat surface.
Plug-in screw terminals connect power and interfaces (except for Ethernet).
Ambient temperature -5…50 °C (23…122 °F)
- Wall, horizontal
– From left to right
– From right to left
Ambient temperature -5…45 °C (23…113 °F)
-
Overhead
-
Wall, vertically
– From top to bottom
– From bottom to top -
On a horizontal surface
| CAUTION
---|---
Risk of overheating for failure to comply with ambient temperature Burning and
damage to the device
● Ensure sufficient ventilation to comply with the permissible ambient
temperature within the panel or installation box. The temperature must be at
least 10 K (18° F) lower outside the installation box.
Installation
**** | WARNING |
---|
Electric shock Incorrect installation of the device may lead to electric shock
injuries when touching the
device!
● Install the device in a lockable cabinet or use terminal covers.
● Do not install the device in locations where children are likely to be
present.
● Conductors with a cross-section of 0.5 mm2 (AWG24) or greater shall comply
with the requirements of IEC 60332-1-2 and IEC 60332-1-3 or IEC TS
60695-11-21.
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic garbage.
- Dispose of the device through channels provided for this purpose.
- Comply with all local and currently applicable laws and regulations.
Technical data
Power supply
Operating voltage 24 V AC (24 V≃, ⏊, )| AC 24 V -15 / +20 % (PELV)
AC 24 V Class 2 (US) 48…63 Hz
---|---
Operating voltage 24 V DC| DC 24 V -15 / +20 % (PELV)
DC 24 V Class 2 (US)
Functional ground (US) Functional earth| The terminal for the functional
ground must be connected on the installation side with the building grounding
system (PE).
Screw terminals for wire cross sections up to| Max. 2.5 mm2 (14 AWG)
Internal fusing| 2.5 A irreversible / non-replaceable
External supply line fusing (EU)| Non-renewable fuse max. 10 A slow or circuit
breaker max. 13 A Tripping characteristic B, C, D per EN 60898 or Power supply
with current limitation of max. 10 A
Power consumption (for transformer planning)
Power consumption AC Base load With USB (not supported)| 10 VA
16 VA
---|---
Power consumption DC
Base load
With USB (not supported)| 5 W
8 W
Function data
Hardware information
Processor| NXP i.MX8 DualX, 1 GHz
Storage| 2 GB RAM
8 GB eMMC
Real-time clock
Energy reserve (Supercap) to support real-time clock (7 days).
Interfaces
Ethernet interface
Plug| 2 x RJ45, shielded
Interface type| 10Base-T / 100Base-TX, IEEE 802.3 compatible
Bit rate| 10/100 Mbps, autosensing
Protocol| BACnet on UDP/IP and HTTPs on TCP/IP
Cabling, cable type| 10 Mbps: Min. CAT3, shielded cable is recommended 100
Mbps: Min. CAT5, shielded cable is recommended
Cable length| Max. 100 m (330 ft)
Screw terminals, plug-in
Cu-wire or Cu-strand with wire end sleeve| 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.0 mm2 (22 to 18 AWG)
Cu-strand without wire end sleeve| 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.5 mm2 (22 to 16 AWG)
Stripping length| 6…7.5 mm (0.24. 0.29 in)
Screw terminals, plug-in
Screwdriver| Slot screws, screwdriver size 1 with shaft ø = 3 mm
Max. tightening torque| 0.6 Nm (0.44 lb ft)
Conformity
Ambient conditions and protection classification
Classification as per EN 60730 Automatic action Control function Degree of
pollution Overvoltage category| Type 1 Class A
2II
Protection against electric shock| Protection class III Suitable for use in
protection class I or II systems
Degree of protection of housing to EN 60529 Front parts in DIN cut-out
Terminal part
| IP30 IP20
Climatic ambient conditions
●Storage / Transport (packaged for transport) as per IEC EN 60721-3-1 / IEC EN
60721‑3‑2
●Operation as per IEC/EN 60721-3-3| ●Class 1K22 / 2K12 Temperature -25…70 °C
(-13…158 °F)Air humidity 5…95 % (non-ondensing
●Class 3K23 Operation in enclosed dry locations, having no temperature or
humidity contro Temperature -5…50 °C (23…122 °F) (for details see chapter
Mounting) Air humidity 5…95 % (non-condensing)
Mechanical ambient conditions
●Transport per IEC/EN 60721-3-2
●Operation as per IEC/EN 60721-3-3
| ●Class 2M4
●Class 3M11
Standards, directives and approvals
Product standards| IEC/EN 60730-1 and IEC/EN 62368-1
Product family standard| IEC/EN 63044-x
Electromagnetic compatibility (EMC)| For residential, commercial, and
industrial environments
EU conformity (CE)| See CE declaration 1)
EAC compliance| Eurasian compliance
RCM conformity| See RCM declaration 1)
UL/cUL certification (US / Canada)| UL916; http://ul.com/database
CSA certification| C22.2, http://csagroup.org/services-
industries/product-
listing
FCC| CFR 47 Part 15B
BACnet| B-OD
Environmental compatibility 1)| The product environmental declaration 1)
contains data on nvironmentally compatible product design and assessments
(RoHS compliance, materials composition, packaging, environmental benefit,
disposal).
¹)Documents can be downloaded at
http://siemens.com/bt/download.
FCC Statement
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. How-
ever, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- this device must accept any interference received, including interference that may cause undesired operation
FCC Caution: Changes or modifications not expressly approved by Siemens
Switzerland Ltd. could void the user’s authority to operate the equipment.
United States representative
https://new.siemens.com/us/en/products/buildingtechnologies/home.html
Industry Canada statement
This device complies with ISED’s licence-exempt RSSs. Operation is subject to
the following two conditions:
- This device may not cause interference, and
- this device must accept any interference received, including interference that may cause undesired operation.
Housing
Color top/bottom | RAL 7035 (light grey) / RAL 7016 (anthracite grey) |
---|---|
Dimensions | per DIN 43 880, see dimensions |
Weight with/without packaging | 350 g / 300 g |
Connection terminals
Terminal| Symbol|
Description
---|---|---
1A, 1B|
| 2 x RJ45 interface for Ethernet with switch LAN (customer network)
2|
| Not supported
5, 6|
≃ , ⏊,
| Operating voltage AC 24 V, DC 24 V
7|
| Functional ground (must be connected on the installation side with the
building grounding system (PE).
USB|
| Not supported
Term| off| Not supported
Polar| off| Not supported
65, 66, 67| COM1| Not supported
68, 69, 70| COM2
Dimensions
All dimensions in mm and inches
© Siemens Switzerland Ltd, 2021
Technical specifications and availability subject to change without notice.
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
References
- Smart Information Delivery
- Product Sourcing and Certifications Database | UL Solutions
- Building technology - Siemens Global
- Building Technologies - Siemens USA
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>