Landis Gyr Ultraheat T550 Ultrasonic Heat and Cooling Meter Instruction Manual

June 3, 2024
Landis Gyr

Landis Gyr Ultraheat T550 Ultrasonic Heat and Cooling Meter Instruction Manual
Landis Gyr Ultraheat T550 Ultrasonic Heat and Cooling
Meter

Note: These operating instructions remain with the end user following installation.

Note: In the following text, the term meter refers to both the heat meter, the cooling meter and the flow meter, unless they are otherwise differentiated.

General

Use

The T550 (UH50…) is used as a meter for heating or cooling consumption measurement in systems with water.

The meter consists of two temperature sensors and an electronic unit that calculates the energy consumption from the volume and temperature difference.

General notes

The meter left the factory in a faultless condition where safety is concerned. The manufacturer will provide additional technical support on request. Calibration relevant security seals on the meter must not be damaged or removed. Otherwise, the warranty and calibration validity of the meter will no longer apply

  • Keep the packaging so that you can transport the meter in its original packaging following expiry of the calibration validity.
  • Lay all cables at a minimum distance of 500 mm to high voltage and high frequency cables.
  • A relative humidity of < 93 % at 25 °C is permissible (without condensation).
  • Avoid cavitation in the whole system due to overpressure i.e. at least 1 bar at qp and approx. 3 bar at qs (applies for approx. 80 °C).
  • At a heat meter or combined heat/cold meter the mounting place of the flow sensor cold side is equivalent to return. The mounting place of the flow sensor hot side is equivalent to flow.
  • At a cooling meter the mounting place of the flow sensor hot side is equivalent to the return. The mounting place of the flow sensor cold side is equivalent to flow

Safety Information

The meter may only be used in building service engineering systems and only for the applications described.

The local regulations (installation etc.) must be adhered to.

The operating conditions according to the type plate must be complied with during use. Non-compliance can result in hazardous situations and the expiry of all claims arising from liability for defects as well as liability based on any expressly granted guarantees.

Requirements for circulating water (CEN/TR 16911: 2016).

The meter is only suitable for circulating water in heating systems.

The meter is not suitable for drinking water.

Do not lift the meter by the electronic unit.

Be aware of sharp points on the edges, flange and measuring tube.

Only personnel, trained in the installation and operation of meters in heating and cooling systems, may install and remove the meter.

Only install or remove the meter when the pipes arepressure-less.

After installing the meter, check the leak-tightness of the system.

Guarantee and calibration validity will lapse if the calibration relevant security seals are broken.

Only clean the meter from outside with a soft, lightly wetted cloth. Do not use any spirit or cleaning solvent.

The 110 V / 230 V connections may only be made by an electrician.

The meter may only be powered up once the installation has been completed. There is otherwise a danger of electronic shock on the terminals.  A defective or obviously damaged appliance must be disconnected from the power supply immediately and replaced.

As far as disposal is concerned, the meter is a waste electronic appliance in the sense of European Directive 2012/19/EU (WEEE) and it must not be disposed of as domestic waste. The relevant national, legal regulations must be observed as the appliance   must be disposed of via the channels provided for this purpose. The local and currently valid legislation mustbe observed.

The meter contains lithium batteries. Do not dispose of the meter and the batteries with domestic waste. Observe the local  stipulationsand laws on disposal.

You can return the lithium batteries to the manufacturer for appropriate disposal following use. When shipping please observe legal regulations, in particular, those governing the labelling and packaging of hazardous goods.

Do not open the batteries. Do not bring batteries intocontact with water or expose to temperatures above 80 °C.

The meter does not have any lightning protection. Ensure lightning protection via the in-house installation.

Only fit one compartment for the power supply. Do not remove the red locking hatch.

Operating

Operating elements

Operating elements

Number Description
1; 6; 7; 8 Cover lugs
2 Button 1
3 Button 2
4 LCD
5 Security seal

Note: Both display range and data displayed can differ from the description depending on the appliance parameterisation. Certain  utton functions can also be blocked.

Displaying current meter status

The meter displays the current meter status in kWh, MWh, MJ or GJ.

Note: In order to prevent reading errors, the decimal places of the values displayed are marked with a frame.
Note: Calibrated values can be recognised by an additionally displayed star symbol.

Display values

Switch to the service loops to display the values. Proceed as follows:

  • To switch from the user loop into the service loops press button 1. The displays of the meter are arranged in several levels (LOOPs).
  • To switch the LCDs between the loops press button 1. The LCD shows the following values one after the other:

Service loop 1

Service loop 2

After the last loop is displayed, the user loop “LOOP 0” comes up again.

Switching in a loop

Proceed as follows to switch to the next display value within a
loop:

  • Press button 2.

The first display value will appear again after the final display value.

User loop “LOOP 0“

The meter is located in the user loop “LOOP 0“.

  • To switch to the next display value press button 2.

The LCD displays the following values one after the other:

Energy accumulated with tariff status
Tariff register 1 (optional)
Volume accumulated
Segment test
Head of the loop
In case of error: message with error code

Service loop 1 “LOOP 1“

Service loop 1 displays the details of the current measurement. The LCD shows the following values one after the other:

Head of the loop
Current flow
Current power
TV current temperature hot side,
TR current temperature cold side;
in 2-sec. cycles
Operating time
Operating time with flow
Missing time
Property number, 8-digit
Date
Yearly set day (DD.MM)
Energy: previous year on set day
Volume: previous year on set day
Firmware version

Service loop 2 “LOOP 2“

Service loop 2 displays the measurement period for establishing the maximum. The LCD shows the following values one after the other:

Head of the loop
Measurement period for establishing the maximum

Service loop 3 “LOOP 3“

Service loop 3 displays the monthly values.

  • In order to display the monthly values, press button 2. The set day of the current month is displayed.
  • To select the desired month, press button 1.

Head of the loop

Set day for July 2011

  • To request the associated values, press button 2. The LCD displays the following values one after the other:

Energy on the set day
Tariff register 1 on the set day
Volume on the set day
Max. flow on the set day,
in 2-sec. cycles with date stamp
Max. power on the set day,
in 2-sec. cycles with date stamp
Max. temperatures on the set day,
in 2-sec. cycles with date stamp
MV for hot side or MR for cold side
Missing time count on the set day
Display values

After the last display the previously selected set day is displayed once again.

  • To select the next set day, press button 1.

Stop “LOOP 3“

To go into the next loop early, proceed as follows:

  • Select a monthly value with button 2.
  • Press button 1.

Service loop 4 “LOOP 4“

Service loop 4 displays appliance parameters.
The LCD displays the following values one after the other:

Head of the loop
Current tariff,
in 2-sec. cycles with threshold value 1
Measurement interval flow
Measurement interval temperature
Module 1: M-Bus module
M-Bus primary address 1
M-Bus secondary address 8-digit
Module 2: Pulse module; channel 1 = energy,
channel 2 = volume; in 2-sec. cycles
Value for energy pulses )
Value for volume pulses
)
Pulse duration in in ms )
) for “fast pulse“
Display values

Previous year’s values

The meter saves the following values on the yearly set day

  • Energy (meter status)
  • Volume (meter status)
  • Tariff register (meter status)
  • Missing time (meter status)
  • Flow measurement time (meter status) and the maxima with date stamp for
  • Flow
  • Power
  • Temperature difference
  • Temperature hot side
  • Temperature cold side

Monthly values

The meter stores the following values for 60 months on the monthly set day

  • Energy (meter status)
  • Volume (meter status)
  • Tariff register (meter status)
  • Missing time (meter status)
  • Flow measurement time (meter status) and the maxima with date stamp for
  • Flow
  • Power
  • Temperature difference
  • Temperature hot side
  • Temperature cold side

The monthly values can be read via the optical and the 20 mAinterface

Note: Central European Time (CET) applies as the standard time. During summer time the storage takes place at the corresponding times.

Error Messages

The meter continuously runs a self-diagnosis and can thus recognise and display various installation or meter error messages. The error message F0 means that no flow measurement is possible, due to air in the volume measurement unit for example; the system must be vented carefully. The error message F4 means the battery must be replaced. When any of the error messages F1, F2 or F5, F6, F8 are displayed, the temperature sensors are defective. The messages F3, F7, F9 mean a defect in the electronic. Contact the service department in all these cases.

Functional Details

If the respective operation thresholds are exceeded and flow and temperature difference are positive, the meter summates the energy and the volume. All segments of the display are switched on for control purposes during the segment test. On the yearly set day, the meter status for energy and volume, the values for the maxima and flow and missing hours arelogged in the previous year’s archive. Flow, power and temperature difference are recorded with the appropriate +/- signs. If the operation threshold has dropped a “u“ is displayed in front. The current temperatures are displayed to an accuracy of 0.1 °C. For maximum formation the power and flow over the measurement period (of  e.g. 60 mins.) are averaged. The maximum values of the average value formation are marked with “Ma“ in   front. The maximum values of the temperatures are marked with “MV“ or “MR“. The 8-digit property number (also the secondary address for M-Bus operation) can be set in the parameterisation mode. The meter number is issued by the manufacturer. The operating time is counted from the first connection of the power supply. Missing hours are summated if there is an error and the meter is thus unable the measure. The date is incremented on a daily  basis.The type of modules installed is displayed. If an M-Bus module is installed, the primary and secondary address is displayed in the subsequent lines. The number for the firmware version is issued by the manufacturer.

Technical Data

Note: The information on the meter must be observed!

General

Measuring accuracy: Class 2 or 3 (EN 1434)
Environment class: A (EN 1434) for indoor installation
Mechanical class: M1 )
Electromagnetic class: E1
)
*) according to 2014/32/EU Directive on Measuring Instruments
Ambient humidity: < 93 % rel. humidity at 25 °C, without condensation
Max. height:  2000 m above sea level
Storage temperature: -20 … 60 °C

Electronic unit

Ambient temperature: 5 … 55 °C
Housing protection rating: IP 54 according to EN 60529
Safety class
Line 110 / 230 V AC: II according to EN 61558
Line 24 V ACDC: III according to EN 61558
Operation threshold f.T: 0.2 K
Temperature difference: T 3 K … 120 K
Temperature measurement range: 2 … 180 °C
LCD: 7 digits
Optical interface: Standard, EN 62056-21
Communication: Optional, e.g. M-Bus
Separability: Always, optional cable length

Sensor

Type: Pt 500 or Pt 100
According to: EN 60751
Temperature range: 0 … 150 °C (up to 45 mm overall length) 0 … 180 °C (from 100 mm overall length)

Volume measurement unit

Protection class: IP 54 / IP 65 according to EN 60529 IP 68 (at qp 150) according to EN 60529
Mounting place: Hot side / cold side
Installation position: Any
Flow straightening: None
Measuring range 1: 100
Temperature range: 5 … 130 °C National type approvals may be different. recommended…
heating application: 10 … 130 °C
cooling application: 5 … 50 °C
Maximum overload: 2.8 × qp
Nominal pressure: PN16 (PS16), PN25 (PS25)

Declaration of conformity

EC Declaration of Conformity No. CE UHSO 018 / 10.21 Product description:

Manufacturer: Landis,_ IGYr Ultrasonic heat meter ULTRAHEAT®T550 (UHSO…) Landis+Gyr GmbH, Humboldtstrasse 64, 90459 Nuremberg, Germany

The notified authority (PTB, 0102) has tested the technical design and certified that it meets the requirements applicable for the device and has issued the following certificate: DE-07-M1004-PTB010, DE-06-M1004-PTB018 and DE 08-M1004-PTB017 The notified authority (PTB, 0102) has evaluated the quality assurance system and recognises it in: DE-M-AQ-PTB006

Brunner, Managing Director Name, Position
Signature

Sturek, Head R&D Name, Position Signature

This declaration certifies conformity with the stated directives and standards, it does not however constitMe a commitment to any specific properties! The safety instructions included in the product documentation must be followed!

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Landis Gyr User Manuals

Related Manuals