Olympia-Electronics GR-1926/4P Emergency Lighting Owner’s Manual

September 29, 2024
olympia electronics

Olympia-Electronics GR-1926/4P Emergency Lighting

Specifications

  • Operation Voltage: 85-250V DC, 100-250V AC/50-60Hz
  • Maximum Power Consumption: 5.3W / 5.4VA, 6.3W / 7VA, 1.5W / 1.9VA, 2.8W / 3.1VA
  • Wire Cross Section: 0.8 – 1.5 mm2
  • Light Source: 4 white LEDs, 6 white LEDs, 15 white LEDs, 30 white LEDs
  • Light Source Luminous Flux: 460 lm, 580 lm, 125 lm, 250 lm
  • Degrees of Cover Protection: IP65
  • Viewing Distance (as safety sign): 22m
  • Operation Temperature Range: -30 to 50 oC
  • Relative Humidity: Up to 95%
  • Construction Material: ABS/PC, PC
  • External Dimensions (L x W x H): 315 x 120 x 65 mm
  • Weight: 550g
  • Guarantee: 3 years

Product Usage Instructions

Luminaire Assembly
To dismantle the luminaire, follow these steps:

  1. Remove the diffuser by gently lifting it upwards after unclipping the plastic latches.
  2. Refit the diffuser carefully ensuring it aligns with the holes.
  3. Secure the plastic latches with a click sound and fasten the screws with a tightening torque of 1.2N*m.

Installation Process
To install the luminaire, perform the following steps:

  1. Install the two rubber gaskets to the holes of the base without deforming them.
  2. Connect the mains cable according to the provided connection diagrams (N for neutral, L for live wire) after isolating the mains power supply.
  3. Fit the screws with metallic washers and rubber sealing rings to preserve the IP65 rating.
  4. Refit the reflector ensuring it aligns with the holes of the indications.

Frequently Asked Questions (FAQ)

  • Q: Can the light source in the luminaire be replaced by the user?
    A: No, the light source contained in this luminaire should only be replaced by the manufacturer, his agent, or a qualified person.

  • Q: What is the difference between Maintained and Non-Maintained operation?
    A: In Maintained operation, the luminaire lights its illumination source when powered by mains supply or not. In Non-Maintained operation, it lights only during power supply failure.

  • Q: What should be done if the plastic latches are clipped during assembly?
    A: Carefully insert a flat-blade screwdriver to unclip them before lifting the diffuser upwards to detach it.

GR-1926/4P
GR-1926/6P
GR-1926/15L
GR-1926/30L

WATERPROOF EMERGENCY LUMINAIRE FOR CBS

Thank you for your trust in our products Olympia Electronics – European manufacturer

Package Contents

  1. Luminaire
  2. Pictograms (R/L/D)
  3. Mounting accessories
  4. Manual

General

These devices are used in places (ta 50oC) where emergency light is needed (CBS). Each device must be permanently connected to mains power supply.

ΑΤΤΕΝΤΙΟΝ!!!

  1. Operations for installation, maintainance or testing must be done by authorized personnel only.
  2. Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type

2x1mm² or any other type, at least equal to it’s mechanical and electrical properties). ATTENTION!! The cable must not be deformed in any way (This requirement is important to ensure the ΙΡ rating).

Dimensional drawing: 315 x 120 x 65 mm

Installation

To dismantle the luminaire, simply remove the difussor.
ATTENTION! If the 2 plastic latches (A) are clipped, carefully insert a flat-blade screwdriver to unclip them. Then, gently lift the diffuser (B) upwards to detach it.

  1. Place a flat blade screwdriver to the recesses (A) and pull up gently the reflector (B) to remove it.

  2. Install the two rubber gaskets to the holes of the base. Make sure that they are not deformed.

  3. Install the plastic base (with the included mounting accessories).
    WARNING!! To preserve the IP65 rating, fit the screws with the metallic washers and rubber sealing rings.

  4. Make a hole in the center of the rubber gasket by using a small screwdriver. Pass the round cable through the rubber gasket. Connect the mains cable according to the connections diagrams above. Ν for neutral, L for live wire WARNING!! Isolate the mains power supply before making the connections.

  5. Install the included tie-wrap to the adhesive tether loop and fasten securely the power cable in order to anchor it.

  6. Refit the reflector (Mind the holes of the indications).

  7. Refit the diffusor (Mind the holes of the indications).

  8. The plastic latches (A) must be secured (click sound). Fasten the 2 screws (B). (Tightening torque 1.2N*m)

NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
Z: Central Supply
1: Maintained/non-maintained operation ()
G: Internally illuminated safety sign
(
) Maintained operation: The luminaire lights its illumination source, when it is powered by the mains power supply or not.
Non Maintained operation: The luminaire lights its illumination source, only in power supply’s failure.
Note!! The installer should fill in, on the specification label, the letter G if the luminaire is used as a safety sign.

ATTENTION
The light source contained in this luminaire shall only be replaced by the manufacturer, or his agent, or a similar qualified person.

NOTE! The light source is non-user replaceable.

Technical Characteristics

GR-1926/4P GR-1926/6P GR-1926/15L GR-1926/30L

OPERATION VOLTAGE 85-250V DC, 100-250V AC/50-60Hz
MAXIMUM POWER CONSUMPTION                5.3W / 5.4VA| 6.3W / 7VA| 1.5W / 1.9VA| 2.8W / 3.1VA
WIRE CROSS SECTION 0.8 – 1.5 mm2
LIGHT SOURCE                                                           4 white LEDs| 6 white LEDs| 15 white LEDs| 30 white LEDs
LIGHT SOURCE LUMINOUS FLUX                                     460 lm| 580 lm| 125 lm| 250 lm

  • DEGREES OF COVER PROTECTION IP65
  • PRODUCED IN ACCORDANCE WITH  EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
  • VIEWING DISTANCE (as safety sign) 22m
  • OPERATION TEMPERATURE RANGE -30 to 50 oC
  • RELATIVE HUMIDITY Up to 95%
  • CONSTRUCTION MATERIAL ABS/PC, PC
  • EXTERNAL DIMENSIONS (L x W x H) 315 x 120x 65 mm
  • WEIGHT 550gr.
  • GUARANTEE 3 years

LED Characteristics

MANUFACTURER Olympia Electronics S.A.

MODEL NUMBER 1509153/4P| 1509153/6P| 2402159/15L| 2402159/30L
VOLTAGE RANGE 11.6-13.6V DC| 8.5-10.5V DC
NOMINAL POWER 4W| 6W| 1W| 2W
CONNECTIONS                                                       Non reversible connection between main pcb and led module
TEMPERATURE (tc)                                                     55OC max. across the board| 47OC max. across the board

Warranty

Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged can be returned to the premises of our company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece www.olympia- electronics.com
info@olympia-electronics.gr

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

olympia electronics User Manuals

Related Manuals