MOXA EDS-4009-3MSC(-T) Ether Device Switch Installation Guide
- September 28, 2024
- MOXA
Table of Contents
MOXA EDS-4009-3MSC(-T) Ether Device Switch
Specifications
- Model: EDS-4009 Series
- Type: Industrial DIN-rail EtherDevice Switch (EDS)
- Ports: 9 ports (3 100BaseFX, 6 10/100BaseT)
- LED Indicators: Various indicators for status monitoring
- Interfaces: Console port (RJ45, RS-232), USB storage port (type A)
- Mounting Options: DIN-rail mounting, Wall mounting
Product Usage Instructions
DIN-rail Mounting
The DIN-rail mounting kit is pre-installed on the EDS device.
Follow these steps to mount the device:
- Insert the upper lip of the DIN rail into the mounting kit.
- Press the EDS device towards the DIN rail until it snaps into place.
Removal
To remove the EDS device from the DIN rail:
- Pull down the latch on the mounting kit with a screwdriver.
- Slightly pull the EDS device forward and lift up to remove it from the DIN rail.
Wall Mounting (Optional)
If wall mounting is preferred, follow these steps:
- Remove the DIN-rail attachment plate from the rear panel of the EDS device.
- Attach the wall mount plates with M3 screws.
- Use four screws with specific size requirements to mount the EDS device on the wall.
Wiring Requirements
Connect power input, digital input, and relay output using the terminal
blocks provided.
FAQ
-
Q: Where can I find software downloads and additional information?
A: You can visit Moxa’s website at www.moxa.com for software downloads and product information. -
Q: How do I reset the device?
A: Use the reset button located near the microSD card slot to reset the device to default settings.
EDS-4009 Series Quick Installation Guide
Moxa EtherDevice™ Switch
Version 1.2, April 2024
Technical Support Contact Information www.moxa.com/support
2024 Moxa Inc. All rights reserved.
P/N: 1802040090012
Package Checklist
The EDS-4009 Series industrial DIN-rail EtherDevice Switch (EDS) is shipped with the following items. If any of these items are missing or damaged, please contact your customer service representative for assistance.
- 1 EDS-4009 Ethernet switch
- Quick installation guide (printed)
- Warranty card
- Substance disclosure table
- Product certificate of quality inspection (Simplified Chinese)
- Product notices (Simplified Chinese)
NOTE You can find information and software downloads on the relevant product pages located on Moxa’s website: www.moxa.com
Default Settings
- IP address: 192.168.127.253
- Subnet Mask: 255.255.255.0
- Username: admin
- Password: moxa
Panel Views of EDS-4009 Series
- 100BaseT(X) LED indicator
- 10BaseT(X) LED indicator
- 10/100BaseT(X) ports, port 4 to 9
- 100BaseFX port (SC/ST type), port 1 to 3
- 100BaseFX LED indicator
- Grounding connector screw
- Terminal blocks for power input, digital input, and relay output
- LED indicators: STATE (S), FAULT (F), PWR1 (P1), PWR2 (P2), MSTR/HEAD (M/H), CPLR/TAIL (C/T), SYNC
- Console port (RJ45, RS-232)
- USB storage port (type A)
- Model name
Bottom Panel View
- microSD card slot
- Reset button
- DIP switches for Turbo Ring, Ring Master, and Ring Coupler
Mounting Dimensions
EDS-4009-3MSC(-T)/EDS-4009-3SSC(-T) Models
EDS-4009-3MST(-T) Models
DIN-rail Mounting
The DIN-rail mounting kit is fixed to the back panel of the EDS device when
you take it out of the box. Mount the EDS device on corrosion-free mounting
rails that meet the EN 60715 standard.
Installation
STEP 1—Insert the upper lip of the DIN rail into the DIN-rail mounting
kit.
STEP 2—Press the EDS device towards the DIN rail until it snaps into
place.
Removal
STEP 1—Pull down the latch on the mounting kit with a screwdriver.
STEP 2 & 3—Slightly pull the EDS device forward and lift up to remove it
from the DIN rail.
NOTE Our DIN rail kit now utilizes a quick release mechanism to make it easier for users to remove the DIN rail from the EDS device.
Wall Mounting (Optional)
For some applications, you will find it convenient to mount the Moxa EDS
device on a wall, as shown in the following illustrations:
STEP 1—Remove the DIN-rail attachment plate from the rear panel of the EDS device, and then attach the wall mount plates with M3 screws. STEP 2—Mounting the EDS device on a wall requires four screws. Use the EDS device, with wall mount plates attached. The heads of the screws should be less than 6.0 mm in diameter, and the shafts should be less than 3.5 mm in diameter, as shown in the figure on at right.
NOTE
Before tightening the screws into the wall, make sure the screw head and shank
size are suitable by inserting the screw through one of the keyhole-shaped
apertures of the Wall Mounting Plates.
NOTE Do not screw the screws in all the way—leave about 2 mm to allow room for sliding the wall mount panel between the wall and the screws.
STEP 3 —Once the screws are fixed to the wall, insert the four screw heads through the wide parts of the keyhole-shaped apertures, and then slide the EDS device downwards, as indicated in the figure at the right. Tighten the four screws for more stability.
Wiring Requirements
ATTENTION
Safety First!
External metal parts are hot. Take the necessary precautions if you are
required to handle the device.
ATTENTION
In order to ensure reliable operations, please make sure the operating
temperature of the environment does not exceed the specifications. When
mounting an EDS device with other operating units in a cabinet without forced
ventilation, a minimum of 4 cm space on both the left and right of the switch
is recommended.
ATTENTION
Safety First!
Be sure to disconnect the power cord before installing and/or wiring your EDS
device. Calculate the maximum possible current in each power wire and common
wire. Observe all electrical codes dictating the maximum current allowable for
each wire size. If the current goes above the maximum ratings, the wiring
could overheat, causing serious damage to your equipment.
Be sure to read and follow these important points below:
- Use separate paths to route wiring for power and devices. If power wiring and device wiring paths must cross, make sure the wires are perpendicular at the intersection point.
NOTE Do not run signal or communications wiring and power wiring through the same wire conduit. To avoid interference, wires with different signal characteristics should be routed separately.
- You can use the type of signal transmitted through a wire to determine which wires should be kept separate. The rule of thumb is that wiring that shares similar electrical characteristics can be bundled together.
- You should separate input wiring from output wiring.
- We advise that you label the wiring to all devices in your system.
Grounding the Moxa EDS Series
Grounding and wire routing help limit the effects of noise due to
electromagnetic interference (EMI). Run the ground connection from the ground
screw (M4) to the grounding surface prior to connecting devices.
NOTE The grounding wire should have a minimum diameter of 1.5 mm2.
ATTENTION
This product is intended to be mounted to a well-grounded mounting surface
such as a metal panel.
Suggested Wire Type for Wiring Relay Contact
(RELAY), Digital Input (DI), and Power Inputs
(P1/P2)
The EDS device includes two 4-pins 3.5 mm pin-pitch terminal blocks. When
wiring the relay contact (RELAY), digital input (DI), and power inputs
(P1/P2), we suggest using the cable type – AWG 18-24 and the corresponding pin
type cable terminals.
NOTE
The wire must be able to withstand at least 105°C and the torque value should
be 4.5 lb-in (0.51 N-m).
NOTE We suggest the length of the pin type cable terminal is 8 mm.
In order to tighten the wire properly, ① use a small flathead screwdriver to
press the push-in button beside each terminal of the terminal block connector
before and during ② inserting the wire. ③ Release the screwdriver after the
wire has been fully inserted. Please refer to the diagram below.
Wiring the Relay Contact
The EDS device has one set of relay output. This relay contact uses two
contacts of the terminal block on the EDS’s power module. Refer to the
following section for detailed instructions on how to connect the wires to the
terminal block connector, and how to attach the terminal block connector to
the terminal block receptor.
Relay:
The two contacts of the 4-pin terminal block connector are used to detect
user-configured events. The two wires attached to the fault contacts form an
open circuit when a user-configured event is triggered or there is no power
supply to the switch. If a user-configured event does not occur, the fault
circuit remains closed.
Wiring the Redundant Power Inputs
The EDS device includes both high-voltage and low-voltage products. For the
low-voltage (LV models) products, there are two power inputs for redundancy;
for the high-voltage (HV models) products, there is only one power input. Both
use terminal block connectors on the right side panel of the product. Refer to
the instructions and diagram below on how to connect the wires to the terminal
block connector on the receptor.
STEP 1: Insert the Positive/Negative DC or Line/Neutral AC wires into the
V+/V- or L/N terminals, respectively.
STEP 2: To keep the DC or AC wires from pulling loose, use a small flat-
blade screwdriver to tighten the wire-clamp screws on the front of the
terminal block connector.
STEP 3: Insert the plastic terminal block connector prongs into the
terminal block receptor, which is located on the EDS devices’ right side.
Wiring the Digital Inputs
The EDS device has one set of digital input (DI). The DI consists of two
contacts of the 4-pin terminal block connector on the EDS’s right-side panel.
Refer to the instructions and diagram below on how to connect the wires to the
terminal block connector on the receptor.
STEP 1: Insert the negative (ground)/positive DI wires into the ┴/I
terminals, respectively.
STEP 2: To keep the DI wires from pulling loose, use a small flat-blade
screwdriver to tighten the wire-clamp button on the front of the terminal
block connector.
STEP 3: Insert the plastic terminal block connector prongs into the
terminal block receptor, which is located on the EDS devices’ right side.
Rotating the Power Module
The power module for the EDS device can be rotated to make it easier to fit
your field site application.
- Step 1: Remove the two screws that fasten the power module to the EDS device.
- Step 2: Remove the power module.
- Step 3: Turn the power module clockwise so that the power, digital input, and relay output connectors can be moved upwards.
- Step 4: Place the module back on to the EDS device and then fasten the two screws on to the module.
Communication Connections
Each EDS-4009 Series switch has various types of communication ports:
- RJ45 console port (RS-232 interface)
- USB storage port (type A connector)
- microSD card slot
- 10/100BaseTX Ethernet ports
- 100BaseFX (SC/ST-type connector) fiber ports
Console Port Connection
The EDS device has one RJ45 console port (RS-232), located on the front panel.
Use either an RJ45-to-DB9 (see the cable following wiring diagrams) to connect
the EDS’s console port to your PC’s COM port. You may then use a console
terminal program, such as Moxa PComm Terminal Emulator, to access the EDS that
has a baud rate of 115200.
RJ45 Console Port Pinouts
Pin | Description |
---|---|
1 | DSR |
2 | RTS |
3 | – |
4 | TxD |
5 | RxD |
6 | GND |
7 | CTS |
8 | DTR |
USB Connection
NOTE The USB port is reserved for use with the Moxa ABC-02-USB tool. This port cannot be used for charging any devices.
10/100BaseT(X) Ethernet Port Connection
The 10/100BaseT(X) ports located on the front panel of the switch are used to connect to Ethernet-enabled devices. Most users will choose to configure these ports for Auto MDI/MDI-X mode, in which case the port’s pinouts are adjusted automatically depending on the type of Ethernet cable used (straight-through or cross-over), and the type of device (NIC-type or HUB/Switch-type) connected to the port.
In what follows, we give pinouts for both MDI (NIC-type) ports and MDI-X (HUB /Switch-type) ports. We also give cable wiring diagrams for straight-through and cross-over Ethernet cables.
10/100Base T(x) RJ45 Pinouts
MDI Port Pinouts
Pin | Signal |
---|---|
1 | Tx+ |
2 | Tx- |
3 | Rx+ |
6 | Rx- |
MDI-X Port Pinouts
Pin | Signal |
---|---|
1 | Rx+ |
2 | Rx- |
3 | Tx+ |
6 | Tx- |
RJ45 (8-pin) to RJ45 (8-pin) Straight-Through Cable Wiring
RJ45 (8-pin) to RJ45 (8-pin) Cross-Over Cable Wiring
100BaseFx Ethernet Port Connection
The concept behind the SC/ST port and cable is quite straightforward. Suppose
you are connecting devices I and II. As opposed to electrical signals, optical
signals do not require a circuit in order to transmit data. Consequently, one
of the optical lines is used to transmit data from device I to device II, and
the other optical line is used transmit data from device II to device I, for
full-duplex transmission.
All you need to remember is to connect the Tx (transmit) port of device I to
the Rx (receive) port of device II, and the Rx (receive) port of device I to
the Tx (transmit) port of device II. If you are making your own cable, we
suggest labeling the two sides of the same line with the same letter (A-to-A
and B-to-B, as shown by the following illustration, or A1-to-A2 and B1-to-B2).
SC-Port Pinouts SC-Port to SC-Port Cable Wiring
ST-Port Pinouts ST-Port to ST-Port Cable Wiring
ATTENTION
This is a Class 1 Laser/LED product. To prevent damage to your eyes, do not
stare directly into the laser beam.
Reset Button
There are two functions available on the Reset Button. One is to reset the
Ethernet switch to factory default settings by pressing and holding the Reset
button for 5 seconds. Use a pointed object, such as a straightened paper clip
or toothpick, to depress the Reset button. This will cause the STATE LED to
blink once a second. After depressing the button for 5 continuous seconds, the
STATE LED will start to blink rapidly. This indicates that factory default
settings have been loaded and you can release the reset button. The other
function is to reboot the device by depressing the reset button for less than
five seconds.
Turbo Ring DIP Switch Settings
The EDS devices are plug-and-play managed redundant Ethernet switches. The
proprietary Turbo Ring protocol was developed by Moxa to provide better
network reliability and faster recovery time. Moxa Turbo Ring’s recovery time
is less than 50 ms (Turbo Ring 2)—compared to a 3- to 5-minute recovery time
for commercial switches—decreasing the possible loss caused by network
failures in an industrial setting.
There are five Hardware DIP Switches for Turbo Ring on the bottom panel of the
EDS device that can help setup the Turbo Ring easily within seconds. If you do
not want to use a hardware DIP switch to setup the Turbo Ring, you can use a
web browser, telnet, or console to disable this function.
NOTE
Please refer to the Turbo Ring section in User’s Manual for more detail
information about the setting and usage of Turbo Ring V2.
Turbo Ring DIP Switch Settings
The default setting for each DIP Switch is OFF. The following table explains
the effect of setting the DIP Switch to the ON position.
Remove the rubber cover on the bottom panel of the device to expose the DIP
switches.
DIP Switch Settings
NOTE
You must enable the Turbo Ring (DIP switch 5) first before using the DIP
switch to activate the Master and Coupler functions.
NOTE
If you do not enable any of the EDS switches to be the Ring Master, the
Turbo Ring protocol will automatically choose the EDS switch with the smallest
MAC address range to be the Ring Master. If you accidentally enable more than
one switch to be the Ring Master, these switches will auto-negotiate to
determine which one will be the Ring Master.
LED Indicators
The front panel of the Moxa EDS-4009 Series contains several LED indicators.
The function of each LED is described in the following table:
Device LED Indicators
LED | Color | State | Description |
---|
STATE
| ****
Green
| ****
On
| When system has passed power- on self-test (POST) and is ready to run.
Blinking (1 time/sec)
|
- When pressing down the reset button for 1 second to reboot the switch.
- Initializing system services.
Blinking
(4 times/sec)
|
- When pressing down the reset button for 5 seconds to reset the switch.
- An external storage device is connected to the switch.
Off| N/A
Red
| ****
On
| The system has initially failed the boot-up process
- System Info. Read Fail or
EEPROM information error
**FAULT**
| ****
Red
| **On**|
- Network loop detected when loop protection is enabled.
- The relay contact is triggered.
- Loading from or saving to the external storage failed.
- The port is disabled because the ingress rate limit for shut down mode was exceeded.
- Invalid Ring port connection.
**Off| When the system boots up and runs correctly or a user-
configured event is not triggered.
****P1| ****Amber| On| Power is being supplied to power input
PWR.
Off| Power is not being supplied to power input PWR.
LED| Color| State| Description
---|---|---|---
****P2| ****Amber| On| Power is being supplied to power input
PWR.
Off**| Power is not being supplied to power input PWR.
MSTR/ HEAD (M/H)
| ****
Green
| **On**| When the switch is Master/Head/Manager of Turbo
Ring/Turbo Chain/MRP.
**Blinking**
(4 times/sec)
|
- The switch has become the Master of Turbo Ring after the Turbo Ring has gone down.
- The switch is set as the Head of Turbo Chain and the Turbo Chain has gone down.
- The switch is set as a Turbo Ring Member and the corresponding Ring port is down.
- The switch is set as the Turbo Chain’s Member/Tail and the corresponding Head-end Chain port is down.
- The switch has become the Manager of the MRP Ring and the ring is open.
**Off| When the switch is not the Master/Head/Manager of this Turbo
Ring/ Turbo Chain/MRP Ring.
****CPLR/ TAIL| **
**Green**
| **On**|
- The switch’s ring coupling or dual homing function is enabled.
- The switch is set as the Tail of Turbo Chain.
**Blinking (4 times/sec)**|
- The switch is set as the Tail of Turbo Chain and the Chain has gone down.
- The switch is set as the Turbo Chain’s Member/Head and the corresponding Tail-end Chain port is down.
**Off**| When the switch disables the coupling or tail role of Turbo Chain.
SYNC
| **Amber| ****On| PTP has been initiated, but the switch has not
yet received a sync packet and is running in Free Run status.
Blinking**
(4 times/sec)
| The switch has received the sync packet and is in the process of
synchronizing clocks.
Off| The PTP function is disabled.
Green| On| The switch clock is synchronized.
Off| The PTP function is disabled.
LED| Color| State| Description
---|---|---|---
System LED (Except PWR)| Green + Amber + Red|
**Blinking (2 times/sec)| The switch is being discovered/located by
the locator function.
System LED (Except PWR)| Green + Amber + Red| Rotate
On - > Off **Sequentially| The switch is importing/exporting a file via
the ABC-02-USB or ABC- 03-microSD-T.
Ports LED Indicators
LED | Color | State | Description |
---|---|---|---|
**10M/ 100M Copper top LED** | **Green** | On | When the |
port is active and links at 100Mbps.
Blinking| When the port’s data is being transmitted at 100Mbps.
Off| When the port is inactive or link down.
10M/ 100M Copper bottom LED| **Amber| On| When the
port is active and links at 10Mbps.
Blinking| When the port’s data is being transmitted at 10Mbps.
Off| When the port is inactive or link down.
****100M**
Fiber LED
| **Green| On**| When the port’s data is being
transmitted at 100Mbps.
Blinking| When the port’s data is being transmitted at 100Mbps.
Off| When the port is inactive or link down.
Specifications
Interface
RJ45 Ports| 10/100BaseT(X) or 10/100/1000BaseT(X)
Fiber Ports| 100BaseFx
Console Port| RS-232 (RJ45)
Button| Reset button
LED Indicators| STATE (S), FAULT (F), PWR1 (P1), PWR2 (P2), MSTR/HEAD (M/H),
CPLR/TAIL (C/T), SYNC
Alarm Contact| 1 normally open electromagnetic relay output with current
carrying capacity of 1 A @ 24 VDC
Digital Input|
- 1 isolated digital input:
- +13 to +30V for state “1”
- -30 to +3V for state “0” Max. input current: 8 mA
Power
Pre-installed Power Module|
- -LV/-LV-T models: PWR-100-LV
- -HV/-HV-T models: PWR-105-HV-I
Note| The EDS-4009 Series supports modular power supplies. The model names and power parameters are determined by the installed power module.
For example:
EDS-4009-T + PWR-100-LV = EDS-4009-LV-T EDS-4009-T + PWR-105-HV-I = EDS-4009-HV-T
If you install a different power module, refer to the specifications of the corresponding model. For example, if you replace the power module of the EDS-4009-LV-T with the PWR-105-HV-I, refer to the specifications of the EDS-4009-HV-T.
---|---
Rated Voltage| -LV/-LV-T models: 12/24/48 VDC, redundant dual inputs
-HV/-HV-T models: 110/220 VDC/VAC, single input
Operating Voltage| -LV/-LV-T models: 9.6 to 60 VDC
-HV/-HV-T models: 88 to 300 VDC, 85 to 264 VAC
Rated Current|
- -LV/-LV-T models: 12-48 VDC, 1.50-0.40 A or 24 VDC, 0.70 A
- -HV/-HV-T models:110-220 VAC, 50-60 Hz, 0.30- 0.20 A or 110-220 VDC, 0.30-0.20 A
Power Consumption| EDS-4009-3MSC-LV(-T) models: 9.51 W EDS-4009-3MSC-HV(-T)
models: 12.14 W EDS-4009-3MST-LV(-T) models: 9.51 W EDS-4009-3MST-HV(-T)
models: 12.17 W EDS-4009-3SSC-LV(-T) models: 9.51 W EDS-4009-3SSC-HV(-T)
models: 12.34 W
Inrush Current| Max. 0.58 A @ 48 VDC (0.1 – 1 ms) (Applied to –
LV models)
Overload Current Protection at Input| Supported
Reverse Polarity
Protection
| Supported
Connection| 2 removable 4-contact terminal blocks
Physical Characteristics
Housing| Metal, IP40 protection
Dimension| EDS-4009-3MSC(-T)/EDS-4009-3SSC(-T) models:
55 x 140 x 120 mm (2.17 x 5.51 x 4.72 in)
EDS-4009-3MST(-T) models:
55 x 140 x 132 mm (2.17 x 5.51 x 5.20 in)
Weight|
- EDS-4009-3MSC(-T) models: 821.5 g (1.81 lb)
- EDS-4009-3MST(-T) models: 920 g (2.03 lb)
- EDS-4009-3SSC(-T) models: 932 g (2.05 lb)
Installation| DIN-rail mounting, wall mounting (with optional
kit)
Environmental Limits
Operating Temperature| -10 to 60°C (14 to 140°F) for standard models
-40 to 75°C (-40 to 167°F) for -T models
Storage Temperature| -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity| 5 to 95% (non-condensing)
Altitude| Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitude.
---|---
Regulatory Approvals
Industrial Cybersecurity| IEC 62443-4-1, IEC 62443-4-2
Safety| UL 61010-2-201, EN 62368-1(LVD)
EMC| EN 55032/35, EN 61000-6-2/6-4
EMI| FCC Part 15 Subpart B Class A
EMS|
- EN 61000-4-2 (ESD) Level 4
- EN 61000-4-3 (RS) Level 3
- EN 61000-4-4 (EFT) Level 4
- EN 61000-4-5 (Surge) Level 4
- EN 61000-4-6 (CS) Level 3
- EN 61000-4-8 Level 4
Shock| IEC 60068-2-27
Free Fall| IEC 60068-2-32
Vibration| IEC 60068-2-6
Hazardous Location| Class I Division 2, ATEX, IECEx
Rail Traffic
(Wayside)
| EN 50121-4
Traffic Control| NEMA TS2
Warranty
Warranty| 5 years
ATTENTION
This device complies with Part 15 of the FCC rules. Operation is subject to
the following conditions:
- This device may not cause harmful interference.
- This device must accept any interference received including interference that may cause undesired operation.
Hazardous Location Information (except for PoE and HV models)
ATEX information| **** II 3G Ex ec nC IIC T4 Gc UL 22 ATEX 2741X
Ambient Range: -40°C ≤ Tamb ≤ +75°C for -T models Ambient Range: -10°C ≤ Tamb ≤ +60°C for models without “-T”
Rated Cable Temp. ≥ 90.4°C
WARNING-DO NOT SEPARATE WHEN ENERGIZED
---|---
IECEx
Certificate no.
| IECEx UL 22.0031X
---|---
Address of manufacturer| No. 1111, Heping Rd., Bade Dist., Taoyuan City
334004, Taiwan
WARNING – EXPLOSION HAZARD
Do not disconnect this equipment unless the power source has been removed or
turned off, or the installation location is known to be non-hazardous.
Standards and Certifications
Hazardous Location|
- IEC 60079-0, Edition 7
- IEC 60079-7, Edition 5.1
- IEC 60079-15, Edition 5
- EN IEC 60079-0:2018
- EN IEC 60079-7:2015+A1:2018 EN IEC 60079-15:2019
---|---
Specific Condition of Use
- The equipment shall only be used in an area of at least pollution degree 2, as defined in IEC/EN 60664-1.
- The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP 54 in accordance with IEC/EN 60079-0 and accessible only by use of a tool.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>