Honeywell RM7895A Primary Control With Pre And Post Purge Intermittent Pilot Instruction Manual
- September 27, 2024
- Honeywell
Table of Contents
RM7895A Primary Control With Pre And Post Purge Intermittent Pilot
“`html
Product Information
Specifications
-
Product Name: RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800
SERIES Relay Modules -
Functions: Automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics,
troubleshooting, postpurge function (RM7896) -
Environmental Ratings: Ambient Temperature: Maximum 85%
relative humidity continuous, noncondensing, moisture
environment -
Approvals: UL Listed, CSA Certified, Factory Mutual Approved,
IRI Acceptable, FCC Part 15 Class B Emissions
Product Usage Instructions
Installation
When Installing this Product…
-
Read the instructions carefully to prevent damage or hazardous
conditions. -
Check ratings to ensure suitability for the application.
-
Installer must be a trained, experienced flame safeguard
service technician. -
After installation, check product operation as per
instructions.
Warnings:
-
Fire or Explosion Hazard: Follow safety requirements to prevent
property damage or injury. -
Electrical Shock Hazard: Disconnect power supply before
installation.
Important Notes:
-
Wiring connections are unique; refer to Fig. 2 and 3 or
appropriate Specifications for proper subbase wiring. -
Wiring must comply with all codes, ordinances, and
regulations. -
Wiring must comply with NEC Class 1 (Line Voltage) wiring
standards.
Location and Humidity
Install the relay module where humidity never reaches saturation
point. Operate in a maximum 85% relative humidity continuous,
noncondensing, moisture environment to prevent safety shutdown due
to condensing moisture.
FAQ
Q: What should I do if I encounter a safety shutdown due to
condensing moisture?
A: If a safety shutdown occurs due to
condensing moisture, immediately disconnect power supply and dry
out the affected area thoroughly before attempting to restart the
product.
Q: Can the relay modules be used in high-temperature
environments?
A: The relay modules are designed to operate
within specified ambient temperature limits. Ensure the ambient
temperature does not exceed the recommended range to prevent damage
or malfunction.
“`
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES Relay Modules
APPLICATION
The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D are microprocessor-based integrated burner controls for automatically fired gas, oil, or combination fuel single burner applications. They are intended to replace the R4795 and R7795 Primary Controls. The RM7895A,B,C,D/EC7895A; RM7896A,B,C,D systems consist of a relay module, subbase, amplifier, and purge card. Options include keyboard display module (KDM), Personal Computer Interface, Data ControlBusTM Module, remote display mounting, expanded annunciator and Combustion System Manager® Software.
Functions provided by the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. The RM7896 provides a postpurge function.
This document provides installation and static checkout instructions. Other applicable publications are:
Publication No.
63-2278 65-0084
65-0090
65-0091
65-0095 65-0097 65-0101 65-0102
65-0109
Product
Q7700 Network Interface Unit Product Data
Q7800A,B 22-Terminal Wiring Subbase Product Data
S7800A Keyboard Display Module Product Data
S7810A Data ControlBus ModuleTM Product Data
S7820 Remote Reset Module Product Data
221729C Dust Cover Packing Instructions
S7830 Expanded Annunciator Product Data
ZM7850A Combustion System ManagerTM Operating Instructions
R7824, R7847, R7848, R7849, R7851, R7861, R7886 Flame Amplifiers for the 7800
Series Product Data
INSTALLATION INSTRUCTIONS
Publication No.
65-0131
65-0229
65-0092 65-0227
Product
221818A Extension Cable Assembly Product Data
7800 SERIES Relay Modules Checkout and Troubleshooting Product Data.
QS7800A ControlBusTM Module, Standard
QS7800B ControlBusTM Module, Multidrop
SPECIFICATIONS
Electrical Ratings (See Table 3): Voltage and Frequency: RM7895/RM7896: 120
Vac (+10/-15%), 50/60 Hz (± 10%). EC7895A,C: 220/240 Vac (+10%/-15%), 50/60 Hz
(±10%) Power Dissipation: 10W maximum. Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A Fast Blow, type SC or
equivalent.
Environmental Ratings: Ambient Temperature:
Operating: -40°F to 140°F (-40°C to +60°C). Storage: -40°F to 150°F (-40°C to
+66°C). Humidity: 85% relative humidity continuous, noncondensing. Vibration:
0.5G environment.
Approvals: RM7895/RM7896:
Underwriters Laboratories Inc. Listed: File No. MP268, Guide No. MCCZ.
Canadian Standards Association Certified: LR9S329-3. Factory Mutual Approved:
Report No. J.I.1V9A0.AF. IRI Acceptable. Federal Communications Commission:
Part 15, Class B,
Emissions. EC7895A,C:
Factory Mutual Approved.
66-1090-06
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them could damage the
product or cause a hazardous condition.
2. Check the ratings given in the instructions and marked on the product to
make sure the product is suitable for the application.
3. Installer must be a trained, experienced, flame safeguard service
technician.
4. After installation is complete, check out the product operation as
provided in these instructions.
WARNING
Fire or Explosion Hazard. Can cause property damage, severe injury, or death.
Follow applicable safety requirements when installing a control on a burner to
prevent death or severe injury.
WARNING
Electrical Shock Hazard. Can cause serious injury, death or equipment damage.
Disconnect power supply before beginning installation.
IMPORTANT
1. Wiring connections for the relay modules are unique; refer to Fig. 2 and 3
or the appropriate Specifications for proper subbase wiring.
2. Wiring must comply with all applicable codes, ordinances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage) wiring. 4. Loads
connected to the RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D must not exceed those listed on the RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D label or the Specifications; see Table 1. 5. Limits and
interlocks must be rated to simultaneously carry and break current to the
ignition transformer, pilot valve, and main fuel valve(s). 6. All external
timers must be listed or component-recognized by authorities who have proper
jurisdiction. 7. For on-off gas-fired systems, some authorities who have
jurisdiction prohibit the wiring of any limit or operating contacts in series
between the flame safeguard control and the main fuel valve(s). 8. Two flame
detectors can be connected in parallel with the exception of Infrared Flame
Detectors (C7015). 9. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, can cause interference with radio communications. It has been
tested and found to comply with the limits for a Class B computing device of
Part 15 of FCC rules, which are designed to provide reasonable protection
against such interference when operated in a commercial environment. Operation
of this equipment in a residential area may cause interference, in which case,
the users, at their own expense, may be required to take whatever measures are
required to correct this interference. 10. This digital apparatus does not
exceed the Class B limits for radio noise for digital apparatus set out in the
Radio Interference Regulations of the Canadian Department of Communications.
Location
Humidity
Install the relay module where the relative humidity never reaches the
saturation point. The relay module is designed to operate in a maximum 85%
relative humidity continuous, noncondensing, moisture environment. Condensing
moisture can cause a safety shutdown.
Vibration
Do not install the relay module where it can be subjected to vibration in
excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weather tight. When installed outdoors,
protect the relay module in an approved weather-tight enclosure.
Mounting Wiring Subbase
1. Mount the subbase in any position except horizontally with the bifurcated
contacts pointing down. The standard vertical position is recommended. Any
other position decreases the maximum ambient temperature rating.
2. Select a location on a wall, burner or electrical panel. The Q7800 can be
mounted directly in the control cabinet. Be sure to allow adequate clearance
for service, installation, access or removal of the RM7895A,B,C,D/ EC7895A,C;
RM7896A,B,C,D, expanded annunciator, keyboard display module, flame amplifier,
flame amplifier signal voltage probes, run/test switch, electrical signal
voltage probes and electrical field connections.
3. For surface mounting, use the back of the subbase as a template to mark
the four screw locations. Then drill the pilot holes.
4. Securely mount the subbase using four no. 6 screws (not provided).
66-1090–06
2
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Wiring Subbase
WARNING
Electrical Shock Hazard. Can cause serious injury, death or equipment damage.
Disconnect the power supply before beginning installation.
The internal block diagram of the RM7895A,B,C,D/ EC7895A,C;RM7896A,B,C,D is
shown in Fig. 1.
1. For proper subbase wiring and sequence chart, refer to Fig. 2 and 3.
2. For remote wiring of the Keyboard Display Module, refer to the
Specifications for the Keyboard Display Module (65-0090), Network Interface
Unit (63-2278), Data ControlBusTM Module (65-0091) or Extension Cable Assembly
(65-0131).
3. Disconnect the power supply from the main disconnect before beginning
installation to prevent electrical shock and equipment damage. More than one
disconnect can be required.
4. All wiring must comply with all applicable electrical codes, ordinances
and regulations. Wiring, where required, must comply with NEC, Class 1 (Line
Voltage) wiring.
5. For recommended wire size and type, see Table 1. 6. For recommended
grounding practices, see Table 2.
1 PROVIDE DISCONNECT MEANS AND
5
OVERLOAD PROTECTION AS REQUIRED.
2 LOCKOUT IF JUMPER JR2 REMOVED.
INDICATES FEEDBACK SENSING TO RELAY STATUS FEEDBACK AND LINE VOLT INPUTS
FIELD WIRING INTERNAL WIRING
RUN/TEST SWITCH
RESET PUSHBUTTON
L1
L2
(HOT)
1
L2 RM7895, RM7896: 120 VAC, 50/60 HZ. EC7895A,C: 220-240 VAC, 50/60 HZ.
CONFIGURATION JUMPERS
PLUG-IN PURGE TIMER CARD
FLAME SIGNAL
TEST JACK
MICROCOMPUTER
2K RELAY 3K DRIVE 4K CIRCUIT 5K
6K 7K
F
PLUG-IN
TEST FLAME
G
AMPLIFIER
22
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
STATUS LEDs
SAFETY RELAY CIRCUIT
1K POWER SUPPLY
CONTROL POWER
DDL
OPTIONAL KEYBOARD DISPLAY MODULE
RS485
DDL COMMUNICATIONS
M23996
1
2
3
REMOTE RESET
1K1 2K1 5K1
6
7
10
IGNITION
LIMITS
CONTROLLER INTERLOCK (INCLUDING
AIRFLOW SWITCH)
2
4K1
8
PILOT
2K2 9 MAIN VALVE
6K1
4
BLOWER
3K1
3
ALARM
Fig. 1. Internal block diagram of RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D (see Fig. 2 and 3 for detailed wiring instructions).
3
66-1090–06
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
LINE VOLTAGE ALARM
BURNER MOTOR (BLOWER)
BURNER CONTROLLER/LIMITS
LOCKOUT INTERLOCK (INCLUDING AIRFLOW SWITCH)
INTERMITTENT PILOT/IGNITION
MAIN FUEL VALVE(S)
IGNITION
FLAME DETECTOR
4
3
Q7800
G
12
L2
13
3
14
4
15
5 (L1) 16
6
17
7
18
FOR DIRECT SPARK IGNITION (OIL OR GAS)
IGNITION 10 TRANSFORMER
L2
8
MAIN VALVE
2
8
19
9
20
10
21
F
22
MASTER SWITCH
L1 (HOT)
L2 1
LED DISPLAY
INITIATE POWER
00 STANDBY
POWER
00 TIMED
START
PURGE
00 PFEP
4 OR 10 SEC
POWER
POWER
POWER
RUN
7 POST PURGE
15 SEC
POWER
POWER
STANDBY POWER
PILOT FLAME MAIN
PILOT FLAME MAIN
PILOT FLAME MAIN
ALARM
ALARM
ALARM
BURNER START
BURNER/BLOWER MOTOR
4
7
10 IGN 5
IGN/ PILOT
8
MAIN VALVE 9
OPERATING CONTROLS AND INTERLOCKS
FLAME SIGNAL
LIMITS AND BURNER CONTROLLER CLOSED L1 TO 6
6 AIRFLOW SW CHECK
LOCKOUT INTERLOCK CLOSED 6 TO 7
SAFE START CHECK
FLAME PROVING
AFSC SSC
1 RM7895, RM7896: 120 VAC , 50/60 HZ; EC7895: 220-240 VAC, 50/60 HZ POWER
SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS.
3 FOR EC7895, A 220 TO 240 VAC TO 120 VAC, 10 VA MINIMUM STEPDOWN TRANSFORMER
(NOT PROVIDED) MUST BE USED TO DRIVE THE SHUTTER.
4 SEE FLAME DETECTOR SPECIFICATIONS FOR CORRECT WIRING.
5 FOR RM7895A1048 (ONLY), IGNITION TERMINAL 10 IS DE-ENERGIZED WHEN FLAME IS PROVEN.
6 AIRFLOW SWITCH CHECK FEATURE IS FOR THE RM7895B,RM7896B.
7 RM7896A,B ONLY.
M23997
Fig. 2. Wiring subbase and sequence chart for RM7895A,B/EC7895A; RM7896A,B.
66-1090–06
4
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
LINE VOLTAGE ALARM
BURNER MOTOR (BLOWER)
BURNER CONTROLLER/LIMITS
LOCKOUT INTERLOCK (INCLUDING AIRFLOW SWITCH).
10 SEC. INTERRUPTED PILOT/IGNITION
MAIN FUEL VALVE(S)
IGNITION
FLAME DETECTOR
4 3
Q7800
G
12
L2
13
3
14
4
15
5 (L1) 16
FOR DIRECT SPARK IGNITION (OIL OR GAS)
10
IGNITION TRANSFORMER
8
L2
9
MAIN VALVE
6
17
2
7
18
8
19
9
20
DELAYED
10
21
(2ND STAGE) MAIN VALVE
F
22
MASTER SWITCH
L1 (HOT)
L2 1
LED DISPLAY
BURNER START
INITIATE POWER
00
STANDBY POWER
00
00
START
TIMED PURGE
PFEP 7 4 OR 10 SEC MFEP
POWER
POWER
POWER
POWER
PILOT
PILOT
PILOT
FLAME
FLAME
FLAME
MAIN
MAIN
MAIN
ALARM
ALARM
ALARM
RUN POWER
6
POST PURGE 15SEC POWER
STANDBY POWER
PILOT FLAME MAIN
ALARM
BURNER/BLOWER MOTOR 4
6
IGN. 10 8 10 SEC. IGN./ PILOT 8
MAIN VALVE
9
2ND STAGE MAIN 21
OPERATING CONTROLS AND INTERLOCKS
FLAME SIGNAL
LIMITS AND BURNER CONTROLLER CLOSED
L1 TO 6
5 AIRFLOW SW. CHECK
LOCKOUT INTERLOCK CLOSED
6 TO 7
SAFE START CHECK
FLAME PROVING
AFSC SSC
1 RM7895, RM7896: 120 VAC , 50/60 HZ; EC7895: 220-240 VAC, 50/60 HZ POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
5 AIRFLOW SWITCH CHECK FEATURE IS FOR THE RM7895D, RM7896D. 6 RM7896C,D ONLY.
2 DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS.
7 RM7895C1020, RM7896C1036 PFEP 10 SECONDS ONLY;
3 FOR EC7895, A 220 TO 240 VAC TO 120 VAC, 10 VA MINIMUM STEPDOWN TRANSFORMER (NOT PROVIDED) MUST BE USED TO DRIVE THE SHUTTER.
RM7895C1053 PFEP 4 SECONDS ONLY, 3 SECONDS ONLY SOFTWARE REVISION 4151.
4 SEE FLAME DETECTOR SPECIFICATIONS FOR CORRECT WIRING.
8 RM7895C1020, RM7896C1036: DURING FIRST 8 SECONDS OF PFEP, WHEN A FLAME SIGNAL IS DETECTED, TERMINAL 10 IS DE-ENERGIZED.
IF FLAME SIGNAL IS LOST, TERMINAL 10 WILL RE-ENERGIZE.
M23998
Fig. 3. Wiring subbase and sequence chart for RM7895C,D/EC7895C; RM7896C,D.
5
66-1090–06
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Table 1. Recommended Wire Sizes and Part Numbers.
Application
Recommended Wire Size
Recommended Part Numbers
Line voltage terminals.
14, 16 or 18 AWG copper conductor, 600 volt insulation, TTW60C, THW75C, THHN90C. moisture-resistant wire.
Keyboard Display Module 22 AWG two-wire twisted pair with ground, or five- wire. Belden 8723 shielded cable or equivalent.
Data ControlBusTM Modulea 22 AWG two-wire twisted pair with ground, or five- wire. Belden 8723 shielded cable or equivalent.
Remote Reset Module
22 AWG two-wire twisted pair, insulated for low voltage. —
Communications Interface 22 AWG two-wire twisted pair with ground. ControlBusTM Modulea
Belden 8723 shielded cable or equivalent.
13 Vdc full-wave rectified transformer power input.
18 AWG wire insulated for voltages and temperatures TTW60C, THW75C, THHN90C. for given application.
a The KDM, Data ControlBusTM Module (for remote mounting or communications) or Communication Interface ControlBusTM Module must be wired in daisy chain configuration, 1(a)-1(a), 2(b)-2(b), 3(c)-3(c). The order of interconnection of all the devices listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration string require a 120 ohm (1/4 watt minimum) resistor termination across terminals 1 and 2 of the electrical connectors for connections over 100 feet (31 meters).
Table 2. Recommended Grounding Practices.
Ground Type
Recommended Practice
Earth ground (subbase and relay module).
1. Use to provide a connection between the subbase and the control panel of
the equipment. Earth ground must be capable of conducting enough current to
blow the 20A fuse (or breaker) in the event of an internal short circuit.
2. Use wide straps or brackets to provide minimum length, maximum surface
area ground conductors. If a leadwire is required, use 14 AWG copper wire.
3. Make sure that mechanically tightened joints along the ground path are
free of nonconductive coatings and protected against corrosion on mating
surfaces.
Signal ground (Keyboard Display Module, Data ControlBusTM Module, Communications Interface ControlBusTM Module.
Use the shield of the signal wire to ground the device to the signal ground terminal 3(c) of each device. Connect the shield at both ends of the daisy chain to earth ground.
7. Recommended wire routing of leadwires: a. Do not run high voltage ignition
transformer wires in the same conduit with the flame detector, Data ControlBus
ModuleTM, or Remote Reset Module wiring. b. Do not route flame detector, Data
ControlBusTM Module, or Remote Reset Module leadwires in conduit with line
voltage circuits. c. Enclose flame detector leadwires without armor cable in
metal cable or conduit. d. Follow directions in flame detector, Data
ControlBusTM Module, or Remote Reset Module Instructions.
8. The KDM is powered from a low voltage, energy limited source. It can be
mounted outside of a control panel if it is protected from mechanical damage.
NOTE: A 13 Vdc power supply must be used any time more than one KDM is used.
9. Maximum wire lengths: a. RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D leadwires:
The maximum leadwire length is 300 feet to terminal inputs (Control,
Running/Lockout Interlock). b. Flame Detector leadwires: The maximum flame
sensor leadwire length is limited by the flame signal strength.
c. Remote Reset leadwires: The maximum length of wire is 1000 feet (305
meters) to a Remote Reset pushbutton.
d. Data ControlBus ModuleTM: The maximum Data ControlBusTM Module cable length
depends on the number of system modules connected, the noise conditions and
the cable used. The maximum length of all Data ControlBusTM Module
interconnecting wire is 4000 feet (1219 meters).
10. Be sure loads do not exceed the terminal ratings. Refer to the label on
the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D or to the terminal ratings in Table
3.
Final Wiring Check
1. Check the power supply circuit. The voltage and frequency tolerance must
match those of the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D. A separate power
supply circuit can be required for the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D.
Add the required disconnect means and overload protection.
2. Check all wiring circuits and complete Static Checkout in Table 6 before
installing the RM7895A,B,C,D/ EC7895A,C; RM7896A,B,C,D on the subbase.
3. Install all electrical connectors. 4. Restore power to the panel.
66-1090–06
6
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Table 3. Terminal Ratings.
Terminal Number
Description
RM7895/RM7896
Ratings
EC7895
G
Flame Sensor Ground
—
—
Earth G Earth Grounda
—
—
L2(N) Line Voltage Common
—
—
3
Alarm
120 Vac, 1A pilot duty.
220-240 Vac, 1A pilot duty.
4
Burner Motor
120 Vac, 9.8A AFL, 58.8 ALR (inrush). 220-240 Vac, 4A at PF = 0.5, 20A inrush.
5
Line Voltage Supply (L1)
120 Vac (+10/-15%), 50 or 60 Hz (±10%).b
220-240 Vac (+10/-15%), 50 or 60 Hz (±10%).
6
Burner Controller and Limits
120 Vac, 1 mA.
220-240 Vac, 1 mA.
7
Lockout Interlock
120 Vac, 8A run, 43A inrush.
8A at PF = 0.5, 40A inrush, 2A at PF = 0.2.
8
Pilot Valve/Ignition
120 Vacc
220-240 Vac, 4A at PF = 0.5, 20A inrush.
9
Main Fuel Valve
120 Vacc
220-240 Vac, 4A at PF = 0.5, 20A inrush.
10
Ignition
120 Vacc
220-240 Vac, 2A at PF = 0.2
F(11) Flame Sensor
60 to 220 Vac, current limited.
60 to 220 Vac, current limited.
12 to 20 Unused
—
—
21
2nd Stage Main Valve (EC7895C, 120 Vacc
RM7895C,D; RM7896C,D)
220-240 Vac, 4A at PF = 0.5, 20A inrush.
22
Shutter
120 Vac, 0.5A
220-240 Vacd
a See Table 2. b 2000 VA maximum load connected to RM7895A,B,C,D/EC7895A,C/RM7896A,B,C,D Assembly. c See Tables 4 and 5. d Requires 220-240 Vac, 10 VA minimum, stepdown transformer to operate the shutter.
Table 4. Combinations for Terminals 8, 9, 10 and 21.
Combination Number
1
C
2
B
3
Fa
4
F
5
Fa
6
D
7
Da
8
D
9
Da
Pilot Fuel 8
Main 9 F F No Load
F No Load F No Load D No Load
Ignition 10 No Load No Load A
A A A A A A
a RM7895C,D: EC7895C, RM7896C,D only, jumper terminals 8 to 9.
Delayed Main Valve 21 No Load No Load No Load
No Load F No Load D No Load D
Table 5. Composition of each Combination.
A 4.5A ignition
B
50 VA Pilot Dutya plus 4.5A ignition.
C
180 VA Ignition plus motor valves with: 660 VA inrush, 360 VA open, 240 VA
hold.
D 2A Pilot Duty.a
a Pilot Duty refers to solenoid-type valves.
F
65 VA Pilot Dutya plus motor valves with: 3850 VA inrush, 700 VA open, 250 VA
hold.
7
66-1090–06
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
STATIC CHECKOUT
After checking all wiring, perform this checkout before installing the
EC7895A,C/RM7895A,B,C,D/RM7896A,B,C,D on the subbase. These tests verify the
Q7800 Wiring Subbase is wired correctly, and the external controllers, limits,
interlocks, actuators, valves, transformers, motors and other devices are
operating properly.
WARNING
Fire or Explosion Hazard. Can cause property damage, severe injury or death.
Close all manual fuel shutoff valve(s) before starting these tests.
Use extreme care while testing the system. Line voltage is present on most
terminal connections when power is on.
Ensure proper selection of configuration jumpers before starting the burner
operation.
CAUTION
Electrical Hazard. Can cause equipment damage or failure. Do not perform a
dielectric test with the relay module installed. Internal surge protectors can
break down, allowing relay module to fail the dielectric test and destroy the
internal lightning and high current protection.
1. Open the master switch before installing or removing a jumper on the
subbase.
2. Before continuing to the next test, be sure to remove the test jumper(s)
used in the previous test.
3. Replace all limits and interlocks that are not operating properly. Do not
bypass limits and interlocks.
Equipment Recommended
1. Voltmeter (1M ohm/volt minimum sensitivity) set on the 0 to 300 Vac scale.
2. Two jumper wires, no. 14 wire, insulated, 12 in. (304.8 mm) long with
insulated alligator clips at both ends.
General Instructions
1. Perform all applicable tests listed in Static Checkout, Table 6, in the
order listed.
2. Make sure all manual fuel shutoff valve(s) are closed. 3. For each test,
open the master switch and install the
jumper wire(s) between the subbase wiring terminals listed in the Test Jumpers
column. 4. Close the master switch before observing operation. 5. Read the
voltage between the subbase wiring terminals listed in the Voltmeter column.
6. If there is no voltage or the operation is abnormal, check the circuits and
external devices as described in the last column. 7. Check all wiring for
correct connections, tight terminal screws, correct wire, and proper wiring
techniques. Replace all damaged or incorrectly sized wires. 8. Replace faulty
controllers, limits, interlocks, actuators, valves, transformers, motors and
other devices, as required. 9. Make sure normal operation is obtained for each
required test before continuing the checkout. 10. After completing each test,
be sure to open the master power switch and remove the test jumper(s) before
proceeding to the next test.
WARNING
Explosion hazard. Can cause serious injury or death. Be sure all manual fuel
shutoff valves are closed.
Table 6. Static Checkout .
Test Relay Module Test Number Model Jumpers Voltmeter
Normal Operation
1
All
None 5-L2
Line voltage at terminal 5.
2
All
3
All
4
All
None 4-5
6-L2 7-L2
5-10
—
Line voltage at terminal 6.
1. Burner motor (fan or blower) starts.
2. Line voltage at terminal 7 within 10 seconds.
1. Ignition spark (if ignition transformer is connected to terminal 10).
If Operation is Abnormal, Check Items Listed Below
1. Master switch. 2. Power connected to master switch. 3. Overload protection
(fuse, circuit breaker,
etc.) has not opened power line.
1. Limits. 2. Burner controller.
1. Burner motor circuit. a. Manual switch of burner motor. b. Burner motor
power supply, overload protection and starter. c. Burner motor.
1. Watch for spark or listen for buzz. a. Ignition electrodes are clean. b.
Ignition transformer is okay.
66-1090–06
8
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Table 6. Static Checkout (Continued).
Test Relay Module Test Number Model Jumpers Voltmeter
Normal Operation
5
All
5-8
—
1. Ignition spark (if ignition transformer is connected to terminal 8).
2. Automatic pilot valve opens (if connected to terminal 8).
If Operation is Abnormal, Check Items Listed Below
1. Watch for spark or listen for buzz. 2. Listen for click or feel head of
valve for
activation. a. Actuator if used. b. Pilot valve.
6
7
8 Final
All
EC7895C; RM7895C,D; RM7896C,D
All All
5-9 5-21 5-3
NOTE: Refer to wiring diagram of system being tested.
—
Automatic fuel valve(s) open(s). If Same as test 5. If using direct spark
using direct spark ignition, check ignition, check first stage fuel valve(s)
first stage fuel valve(s) instead of instead of pilot valve.
pilot valve.
—
Automatic second stage main fuel 1. Listen for and observe operation of
valve(s) open(s).
second stage main fuel valve(s) and
actuator(s).
2. Valve(s) and actuator(s).
—
Alarm (if used) turns on.
1. Alarm.
CAUTION
Equipment Damage Hazard. Can cause equipment damage. After completing these
tests, open master switch and remove all test jumpers from subbase terminals.
Also remove bypass jumpers, if used, from low fuel pressure limits.
Mounting RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D Relay Module
1. Mount the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D vertically on the Q7800
Subbase or mount horizontally with the knife blade terminals pointing down.
When mounted on the Q7800A, the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D must be
in an electrical enclosure.
2. When mounting in an electrical enclosure, provide adequate clearance for
servicing, installation and removal of the RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D, KDM, flame amplifier, flame amplifier signal voltage probes,
electrical signal voltage probes and electrical connections. a. Allow an
additional two inches (51 mm) below the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D
for the flame amplifier mounting. b. Allow an optional three-inch (76 mm)
minimum on both sides of the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D for
electrical signal voltage probes.
3. Make sure no subbase wiring is projecting beyond the terminal blocks. Tuck
in wiring against the back of the subbase so it does not interfere with the
knife blade terminals or bifurcated contacts.
IMPORTANT
The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D must be installed with a plug-in
motion rather than a hinge action.
4. Mount the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D by aligning the four
L-shaped corner guides and knife blade terminals with the bifurcated contacts
on the wiring subbase and securely tightening the two screws without deforming
the plastic.
Mounting Other System Components (Fig. 4)
Refer to the applicable specifications for mounting other system components.
PRINCIPAL TECHNICAL FEATURES
The RM7895 provides all customary flame safeguard functions as well as
significant advancements in safety, annunciation, and system diagnostics.
Safety Shutdown (Lockout) Occurs if:
1. INITIATE PERIOD a. Purge card is not installed or removed. b. Purge card
is bad. c. Configuration jumpers have been changed (after 200 hours)–Fault
Code 110. d. AC line power errors occurred, see Operation. e. Four minute
INITIATE period has been exceeded.
9
66-1090–06
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
WIRING SUBBASE
RUN/TEST (C,D ONLY) SWITCH
RELAY MODULE
CONFIGURATION JUMPERS
PURGE TIMER
SEQUENCE STATUS LED PANEL
RESET BUTTON
DUST COVER
POWER PILOT FLAME MAIN ALARM
RESET
HONEYWELL
CAPTIVE MOUNTING SCREW
BURNER CONTROL
FLAME AMPLIFIER
M15122
Fig. 4. RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D Relay Module, exploded view.
2. STANDBY PERIOD a. Airflow lockout feature is enabled and the airflow
switch does not close after ten seconds or within the specified purge card
timing. b. Flame signal is detected after 30 seconds. c. Ignition/pilot
valve/intermittent pilot valve terminal is energized. d. Main valve terminal
is energized. e. Delayed main valve terminal is energized (RM7895C,D). f.
Internal system fault occurred. g. Purge card is removed. h. Purge card is
bad.
3. PREPURGE PERIOD a. Airflow lockout feature is enabled and the airflow
switch opens. b. Ignition/pilot valve terminal is energized. c. Main valve
terminal is energized. d. Delayed main valve terminal is energized
(RM7895C,D). e. Internal system fault occurred.
f. Purge card is removed. g. Purge card is bad. h. Flame signal is detected.
4. PILOT FLAME ESTABLISHING PERIOD (PFEP) a. Airflow lockout feature is
enabled and the airflow
switch opens. b. No flame signal at end of PFEP. c. Ignition/pilot
valve/intermittent pilot valve terminal is
not energized.
NOTE:
For the RM7895C1020 and RM7896C1036, during the first 8 seconds of PFEP, when a flame signal is detected, terminal 10 is de-energized. If the flame signal is lost, terminal 10 will re-energize.
d. Main valve terminal is energized. e. Delayed (second stage) main valve
terminal is
energized (RM7895C,D/EC7895C; RM7896C,D). f. Internal system fault occurred.
g. Purge card is removed. h. Purge card is bad.
66-1090–06
10
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
5. MAIN FLAME ESTABLISHING PERIOD (MFEP) (RM7895C, RM7896C,D; EC7895C) a.
Airflow lockout feature is enabled and the airflow switch opens. b. Ignition
terminal is energized. c. Ignition/pilot valve terminal is not energized. d.
Main valve terminal is not energized. e. Delayed main valve terminal is
energized. f. No flame signal at end of Flame Failure Response Time. g.
Internal system fault occurred. h. Purge card is removed. i. Purge card is
bad.
6. RUN PERIOD a. No flame present. b. Airflow lockout feature is enabled and
the airflow switch opens. c. Interrupted pilot valve terminal is energized
(RM7895C, RM7896C,D; EC7895C). d. Main valve terminal is not energized. e.
Delayed main valve terminal is not energized (RM7895C, RM7896C,D; EC7895C). f.
Internal system fault occurred. g. Purge card is removed. h. Purge card is
bad. i. Ignition terminal is energized.
OPERATION
Sequence of Operation
The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D has the operating sequences listed
below; see Fig. 2 and 3. The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D LED
provide positive visual indication of the program sequence: POWER, PILOT,
FLAME, MAIN and ALARM.
Initiate
The EC7895A,C/RM7895A,B,C,D;RM7896A,B,C,D Relay Module enters the INITIATE
sequence when the relay module is powered. The EC7895A,C/RM7895A,B,C,D;
RM7896A,B,C,D can also enter the INITIATE sequence if the relay module
verifies voltage fluctuations of +10/-15% or frequency fluctuations of ±10%
during any part of the operating sequence. The INITIATE sequence lasts for ten
seconds unless the voltage or frequency tolerances are not met. When not met,
a hold condition is initiated and displayed on the optional KDM for at least
five seconds; when met, the INITIATE sequence restarts. If the condition is
not corrected and the hold condition exists for four minutes, the
EC7895A,C/RM7895A,B,C,D; RM7896A,B,C,D locks out. Causes for hold conditions
in the INITIATE sequence:
1. AC line dropout detection. 2. AC line noise that can prevent a sufficient
reading of the
line voltage inputs. 3. Low line voltage brownouts. The INITIATE sequence also
delays the burner motor starter from being energized and de-energized from an
intermittent AC line input or control input.
Standby
The EC7895A,C/RM7895A,B,C,D;RM7896A,B,C,D is ready to start an operating
sequence when the operating control input determines a call for heat is
present. The burner switch, limits, operating limit control and all
microcomputer-monitored circuits must be in the correct state for the relay
module to continue into the PREPURGE sequence.
Normal Start-Up Prepurge
The EC7895A,C/RM7895A,B,C,D/RM7896A,B,C,D Relay Module provides PREPURGE
timing selectable from two seconds to thirty minutes with power applied and
the operating control indicating a call for heat.
1. The Airflow Interlock, burner switch, Run/Test switch and all
microcomputer-monitored circuits must also be in the correct operating state.
2. The motor output, terminal 4, is powered to start the PREPURGE sequence.
3. The Airflow Interlock input closes ten seconds into PREPURGE or within the
specified purge card timing; otherwise, a recycle to the beginning of PREPURGE
or lockout occurs, depending on how the Airflow Switch selectable jumper (JR3)
is configured.
Ignition Trials
1. Pilot Flame Establishing Period (PFEP): a. When the PFEP begins: (1) The
pilot valve and ignition transformer, terminals 8 and 10, are energized. The
EC7895A, RM7895A,B, and RM7896A,B have an intermittent pilot valve, terminal
8. The EC7895C, RM7895C,D, and RM7896C,D have an interrupted pilot valve,
terminal 8. (2) Flame must be proven by the end of the ten second PFEP (four
seconds if Configuration Jumper JR1 is clipped) to allow the sequence to
continue. If a flame is not proven by the end of PFEP, a safety shutdown
occurs. b. With flame proven, the ignition, terminal 10, is de-energized.
NOTE:
For the RM7895C1020 and RM7896C1036, during the first 8 seconds of PFEP, when a flame signal is detected, terminal 10 is de-energized. If the flame signal is lost, terminal 10 will re-energize.
2. Main Flame Establishing Period (MFEP): a. After PFEP, and with the presence of flame, the main fuel valve, terminal 9, is powered. If a flameout occurs, the relay module locks out or recycles (depending on status of jumper JR2) within 0.8 or 3 seconds, depending on the Flame Failure Response Time (FFRT) of the amplifier. b. The EC7895C, RM7895C,D and RM7896C,D have a ten second MFEP. After the Ignition Trials, the pilot valve, terminal 8, is de- energized. If a flameout occurs, the relay module locks out or recycles (depending on status of jumper JR2) within 0.8 or 3 seconds, depending on the Flame Failure Response Time (FFRT) of the amplifier.
11
66-1090–06
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Run
1. The EC7895C, RM7895C,D, RM7896C,D has a delayed main valve that is
energized once the RUN period is entered.
2. The relay module is now in RUN and remains in RUN until the controller
input, terminal 6, opens, indicating that the demand is satisfied or a limit
has opened.
Post Purge (RM7896A,B,C,D Only)
After demand is satisfied or a limit opens, de-energizing terminal 6, the
Ignition/Pilot valve, main valve and delayed main valve, terminals 8, 9 and
21, are de-energized. The blower motor, terminal 4, remains powered for 15
seconds.
Run/Test Switch (RM/EC7895C,D; RM7896C,D only)
The Run/Test Switch is located on the top side of the relay module, see Fig.
5. The Run/Test Switch allows the burner sequence to be altered as follows:
1. In the measured PREPURGE sequence, the Run/Test Switch, placed in the TEST
position, causes the PREPURGE timing to stop.
2. In the Pilot Flame Establishing Period, the Run/Test Switch, placed in the
TEST position, stops the timer during the first eight seconds of a ten-second
PFEP selection or during the first three seconds of a four-second PFEP
selection. It also allows for pilot turn-down test and other burner
adjustments. This activates a fifteensecond flameout timer that permits pilot
flame adjustment without nuisance safety shutdowns. The Run/Test Switch is
ignored during PFEP for the C and D relay modules if terminals 8 and 9 or 9
and 21 are jumpered.
IMPORTANT
When the relay module is switched to the TEST mode, it stops and holds at the
next Run/Test Switch point in the operating sequence. Make sure that the
Run/Test Switch is in the RUN position before leaving the installation.
RUN/TEST SWITCH
CAPTIVE MOUNTING
SCREW
PLUG-IN PURGE CARD
SEQUENCE STATUS LEDs
DUST COVER
RELAY MODULE
RESET PUSHBUTTON
FLAME SIMULATOR INPUT
FLAME AMPLIFIER
FLAME CURRENT TEST JACKS M7552A
Fig. 5. Sequence Status LEDs.
SETTINGS AND ADJUSTMENTS
Selectable Site-Configurable Jumpers
The relay module has three site-configurable jumper options, see Fig. 6 and
Table 6. If necessary, clip the site-configurable jumpers with side cutters
and remove the resistors from the relay module.
SERVICE NOTE: Clipping and removing a site-configurable jumper enhances the
level of safety.
SELECTABLE CONFIGURATION JUMPERS RUN/TEST SWITCH (EC7895C; RM7895C,D;
RM7896C,D)
M7553A
Fig. 6. Selectable site-configurable jumpers.
Table 7. Site-configurable jumper options.
Jumper Number JR1a, b
JR2c JR3
Description Pilot Flame Establishing Period (PFEP) Flame Failure Action
Airflow Switch (ILK) Failure
Intact 10 seconds Recycle
Recycle
Clipped 4 seconds
Lockout Lockout
a The RM7895C1020 and RM7896C1036 have fixed PFEP of ten seconds and do not
have jumper JR1 (3 seconds software revision 4151 or greater).
b The RM7895C1053 has fixed PFEP of four seconds and does not have jumper JR1.
c The RM7895C1053 locks out on Flame Failure Action and does not have jumper
JR2.
IMPORTANT
Clipping and removing a jumper after 200 hours of operation causes a
nonresettable Fault 110. The relay module must then be replaced.
Automation and Control Solutions
Honeywell International Inc.
Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North
35 Dynamic Drive
Golden Valley, MN 55422
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2007 Honeywell International Inc. 66-1090–06 M.S. Rev. 06-07
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>