MGC 400 Series Low Frequency Sounder User Manual
- September 20, 2024
- MGC
Table of Contents
400 Series Low Frequency Sounder
“`html
Specifications
- Operating temperature: Not specified
- Humidity range: Not specified
- Nominal Voltage: 16 – 33 VDC / VFWR
- Operating Voltage Range (RMS): Not specified
- Frequency Range: Not specified
- Input terminal wire gauge: Not specified
- Installation environment: Not specified
Product Usage Instructions
Setting the DIP Switches
Instructions on how to set the DIP switches for synchronized and
non-synchronized operation.
SW1 Settings
- Signal Rate:
- Continuous: OFF
- Temporal 4: ON
- Temporal 3: ON
- 20 BPM: OFF
SW2 Settings
- Input:
- SYNCHRONIZED: OFF (default)
- NON-SYNCHRONIZED: ON
Mounting Sounder to the Wall or Ceiling
Detailed steps on how to mount the sounder to the wall or
ceiling, including disassembly, attaching the mounting plate,
attaching the sounder, and setting the DIP switches before
installation.
Removing the Cover from the Mounting Plate
Instructions on how to remove the cover from the mounting plate
for maintenance or adjustments.
FAQ
What is the recommended spacing for notification
appliances?
MGC recommends spacing notification appliances in compliance
with CAN/ULC S524 and NFPA 72.
What are the audible ratings of the sounder?
The sounder has audible ratings for high volume and normal
volume at different operating voltages.
“`
Low Frequency 400 Series Notification Appliance – Sounder
About this Manual
This manual is included as a quick reference for installation. For further
information on the use of this device with an FACU, please refer to the
panel’s manual.
Note: This manual should be left with the owner/operator of this equipment.
This manual covers the following models:
FH-400-LF-RR Red wall and ceiling mounted low frequency sounder
FH-400-LF-WW White wall and ceiling mounted low frequency sounder
Notes · DO NOT PAINT OR ALTER FACTORY APPLIED FINISH IN
ANY WAY. · NE PAS PEINDRE OU MODIFIER LA FINITION
ORIGINALE. · Use the information in this document to determine the total
current draw of the devices. The total current draw of the devices must not
exceed the power supply of the panel. In all cases, the installer should
consider the voltage drop to ensure that the last device on the circuit
operates within its rated voltage. · Wiring must be in accordance with CSA
C22.1 Section 32
Description
The low frequency 400 series sounder provides a wide range of low frequency
audible settings in a single compact device. These low frequency devices
operate within a range of 520 Hz ± 10% which address the NFPA 72 sleeping
space requirements. The low frequency sounder can be synchronized using an
FACU or PSU with the MGC protocol or through an external sync module for
compatibility with any UL/ULC listed FACU or PSU.
Sounder models are approved for wall and ceiling installations.
Specifications
Operating temperature: Humidity range: Nominal Voltage: Operating Voltage Range (RMS): Frequency Range: Input terminal wire gauge: Installation environment:
0°C to 50°C (32°F to 122°F) 0% to 93% Regulated 24 VDC / 24 VFWR
16 – 33 VDC / VFWR
520 Hz ± 10% 22 AWG to 12 AWG For indoor use only
Setting the DIP Switches
12 12 OFF ON
SW1 SW2
NOTE for SW2: Use NON-SYNCHRONIZED when the appliances do not need to be
synchronized. Use SYNCHRONIZED when synchronization is required, either
through a sync module or built-in synchronization on the control unit.
When SYNCHRONIZED is selected, the settings for DIP switch SW1 are ignored.
When NON-SYNCHRONIZED is selected, the sounder will sound only the audible
pattern as selected through DIP switch SW1.
SW1
Signal Rate Continuous Temporal 4 Temporal 3 20 BPM
1 OFF ON ON (default) OFF
2 OFF OFF ON (default) ON
SW2
Input SYNCHRONIZED NON-SYNCHRONIZED
1 OFF (default) ON
Sounder Volume High Normal
2 ON OFF (default)
1
www.mircomgroup.com LT-6769 Rev. 0 July 2024
Wiring
From FACU or previous
+ –
device
To next
– +
device or end of line
Dimensions
6.06″ (154 mm)
Mounting Sounder to the Wall or Ceiling
MGC recommends spacing notification appliances in compliance with CAN/ULC S524
and NFPA 72.
When mounting the device on the wall, mount the unit with the MGC logo at the
bottom. The appliance is compatible with single gang, double gang or 4″ square
boxes.
1. Before mounting, disassemble the unit as shown below. Remove the nameplate
and securing screw first.
2. Attach the mounting plate to the electrical box with the 2 included
mounting screws.
3. Attach the sounder to the mounting plate with the 2 included screws.
4. Attach the cover with the included securing screw and snap the nameplate
over the securing screw.
Note: Set the DIP switches before installing the device in the mounting plate.
2 #6-32 x 0.5 screws for attaching mounting plate to gang box
2 #6-32 x 0.5 screws for attaching device to mounting plate
Cover
Front view
6.06″ (154 mm)
Bottom view
1.38″ (35 mm)
1.31″ (33 mm)
Single gang box
Mounting plate
Sounder
6-32. 25 securing screw
Nameplate
Removing the Cover from the Mounting Plate
To remove the cover from the mounting plate, remove the nameplate and the securing screw, then insert a flathead screwdriver into the slot between the cover and the mounting plate, and rotate the screwdriver.
2
www.mircomgroup.com LT-6769 Rev. 0 July 2024
Operating RMS Currents (mA)
Sounder Operating RMS Currents (mA)
Volume High Normal
16 VDC – 33 VDC
Coded Tone*
Continuous Tone
151
200
55
77
*Coded tone is representative of T4, T3 and 20bpm.
16 VFWR – 33 VFWR
Coded Tone* Continuous Tone
230
310
93
125
Audible Ratings
Overall Sound Pressure Level (Reverberant) @ 10 feet (dBA)
Volume 16 VDC 24 VDC
33 VDC 16 VFWR 24 VFWR
High
81
81
Normal 78
78
81
81
82
79
79
79
Testing conducted on continuous signal rate.
Directional Sound Characteristics
Horizontal Axis ± 87° ± 90°
OSPL (dBA) -3 -5.1
33 VFWR
82 79
Vertical Axis ± 90°
OSPL (dBA) -3
At no point was there a 6 dBA decrease.
Warranty
Purchase of all MGC products is governed by: https://www.mircom.com/product-
warranty https://www.mircom.com/purchase-terms-and-conditions
https://www.mircom.com/software-license-terms-and-conditions
3
www.mircomgroup.com LT-6769 Rev. 0 July 2024
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>