UNITED ELECTRIC CONTROLS 12 Series Explosion Proof Pressure Switches Instructions

September 16, 2024
UNITED ELECTRIC CONTROLS

UNITED ELECTRIC CONTROLS 12 Series Explosion Proof Pressure Switches

Specifications:

  • Product Name: 12 Series Explosion-Proof Pressure, Vacuum, and Differential Pressure Switches

  • Certifications:

    • North America: UL 1203, UL 508; CAN/CSA C22.2 No. 14, CAN/CSA
      C22.2 No. 25, CAN/CSA C22.2 No. 30

    • Europe (EU): EN IEC 60079-0, EN 60079-1, EN 60079-31

    • International: IEC 60079-0, IEC 60079-1, IEC 60079-31

  • Mounting Options: Pressure connection, Panel mounting via 1/2 NPTM or M20 Electrical Connection, Surface Mounting Bracket Kit (P/N 62169-13)

Product Usage Instructions

Installation Mounting:

  • Mount the device via the pressure connection. Do not turn the switch housing.
  • Install the device in locations with minimal shock, vibration, and temperature fluctuations.
  • If using with a junction box, mount the product vertically with the pressure connection facing down.
  • Ensure that the adjustment opening is accessible and the front marking on the nameplate faces the operator after mounting.

Panel Mounting via 1/2 NPTM or M20 Electrical Connection:

  • When panel mounting, use a 7/8 clearance hole in the panel an secure in place with a 1/2 or M20 conduit nut. Support the product by holding a wrench on the hex.

Surface Mounting Bracket Kit (P/N 62169-13):

  • Open the adjustment cover and orient the unit so that the adjustment opening will be accessible when the switch is mounted.

FAQ:

  • Q: Can I modify the device after shipment?
    A: No, the device must not be altered or modified after shipment. Consult UE if modification is necessary.

  • Q: Are there any field replaceable parts in this product?
    A: No, this product does not have any field replaceable parts. Substitution of components will invalidate agency certifications.

12 Series
Explosion-Proof, Pressure, Vacuum, and Diff erential Pressure Switches

InstCEDUAL SEallaRTIFIEALDtion and Operation Instructions
Please read all instructional literature carefully and thoroughly before starting.
Refer to the final page for the Warranty.

GENERAL

MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION AND PERSONAL INJURY. THESE INSTRUCTIONS MUST BE THOROUGHLY READ AND UNDERSTOOD BEFORE UNIT IS INSTALLED.

Cert number E40857-19971015
Applicable Area North America
Markings Class I, Groups A, B, C and D; Class II, Groups E, F and G;

Class III
Applicable Standards| UL 1203, UL 508; CAN/CSA C22.2 No. 14, CAN/CSA C22.2 No. 25

CAN/CSA C22.2 No. 30

Cert number DEMKO C8 ATEX 0717128X
Applicable Area Europe (EU)
Markings II 2 G Ex db IIC T6 Gb; II 2 D Ex tb IIIC T85 °C Db
Applicable Standards EN IEC 60079-0; EN 60079-1; EN 60079-31
Cert number IECEx UL 14.0072X
--- ---
Applicable Area International
Markings Ex db IIC T6 Gb

Ex tb IIIC T85 °C Db IP66

-50 °C to +80 °C

Applicable Standards| IEC 60079-0; IEC 60079-1; IEC 60079-31
Cert number| DEMKO 11 ATEX 1105261X
---|---
Applicable Area| Europe (EU)
Markings| II 1 G Ex ia IIC T6 Ga; -50 °C to +60 °C
Applicable Standards| EN IEC 60079-0; EN 60079-11
Cert number| IECEx UL 14.0075X
---|---
Applicable Area| International
Markings| Ex ia IIC T6 Ga

-50 °C ≤ Tamb ≤ +60 °C

Applicable Standards| IEC 60079-0; IEC 60079-11

12 SERIES FOR USE IN CLASS I, DIV. 1, GROUPS A, B, C & D; CLASS II, DIV. 1, GROUPS E, F & G; CLASS III HAZARDOUS LOCATIONS. ENCLOSURE TYPE 4X, IP66. AMBIENT TEMPERATURE RANGE -50°C (-58°F) TO 95°C (203°F).

ATEX AND IEC SPECIFIC CONDITIONS OF USE : THE WIRING
TO THE PRESSURE SWITCH MUST ONLY BE CONNECTED IN A SAFE AREA OR BY AN APPROVED TERMINAL BOX CERTIFIED TO EN 60079-0/IEC 60079-0, EN 60079-1/IEC 60079-1, AND EN 60079-31/IEC 60079-31 FOR HAZARDOUS LOCATIONS. THE EPOXY RESIN SHALL NOT BE SUBJECTED TO A TEMPERATURE GREATER THAN 125°C (257°F).

THE WIRES SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE, E.G., BY USE OF CONDUIT. OPTION M515 WITH DIN CONNECTOR IS NOT COVERED BY THIS CERTIFICATE. OPTION M460, EXTERNAL EARTH GROUND SCREW, IS TO BE USED IF METAL CONDUIT IS NOT USED. ELECTRICAL CONDUIT FITTING THREADED CONNECTION SHALL BE M20 X 1.5 WITH 7 THREADS MINIMUM ENGAGEMENT.

UE declarations and third-party issued Agency certifi cations are available for download at www.ueonline.com.

PRIOR TO INSTALLATION, CHECK THE WETTED PARTS MATERIAL FOR COMPATIBILITY TO THE PROCESS MEDIA.

THE DUAL SEAL DEVICE METHOD OF PRIMARY SEAL FAILURE ANNUNCIATION IS VISIBLE LEAKAGE FROM THE ENCLOSURE. DEPENDING UPON MEDIA SENSED, ADDITIONAL METHODS OF LEAK DETECTION SHALL BE REQUIRED.

THIS PRODUCT DOES NOT HAVE ANY FIELD  REPLACEABLE PARTS. ANY SUBSTITUTION OF COMPONENTS SHALL INVALIDATE AGENCY CERTIFICATION(S), AND IMPAIR SUITABILITY FOR CLASS I, DIV. 1 LOCATION.

PROOF PRESSURE * LIMITS STATED IN THE LITERATURE AND ON NAMEPLATES MUST NEVER BE EXCEEDED, EVEN BY SURGES IN THE SYSTEM. OCCASIONAL OPERATION OF UNIT UP TO PROOF PRESSURE IS ACCEPTABLE (E.G., START-UP, TESTING). CONTINUOUS OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER RANGE ** OR WORKING PRESSURE RANGE.

  • Proof Pressure – the maximum pressure to which a pressure sensor may be occasionally subjected, which causes no permanent damage (e.g., start-up, testing). The unit may require re-gapping.
  •  Over Range Pressure – the maximum pressure to which a pressure sensor may be continuously subjected without causing damage and maintaining set point repeatability.
  • Working Pressure Range – the pressure range in which two opposing sensors can be safely operated and still maintain set point provided the difference in pressure between the low and high sides does not exceed the designated adjustable range.

The 12 Series switch utilizes a diaphragm or a piston sensor to detect a pressure change. The response, at a predetermined set point, actuates a  SPDT or DPDT snap-acting switch, converting a pressure signal into an electrical signal. Control set point may be varied by turning the internal slotted adjustment screw according to procedures outlined in Part II-Adjustments. Please refer to product datasheet at www.ueonline.com for product specifications. Date code format on nameplate is “YYWW” for year and week.

DEVICE MUST NOT BE ALTERED OR MODIFIED AFTER SHIPMENT. CONSULT UE IF MODIFICATION IS NECESSARY.

Part I – Installation

Mounting

1 1/16” Open end wrench

  • INSTALL DEVICE WHERE SHOCK, VIBRATION AND TEMPERATURE FLUCTUATIONS ARE MINIMAL. DO NOT INSTALL DEVICE IN AMBIENT TEMPERATURES THAT EXCEED PUBLISHED LIMITS ON THE NAMEPLATE.
  • DEVICE SHOULD BE MOUNTED TO PREVENT MOISTURE FROM ENTERING THE ENCLOSURE. VERTICAL MOUNTING IS RECOMMENDED.

NOTE : Due to product sensitivity on sensor Type W, it is recommended that these models be mounted vertically with pressure connection facing down. Other types of mounting may cause slight set-point shifts, which may require readjustment.

  • CONSIDER THE USE OF A PRESSURE SNUBBER IF SEVERE PRESSURE SURGES ARE EXPECTED.
  • FOR PRESSURE MODELS, MOUNT VIA PRESSURE CONNECTION. ALWAYS USE A WRENCH ON PRESSURE CONNECTION HEX (SEE FIGURE 1). DO NOT TIGHTEN BY TURNING THE ENCLOSURE AS THIS WILL DAMAGE THE SENSOR AND WEAKEN WELDED JOINTS.
  • FOR DIFFERENTIAL PRESSURE MODELS, MOUNT USING THE ATTACHED MOUNTING BRACKET AGAINST A RIGID SUPPORT, AND THEN CONNECT LOW AND HIGH PRESSURE PORTS.
  • IF USING WITH A JUNCTION BOX, IT IS RECOMMENDED THAT THE PRODUCT BE MOUNTED VERTICALLY WITH THE PRESSURE CONNECTION FACING DOWN.
  • If  product is to be set after mounting, verify that adjustment opening is accessible, “Front” marking on nameplate facing operator.

Panel Mounting via 1/2” NPTM or M20 Electrical Connection
When panel mounting, mount through 7/8” clearance hole in panel. Use 1/2” or M20 conduit nut to secure in place. Always support the product by holding a wrench on the hex.

Surface Mounting Bracket Kit (P/N 62169-13) (see Fig. 6)

  1. Open the adjustment cover and orient the unit so that adjustment opening will be accessible when the switch is mounted.
  2. Close the adjustment cover ensuring that the bracket does not interfere with the cover as this serves as the Dual Seal device method of primary seal failure annunciation and venting.

Failure to install the unit correctly with the mounting bracket may result in improper venting of the adjustment cover.

Wiring

  • DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING UNIT. WIRE UNITS ACCORDING TO NATIONAL AND LOCAL ELECTRICAL CODES. THE WIRES SHOULD BE PROTECTED AGAINST MECHANICAL DAMAGE BY USE OF A CONDUIT OR OTHER SUITABLE MEANS.
  • DO NOT EXCEED ELECTRICAL RATINGS LISTED ON NAMEPLATE. OVERLOAD ON A SWITCH CAN CAUSE FAILURE, EVEN ON THE FIRST CYCLE.
  • DIN CONNECTOR (OPTION M515, FIGURE 4) IS NOT APPROVED FOR CLASS I, DIV. 1 HAZARDOUS LOCATIONS/FLAMEPROOF ATMOSPHERES.

1/2” NPT (male) or M20 (male) conduit connection is provided on top of the product with 72” long, 18 AWG leadwires. The product is available with SPDT or DPDT operation. External grounding screw and clamp is provided with option M460 for ATEX installation with non-metallic conduit systems (See Figure 2). To attach conduit connection hold electrical connection steady with wrench on hex, then thread on conduit.

Factory Sealed Leadwires are color coded:

TERMINALS SPDT DPDT
Circuit 1 Circuit 2
Common Brown Brown
Normally Closed Red Red
Normally Open Blue Blue
Ground Green Green

DIN Connector with 4 Male Terminals (see Figure 4)
Connector conforms to DIN 43650. Use a female mating DIN connector (not UE supplied).

Coding: TERMINALS

Terminal #1 Common
Terminal #2 Normally Closed
Terminal #3 Normally Open
Ground

Part II – Adjustments

Flathead screwdriver with 3/16” or 1/4” wide blade

  1. Connect control to pressure source.
  2. With power disconnected, slide cover toward electrical terminations while twisting it to overcome friction.
  3. Connect power to terminals or leads.
  4. Insert screwdriver into adjustment slot and turn clockwise to increase setting or counter  clockwise to decrease setting (See Figure 3).

Part III – Dimensions

Dimensional drawings for all models may be found at: www.ueonline.com

Standard Configuration

PRESSURE SWITCH / CONNECTION CHART

Type Description     Dimension A Dimension B     Dimension C


| | In| mm| In| mm| In| mm
2| 1/2” NPT (female)| 4.4| 111.1| 0.7| 16.5| 1 1/16| 27.0
3, 5| 1/2” NPT (female)| 4.4| 111.1| 0.6| 15.2| 1 1/16| 27.0
4, 6, 8| 1/4” NPT (female)| 4.4| 111.1| 0.6| 15.2| 1 1/16| 27.0
7, 9| 1/2” NPT (female)| 4.0| 100.3| 1.6| 40.6| 1 1/8| 28.6
P0- P9| 1/4” NPT (female)| 4.4| 111.1| 1.0| 25.4| 1 1/16| 27.0
W1- W2| 1/2” NPT (female)| 4.0| 100.3| 2.2| 55.9| 1 1/16| 27.0
W3- W4| 1/2” NPT (female)| 4.0| 100.3| 1.7| 42.9| 1 1/16| 27.0
K1- K3| 1/8” NPT (female)| 4.4| 111.1| 1.7| 42.9| N/A| N/A
K4- K6| 1/8” NPT (female)| 4.4| 111.1| 1.8| 44.5| N/A| N/A
Option Description Dimension “A”   Dimension  Dimension “C”

“B”

M511| 1/4” NPT (male)| | | 1.1| 27.9| 1 1/16| 27.0
XP112| 1/2” NPT (female)| | | 0.6| 15.2| 1 1/16| 27.0
XP113| 1/2” NPT (female)| | | 0.6| 15.2| 1 1/16| 27.0

Pressure Connections

Differential Pressure Connections

Option M515 DIN Connection

Terminal #1 Common
Terminal #2 Normally Closed
Terminal #3 Normally Open
Ground

NOTE : Does not meet Div. 1 or 2, or ATEX requirements.

Option M421, M423 & M513 Junction Boxes

  • M421 – EAC only; M423 – ATEX or IEC  Not cULus approved. Cover not shown. M513
  • cULus only. Does not meet Enclosure Type 4X. Cover not shown.

Option M430 Adjustment Cover Lock

NOTE: A 1/32” min. space must be maintained between the bottom of the cover lock and the top of the adjustment cover to ensure proper dual seal annunciation and venting .

FRENCH WARNING TRANSLATIONS

Pg| Warning Text|
1| MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION AND PERSONAL INJURY. THESE INSTRUCTIONS MUST BE THOROUGHLY READ AND UNDERSTOOD BEFORE UNIT IS INSTALLED.|

1

| 12 SERIES PRESSURE-OPERATED SWITCH FOR USE IN CLASS I, GROUPS A, B, C AND D; CLASS II, GROUPS E, F AND G; CLASS III HAZARDOUS LOCATIONS. ENCLOSURE TYPE 4X, IP66. AMBIENT TEMPERATURE RANGE: -50°C (-58°F) TO 71°C (160°F).|

1

| ATEX AND IEC SPECIFIC CONDITIONS OF USE: THE WIRING TO THE PRESSURE SWITCH MUST ONLY BE CONNECTED IN A SAFE AREA OR BY AN APPROVED TERMINAL BOX CERTIFIED
TO EN 60079-0/IEC 60079-0, EN 60079-1/IEC 60079-1, AND EN 60079-31/IEC 60079-31 FOR HAZARDOUS LOCATIONS. THE EPOXY RESIN SHALL NOT BE SUBJECTED TO A TEMPERATURE GREATER THAN 125°C (257°F). THE WIRES SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE, E.G. BY USE OF CONDUIT. OPTION M515 WITH DIN CONNECTOR IS NOT COVERED BY THIS CERTIFICATE. OPTION M460, EXTERNAL EARTH GROUND SCREW, IS TO BE USED IF METAL CONDUIT IS NOT USED. ELECTRICAL CONDUIT FITTING THREADED CONNECTION SHALL BE M20 X 1.5 WITH 7 THREADS MINIMUM ENGAGEMENT.|

1

| THE DUAL SEAL DEVICE METHOD OF PRIMARY SEAL FAILURE ANNUNCIATION IS VISIBLE LEAKAGE FROM THE ENCLOSURE. DEPENDING UPON MEDIA SENSED, ADDITIONAL METHODS OF LEAK DETECTION MAY BE REQUIRED (PRESSURE MODELS ONLY)|

1

| THIS PRODUCT DOES NOT HAVE ANY FIELD REPLACEABLE PARTS. ANY SUBSTITUTION OF COMPONENTS SHALL INVALIDATE AGENCY CERTIFICATION(S), AND IMPAIR SUITABILITY FOR CLASS I, DIV. 1 LOCATION.|

2

| INSTALL DEVICE WHERE SHOCK, VIBRATION AND TEMPERATURE FLUCTUATIONS ARE MINIMAL. DO NOT INSTALL DEVICE IN AMBIENT TEMPERATURES THAT EXCEED PUBLISHED LIMITS ON THE NAMEPLATE.|

2

| DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING DEVICE. WIRE DEVICE IN ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL CODES. WIRES SHOULD BE PROTECTED AGAINST MECHANICAL DAMAGE BY USE OF A CONDUIT OR OTHER SUITABLE MEANS.|
2| DO NOT EXCEED ELECTRICAL RATINGS LISTED ON NAMEPLATE. OVERLOAD ON A SWITCH CAN CAUSE FAILURE, EVEN ON THE FIRST CYCLE.|
2| DIN CONNECTOR (OPTION M515) IS NOT APPROVED FOR CLASS I, DIV. 1 HAZARDOUS LOCATION/FLAMEPROOF ATMOSPHERE.|

LIMITED WARRANTY

Seller warrants that the device hereby purchased is, upon delivery, free from defects in material and workmanship and that any such device which is found to be defective in such workmanship or material will be repaired or replaced by Seller (Ex-works, Factory, Watertown, Massachusetts. INCOTERMS); provided, however, that this warranty applies only to device found to be so defective within a period of 24 months from the date of manufacture by the Seller.

Seller shall not be obligated under this warranty for alleged defects which examination discloses are due to tampering, misuse, neglect, improper storage, and in any case where devices are disassembled by anyone other than authorized Seller’s representatives. EXCEPT FOR THE LIMITED WARRANTY OF REPAIR AND REPLACEMENT STATED ABOVE, SELLER DISCLAIMS ALL WARRANTIES WHATSOEVER WITH RESPECT TO THE DEVICE, INCLUDING ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE.

LIMITATION OF SELLER’S LIABILITY

Seller’s liability to Buyer for any loss or claim, including liability incurred in connection with (i) breach of any warranty whatsoever, expressed or implied, (ii) a breach of contract, (iii) a negligent act or acts (or negligent failure to act) committed by Seller, or (iv) an act for which strict liability will be inputted to seller, is limited to the “limited warranty” of repair and/
or replacement as so stated in our warranty of device.

In no event shall the Seller be liable for any special, indirect, consequential or other damages of a like general nature, including, without limitation, loss of profits or production, or loss or expenses of any nature incurred by the buyer or any third party.
UE specifications subject to change without notice.

FOR A LIST OF OUR INTERNATIONAL AND DOMESTIC REGIONAL SALES OFFICES PLEASE VISIT OUR WEBPAGE
WWW.UEONLINE.COM

  • 180 Dexter Avenue
  • Watertown, MA 02472 – USA
  • Telephone: 617 926-1000 –
  • Fax: 617 926-2568 www.ueonline.com

Buy: www.ValinOnline.comPhone 844-385-3099 Email: CustomerService@valin.com