Arcel ADL400 3 Phase Din Rail Energy Meter User Manual

September 14, 2024
Arcel

ADL400 – User Manual

GENERAL

This CT operated DIN Rail meter is for use with three phase supplies and measures electrical parameters including Current (I), Voltage (V), Power (kW/KVA/KVAr), Power Factor (PF), Frequency (Hz), Imported, Exported and Total Energy (kWh/kVArh).
It’s MID approved, allowing it to be used for billing applications and is highly accurate, (Class C, ±0.5%). With both a Pulse Output and RS485 Modbus RTU it can be integrated with BMS or remote monitoring systems.

SPECIFICATION

Meter Type Three Phase (3P4W / 3P3W)
Fitting Type DIN Rail
Max. Current (Amps) 6 A
MID Approved Yes
Smart No
Input Type Current Transformer
Tariffs Single
Import / Export Import & Export
Module Width 4
Reference voltage 3 × 230/400V
Consumption <10VA (Single phase)
Impedance >2MΩ
Power Active, Reactive, Apparent Power, error ±0.5%
Frequency 45 – 65Hz,Error±0.2%
Energy Accuracy Active energy (Class: 0.5)

Reactive energy (Class 2)
Clock| ≤0.5 s/d
Energy pulse output| 1 active photocoupler output
Width of pulse| 80±20ms
Pulse constant| 400imp/kWh, 10000imp/kWh calculated at base current
Interface and communication protocol| RS485: Modbus RTU
Range of communication address| Modbus RTU: 1 – 254
Baud rate| 1200bps – 19200bps
Working temperature| -25℃ – +55℃
Relative humidity| ≤95% (No condensation)
IP Rating| IP20
LCD Display| 12 bits section LCD display, background 12 digit LCD backlit display
Key programming| 3 keys to communication and set parameters

MEASURED PARAMETERS

  • Active Energy (kWh)
  • Active Power (W)
  • Apparent Energy (kVAh)
  • Apparent Power (VA)
  • Current (I)
  • Frequency (Hz)
  • Line to Line Voltage (V)
  • Power Factor (PF)
  • Reactive Energy (kVArh)
  • Reactive Power (VAr)
  • Total Harmonic Distortion (Amps)
  • Total Harmonic Distortion (Volts)
  • Voltage (V)

SETUP

The following instruction directs how to set the CT ratio on this meter. This MUST be done before use to ensure accurate readings. All other settings can be adjusted using the same method.

  1. Press and hold the to enter the setup menu. Enter the password, (default is “0001”), using the button to move the cursor and the button to change the value, then press .
  2. Use the or buttons to scroll through the values until it says “Ct” on the top line. Press and the last value will start to flash.
  3. Using the button to move the cursor and the button to change the value, set this to the CT rate required, (e.g. if using a 200/5 CT, this value would be set at 40, i.e. 200 ÷ 5), then press and the values will stop flashing.
  4. Once complete, press and hold the button and select Yes to save or No to exit without saving changes.

List of Available Settings

Symbol Description Range
Addr Modbus Address 1 – 254
bAUd Baud rate 1200, 2400, 4800, 9600, 19200
Pari Parity None, Odd, Even
Hi High 645 Comms protocol (N/A)
Lo Low
Led Backlight time 0-255 minutes, more than 250 lights stay on
PL Wiring sample 3P4L: 3 phase 3 wires

3P3L: 3 phase 4 wires
Dir| Direction of current| no-Forward, yes-Reverse
S-ty| App. Power Calc.| P Q or U I (N/A)
EF-E| Tariff Set| N/A on this model
Pt| Voltage transformer settings (primary)| 1 – 9999
Ct| Current transformer settings (primary)| 1 – 9999
COdE| Code settings| 1 – 9999
PHAS| Phase Angle Calc.| Ua/Ub/Uc to Ia, Ua to Ia, Ub to Ib, Uc to Ic
nOSt| Starting power Freq.| 0.1 – 2.0

WIRING & INSTALLATION

The ADL400 is designed to be installed on a 35mm DIN Rail

Three phase four wire

Three phase three wire

  • Voltage references require a 100mA fuse
    (Torque setting should not be greater than 1.5-2Nm)

RS485           active energy pulse

Wiring diagram of communication and pulse terminals

DIMENSIONS

HOW TO USE

This unit features 3 buttons used to display the measured electrical parameters:

Voltage & Current

Power

Energy

Voltage & Current


Using the button displays the following parameters:

Voltage (V)                   Line to Line Voltage (V)

Current (A)
Frequency (Hz)

Total Harmonic Distortion (V)      Total Harmonic Distortion (A)

Phase Angle              Check bit, baud rate, table add.

645 Comms protocol (N/A)
Software Version & Unique Meter ID
Software Verification Code
Error Indication (0 = normal)
Full Display

Power


Using the button displays the following parameters:

Active Power per Phase (W)        Total Active Power (kW)

Reactive Power per Phase (VAr)       Total Reactive Power (kVar)

Apparent Power per Phase (kVa)        Total Apparent Power (kVa)

Power Factor per Phase                Total Power Factor

Energy


Using the button displays the following parameters:

Total Active Energy (kWh)        Imported Active Energy (kWh)

Exported Active Energy              Total Reactive Energy
(kWh)                                    (kVArh)

Imported Reactive Energy        Exported Reactive Energy
(kVArh)                                (kVArh)

Imported Active Energy (kWh) – Phase 1
Imported Active Energy (kWh) – Phase 2
Imported Active Energy (kWh) – Phase 3

MODBUS PROTOCOL

For the full Modbus Protocol please visit:

http://downloads.spwales.com/tpdac400-protocol.pdf

Or use the following QR code: