Arcel ADL400 3 Phase Din Rail Energy Meter User Manual
- September 14, 2024
- Arcel
Table of Contents
ADL400 – User Manual
GENERAL
This CT operated DIN Rail meter is for use with three phase supplies and
measures electrical parameters including Current (I), Voltage (V), Power
(kW/KVA/KVAr), Power Factor (PF), Frequency (Hz), Imported, Exported and Total
Energy (kWh/kVArh).
It’s MID approved, allowing it to be used for billing applications and is
highly accurate, (Class C, ±0.5%). With both a Pulse Output and RS485 Modbus
RTU it can be integrated with BMS or remote monitoring systems.
SPECIFICATION
Meter Type | Three Phase (3P4W / 3P3W) |
---|---|
Fitting Type | DIN Rail |
Max. Current (Amps) | 6 A |
MID Approved | Yes |
Smart | No |
Input Type | Current Transformer |
Tariffs | Single |
Import / Export | Import & Export |
Module Width | 4 |
Reference voltage | 3 × 230/400V |
Consumption | <10VA (Single phase) |
Impedance | >2MΩ |
Power | Active, Reactive, Apparent Power, error ±0.5% |
Frequency | 45 – 65Hz,Error±0.2% |
Energy Accuracy | Active energy (Class: 0.5) |
Reactive energy (Class 2)
Clock| ≤0.5 s/d
Energy pulse output| 1 active photocoupler output
Width of pulse| 80±20ms
Pulse constant| 400imp/kWh, 10000imp/kWh calculated at base current
Interface and communication protocol| RS485: Modbus RTU
Range of communication address| Modbus RTU: 1 – 254
Baud rate| 1200bps – 19200bps
Working temperature| -25℃ – +55℃
Relative humidity| ≤95% (No condensation)
IP Rating| IP20
LCD Display| 12 bits section LCD display, background 12 digit LCD
backlit display
Key programming| 3 keys to communication and set parameters
MEASURED PARAMETERS
- Active Energy (kWh)
- Active Power (W)
- Apparent Energy (kVAh)
- Apparent Power (VA)
- Current (I)
- Frequency (Hz)
- Line to Line Voltage (V)
- Power Factor (PF)
- Reactive Energy (kVArh)
- Reactive Power (VAr)
- Total Harmonic Distortion (Amps)
- Total Harmonic Distortion (Volts)
- Voltage (V)
SETUP
The following instruction directs how to set the CT ratio on this meter. This MUST be done before use to ensure accurate readings. All other settings can be adjusted using the same method.
- Press and hold the to enter the setup menu. Enter the password, (default is “0001”), using the button to move the cursor and the button to change the value, then press .
- Use the or buttons to scroll through the values until it says “Ct” on the top line. Press and the last value will start to flash.
- Using the button to move the cursor and the button to change the value, set this to the CT rate required, (e.g. if using a 200/5 CT, this value would be set at 40, i.e. 200 ÷ 5), then press and the values will stop flashing.
- Once complete, press and hold the button and select Yes to save or No to exit without saving changes.
List of Available Settings
Symbol | Description | Range |
---|---|---|
Addr | Modbus Address | 1 – 254 |
bAUd | Baud rate | 1200, 2400, 4800, 9600, 19200 |
Pari | Parity | None, Odd, Even |
Hi | High | 645 Comms protocol (N/A) |
Lo | Low | |
Led | Backlight time | 0-255 minutes, more than 250 lights stay on |
PL | Wiring sample | 3P4L: 3 phase 3 wires |
3P3L: 3 phase 4 wires
Dir| Direction of current| no-Forward, yes-Reverse
S-ty| App. Power Calc.| P Q or U I (N/A)
EF-E| Tariff Set| N/A on this model
Pt| Voltage transformer settings (primary)| 1 – 9999
Ct| Current transformer settings (primary)| 1 – 9999
COdE| Code settings| 1 – 9999
PHAS| Phase Angle Calc.| Ua/Ub/Uc to Ia, Ua to Ia, Ub to Ib, Uc to Ic
nOSt| Starting power Freq.| 0.1 – 2.0
WIRING & INSTALLATION
The ADL400 is designed to be installed on a 35mm DIN Rail
Three phase four wire
Three phase three wire
- Voltage references require a 100mA fuse
(Torque setting should not be greater than 1.5-2Nm)
RS485 active energy pulse
Wiring diagram of communication and pulse terminals
DIMENSIONS
HOW TO USE
This unit features 3 buttons used to display the measured electrical parameters:
Voltage & Current
Power
Energy
Voltage & Current
Using the button displays the following parameters:
Voltage (V) Line to Line Voltage (V)
Current (A)
Frequency (Hz)
Total Harmonic Distortion (V) Total Harmonic Distortion (A)
Phase Angle Check bit, baud rate, table add.
645 Comms protocol (N/A)
Software Version & Unique Meter ID
Software Verification Code
Error Indication (0 = normal)
Full Display
Power
Using the button displays the following parameters:
Active Power per Phase (W) Total Active Power (kW)
Reactive Power per Phase (VAr) Total Reactive Power (kVar)
Apparent Power per Phase (kVa) Total Apparent Power (kVa)
Power Factor per Phase Total Power Factor
Energy
Using the button displays the following parameters:
Total Active Energy (kWh) Imported Active Energy (kWh)
Exported Active Energy Total Reactive Energy
(kWh) (kVArh)
Imported Reactive Energy Exported Reactive Energy
(kVArh) (kVArh)
Imported Active Energy (kWh) – Phase 1
Imported Active Energy (kWh) – Phase 2
Imported Active Energy (kWh) – Phase 3
MODBUS PROTOCOL
For the full Modbus Protocol please visit:
http://downloads.spwales.com/tpdac400-protocol.pdf
Or use the following QR code:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>