REZNOR UEZ Gas Fired Unit Heater Installation Guide
- September 17, 2024
- Reznor
Table of Contents
UEZ Gas Fired Unit Heater
“`html
Specifications:
- Model: UEZ
- Unit Type: Gas-Fired Unit Heater
- Installation, Operation, and Maintenance Manual: UEZ-IOM
(07-24) 1034347-L
Product Information:
Important Safety Information:
WARNING: To prevent damage to the unit or its
internal components, use two wrenches when loosening or tightening
nuts. Do not over tighten!
Condensate Drain Requirements:
CAUTION: DO NOT use copper or copper-based
alloys for condensate drains. The heater is equipped with a
1/2-inch (12.7-mm) PVC pipe for connecting to a condensate drain.
The water condensed from the products of combustion will be
acidic.
Installation Instructions:
-
Refer to the certification and warranty information provided in
the literature bag. -
Ensure the heater is mounted according to specified rules for
best results.
Heater Location and Throw Patterns:
The throw patterns and distances vary based on the unit size and
the angle of the louvers. Refer to Figure 1 and Table 1 for
specific throw distances with standard horizontal louvers.
Mounting Height Requirements:
Mount the heater at the appropriate height to achieve optimal
heating efficiency.
FAQ:
What should I do if I smell gas?
If you smell gas, immediately turn off the unit and any other
appliances, open windows for ventilation, and contact a qualified
technician to inspect the unit.
What type of material should I use for condensate drains?
Avoid using copper or copper-based alloys for condensate drains.
The heater comes with a 1/2-inch PVC pipe for connecting to a
condensate drain.
“`
Revision: UEZ-IOM (07-24) 1034347-L Supersedes: UEZ-IOM (04-24) 1034347-K
GAS-FIRED UNIT HEATER INSTALLATION, OPERATION, AND MAINTENANCE
MODEL UEZ
DANGER
FIRE OR EXPLOSION HAZARD · Failure to follow safety warnings exactly could
result in serious injury, death, or property
damage. · Improper installation, adjustment, alteration, service, or
maintenance can cause serious injury,
death, or property damage. · Installation and service must be performed by a
qualified installer, service agency, or the
gas supplier. · Be sure to read and understand the installation, operation,
and service instructions in this
manual. · Do not store or use gasoline or other flammable vapors and liquids
in the vicinity of this or
any other appliance. WHAT TO DO IF YOU SMELL GAS
· Do not try to light any appliance. · Do not touch any electrical switch; do
not use any phone in your building. · Leave the building immediately. ·
Immediately call your gas supplier from a phone remote from the building.
Follow the gas
supplier’s instructions. · If you cannot reach your gas supplier, call the
fire department. DO NOT DESTROY. PLEASE READ CAREFULLY. KEEP IN A SAFE PLACE
FOR FUTURE REFERENCE.
TABLE OF CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Important Safety Information . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 4 Condensate Drain Requirements . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 5 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 5 Installation Codes . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 5 Heater Location . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . 5 Heater Throw . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Mounting Height
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Halogenated
Hydrocarbons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Clearances . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Weights
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 8
VENTING AND COMBUSTION AIR REQUIREMENTS . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 10 Vent/Combustion Air
System Piping Requirements . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 10 Vent/Combustion Air Piping
Requirements (Unit Sizes 55110) . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 10 Vent/Combustion Air Piping Requirements (Unit Sizes
130310) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Vent/Combustion Air System Piping Joints . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Vent/Combustion Piping Joints (Unit Sizes 55110) . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Vent/Combustion
Piping Joints (Unit Sizes 130310) . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 13 Vent/Combustion Air System Piping
Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 14 Vent/Combustion Piping Support (Unit Sizes
55110) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 14 Vent/Combustion Piping Support (Unit Sizes 130310) . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 15 Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 15 Pre-Installation Checklist . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 15 Heater Suspension . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 16 Suspension of Heater Using Option CK8 or CK10
Hanger Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 16 Heater Suspension Using Field-Supplied Threaded Rods . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Suspension of
Heater with Downturn Nozzle . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 17 Piping Connections . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Gas Supply Pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Gas Supply Piping .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Supply Piping
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Vent Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Concentric Adapter Box Connections . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Vent
Terminal Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Vertical Vent Terminal (Option CC2) Installation . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Horizontal
Vent Terminal (Option CC6) Installation . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 26 Condensate Drain
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Vent Condensate
Drain Installation (Unit Sizes 55110) . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 32 Vent Condensate Drain Installation
(Unit Sizes 130310) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 33 Heat Exchanger Condensate Drain Installation . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 34 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 34
2
UEZ-IOM (07-24) 1034347-L
TABLE OF CONTENTS–CONTINUED
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 36 Thermostat Options . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 37 Combination Gas Valve . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 37 Pressure Switch . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 37 High Temperature Limit Control . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 38 Vent Temperature Limit Switch . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 38 Interlock Door Switch . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 38 Fan Motor . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 38 Circuit Board (DSI Control
Module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 38 Venter Motor . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Flame Rollout
Switch (Unit Sizes 55110) . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 39
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 39 Pre-Startup Checklist . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 40 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 40 Operating Sequences . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 41 Vent System Testing . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 44 Post-Startup Checklist . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 45
ADJUSTMENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 45 Pressure Switch Replacement . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 45 Measure and Adjust Manifold (Outlet) Gas Pressure . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Measure
and Adjust Manifold Gas Pressure–Elevation 2,000 Feet (610 Meters) . . . . . .
. . . . . . . . . . . . 47 Measure and Adjust Manifold Gas Pressure–Elevation
2,000 Feet (>610 Meters) . . . . . . . . . . . . . . . . . . 48 Converting Unit from Natural Gas to Propane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Service Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Maintenance Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Burner Maintenance (Unit Sizes 55110) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Burner Maintenance (Unit Sizes 130310) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Burner Orifice Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Heat Exchanger Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Ignition System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Fan and Motor Assembly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Venter Motor and Wheel Assembly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Combination Gas Valve Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Pressure Switch Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 High Temperature Limit Control Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Interlock Door Switch Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Transformer Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Vent Temperature Limit Switch Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Disconnect Switch Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Flame Rollout Switch Maintenance (Unit Sizes 55110) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Vent or Vent/Combustion Air System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Condensate Drain System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 General Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Unit Troubleshooting Using DSI Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
INSTALLATION RECORD (TO BE COMPLETED BY INSTALLER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
UEZ-IOM (07-24) 1034347-L
3
GENERAL INFORMATION
· This unit heater has been tested for capacity and efficiency so as to
provide many years of safe and dependable comfort providing it is properly
installed and maintained . With regular maintenance, this unit will operate
satisfactorily year after year . Abuse, improper use, and/or improper
maintenance can shorten the life of the appliance and create unsafe hazards .
· To achieve optimum performance and minimize equipment failure, it is
recommended that periodic maintenance be performed on this unit . The ability
to properly perform maintenance on this equipment requires certain tools and
mechanical skills .
· This manual applies only to UEZ models (high-efficiency, separated-
combustion, low-static) .
Important Safety Information
Please read all information in this manual thoroughly and become familiar with
the capabilities and use of your appliance before attempting to operate or
maintain this unit . Pay attention to all dangers, warnings, cautions, and
notes highlighted in this manual . Safety markings should not be ignored and
are used frequently throughout to designate a degree or level of seriousness .
DANGER: A danger statement describes a potentially hazardous situation that if
not avoided, will result in severe personal injury or death and/or property
damage . WARNING: A warning statement describes a potentially hazardous
situation that if not avoided, can result in severe personal injury and/or
property damage . CAUTION: A caution statement describes a potentially
hazardous situation that if not avoided, can result in minor or moderate
personal injury and/or property damage . NOTE: A note provides important
information that should not be ignored .
WARNING
· Gas-fired appliances are not designed for use in hazardous atmospheres
containing flammable vapors or combustible dust, in atmospheres containing
chlorinated or halogenated hydrocarbons, or in applications with airborne
silicone substances.
· Should overheating occur, or the gas supply control system fail to shut off
the flow of gas, shut off the manual gas valve to the unit before shutting off
the electrical supply.
· Do not use this appliance if any part has been under water. Immediately call
a qualified service technician to inspect the appliance and replace any gas
control that has been under water.
· Installation should be done by a qualified agency in accordance with these
instructions. The qualified service agency installing this heater is
responsible for the installation.
· This appliance is not intended for use by persons with reduced physical,
sensory, or mental capabilities or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
· Children should be supervised to ensure that they do not play with the
appliance.
CAUTION
To prevent damage to the unit or to its internal components, it is recommended
that two wrenches be used when loosening or tightening nuts. Do not over
tighten!
Condensate Drain Requirements
CAUTION
DO NOT use copper or copper-based alloys for condensate drains.
The combustion process forms condensation, which is collected and directed to
a drainage point inside the unit . The heater is equipped with a 1/2-inch (12
.7-mm) PVC pipe for connecting to a condensate drain . The water condensed
from the products of combustion will be acidic . The level of concentration is
dependent upon the environment where the appliance is installed and may be as
high as 6 pH .
4
UEZ-IOM (07-24) 1034347-L
Certification
· These unit heaters are listed by Intertek for use in industrial and
commercial installations in the United States and Canada . In addition, unit
sizes 55, 85, and 110 are listed in the United States and Canada as utility
heaters for use in non-living spaces that are attached to, adjacent to, or
part of a structure that contains space for family living quarters .
· These unit heaters are available for use with either natural or propane gas
. The type of gas, the input rate, and the electrical supply requirement are
shown on the heater rating plate . Check the rating plate to determine if the
heater is appropriate for the intended installation . All heaters are factory-
equipped for use with natural gas and include a conversion kit for field-
conversion for use with propane .
· These unit heaters have a titanium stabilized primary heat exchanger with a
MacroChannel® secondary heat exchanger .
Warranty
Refer to the limited warranty form in the literature bag provided with the
unit . The warranty is void if:
· Wiring is not in accordance with the diagram furnished with the heater .
· The unit is installed without proper clearance to combustible materials .
· A fan model is connected to a duct system or if the air delivery system is
modified .
Installation Codes
· These units must be installed in accordance with local building codes . In
the absence of local codes, in the United States, the unit must be installed
in accordance with the National Fuel Gas Code (ANSI Z223 .1, latest edition) .
A Canadian installation must be in accordance with the Natural Gas and Propane
Installation Code (CSA B149, latest edition) . This code is available from CSA
Information Services, 1-800-463-6727 .
Local authorities having jurisdiction should be consulted before installation
is made to verify local codes and installation procedure requirements .
· Installations in aircraft hangars should be in accordance with the Standard
for Aircraft Hangars (ANSI/NFPA No . 409, latest edition) . Installations in
public garages should be in accordance with the Standard for Parking
Structures (ANSI/NFPA No . 88A, latest edition) . Installations in repair
garages should be in accordance with the Standard for Repair Garages
(ANSI/NFPA No . 88B, latest edition) . In Canada, installations in aircraft
hangars should be in accordance with the requirements of the enforcing
authorities, and in public garages, in accordance with the CSA B149 code .
· If the heater is being installed in the Commonwealth of Massachusetts,
installation must be performed by a licensed plumber or licensed gas fitter .
Heater Location
CAUTION
· Unit heaters should not be used in an application where the heated space
temperature is below 40°F (4°C). The combination of low space and combustion
air temperatures may result in condensate freezing in the secondary heat
exchanger and/or condensate drain.
· Do not locate the heater where it may be exposed to water spray, rain, or
dripping water.
For best results, the heater should be mounted with certain rules in mind:
· Units should always be arranged to blow toward or along exposed wall
surfaces, if possible . Where two or more units are installed in the same
room, a general scheme of air circulation should be maintained for best
results .
· Suspended heaters are most effective when located as close to the working
zone as possible, and this fact should be kept in mind when determining the
mounting heights to be used . However, care should be exercised to avoid
directing the discharged air directly on the room occupants .
· Partitions, columns, counters, or other obstructions should be taken into
consideration when locating the unit heater so that a minimum quantity of
airflow will be deflected by such obstacles .
· When units are located in the center of the space to be heated, the air
should be discharged toward the exposed walls . In large areas, units should
be located to discharge air along exposed walls with extra units provided to
discharge air in toward the center of the area .
UEZ-IOM (07-24) 1034347-L
5
GENERAL INFORMATION–CONTINUED
Heater Location–Continued
Heater Throw
Figure 1 shows throw patterns for fan model units . Table 1 lists throw
distances for standard, adjustable horizontal louvers at the angles listed .
The louver angles listed are relative to the top of the heater . The throw
pattern changes with the addition of optional vertical louvers and/or downturn
nozzles .
Z = Distance at which air velocity drops below 50 feet (15.2 meters) per
minute
Figure 1. Heater Throw Patterns (Refer to Table 1)
Table 1. Heater Throw Distances with Standard Horizontal Louvers
H*
(Feet
Distance* or Angle
55
(Meters))
Unit Size (MBTUh)
85
110
130
180
260
Feet (Meters)
X
13 (4)
11 (3)
12 (4)
Y
17 (5)
15 (5)
17 (5)
5 (1 .5)
—
Z
37 (11)
44 (13)
49 (15)
Downward louver angle
15°
X
11 (3)
14 (4)
13 (4)
13 (4)
16 (5)
15 (5)
Y
16 (5)
17 (5)
21 (6)
24 (7)
30 (9)
28 (9)
8 (2 .4)
Z
35 (11)
42 (13)
46 (14)
73 (22)
93 (28)
94 (29)
Downward louver angle
27°
22°
26°
20°
24°
X
13 (4)
13 (4)
14 (4)
14 (4)
17 (5)
16 (5)
Y
17 (5)
24 (7)
31 (9)
28 (9)
10 (3 .0)
Z
33 (10)
38 (12)
43 (13)
69 (21)
91 (28)
89 (27)
Downward louver angle
32°
27°
32°
25°
29°
X
16 (5)
14 (4)
18 (6)
17 (5)
Y 12 (3 .7)
Z
19 (6) 35 (11)
17 (5) 41 (12)
24 (7) 64 (20)
31 (9) 88 (27)
28 (9) 85 (26)
Downward louver angle —
X
32°
39°
30°
34°
14 (4)
19 (6)
17 (5)
Y 14 (4 .3)
Z
17 (5) 30 (9)
18 (6) 41 (12)
22 (7) 59 (18)
30 (9) 84 (26)
27 (8) 80 (24)
Downward louver angle
39°
36°
45°
34°
40°
X
13 (4)
19 (6)
17 (5)
Y 16 (4 .9)
Z
20 (6) 53 (16)
29 (9) 79 (24)
25 (8) 74 (23)
Downward louver angle —
X
51° 11 (3)
39° 19 (6)
45° 16 (5)
Y 18 (5 .5)
Z
17 (5) 44 (13)
28 (9) 74 (23)
24 (7) 66 (20)
Downward louver angle
58°
44°
51°
*See Figure 1 .
310
17 (5) 31 (9) 105 (32)
20° 18 (6) 32 (10) 103 (31)
25° 19 (6) 32 (10) 98 (30)
30° 20 (6) 32 (10) 95 (29)
34° 21 (6) 31 (9) 90 (27)
38° 20 (6) 30 (9) 85 (26)
43°
6
UEZ-IOM (07-24) 1034347-L
Mounting Height Requirements
WARNING
If touched, the vent pipe and internal heater surfaces that are accessible
from outside the heater will cause burns. Suspend the heater a minimum of 5
feet (1.5 meters) above the floor.
In general, a unit should be located 812 feet (2 .43 .7 meters) above the
floor . At those points where infiltration of cold air is excessive, such as
at entrance doors and shipping doors, it is desirable to locate the unit so
that it will discharge directly toward the source of cold air from a distance
of 1520 feet (4 .6 6 .1 meters) .
Halogenated Hydrocarbons
Halogenated hydrocarbons are a family of chemical compounds characterized by
the presence of halogen elements (fluorine, chlorine, bromine, etc .) . These
compounds are used in refrigerants, cleaning agents, and solvents and are
heavier than air, a fact that should be kept in mind when determining the
installation location of heaters and building exhaust systems .
CAUTION
CORROSION HAZARD: Halogenated hydrocarbons, when exposed to flame, precipitate
with any condensation present in the heater to form hydrochloric acid, which
readily attacks all metals, including 300 grade stainless steel. Care should
be taken to separate these vapors from the combustion process. An outside air
supply MUST BE provided to the burner whenever the presence of these compounds
is suspected.
Clearances
Units must be located so that the clearances listed in Table 2 are provided
for with regards to combustion air space, inspection, and service and for
proper spacing from combustible construction . Clearance to combustibles is
defined as the minimum distance from the heater to a surface or object for
which it is necessary to ensure that a surface temperature of 90°F (32°C)
above the surrounding ambient temperature is not exceeded . Refer to the
Dimensions section when determining clearances to combustibles .
Table 2. Clearances
HeaterSurface
Minimum Clearance (Inches (mm))
Top
4 (102)
Flue connector
6 (152)
Access panel
18 (457)
Non-access side
2 (51)
Bottom*
1 (25)
Rear**
18 (457)
Front
Refer to values for variable X (distance from heater to start of floor coverage) in Heater Throw section
*Suspend the heater so that the bottom is a minimum of 5 feet (1 .5 meters) above the floor .
**Measure rear clearance from the fan motor .
Weights
55 85 (39)
85 103 (47)
110 123 (56)
Table 3. Weights
Unit Size (MBTUh) 130
Pounds (kg) 230 (104)
180 245 (111)
260 360 (163)
310 395 (179)
UEZ-IOM (07-24) 1034347-L
7
Dimensions
F
E H
GENERAL INFORMATION–CONTINUED
G
TOP VIEW B
D
W
S T
THERMOSTAT CONNECTION
VENT CONNECTION
L
LOW VOLTAGE ENTRANCE
X YZ
DISCONNECT SWITCH
GAS CONNECTION
M N P R
COMBUSTION AIR INLET
CONDENSATE DRAIN
REAR VIEW K
J
A C
FRONT VIEW
RIGHT SIDE VIEW
Figure 2. Dimensions–Unit Sizes 55110 (Refer to Table 4)
Table 4.
Unit Size (MBTUh)
A
B
55
17-5/8 (448) 28-1/4 (718)
85
21 (533)
30-1/4 (768)
110
24-1/2 (622) 32-1/4 (819)
H*
J
55
85
15 (381)
24-1/4 (616)
110
R
S
55
6 (152)
7-1/4 (184)
85
10-11/16 (271)
110
7-7/8 (200)
14-1/8 (359)
*Heater suspension points (3/8-16 FEM) .
Dimensions (Unit Sizes 55110)
Dimension (See Figure 2)
C
D
E*
Inches (mm)
12-1/2 (318) 15-7/8 (403)
16-7/8 (429) 17-7/8 (454) 2-27/32 (72)
19-1/4 (489) 18-7/8 (479)
K
L*
M
31 (787)
12 (305)
2 (51)
33 (838)
10-7/8 (276)
1-7/8 (48)
T
W
X
3-1/4 (83) 3-11/16 (94)
3-3/16 (81)
6-1/8 (156) 10-11/16 (271)
7-7/8 (200)
5-1/8 (130)
8-1/8 (206)
8
F*
1-9/16 (40)
N 3-3/16 (81) 5-3/16 (132)
Y 2-1/4 (57) 2-3/4 (70) 3-3/8 (86)
G*
18-1/8 (460) 20-1/8 (511)
P 4-7/8 (124) 6-7/8 (175)
Z
3/4 (19)
UEZ-IOM (07-24) 1034347-L
F
G
E
25 (635)
TOP VIEW
B D
R
5-5/8 (143)
1-9/16 (40)
P
DISCONNECT SWITCH LINE VOLTAGE ENTRANCE
GAS CONNECTION
COMBUSTION AIR INLET
THERMOSTAT CONNECTION
8-3/16 (208)
3-3/16 (81)
N M
CONDENSATE DRAIN
S
VENT CONNECTION
K REAR VIEW
H J
A C
FRONT VIEW
RIGHT SIDE VIEW
Figure 3. Dimensions–Unit Sizes 130310 (Refer to Table 5)
Table 5. Dimensions (Unit Sizes 130310)
Unit Size
A
Dimension (See Figure 3)
B
C
D
Inches (mm)
130, 180 260, 310
20-1/8 (511) 34-1/8 (867)
39-3/16 (995) 41 (1041)
16 (406) 30 (762)
23 (584)
F*
G*
H
J
130, 180
2-3/8 (60)
25-11/16 (652)
55-13/32 (1407)
46-1/32 (1169)
260, 310
1-13/32 (36)
27-11/16 (703)
58 (1473)
48-21/32 (1236)
M
N
P
R
130, 180
8-5/16 (211)
4-5/16 (110)
5-1/16 (129)
6-9/32 (160)
260, 310
9-3/32 (231)
5-3/32 (129)
18-13/16 (478)
7-1/32 (179)
*Heater suspension points (3/8-16 FEM) .
E*
11-31/32 (304) 13-31/32 (355)
K 15-19/32 (396) 16-15/32 (418)
S 1-3/4 (45) 1-3/8 (35)
UEZ-IOM (07-24) 1034347-L
9
VENTING AND COMBUSTION AIR REQUIREMENTS
NOTE: Refer to the Vent Connections section for details on vent system
installation. These units are certified as Category IV heaters . These heaters
are very thermal efficient and will produce condensate during operation .
Refer to Table 6 for suggested Category IV venting system providers .
Table 6.
IPEX USA LLC Centrotherm ECO Systems
The Schebler Co . Cheminee Lining E Inc .
Selkirk Corporation Z-FLEX US Inc . DuraVent Inc .
Suggested Category IV Venting System Providers
ENERVEX Inc . METAL-FAB Inc . Tokyo Gas Renovation Co . Ltd . Lifetime Chimney Supply LLC Van-Packer Co . Inc .
Industrial Chimney Co . SFL Flue & Chimney Industrial Combustion LLC
CaptiveAire Systems
Sunair Products
Security Chimneys International Ltd .
ECCO Manufacturing Division of ECCO Heating Products Ltd .
Vent/Combustion Air System Piping Requirements
DANGER
All separated-combustion units MUST BE equipped with both combustion air and
exhaust piping to the outdoors.
Vent/Combustion Air Piping Requirements (Unit Sizes 55110)
NOTE: Unit sizes 55, 85, and 110 are recommended for use with
UL-1738-compliant Category IV venting systems in the US, and with any
ULC-S636-listed Category IV venting system in Canada. Venting may be
terminated horizontally or vertically, provided that instructions for the
selected system are followed.
· Where permitted by local codes, PVC/CPVC pipes meeting ASTM D1785 and/or
ASTM F441 designated Schedule 40 are permitted to be used .
· Refer to Table 7 for vent and combustion air piping size requirements .
· The venter outlet and combustion air inlet are located at the rear of the
heater (see Figure 4) .
Table 7. Vent/Combustion Air Piping Size Requirements (Unit Sizes 55110)
Vent Piping
Combustion Air Piping
Unit Size
Diameter (Inches (mm))
Maximum Length
Equivalent Straight Length for Elbows
90-Degree 45-Degree Elbow* Elbow
Pipe Section
Diameter (Inches (mm))
Length (Feet (Meters))
Feet (Meters)
Minimum
Maximum
55, 85 110
2 (51) or 3 (76) 50 (15 .2)
2 (51)
25 (7 .6)
3 (76)
50 (15 .2)
8 (2 .4)
4 (1 .2)
Heater to concentric vent
2 (51) 2 (51) 3 (76)
3 (914) 3 (914) 3 (914)
50 (15 .2) 25 (7 .6) 50 (15 .2)
*All 90-degree elbows in the vent system must be sweep type .
10
UEZ-IOM (07-24) 1034347-L
C
A
TERMINAL STRIP VENT PIPE
LINE VOLTAGE ENTRANCE
COMBUSTION AIR PIPE COLLAR
B
DISCONNECT SWITCH
D
CONDENSATE DRAIN
GAS CONNECTION
Figure 4. Connections at Rear of Unit–Unit Sizes 55110 (Refer to Table 8)
Table 8.
Dimension (See Figure 4) or Connection
A B C D Combustion air pipe collar PVC vent pipe PVC condensate drain pipe
Connection Sizes and Locations (Unit Sizes 55110)
Unit Size (MBTUh)
55
85
Dimension/Diameter (Inches (mm))
3-1/4 (83)
3-11/16 (94)
7-1/4 (184)
10-11/16 (271)
3-3/16 (81)
6 (152)
2 (51)
3/4 (19)
110
7-1/8 (181) 14-1/8 (359) 5-1/8 (130) 7-7/8 (200)
Vent/Combustion Air Piping Requirements (Unit Sizes 130310)
NOTE: Concentric horizontal and vertical vent/combustion air systems (option
CC6 or CC2) are the only venting/combustion air systems approved for unit
sizes 130, 180, 260, and 310. The unique concentric adapter box required with
this heater allows for both combustion air and exhaust piping with only one
horizontal or vertical penetration hole in the building.
· Vent pipe: schedule 40 PVC or CPVC pipe or listed venting system of any type
(polypropylene, metallic, etc .)–in Canada, all vent pipe must be approved to
ULC-636 .
· Vent pipe clearance: do not install the vent piping near any high
temperature steam lines, radiant heaters, or other sources of heat .
· Vent piping size requirements: from heater to terminal end of vertical or
horizontal vent (refer to Table 9) .
· Combustion air inlet pipe: sealed, single-wall galvanized pipe is
recommended .
· Combustion air piping size requirements: from heater to concentric adapter
box and from concentric adapter box to outdoors (refer to Table 9) .
· Condensate drain connections: during operation, condensate is produced both
in the heater and in the venting system . Therefore, the installation requires
a condensate drain from the secondary heat exchanger and from the vent pipe .
For safe performance of the heater, each condensate drain must include a trap
. Install the condensate drains in accordance with the Condensate Drain
Installation section .
· Venter outlet and combustion air inlet: located at rear of heater (see
Figure 5) .
UEZ-IOM (07-24) 1034347-L
11
VENTING AND COMBUSTION AIR REQUIREMENTS–CONTINUED Vent/Combustion Air System
Piping Requirements–Continued
Vent/Combustion Air Piping Requirements (Unit Sizes 130310)–Continued
Table 9. Vent/Combustion Air Piping Size Requirements (Unit Sizes 130310)
Vent Piping
Combustion Air Piping
Diameter (Inches (mm))
Maximum Length
Equivalent Straight Length for Elbows
90-Degree 45-Degree
Elbow*
Elbow
Pipe Section
Diameter (Inches (mm))
Length (Feet (Meters))
Feet (Meters)
Minimum
Maximum
4 (102)
50 (15 .2)
8 (2 .4)
4 (1 .2)
Heater to concentric adapter box
Concentric adapter box to outdoors
6 (152) 8 (203)
3 (914)
Same as vent pipe
Refer to Vent Connections section
*All 90-degree elbows in the vent system must be sweep type .
NOTE: The minimum/maximum requirements for the length of vent pipe that extends outdoors are different for horizontal and vertical vent terminals (refer to Vent Connections section) .
DISCONNECT SWITCH
LINE VOLTAGE ENTRANCE
GAS CONNECTION
COMBUSTION AIR PIPE COLLAR
A B
CONDENSATE DRAIN
C
TERMINAL STRIP
D
VENT PIPE
Figure 5. Connections at Rear of Unit–Unit Sizes 130310 (Refer to Table 10)
Table 10.
Dimension (See Figure 5) or Connection
A B C D Combustion air pipe collar PVC vent pipe PVC condensate drain pipe
Connection Sizes and Locations (Unit Sizes 130310)
Unit Size (MBTUh)
130, 180
260, 310
Dimension/Diameter (Inches (mm))
8-1/4 (210)
3-1/4 (83)
8-5/16 (211)
9-3/32 (231)
4-5/16 (110)
5-1/16 (129)
6 (153)
4 (102)
1/2 (13)
12
UEZ-IOM (07-24) 1034347-L
Vent/Combustion Air System Piping Joints
Vent/Combustion Piping Joints (Unit Sizes 55110)
All vent/combustion piping joints for unit sizes 55, 85, and 110 must comply
with the vent system manufacturer’s requirements .
Vent/Combustion Piping Joints (Unit Sizes 130310)
NOTE: If using a UL-1738-listed Category IV venting system in the US or a
ULC-S636-listed Category IV venting system in Canada, follow the instructions
provided for that system.
When ready to install the vent system, ensure that piping joints are in
accordance with the following: · Combustion air piping: secure slip-fit joints
of single-wall combustion air pipe using sheet metal screws or rivets .
Seal joints and seams with aluminium tape or silicone sealant . · Vent piping:
the vent system should be installed in a manner consistent with normal
industry standards and in
compliance with all local fire and building code requirements . Failure to
follow proper installation practices, procedures, or techniques can result in
system failure, property damage, or personal injury . The installer is
responsible for the installation . Read the following procedure before
beginning installation:
NOTE: Install piping joints one at a time. Pipe and fittings should be
assembled quickly while cement is fluid.
1 . Cut pipe square–angled cut may result in joint failure: a . Remove all
burrs from inside and outside diameter of cut end of pipe burrs using
deburring tool, file, or knife edge . b . Chamfer (bevel) end of pipe 10 to 15
degrees . c . Remove surface dirt, grease, and moisture from pipe sections and
fittings using clean dry cloth .
2 . Check for proper fit–test fit using light pressure: a . Install dry pipe
one-half to one-third of way into fitting hub . b . Ensure that pipe and
fittings are not too tight or too loose .
3 . Apply primer to pipe and fitting surfaces using 2- to 3-inch applicator
brush: a . Ensure that primer conforms to ASTM F656 . b . Ensure that primer
does not puddle inside system .
4 . Apply cement using 2- to 3-inch applicator brush, quickly assembling joint
while cement is fluid: a . Ensure that cement conforms to ASTM D2564 . b .
Apply full even layer of cement to pipe OD slightly greater than depth of
socket on coupler (fitting) . c . Coat coupler (fitting) socket with medium
layer of cement, ensuring that cement does not puddle inside system . d .
Apply second full even layer of cement to pipe OD .
5 . Join pipe and coupler (fitting): a . Working quickly while cement is
fluid, insert pipe into coupler (fitting) until it touches socket bottom . a .
Turn pipe quarter turn and hold joint together until pipe will not pull out .
b . Clean excessive cement from exterior–properly made joint will have
continuous bead of cement around perimeter .
UEZ-IOM (07-24) 1034347-L
13
VENTING AND COMBUSTION AIR REQUIREMENTS–CONTINUED
Vent/Combustion Air System Piping Support
Vent/Combustion Piping Support (Unit Sizes 55110)
All vent/combustion piping supports for unit sizes 55, 85, and 110 must comply
with the vent system manufacturer’s requirements .
Vent/Combustion Piping Support (Unit Sizes 130310)
CAUTION
DO NOT use the heater or concentric adapter box to provide vent pipe support.
· Vent pipe support: for continued safe operation, the vent system must be
properly supported . A 10-foot (3-meter) length of PVC pipe weighs 20 pounds
(9 kg) and has an expansion rate of four times that of metal pipe .
· Horizontal CPVC or PVC vent: must be supported every 6 feet (1 .8 meters) .
The hangers should provide as much bearing surface as possible and must be
free of sharp edges and burrs . Hangers must allow the pipe to expand
laterally . Consider pipe expansion when placing hangers . Changes in pipe
direction will allow for expansion . Hangers must be placed to allow for some
direction movement . The slip joint at the concentric adapter box is designed
to permit some limited expansion .
· Vertical CPVC or PVC vent: it is recommended that an engineer design the
vertical support system . An acceptable field-supplied cradle-type support
that allows for expansion for a simple vertical vent that is 30 feet (9 .1
meters) or less and rises closely from the heater is shown in Figure 6 .
UNIT
3/8-inch threaded rod attached to building structural member
Vertical single-wall combustion air pipe may be supported by heater and
concentric adapter box
Vertical Vent
Cradle Support
Slope horizontal run downward slightly toward vent condensate drain at heater
Sweep-type elbow only
3 to 6 inches (76 to 152 mm)
Maximum length 6 feet (1.8 M) for single support
Figure 6. Vent Pipe Support
· Combustion air pipe support: support a single-wall metal horizontal
combustion air run every 6 feet (1 .8 meters) . Support a vertical single-wall
metal combustion air pipe in accordance with accepted industry practices . The
heater and concentric adapter box may be used to support a vertical combustion
air pipe .
· This unit heater is a high-efficiency appliance designed to extract part of
the latent heat from the products of combustion .
14
UEZ-IOM (07-24) 1034347-L
INSTALLATION
Unpacking and Inspection
· The unit was test-operated and inspected at the factory prior to crating and
was in operating condition . · It is important to note when uncrating the unit
that shipping brackets are attached with cabinet screws . When
removing shipping brackets, re-insert ALL screws into the cabinet . · If, upon
removing it from its crate, the unit has been found to have incurred any
damage in shipment, document
the damage with the transporting agency and contact an authorized Factory
Distributor . If you are an authorized Distributor, follow the FOB freight
policy procedures . · A conversion kit is included with the heater for
converting for use with propane (refer to Converting Unit from Natural Gas to
Propane section) .
Pre-Installation Checklist
Check the rating plate for the gas specifications and electrical
characteristics of the heater to ensure that they are compatible with the gas
and electric supplies at the installation site .
Read this manual and become familiar with the installation requirements of
your particular heater . If you do not have knowledge of local requirements,
check with the local gas company or any other local agencies
who might have requirements concerning this installation . Before beginning,
make preparations for necessary supplies, tools, and manpower . Check to see
if there are any field-installed options (refer to Table 11) that need to be
assembled/installed
prior to unit installation . Ensure that all options ordered are at the
installation site .
Option CC2 CC6 CC18 CC19 CC20 CC22 CC23 CC24 CC25 CD1 CD2 CD3 CD4 CE1 CG1 CG4
CG5 CK8 CK10 CL1
CL31, CL32
CM1
Table 11. Field-Installed Options
Description Vertical vent terminal/combustion air kit Horizontal vent
terminal/combustion air kit Universal vent terminal assembly, 2-inch diameter
× 40 inches long Horizontal vent terminal assembly, 3-inch diameter × 20
inches long Universal vent terminal assembly, 3-inch diameter × 44 inches long
Low profile horizontal vent terminal assembly, 2-inch diameter Low profile
horizontal vent terminal assembly, 3-inch diameter Horizontal vent terminal
assembly, 2-inch diameter × 16 inches long Universal vent terminal assembly,
2- or 3-inch diameter × 24 inches long Vertical louvers, direct discharge air
to provide wider throw pattern Downturn nozzle, 25- to 65-degree variable air
deflection range Downturn nozzle, 50- to 90-degree variable air deflection
range Downturn nozzle, 25- to 65-degree variable air deflection range with
vertical louvers Manual shutoff valve, natural gas or propane 208V115V
stepdown transformer 230V115V or 460V115V stepdown transformer 575V115V
stepdown transformer Adapts 3/8-inch hangers for two-point suspension from
1-inch threaded pipe Adapts 3/8-inch hangers for four-point suspension from
1-inch threaded pipe Single-stage thermostat Multiple unit control: option
CL31 includes components for one control unit and one additional unit– option
CL32 includes components for each additional non-control unit Locking cover
for CL1 thermostat
UEZ-IOM (07-24) 1034347-L
15
INSTALLATION–CONTINUED Heater Suspension
WARNING
· Before suspending the heater, check the supporting structure to be used to
verify that it has sufficient load-carrying capacity to support the weight
(refer to Weights section) of the unit.
· The heater must be level for proper operation. DO NOT place or add
additional weight to a suspended heater.
CAUTION
· Before lifting the heater, verify that any screws used for holding shipping
brackets were reinstalled in the cabinet.
· Before lifting the heater, any unused suspension points MUST be plugged.
Seal any unused holes in the top of the heater after installing the hanging
hardware using capscrews and washers.
· When the heater is lifted for suspension, support the bottom of the heater
with plywood or other appropriately placed material. If the bottom is not
supported, damage could occur.
NOTE: Four-point suspension is recommended. Two-point suspension is permitted
only on unit sizes 55110 when installed without a downturn nozzle. A 3/8-16
threaded nut retainer is located at each suspension point . The heater may be
suspended using either 3/8inch threaded rods or a hanger kit option package .
Suspension of Heater Using Option CK8 or CK10 Hanger Kit Options CK8 (two-
point suspension, unit sizes 55110) and CK10 (four-point suspension) are for
suspending the heater using swivel connectors connected to 1-inch pipe .
Attach the swivel connectors at the 3/8-16 threaded nut retainers . Ensure
that the swivel connectors are locked to the heater as shown in Figure 7 .
Figure 7. Option CK8 or CK10 Hanger Kit
16
UEZ-IOM (07-24) 1034347-L
Heater Suspension Using Field-Supplied Threaded Rods
The heater may be suspended from 3/8-inch threaded rods using either two-
(unit sizes 55110) or four-point suspension . The recommended maximum rod
length is 6 feet (1 .8 meters) . The length of the threaded rod extending into
the heater MUST NOT exceed 1/2 inch (13 mm) . Ensure that the threaded rods
are locked to the heater as shown in Figure 8 .
ADD 3/8-INCH NUT AND WASHER TO LOCK ROD TO HEATER
3/8-INCH THREADED ROD
Figure 8. Heater Suspension Using Field-Supplied Threaded Rods
Suspension of Heater with Downturn Nozzle
Ensure that any unit with a downturn nozzle (option CD2, CD3, or CD4) is
installed using one of the above FOURPOINT suspension methods . Follow the
instructions provided with the downturn nozzle kit .
Piping Connections
Gas Supply Pressure
· The unit is equipped for a maximum gas supply pressure of 1/2 psi, 3 .5 kPa,
or 14 IN WC for natural gas or propane . The minimum supply pressure, as
measured while the unit is operating at full fire, is 5 IN WC for natural gas
or 11 IN WC for propane .
· Supply pressure higher than 1/2 psi requires the installation of an
additional service regulator external to the unit . · Pressure testing supply
piping: For test pressures above 1/2 psi, disconnect the heater and manual
valve from
the gas supply line to be tested and cap or plug the supply line . For test
pressures below 1/2 psi, before testing, close the manual valve on the heater
.
UEZ-IOM (07-24) 1034347-L
17
INSTALLATION–CONTINUED
Piping Connections–Continued
Gas Supply Piping
DANGER
· All components of a gas supply system must be leak tested prior to placing
equipment in service. NEVER TEST FOR LEAKS WITH AN OPEN FLAME. Failure to
comply could result in personal injury, property damage, or death.
· Pipe joint compounds (pipe dope) shall be resistant to the action of
liquefied petroleum gas or any other chemical constituents of the gas being
supplied.
· All piping must be in accordance with requirements outlined in the National
Fuel Gas Code (ANSI/Z223 .1, latest edition) or the Natural Gas and Propane
Installation Code (CSA-B149 .1, latest edition) .
· Gas supply piping installation shall conform with good practice and with
local codes . · Support gas piping with pipe hangers, metal strapping, or
other suitable material . Do not rely on the heater to
support the gas pipe . · The heater is orificed for operation with natural gas
having a heating value of 1,000 (±50) BTU per cubic foot or
with propane gas having a heating value of 2,500 (±100) BTU per cubic foot .
Sizing of gas supply lines depends on piping capacity and is based on cubic
feet per hour based on a 0 .3 IN WC pressure drop, a 0 .6 specific gravity for
natural gas at 1,000 BTU per cubic feet, and a 1 .6 specific gravity for
propane at 2,550 BTU per cubic feet . If the gas at the installation does not
meet this specification, consult the factory for proper orificing . ·
Variables for sizing gas supply lines are listed in Table 12 . When sizing
supply lines, consider the possibility of future expansion and increased
requirements (refer to the National Fuel Gas Code for additional information)
.
Table 12. Gas Supply Line Sizes
Natural Gas
Pipe
Length
(Feet)
1/2
3/4
Pipe Diameter (Inches)
1
1-1/4 1-1/2
2
1/2
3/4
Cubic Feet per Hour
Propane
1
1-1/4
1-1/2
2
20
92
190
350
730 1100 2100
56
116
214
445
671
1281
30
73
152
285
590
890 1650
45
93
174
360
543
1007
40
63
130
245
500
760 1450
38
79
149
305
464
885
50
56
115
215
440
670 1270
34
70
131
268
409
775
60
50
105
195
400
610 1105
31
64
119
244
372
674
70
46
96
180
370
560 1050
28
59
110
226
342
641
80
43
90
170
350
530
990
26
55
104
214
323
604
90
40
84
160
320
490
930
24
51
98
195
299
567
100
38
79
150
305
460
870
23
48
92
186
281
531
125
34
72
130
275
410
780
21
44
79
168
250
476
150
31
64
120
250
380
710
19
39
73
153
232
433
175
28
59
110
225
350
650
17
36
67
137
214
397
200
26
55
100
210
320
610
16
34
61
128
195
372
18
UEZ-IOM (07-24) 1034347-L
Supply Piping Connections
· Install a ground joint union and manual shutoff valve upstream of the unit
control system, as shown in Figure 9 .
· The 1/8-inch plugged tapping in the manual shutoff valve in Figure 9
provides connection for a supply line pressure test gauge .
· The National Fuel Gas Code requires the installation of a trap with a
minimum 3-inch drip leg (see Figure 9) . Local codes may require a drip leg
longer than 3 inches (typically 6 inches) . To permit burner removal, this
drip leg must extend beyond the edge of the heater .
· Leak-test all connections by brushing on a leak-detecting solution . Bleed
trapped air from gas lines as needed .
· The gas connection is made at the pipe nipple that extends outside the
cabinet, as shown in Figure 9 . Gas connection sizes are listed in Table 13 .
Figure 9. Gas Connections
Table 13. Gas Connection Sizes
Unit Size (MBTUh)
Natural Gas
Connection (Inches)*
130, 180
1/2
260, 310
3/4
*Connection size for a standard unit (not gas supply line size) .
Propane
1/2 3/4
Vent Connections
NOTE: IMPORTANT: For unit sizes 55, 85, and 110, install the venting system in
accordance with the venting system manufacturer’s instructions. For unit sizes
130, 180, 260, and 310, install the venting system in accordance with the
following paragraphs.
UEZ-IOM (07-24) 1034347-L
19
INSTALLATION–CONTINUED Vent Connections–Continued
Concentric Adapter Box Connections · The concentric adapter box is included in
the vent/combustion air kit, which is ordered with the heater . · A horizontal
terminal vent/combustion air kit is option CC6; a vertical terminal
vent/combustion air kit is option CC2 .
The concentric adapter box is included in both the horizontal and vertical
vent/combustion air kits . Installation is included in the instructions for
options CC6 and CC2 . · The concentric adapter box is shown Figure 10 .
Dimensions and connections are shown in Figure 11 .
HEATER SIDE VIEW
There is silicone ring around this opening in box. Loosen screws on pipe
support bracket. Adjust bracket to provide good seal with ring and tighten
screws. Figure 10. Concentric Adapter Box
20
UEZ-IOM (07-24) 1034347-L
1-7/8″ (48mm)
Top View
6-3/16″ (157mm)
8″ diameter Collar for Combustion Air Pipe
2″ (51mm)
Heater Side View
4-3/32″ (104mm)
14-3/8″ (365mm)
5-9/32″ (134mm)
9-11/32″ (237mm)
5-11/23″ (136mm)
6″ diameter Collar for Combustion Air Pipe
6″ diameter Collar for Combustion Air Pipe
Silicone Ring
Opening for 4″ diameter Vent Pipe 16″ (406mm) 17″ (432mm)
6-1/8″ (156mm)
6-1/8″ (156mm)
1-1/16″ (27mm)
Figure 11. Concentric Adapter Box Dimensions and Connections
UEZ-IOM (07-24) 1034347-L
21
INSTALLATION–CONTINUED Vent Connections–Continued
Vent Terminal Options Vent terminal options CC2 (vertical vent configuration)
and CC6 (horizontal vent configuration) are shown in Figure 12 .
VERTICAL (OPTION CC2)
HORIZONTAL (OPTION CC6)
Figure 12. Vent Terminal Options
Vertical Vent Terminal (Option CC2) Installation
· Field-supplied components required for installation of the vertical vent kit
are as follows: a . Vent and combustion air piping: 6- and 8-inch single-wall
galvanized pipe b . Tapered vent pipe diameter reducers and/or increasers, as
required c . Thimble (not required if wall is of non-combustible construction)
d . Flashing e . Sheet metal screws, tape, and sealant, as required
· Factory-supplied components for installation of the vertical vent kit are
listed in Table 14 and shown in Figure 13 .
Table 14.
PN 221248 221069 221185 221250 221091 221215 37661
Vertical Vent Terminal/Combustion Air Package (Option CC2) Components
Description
Quantity
Kit package
1
Concentric adapter box with silicone sealing ring (see Figure 10 and Figure 11)
1
Rain collar (see Figure 13)
1
Combustion air inlet (see Figure 13)
1
Cap, condensate drain connection, 4-inch PVC
1
Bird guard (see Figure 13)
1
Screw, self-drilling, #10-16 × 1/2, bird guard
2
22
UEZ-IOM (07-24) 1034347-L
RAIN COLLAR
COMBUSTION AIR INLET
BIRD GUARD
Figure 13. Option CC2 Components
· Install the vertical vent kit as follows:
DANGER
To prevent combustion products from entering the occupied space, all vent
terminals must be positioned or located away from fresh air intakes, doors,
and windows. Failure to comply could result in severe personal injury or death
and/or property damage.
1 . Determine vent terminal location on outside wall: a . If more than one
vertical vent terminal is being installed, minimum spacing between vent center
lines is determined by minimum outdoor design temperature (coldest outdoor
condition at installation site) . Refer to Table 15 to ensure that location
complies with minimum outdoor design temperature requirements .
Table 15. Minimum Spacing Between Center Lines of Vertical Vent Pipes
Minimum Outdoor Design Temperature
Minimum Spacing Between Center Lines of Vertical Vent Pipes (Inches (mm))
31°F (0°C)
36 (914)
-10 to 30°F (-23 to -1°C)
60 (1524)
< -10°F (< -23°C)
84 (2134)
b . Select location away from fresh air intakes, allowing space for concentric
adapter box inside . Vent terminal must be located away from adjacent
buildings as shown in Figure 14 .
2 . Install vent pipe and combustion air pipe runs:
a . Connect piping to heater in accordance with specifications listed in
Vent/Combustion Air System Piping Requirements section .
b . Seal all joints in accordance with specifications listed in
Vent/Combustion Air System Piping Joints section. Due to high temperature
considerations, do not enclose exhaust pipe or place pipe closer than 6 inches
(152 mm) to combustible material .
c . Extend piping runs close to roof at location selected in step 1 and
support piping in accordance with specifications listed in Vent/Combustion Air
System Piping Support section .
NOTE: The vent pipe will extend through the roof after the concentric adapter
box is installed. The indoor combustion air pipe will end at the box.
3 . Cut hole through outside wall for combustion air pipe .
a . Ensure that location and orientation of concentric adapter box are correct
and mark and cut hole .
b . Ensure that hole accommodates 8-inch (203-mm) combustion air pipe .
UEZ-IOM (07-24) 1034347-L
23
INSTALLATION–CONTINUED Vent Connections–Continued
Vertical Vent Terminal (Option CC2) Installation–Continued
Rear View
Side View
Figure 14. Option CC2 Installation
4 . Connect combustion air pipe to concentric adapter box (see Figure 15):
a . Determine length of combustion air pipe so that dimension X in Figure 15
is equal to roof thickness plus anticipated snow depth . Ensure that length of
combustion air pipe does not exceed 48 inches (1,219 mm) or does not extend
less than 18 inches (457 mm) above roof .
b . Secure inlet air pipe to collar of concentric adapter box using sheet
metal screws . Seal joint and seam using tape or sealant .
5 . Secure concentric adapter box to underside of roof (see Figure 14):
a . Insert combustion air pipe through roof as shown in Figure 15, DETAIL A .
b . Position concentric adapter box to match pipe runs and secure box to
underside of roof using field-supplied hardware .
24
UEZ-IOM (07-24) 1034347-L
DETAIL A
Figure 15. Combustion Air Pipe Installation
6 . Install terminal-end vent pipe:
NOTE: The length of the terminal-end vent pipe is determined by the
installation within maximum and minimum requirements. The vent pipe extending
through the box, through the combustion air inlet pipe, and above the
combustion air inlet air pipe must be one piece without joints.
a . Refer to Figure 15 to determine required length of continuous section of
vent pipe . Determine length as follows: 1) start with at least 6 inches (152
mm) below concentric adapter box for connecting to coupler, 2) plus 6 inches
(152 mm) through box, 3) plus length of combustion air pipe, 4) plus minimum
of 23 inches (584 mm) beyond top of combustion air pipe–total is minimum
length of vent pipe section .
NOTE: A longer vent pipe may be required.
b . Ensure that vent pipe is in proper flow direction and slide end of pipe
into box and out through combustion air pipe . Position vent pipe to lengths
determined above .
c . Ensure that silicone ring is seated properly and connect terminal vent
pipe to vent pipe run . d . Recheck silicone ring to ensure that it is still
properly seated . 7 . Install indoor combustion air pipe: a . Secure single-
wall combustion air pipe run to collar on concentric adapter box using field-
supplied sheet metal
screws . b . Seal pipe joint using tape or sealant .
UEZ-IOM (07-24) 1034347-L
25
INSTALLATION–CONTINUED Vent Connections–Continued
Vertical Vent Terminal (Option CC2) Installation–Continued 8 . Install outdoor
combustion air inlet, rain collar, bird screen, and field-supplied flashing
(see Figure 16):
a . Slide combustion air inlet over vent pipe and secure collar to combustion
air pipe using sheet metal screws . b . Seal pipe joint using tape or sealant
. c . To prevent rainwater leakage, slide rain collar over end of 4-inch vent
pipe and seat it flush on top of combustion
air inlet . Do not paint or use petroleum-based products on rain collar
(silicone sealant is allowed) . d . Install bird guard and secure using two
sheet metal screws provided . e . Flash combustion air pipe on outside using
field-supplied flashing .
BIRD GUARD
RAIN COLLAR
COMBUSTION AIR INLET
Figure 16. Combustion Air Inlet, Rain Collar, and Bird Guard 9 . Verify
compliance with Figure 14 and with all specifications listed in VENTING AND
COMBUSTION AIR
REQUIREMENTS and Halogenated Hydrocarbons sections . Horizontal Vent Terminal
(Option CC6) Installation · Field-supplied components required for
installation of the horizontal vent kit are as follows:
a . Vent and combustion air piping: 6- and 8-inch single-wall galvanized pipe
b . 22 .5-degree elbow (if available) c . Flashing d . Sheet metal screws,
tape, and sealant, as required · Factory-supplied components for installation
of the horizontal vent kit are listed in Table 16 and shown in Figure 17 .
26
UEZ-IOM (07-24) 1034347-L
Table 16.
PN 221247 221069 221089 124940 221186 37661 221091
Horizontal Vent Terminal/Combustion Air Package (Option CC6) Components
Description
Quantity
Kit package
1
Concentric adapter box with silicone sealing ring (see Figure 10 and Figure 11)
1
Bird screen, exhaust outlet (see Figure 17)
1
Ring guard, air inlet (see Figure 17)
1
Spacer, inlet air guard
4
Screw, self-drilling, #10-16 × 1/2, inlet air guard
4
Cap, condensate drain connection, 4-inch PVC
1
BIRD SCREEN
RING GUARD
Figure 17. Option CC6 Components
· Install the horizontal vent kit as follows:
DANGER
· To prevent combustion products from entering the occupied space, all vent
terminals must be positioned or located away from fresh air intakes, doors,
and windows. Failure to comply could result in severe personal injury or death
and/or property damage.
· In climates with below freezing temperatures, condensate may form icicles on
the vent terminal. Locate the terminal where falling icicles do not present a
hazard.
· Consider local snow depth conditions. The vent must be at least 6 inches
(152 mm) above the anticipated snow depth.
1 . Determine vent/combustion air terminal location on outside wall: a . Refer
to Table 7 and Table 8 or Table 9 and Table 10 to ensure that location
complies with vent length requirements . b . For most applications, ensure
that vent terminal is level with heater mounting height . c . Allow downward
pitch of 1/4-inch per foot (6 mm per 305 mm) for condensate drain .
NOTE: Local codes supersede all provisions in these instructions and in the
National Fuel Gas Code (ANSI Z223.1).
WARNING
Avoid positioning the vent terminal above a walkway as there may be a small
amount of condensate that drips from the end of the vent/combustion air
terminal. In cold climates, the condensate may form icicles.
d . Ensure that distance of vent terminal from adjacent public walkways and
buildings and window and building openings complies with local codes . Absent
any local codes, distance must comply with National Fuel Gas Code (ANSI Z223
.1) .
UEZ-IOM (07-24) 1034347-L
27
INSTALLATION–CONTINUED
Vent Connections–Continued
Horizontal Vent Terminal (Option CC6) Installation–Continued
CAUTION
Products of combustion can cause discoloration of some building finishes and
deterioration of masonry materials. A clear silicone sealant normally used to
protect concrete driveways may be used to protect masonry materials from
discoloration and deterioration. If discoloration is an esthetic problem
relocate the vent or install a vertical vent.
e . Refer to Table 17 to ensure that location complies with minimum clearance requirements .
Table 17. Minimum Clearance Requirements for Horizontal Vent Termination Location
Component/Structure
Minimum Clearance, All Directions Unless Specified (Feet (Meters))
Forced air inlet within 10 feet (3 .1 meters)*
3 (0 .9) above
Combustion air inlet of another appliance
6 (1 .8)
Mechanical air supply inlet to any building
Canada: 6 (1 .8)
Any building opening (door, window, or gravity air inlet)
4 (1 .2) horizontal and below 1 (0 .3) above
Gas meter,** electric meter, and relief equipment
US: 4 (1 .2) horizontal Canada: 6 (1 .8) horizontal
Gas regulator**
US: 3 (0 .9) horizontal Canada: 6 (1 .8) horizontal
Adjoining building or parapet
6 (1 .8)
Adjacent public walkway
7 (2 .1) above
Grade (ground level)
3 (0 .9) above
*Does not apply to the inlet of a direct vent appliance .
**Do not terminate the vent directly above a gas meter or service regulator .
2 . Install vent pipe and combustion air pipe runs: a . Connect piping to
heater in accordance with specifications listed in Vent/Combustion Air System
Piping Requirements section . b . Seal all joints in accordance with
specifications listed in Vent/Combustion Air System Piping Joints section. Due
to high temperature considerations, do not enclose exhaust pipe or place pipe
closer than 6 inches (152 mm) to combustible material . c . Extend piping runs
close to wall at location selected in step 1 and support piping in accordance
with specifications listed in Vent/Combustion Air System Piping Support
section .
NOTE: The vent pipe will extend through the wall after the concentric adapter
box is installed. The indoor combustion air pipe will end at the concentric
adapter box.
3 . Cut hole through outside wall for combustion air pipe . a . Ensure that
outside wall construction thickness is between 1 inch (25 mm) minimum and 48
inches (1,219 mm) maximum . b . Ensure that hole accommodates 8-inch (203-mm)
combustion air pipe .
4 . Connect concentric adapter box (see Figure 18): a . Determine length of
combustion air pipe by measuring wall thickness plus 416 inches (102406 mm)
beyond minus width of pipe crimp that will be cut off . b . Cut crimp off end
of combustion air pipe so that 8-inch inlet air guard will fit properly . c .
Turn combustion air pipe so that is toward top side of concentric adapter box
and slide it on collar . d . Secure combustion air pipe to collar using sheet
metal screws and seal joint and seam using sealant or tape .
28
UEZ-IOM (07-24) 1034347-L
Unit
X
Y
Size feet meters inches mm
130, 180 8 2.4
36 914
260, 310 10 3.0
48 1219
**Minimum: check for and comply with local codes.
Figure 18. Option CC6 Installation
5 . Drill drain hole: a . Mark location on bottom side of pipe that will be
outside between end of pipe and building–about 2/3 of distance from end of
pipe to edge of building–when concentric adapter box is installed . b . Drill
1/2-inch diameter drain hole at location marked in step 5a .
6 . Install air inlet ring guard: a . Position inlet air ring guard over end
of combustion air pipe in accordance with Figure 18 . b . Secure inlet air
ring guard to inlet air pipe using four 1/2-inch-long screws provided .
UEZ-IOM (07-24) 1034347-L
29
INSTALLATION–CONTINUED
Vent Connections–Continued
Horizontal Vent Terminal (Option CC6) Installation–Continued 7 . Secure
concentric adapter box to the wall:
a . Insert combustion air pipe with inlet guard attached out through wall . b
. Position concentric adapter box so that pipe is centered in opening and
secure box brackets to wall using
field-supplied hardware . 8 . Install terminal-end vent pipe:
NOTE: The length of the continuous piece of terminal-end vent pipe is
determined by the installation within maximum and minimum requirements. The
vent pipe extending through the box and through the combustion air inlet pipe
must be one piece without joints.
a . Refer to Figure 18 to determine lengths of each pipe segment and to
calculate total length required . b . Ensure that terminal-end vent pipe is in
proper flow direction and temporarily fit elbow pointing down on exhaust
end of vent pipe .
NOTE: For easier future service, the elbow is secured to the vent pipe using
one field-provided 3/4-inch-long sheet metal screw.
c . Drill hole through top center of elbow socket and vent pipe using drill
bit one size smaller than 3/4-inch-long sheet metal screw . Remove elbow and
enlarge drilled hole in elbow to 7/32 inch .
d . Turn vent pipe so that drilled hole is at top and slide end of pipe out
through concentric adapter box and combustion air pipe .
e . Position vent pipe so that it extends 36 inches (76152 mm) past end of
combustion air pipe . Turn pipe so that screw hole is in top center .
f . Ensure that silicone sealing ring on concentric adapter box is properly
seated . Do not add sealant to ring . g . Connect terminal-end vent pipe to
vent pipe run and recheck sealing ring to ensure that it is still properly
seated . 9 . Install indoor section of combustion air pipe: a . Secure single-
wall combustion air pipe run to collar on concentric adapter box using sheet
metal screws . b . Seal pipe joint using tape or sealant . 10 . Install inlet
air guard spacers, elbow, and bird screen on outdoor section of combustion air
pipe: a . Remove inlet air ring guard screws installed in step 6b . Slide
spacers onto ends of four spokes that support
vent pipe . Re-install guard and secure using screws . b . Slide elbow
pointing down on end of pipe, align hole drilled in step 8c, and secure elbow
using field-supplied
3/4-inch-long sheet metal screw . c . Insert bird screen into socket on open
end of elbow . 11 . Seal or flash around combustion air pipe: a . Seal around
combustion air pipe using an outdoor caulking material, masonry cement, or
combination of
flashing and caulking . b . Adjust sealant and pipe so that pipe has slight
downward slope to outside . Downward slope and drain hole
drilled in step 5b prevents rain water from running through pipe into
concentric adapter box . 12 . Verify compliance with Figure 18 and with all
specifications listed in VENTING AND COMBUSTION AIR
REQUIREMENTS and Halogenated Hydrocarbons sections .
30
UEZ-IOM (07-24) 1034347-L
Condensate Drain Installation
CAUTION
Apply general plumbing practices if pipe insulation or heat tapes are required
to prevent freezing of the condensate drain system.
· Because condensate is produced both in the heater and in the venting system,
the installation requires a condensate drain from the vent pipe and from the
secondary heat exchanger .
· Condensate from the heater has a pH of 6 and is not harmful to a sanitary
drain . Actual pH may vary ±1 depending on fuel and combustion air .
· Unit sizes 55, 85, and 110 produce approximately 1/2 gallon (2 liters) of
condensate per hour . Unit sizes 130 and 180 produce approximately 1 gallon (4
liters) of condensate per hour . Unit sizes 260 and 310 produce approximately
2 gallons (8 liters) of condensate per hour .
· A condensate disposal system that relies on gravity should be satisfactory
for most installations as unit heaters are normally installed several feet
above the floor . If a gravity system is not possible, a condensate pump may
be installed . There are a number of commercially-available pumps made for
this purpose . If using a condensate pump, follow the pump manufacturer’s
installation recommendations .
· The orientation of the piping is not critical and may be arranged to suit
the installation . Unions are recommended to permit maintenance of the drains
and to facilitate service of the heater . A union is shown in both of the
traps and a third union is recommended in the drain pipe . If pipe insulation
or heat tapes are required to prevent freezing, use should be in accordance
with general accepted plumbing practices .
· Each condensate drain must include a drain trap . Downstream from the traps,
the condensate drains may be joined and both must be connected to a common
pipe that is connected to a sanitary drain within the building . Check codes
to ensure that this is permitted .
· The most important part of fabricating and assembling the drain traps is the
length of the individual legs of the traps . If the difference in the lengths
of the legs of the traps are not as shown (see Figure 19 for vent drain trap
or Figure 20 for heat exchanger drain trap), it could prevent proper drainage
of the condensate and possibly permit vent gas to enter the building . Note
that the length difference is also what provides a water seal to prevent the
leakage of vent gas into the sanitary drain .
Minimum Dimensions for Vent Pipe Condensate Drain Trap C = to suit installation D = C + at least 1-1/2 inches (38 mm) Use 1/2-inch PVC pipe or larger for drain trap
UNIT
4-inch PVC cleanout cap shown is in vent/combustion air kit (option CC6 or CC2)
Cap is drilled and tapped
for 1/2-inch NPT fitting
OR Vent drain connection fittings may be field-supplied as shown
C
Drain must be 1/2-inch or larger
Trap requirements are same for either type of connection
Drain Trap
Figure 19. Vent Condensate Drain Trap
Continue into sanitary drain
D
UEZ-IOM (07-24) 1034347-L
31
INSTALLATION–CONTINUED Condensate Drain Installation–Continued
UNIT
Minimum Dimensions for Secondary Heat Exchanger Condensate Drain Trap A = 3
inches (76 mm) minimum B = A + at least 5 inches (127 mm)
Use 1/2-inch PVC pipe or larger for condensate drain
NOTE: Bottom of fan guard is removed for better view.
Continue into sanitary drain
B
A
Drain Trap Figure 20. Heat Exchanger Condensate Drain Trap
Vent Condensate Drain Installation (Unit Sizes 55110)
NOTE: In Canada, all PVC vent pipe must be approved to ULC S636.
Install the vent condensate drain on unit sizes 55110 using the PVC cleanout
cap provided with the heater as follows (see Figure 21): 1 . Connect field-
supplied PVC tee to 4-inch vent outlet on back of heater . 2 . Connect 4-inch
PVC cleanout cap to tee . Cap is drilled and tapped for 1/2-inch NPT drain
connection . 3 . Connect field-supplied condensate drain to cap .
32
UEZ-IOM (07-24) 1034347-L
TO VENT OUTLET ON
BACK OF HEATER
CLEANOUT CAP
FIELD-SUPPLIED TEE
FIELD-SUPPLIED DRAIN
TO VENT OUTLET ON
BACK OF HEATER
FIELD-SUPPLIED TEE
CLEANOUT CAP
FIELD-SUPPLIED
FIELD-SUPPLIED DRAIN
Figure 21. Installing Condensate Drain (Unit Sizes 55110)
Vent Condensate Drain Installation (Unit Sizes 130310)
NOTE: In Canada, all PVC vent pipe must be approved to ULC S636.
Install the vent condensate drain on unit sizes 130310 as follows . Ensure
that the drain trap is in accordance with Figure 19 . 1 . For vertical vent
(see Figure 22):
a . Connect field-supplied 4-inch coupling to 4-inch vent outlet on back of
heater . Ensure that coupling slopes downward away from heater .
b . Connect 4-inch diameter vent pipe–12-inch (305-mm) minimum length, 24-inch
(610-mm) maximum length–to coupling .
c . For US installations only (see Figure 22, DETAIL A): (1) Connect field-
supplied 4 × 4 × 4 PVC tee to vent pipe . (2) Connect PVC cap included in
option CC2 to tee . Cap is drilled and tapped for 1/2-inch NPT drain
connection . (3) Connect field-supplied condensate drain to cap .
d . For US or Canadian installations (see Figure 22, DETAIL B): (1) Connect
field-supplied PVC tee to vent pipe . (2) Connect field-supplied fitting(s) to
tee as needed for 1/2-inch or larger condensate drain line .
TEE COUPLING
TEE COUPLING
VENT PIPE
1224 (305610)
CAP
DETAIL A (US ONLY)
VENT PIPE
1224 (305610)
DRAIN FITTING(S)
DETAIL B (US AND CANADA)
Figure 22. Installing Condensate Drain in Vertical Vent (Unit Sizes 130310)
UEZ-IOM (07-24) 1034347-L
33
INSTALLATION–CONTINUED
Condensate Drain Installation–Continued
Vent Condensate Drain Installation (Unit Sizes 130310)–Continued 2 . For
horizontal or vertical vent (see Figure 23):
a . For US installations only (see Figure 23, DETAIL A): (1) Connect field-
supplied 4 × 4 × 4 PVC tee to 4-inch vent outlet on back of heater . (2)
Connect PVC cap included in option CC2 or CC6 to tee . Cap is drilled and
tapped for 1/2-inch NPT drain connection . (3) Connect field-supplied
condensate drain to cap . Balance of vent may be either horizontal or vertical
. Ensure that horizontal vent slopes downward toward drain .
b . For US or Canadian installations (see Figure 23, DETAIL B): (1) Connect
field-supplied PVC tee to 4-inch vent outlet on back of heater . (2) Connect
field-supplied fitting(s) to tee as needed for 1/2-inch or larger condensate
drain line . Balance of vent may be either horizontal or vertical . Ensure
that horizontal vent slopes downward toward drain .
TEE
TEE
CAP
DETAIL A (US ONLY)
DRAIN FITTING(S)
DETAIL B (US AND CANADA)
Figure 23. Installing Condensate Drain in Vertical or Horizontal Vent (Unit Sizes 130310)
Heat Exchanger Condensate Drain Installation
Install the heat exchanger condensate drain in accordance with all piping
requirements listed in this manual and with Figure 20 . For drain kit
components and installation instructions for replacement heat exchangers,
refer to the replacement parts manual found at www.reznorhvac.com .
Electrical Connections
CAUTION
· All electrical wiring and connections, including electrical grounding MUST
be made in accordance with the National Electric Code (ANSI/NFPA No. 70,
latest edition) or, in Canada, the Canadian Electric Code (Part 1, CSA
C.22.1). In addition, the installer should be aware of any local ordinances or
gas company requirements that might apply.
· Route wires so that they do not contact the flue wrapper or venter housing.
· If any of the original wire supplied with the appliance must be replaced, it
must be replaced with wiring material having a temperature rating of at least
220°F (105°C), except for limit control, flame rollout, and sensor lead wires
which must be rated at 302°F (150°C).
NOTES: · Ensure that all wiring is in accordance with the wiring diagram provided with the unit. · A two-stage valve circuit is NOT available on all models.
34
UEZ-IOM (07-24) 1034347-L
· Check the rating plate on the heater for the supply voltage and current
requirements . A dedicated line voltage supply with a disconnect switch should
be run directly from the main electrical panel to the heater .
· All external wiring must be within approved conduit and have a minimum
temperature rise rating of 140°F (60°C) . Conduit must be run so as not to
interfere with the heater access panel .
· If the installation requires a stepdown transformer (option CG), follow the
instructions shipped with the option package for installing the transformer .
· The unit includes a built-in disconnect switch (20A@115V or 10A@230V rating)
. · The supply wiring enters at the rear of the heater, as shown in Figure 24
. Supply wiring connects to leads located
inside a sealed electrical box . To maintain the sealing feature of the
electrical box, always replace the cover plate . · The terminal strip for the
24V thermostat connections is located on the outside of the cabinet at the
back of the
heater, as shown in Figure 24 . Wires from the terminal strip are factory-
wired to the circuit board . · The circuit board (see Figure 25) is located
inside on the bottom of the control compartment . The circuit board is
polarity sensitive . It is advisable to check the electrical supply to ensure
that the black wire is the hot wire and that the white wire is the neutral
wire . The hot wire must be connected to terminal L1 on the circuit board .
TERMINAL STRIP FOR THERMOSTAT CONNECTION
LINE VOLTAGE ENTRANCE
TERMINAL STRIP FOR THERMOSTAT
CONNECTION
UNIT SIZES 055110
UNIT SIZES 130310
C R G W1 W2
Figure 24. Supply Wiring Entrance and Control Connection Terminal Strip
Figure 25. Circuit Board (DSI Control Module)
UEZ-IOM (07-24) 1034347-L
35
CONTROLS
NOTE: Refer to the TROUBLESHOOTING section for probable causes and reset
instructions for the following controls.
Locations for the following controls are shown in Figure 26 .
DSI CONTROL MODULE
IGNITOR HIGH TEMPERATURE
LIMIT CONTROL
PRESSURE SWITCH TRANSFORMER INTERLOCK DOOR SWITCH FAN MOTOR
FLAME ROLLOUT SWITCH FLAME SENSOR
COMBINATION GAS VALVE
VENT TEMPERATURE LIMIT SWITCH
DISCONNECT SWITCH
PRESSURE SWITCH
VENTER MOTOR
UNIT SIZES 055110
HIGH TEMPERATURE LIMIT CONTROL
DISCONNECT SWITCH
FLAME SENSOR
IGNITOR
INTERLOCK DOOR
SWITCH
VENTER MOTOR
FAN MOTOR
DSI CONTROL MODULE
TRANSFORMER
COMBINATION GAS VALVE
UNIT SIZES 130310
Figure 26. Component Locations
VENT TEMPERATURE LIMIT SWITCH
36
UEZ-IOM (07-24) 1034347-L
Thermostat Options
NOTES:
· IMPORTANT: all units MUST be operated by a 24V thermostat. Never use a line
voltage disconnect switch as a means of operating the heater.
· For all availaible thermostat and thermostat accessory options, contact
contact an authorized Factory Distributor.
· Install an optional thermostat (available with the heater) or a field-
supplied 24V thermostat in accordance with the thermostat manufacturer’s
instructions . Pay particular attention to the requirements regarding the
location of the thermostat .
· Ensure that if there is a heat anticipator setting on the thermostat, it is
set at 0 .6 amps or in accordance with the amperage value noted on the heater
wiring diagram .
· Make thermostat connections at the terminal strip on the back of the heater
(see Figure 24) . The strip has five terminals: C, R, G, W1, and W2 . Refer to
the wiring diagram provided with the heater .
· If the heater was ordered with a multiple heater control option, one
thermostat can be used to control up to five heaters . This option includes a
40VA transformer that replaces the standard transformer in the control unit
and a relay assembly that attaches to the additional unit . Option CL31
provides for control of two heaters . If control of additional heaters is
desired (up to five total), option CL32, which is the relay assembly only,
must be added to each additional heater . The option packages are shipped
separately and include complete instructions on installation and wiring .
Combination Gas Valve
WARNING
The combination gas valve is the prime safety shutoff. All gas supply lines
must be free of dirt or scale before connecting the unit to ensure positive
closure.
The combination gas valve (see Figure 26 for location) is powered by the 24V
control circuit through the thermostat and safety controls . The diaphragm-
type valve is pre-set at the factory and provides regulated gas flow .
Pressure Switch
DANGER
Safe operation of this unit requires proper venting flow. NEVER bypass the
pressure switch or attempt to operate the unit without the venter running and
the proper flow in the vent system. Hazardous conditions could result.
· The pressure (combustion air proving) switch (see Figure 26 for location) is
a pressure-sensitive switch that monitors air pressure to ensure that proper
combustion airflow is available .
· The pressure switch senses the differential pressure between the negative
pressure in the venter housing and the pressure in the cabinet .
· At startup when the heater is cold, the sensing pressure is at the most
negative level, and as the heater and vent system warm up, the sensing
pressure becomes less negative . After the system has reached equilibrium
(about 20 minutes), the sensing pressure levels off .
· If a restriction or excessive vent length/turns cause the sensing pressure
to be outside the pressure switch setpoint, the switch will function to shut
off the main burner . The main burner will remain off until the system has
cooled and/or the flue system resistance is reduced .
· Pressure switch settings are listed in Table 18 .
UEZ-IOM (07-24) 1034347-L
37
Pressure Switch–Continued
CONTROLS–CONTINUED
Table 18. Pressure Switch Settings
Unit Size
Startup Cold
Negative Pressure (IN WC)
Equilibrium Hot
Setpoint OFF
Setpoint ON
Label Color
55
1 .90
1 .60
0 .60
0 .75
85
1 .80
1 .30
0 .60
0 .75
Purple
110
1 .15
1 .15
0 .60
0 .75
130
3 .50
3 .00
2 .40
2 .65
White
180
3 .20
2 .50
2 .30
2 .45
Blue
260
3 .50
3 .10
2 .40
2 .65
White
310
3 .30
2 .80
2 .40
2 .65
High Temperature Limit Control
WARNING
The automatic-reset high temperature limit control will continue to shut down
the heater until the cause is corrected. Never bypass this control as
hazardous conditions could result.
All units are equipped with a temperature-activated, automatic-reset high
temperature limit control (see Figure 26 for location) . The control is
factory-set and is non-adjustable . If the setpoint is reached, the control
interrupts the electric supply to the combination gas valve . This safety
device provides protection in the case of motor failure or lack of airflow due
to a restriction at the inlet or outlet .
Vent Temperature Limit Switch
WARNING
If the manual vent temperature limit switch activates, identify and correct
the cause before resetting the switch. Never bypass the vent temperature
switch as hazardous conditions could result.
All units are equipped with a temperature-activated, manual-reset switch to
limit the temperature of vent gases to below 145°F . The switch is attached to
the side of the combustion air venter housing (see Figure 26 for location) .
If the setpoint is reached, the switch interrupts the electric supply to the
combination gas valve . If the switch is activated, identify and correct the
cause before resetting the switch .
Interlock Door Switch
All units are equipped with an interlock door switch (see Figure 26 for
location) that prevents the heater from operating when the service door panel
is open . The service panel is equipped with a pliable gasket that fully seals
the door to provide added protection to prevent building air from entering the
combustion zone of the heater .
Fan Motor
The fan motor is equipped with automatic-reset thermal overload protection .
If the motor does not run, the cause may be due to improper current . Ensure
that the correct voltage is available at the motor .
Circuit Board (DSI Control Module)
The heater’s ignition system is controlled by a circuit board (Direct-Spark
Integrated (DSI) control module, see Figure 25) that monitors the safety
devices and controls the operation of the fan and venter motors and the
combination gas valve between heat cycles . To view the Seven-Segment Display
(SSD), the door panel requires removal . In addition, there is a status LED on
the bottom of the heater . Its status indications are off (heater is not
powered or control board fault), steady on (heater is on with no faults), or
flashing (heater is on with fault(s)) . Additional status indications appear
on the display at the bottom of the control module (labeled as DSP1, see
Figure 25) . The display’s codes are listed and described in the Unit
Troubleshooting Using DSI Control Module section .
38
UEZ-IOM (07-24) 1034347-L
Venter Motor
The venter motor (see Figure 26 for location) is assembled to the venter wheel
and operates to provide combustion airflow . Operation is controlled by the
circuit board (see Figure 25) . Refer to the Circuit Board (DSI Control
Module) section for details .
Flame Rollout Switch (Unit Sizes 55110)
DANGER
If the manual-reset flame rollout switch activates, identify and correct the
cause before resetting the switch. Never bypass the flame rollout switch;
hazardous conditions could result.
Unit sizes 55, 85, and 110 are equipped with a temperature-activated,
manually-reset flame rollout switch (see Figure 26 for location) . The switch
is factory-set and is non-adjustable . If the setpoint is reached, the switch
interrupts the electric supply to the combination gas valve . If the flame
rollout switch activates, identify and correct the cause before resetting the
switch .
OPERATION
DANGER
· For your safety, read before operating. If you do not follow these
instructions exactly, a fire or explosion may result, causing property damage,
personal injury, or loss of life.
· This appliance does not have a pilot. It is equipped with an ignition device
which automatically lights the burner. Do not try to light the burner by hand.
· Before operating, smell all around the appliance area for gas. Be sure to
smell next to the floor because some gas is heavier than air and will settle
on the floor.
· WHAT TO DO IF YOU SMELL GAS: a. Do not try to light any appliance. b. Do not
touch any electrical switch; do not use any phone in your building. c. Leave
the building immediately. d. Immediately call your gas supplier from a phone
remote from the building. Follow the gas supplier’s instructions. e. If you
cannot reach your gas supplier, call your fire department.
· Use only your hand to turn the gas control ON/OFF knob on the combination
gas valve. Never use tools. If the valve ON/OFF knob will not turn by hand, do
not try to repair it. Call a qualified service technician. Force or attempted
repair may result in a fire or explosion.
· Should overheating occur, or the gas supply control system fail to shut off
the flow of gas, turn off the manual gas valve to the appliance before
shutting off the electrical supply.
· Do not use this appliance if any part has been under water. Immediately call
a qualified service technician to inspect the appliance and to replace any
part of the control system and any gas control which has been under water.
· All components of a gas supply system must be leak tested prior to placing
equipment in service. NEVER TEST FOR LEAKS WITH AN OPEN FLAME. Failure to
comply could result in personal injury, property damage, or death.
UEZ-IOM (07-24) 1034347-L
39
OPERATION–CONTINUED
Pre-Startup Checklist
Check the following before startup: Check to ensure that all screws used to
secure shipping brackets have been re-installed in heater cabinet . Check
suspension–unit must be secure and level . Check to ensure that clearances
from combustibles are in accordance with Table 2 . Check vent system to ensure
that it is installed in accordance with Vent Connections section . Check
condensate drain system to ensure that it is installed in accordance with
Condensate Drain Installation
section . Check piping for leaks and proper gas line pressure and bleed
trapped air from gas lines (refer to Supply Piping
Connections section) . Check electrical wiring–ensure that all wire gauges are
as recommended–service disconnect switch should be
used–verify that fusing or circuit breakers are adequate for load use . Check
polarity–verify that line voltage exists between black L1 wire and earth
ground . If installation elevation is >6,000 feet (>1,830 meters), replace
pressure switch in accordance with Pressure
Switch Replacement section .
Startup
Start up the heater as follows: 1 . Set thermostat at lowest setting . 2 .
Turn OFF all electric power to appliance .
NOTE: This appliance is equipped with an ignition device that automatically
lights the burner. Do not try to light the burner by hand.
3 . Open access door and locate gas control (ON/OFF) knob or switch on
combination gas valve (see Figure 27) .
Top View ON/OFF Switch
Figure 27. Combination Gas Valve ON/OFF Control
40
UEZ-IOM (07-24) 1034347-L
4 . Turn gas control switch to OFF or turn knob clockwise to OFF . 5 . Wait 5
minutes to clear out any gas and then smell for gas (including near floor) .
a . If you smell gas, STOP! and follow steps in DANGER message listed above or
on heater operating label . b . If you do not smell gas, proceed to step 6 . 6
. Turn gas control switch to ON or turn knob counterclockwise to ON . 7 .
Close access door . 8 . Turn ON electric power to heater . 9 . Set thermostat
to desired setting . a . If heater does not operate, follow instructions in
step 13 or on heater operating label and call your service
technician . b . If heater operates, thermostat calls for heat, which
energizes venter motor . 10 . Pressure switch closes, which fires unit . 11 .
Burner flame is sensed and in 30 seconds after combination gas valve is
energized, fan motor is energized . 12 . If flame is extinguished during main
burner operation, integrated control system closes main valve and must be
reset by interrupting power to control circuit (refer to lighting instructions
provided with heater) . 13 . TO TURN OFF GAS TO APPLIANCE: a . Set thermostat
to lowest setting . b . If service is to be performed, turn off all electric
power to appliance . c . Open the access door . d . Turn gas control switch to
OFF or turn knob clockwise to OFF (do not force) . e . Close access door .
Operating Sequences
Table 20 describes the heater’s normal operating sequence . Table 20 describes
the heater’s abnormal heat cycle functions . Table 21 describes the heater’s
fault modes . Refer to Table 27 for LED indications .
Step
1 . Call for heat
Table 19. Operating Sequence (Normal Heat Cycle)
Condition
Action
Terminal W is energized
Thermostat calls for heat by energizing terminal W
Control determines whether limit switch is open or closed and if pressure switch is open
Limit switch is open
Control deenergizes gas valve, turns fan/blower motor onto heat speed, and runs venter motor
SSD displays “5”
Control is in soft lockout “L” before returning to normal operation
Pressure switch is closed SSD displays “4”
Control waits indefinitely for pressure switch to open
Pressure switch is open
Control proceeds to step 2
UEZ-IOM (07-24) 1034347-L
41
OPERATION–CONTINUED Operating Sequences–Continued
Table 19. Operating Sequence (Normal Heat Cycle)–Continued
Step
Condition
Action
2 . Prepurge Venter motor is energized Control waits for pressure switch to close
Pressure switch not closed within 30 seconds of venter motor energizing
SSD displays “3”
Control maintains venter motor energized indefinitely as long as call for heat
remains and pressure switch is open
Pressure switch is proven closed
Control begins prepurge
Flame is present at any time Prepurge is restarted during prepurge
Flame is present long enough to cause lockout
Control runs venter motor and runs fan/blower motor on heat speed
When flame is no longer sensed, venter motor runs through post-purge and
fan/blower motor runs through selected delay OFF time
Control proceeds to soft lockout but still responds to open limit and flame
SSD displays “6” when lockout is due to undesired flame
Venter motor runs for 20-second prepurge time
Control proceeds to step 3
3 . Ignition trial period
Spark and main gas valve are energized
Venter remains energized
Flame is sensed during first Control deenergizes spark and proceeds to heat fan/blower on delay 16 seconds
Flame is not sensed during Control deenergizes spark and maintains gas valve energized for additional 1-second flame-
first 16 seconds
proving period
Flame is not present after flame-proving period
Control deenergizes gas valve and proceeds with ignition retries as specified in Table 20: abnormal function Ignition Retry
Flame is present after flame- Control proceeds to step 4 proving period
4 . Fan/blower 30 seconds after gas valve Control energizes fan/blower motor
ON delay
has opened
Gas valve and venter motor Control proceeds to step 5 remain energized
5 . Steady heat
Limit switch is closed Pressure switch is closed
Control continuously monitors inputs
Flame is established
Thermostat call for heat remains
Thermostat call for heat is Control deenergizes gas valve and proceeds to steps 6 and 7 removed
6 . Post-purge Thermostat is satisfied
Venter motor remains on for 45-second post-purge period
7 . Fan/blower OFF delay
Fan/blower motor is deenergized after selected fan/blower OFF delay
42
UEZ-IOM (07-24) 1034347-L
Table 20. Operating Sequence (Abnormal Heat Cycle)
Abnormal Function
Condition
Action
Interrupted thermostat call for heat
Thermostat demand for heat is removed before flame is recognized
Thermostat demand for heat is removed after successful ignition
Control runs venter motor for post-purge period All outputs are deenergized Control deenergizes gas valve Control runs venter motor through post-purge period
Control runs fan/blower motor on heat speed for selected delay OFF time
Ignition retry Flame is not established on first trial for ignition period
Control deenergizes gas valve Venter motor remains energized for 10-second inter-purge period
Spark and gas valve are re-energized
Control initiates another trial for ignition
Flame is not established on second trial for ignition
Control deenergizes gas valve Control runs fan/blower motor on heat speed
Venter motor remains energized
Fan/blower motor deenergizes after selected delay OFF period and spark and gas valve are re-energized
Control initiates another trial for ignition (this fan delay is self-healing feature for open auxiliary limit switch)
Flame is not established on third trial Control deenergizes gas valve
for ignition
Venter motor remains energized for 10-second inter-purge period
Spark and gas valve are re-energized
Control initiates another trial for ignition
Flame is not established on fourth trial Control deenergizes gas valve and proceeds to lockout for ignition (initial try plus three re-tries) SSD displays “L” to indicate ignition failure lockout
Limit switch* Limit switch is open and call for heat is Control deenergizes gas valve
present
Control runs venter motor and runs fan/blower motor on heat speed
Control is in soft lockout (SSD displays “L”) before returning to normal operation
Limit switch re-closes or call for heat is Control runs venter motor through post-purge period
not present
Control runs fan/blower motor on heat speed through selected delay OFF period
Pressure switch operation
Pressure switch opens before trial for ignition period
Venter motor runs through 2-second pressure switch recognition delay Control deenergizes gas valve Control runs venter motor through post-purge period
Control restarts heat cycle at pressure switch proving state if call for heat still exists
Pressure switch opens for less than 2 Control deenergizes gas valve while pressure switch is open seconds during trial for ignition period (shall not interrupt heat cycle)
Pressure switch opens after successful Control deenergizes gas valve ignition
Flame is lost before end of 2-second Control responds to loss of flame pressure switch recognition delay
Pressure switch remains open for 2 seconds and flame remains
Control deenergizes gas valve Control runs venter motor through post-purge period
Control runs fan/blower motor on heat speed through selected delay OFF period
When fan OFF delay ends, fan/blower motor is deenergized, and heat cycle begins if call for heat still exists
Continuous Thermostat calls for continuous fan (G) Fan motor is energized after 0 .25-second delay (this brief ON delay allows terminal
fan operation without call for heat
G to energize slightly before terminal Y and allows external changeover relay to
switch from terminal G to terminal W without causing momentary glitches in fan/
blower output
Fan remains energized as long as call for fan remains without call for heat
Thermostat calls for heat (W) during continuous fan operation
Fan/blower is deenergized Call for fan is ignored during lockout
*The limit switch is ignored unless a call for heat is present (terminal W energized) .
UEZ-IOM (07-24) 1034347-L
43
OPERATION–CONTINUED Operating Sequences–Continued
Fault Mode Undesired flame
Gas valve relay fault
Soft lockout
Hard lockout Power interruption
Table 21. Fault Modes
Condition
Action
Flame is sensed longer than 20 seconds while gas valve is deenergized
Control runs venter motor and runs fan/blower motor on heat speed
When flame is no longer sensed, venter motor runs through post-purge and fan/
blower motor runs through selected delay OFF time
Control proceeds to soft lockout but still responds to open limit and flame
SSD displays “6” when lockout is due to undesired flame
Control senses that gas valve is energized for more than 1 second when control is not attempting to energize gas valve or control senses that gas valve is not energized when it is supposed to be energized
Control proceeds to lockout (SSD is blank)
Control assumes either that contacts of relay driving gas valve have welded
shut or that sensing circuit has failed
Venter motor is forced OFF to open pressure switch to stop gas flow unless
flame is present
Control senses that gas valve is
Venter motor is re-energized to vent unburned gas
closed when it should be open (has
not deenergized after venter motor has
been shut off for 15 seconds
Control does not initiate call for heat or call for continuous fan operation while in lockout
Control still responds to open limit and undesired flame
Lockout is automatically reset after 1 hour
Lockout may be manually reset by removing power from control for more than 1
second or by removing thermostat call for heat for more than 1 but less than
20 seconds
Control detects fault on control board SSD is blank or displays “L” (fault dependent)
Control remains in lockout as long as fault remains
Hard lockout automatically resets when hardware fault clears
Momentary interruption or voltage level System self-recovers without lockout when voltage returns to operating range is below minimum operating voltage (line voltage or low voltage)
Interruption <80 milliseconds
Control does not change operating state
Interruption >80 milliseconds
Control may interrupt current operating cycle to restart
Vent System Testing
For each heater or utility heater connected to the venting system and placed
in operation while any other appliance(s) connected to the venting system(s)
is not in operation, test the vent system as follows:
1 . Seal unused openings(s) in vent system .
2 . Inspect vent system for proper size and horizontal pitch as required in
National Flue Gas Code (ANSI Z223 .1/ NFPA 54) or Natural Gas and Propane
Installation Code (CSA B149 .1) and in venting instructions .
3 . Verify that there is no blockage or restriction, leakage, corrosion,
and/or other deficiencies that could cause any unsafe condition .
4 . In so far as is practical, close all doors, windows, and other open spaces
within building and all doors between space in which appliance(s) is connected
and space where vent system is located .
5 . Close any fireplace dampers .
6 . Turn on clothes dryers and any exhaust fans (such as range hoods and
bathroom exhausts) so that they operate at maximum speed . Do not operate a
summer exhaust fan .
7 . Following lighting instructions provided with heater, place utility heater
being inspected in operation . Adjust thermostat so that utility heater will
operate continuously .
44
UEZ-IOM (07-24) 1034347-L
8 . After it has been determined that each utility heater connected to vent
system properly vents when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers, and any other gas-burning appliance to their
previous condition of use .
9 . If improper venting is observed during above tests, vent system must be
corrected .
Post-Startup Checklist
Check the following after startup: Ensure that vent system has been tested in
accordance with Vent System Testing section . With unit in operation, measure
manifold (outlet) gas pressure in accordance with Measure and Adjust Manifold
(Outlet) Gas Pressure section . Turn unit OFF and ON, pausing 2 minutes
between each cycle; observe for smooth ignition . Place literature bag that
contains Limited Warranty, this manual, and any control or optional
information in
accessible location near heater .
DANGER
· The gas burner in this gas-fired equipment is designed and equipped to
provide safe controlled complete combustion. However, if the installation does
not permit the burner to receive the proper supply of combustion air, complete
combustion may not occur. The result is incomplete combustion, which produces
carbon monoxide, a poisonous gas that can cause death. Safe operation of
indirect-fired gas burning equipment requires a properly operating vent system
that vents all flue products to the outside atmosphere. FAILURE TO PROVIDE
PROPER VENTING WILL RESULT IN A HEALTH HAZARD THAT COULD CAUSE SERIOUS
PERSONAL INJURY OR DEATH.
· Always comply with the combustion air requirements listed in the
installation codes and in this manual. Combustion air at the burner should be
regulated only by manufacturer-provided equipment. NEVER RESTRICT OR OTHERWISE
ALTER THE SUPPLY OF COMBUSTION AIR TO ANY HEATER. MAINTAIN THE VENT OR
VENT/COMBUSTION AIR SYSTEM IN STRUCTURALLY SOUND AND PROPER OPERATING
CONDITION.
ADJUSTMENTS
After startup, the combination gas valve outlet pressure must be measured and
adjusted if necessary in accordance with the Measure and Adjust Manifold
(Outlet) Gas Pressure section . If the heater is being installed at an
elevation of >6,000 feet (>1,830 meters), the pressure switch must be replaced
in accordance with the Pressure Switch Replacement section before the gas
pressure is adjusted .
Pressure Switch Replacement
For installations at elevations >6,000 feet (>1,830 meters), the pressure
switch (see Figure 28) must always be replaced before the heater is operated .
If ordered with the unit as part of a high-elevation kit (refer to Table 11),
the switch is shipped separately for field-installation . Replace the pressure
switch as follows:
1 . Locate pressure switch in control compartment (see Figure 26) and mark and
disconnect two switch wires .
2 . Mark and disconnect sensing tube(s) from pressure switch .
3 . Remove two screws that secure mounting bracket and remove bracket and
pressure switch . Save bracket and screws for reuse .
4 . Install replacement pressure switch (refer to replacement parts manual
found at www.reznorhvac.com for PN) using mounting bracket and two screws .
Reconnect sensing tube(s) and wires .
UEZ-IOM (07-24) 1034347-L
45
ADJUSTMENTS–CONTINUED Pressure Switch Replacement–Continued
Figure 28. Pressure Switch
Measure and Adjust Manifold (Outlet) Gas Pressure If the heater is being
installed at an elevation 2,000 feet (610 meters), adjust the manifold
(outlet) gas pressure in accordance with the Measure and Adjust Manifold Gas
Pressure–Elevation 2,000 Feet (610 Meters) section . If the heater is being
installed at an elevation >2,000 feet (>610 meters), adjust the manifold
(outlet) gas pressure in accordance with the Measure and Adjust Manifold Gas
Pressure–Elevation >2,000 Feet (>610 Meters) section .
WARNING
Valve outlet gas pressure must never exceed 3.5 IN WC for natural gas or 10 IN
WC for propane. The maximum inlet supply pressure for natural gas or propane
is 14 IN WC.
CAUTION
Before attempting to measure or adjust valve outlet gas pressure, the inlet
supply pressure must be within the specified range, both when the heater is in
operation and when it is on standby. Incorrect inlet pressure could cause
excessive valve outlet gas pressure immediately or at some future time. If
natural gas supply pressure is too high, install a regulator in the supply
line before it reaches the heater. If natural gas supply pressure is too low,
contact your gas supplier.
NOTES: · Measuring outlet pressure cannot be done until the heater is in
operation. · During normal operation with natural gas at sea level, adjustment
to factory-setting should not
be necessary. · For natural gas: when the heater leaves the factory, the
combination gas valve is set so that the
valve outlet gas pressure for a single-stage valve is regulated to 3.5 IN WC.
Inlet supply pressure to the valve for natural gas must be a minimum of 5 IN
WC or as noted on the rating plate and a maximum of 14 IN WC. · For propane:
the heater is shipped factory-equipped for use with natural gas. A propane
conversion kit is included. Follow the instructions in the Converting Unit
from Natural Gas to Propane section to convert for use with propane. Inlet
supply pressure to the valve for propane must be a minimum of 11 IN WC and a
maximum of 14 IN WC.
46
UEZ-IOM (07-24) 1034347-L
Measure and Adjust Manifold Gas Pressure–Elevation 2,000 Feet (610 Meters) For installations at normal elevations, measure and adjust the manifold (outlet) gas pressure as follows: 1 . Turn knob or switch on top of valve to OFF to prevent flow to combination gas valve . NOTE: Use a water column manometer that is readable to the nearest tenth of an inch. 2 . Connect manometer to 1/8-inch output pressure tap on valve (see Figure 29) .
REGULATOR SCREW
1/8-INCH OUTLET PRESSURE TAP
REGULATOR SCREW
1/8-INCH OUTPUT PRESSURE TAP
INLET PRESSURE TAP
UNIT SIZES 055, 085, 110, 130, AND 180
INLET PRESSURE TAP
UNIT SIZES 260 AND 310
Figure 29. Combination Gas Valves
3 . Open manual valve and operate heater . Depress and hold door safety switch
. 4 . Cycle burner once or twice to properly seat adjustment spring in valve
and observe manometer gauge to measure
outlet pressure of combination gas valve .
CAUTION
DO NOT bottom out the combination gas valve regulator screw. This can result
in excessive overfire and heat exchanger failure due to unregulated manifold
pressure.
5 . If manometer reading does not indicate that valve outlet pressure is in
accordance with Table 22, remove cap from regulator screw(s) (see Figure 29)
and adjust pressure by turning regulator screw IN (clockwise) to increase
pressure or OUT (counterclockwise) to decrease pressure .
6 . When manometer reading indicates that outlet pressure is in accordance
with Table 22, disconnect manometer and install cap(s) on regulator screw(s) .
Feet
02000 20013000 30014000 4001- 5000 50016000 60017000 70018000 80019000
900110,000
02000 20014500
Elevation
Table 22.
Meters
0610 611915 9161220 12211525 15261830 18312135 21362440 24412745
27463045
0610 6111373
Required Manifold (Outlet) Gas Pressure
Unit Size (MBTUh)
Natural Gas
55, 85, 110, 130, 260
180, 310
Propane
Manifold Pressure (IN WC)
US
3 .5
10 .0
9 .5
3 .1
8 .8
8 .4
3 .0
8 .5
8 .0
2 .8
8 .1
7 .7
2 .7
7 .7
7 .3
2 .6
7 .4
7 .0
2 .5
7 .1
6 .7
2 .4
6 .7
6 .3
2 .2
6 .4
6 .0)
Canada
3 .5
10 .0
9 .5
2 .8
8 .1
7 .7
UEZ-IOM (07-24) 1034347-L
47
ADJUSTMENTS–CONTINUED
Measure and Adjust Manifold (Outlet) Gas Pressure–Continued
Measure and Adjust Manifold Gas Pressure–Elevation >2,000 Feet (>610 Meters)
For installations at high elevations, measure and adjust the manifold (outlet)
gas pressure as follows: 1 . If installation is at elevation >6,000 feet
(1,830 meters), replace pressure switch in accordance with Pressure
Switch Replacement section .
WARNING
Manifold gas pressure must never exceed 3.5 IN WC for natural gas or 10 IN WC
for propane.
2 . Determine correct outlet pressure (refer to Table 22) for elevation of
installation . If unsure of elevation, contact local gas supplier .
3 . Turn knob or switch on top of valve to OFF to prevent flow to combination
gas valve .
NOTE: Use a water column manometer that is readable to the nearest tenth of an
inch.
4 . Connect manometer to 1/8-inch output pressure tap on valve (see Figure 29)
.
CAUTION
DO NOT bottom out the gas valve regulator screw. This can result in excessive
overfire and heat exchanger failure due to unregulated manifold pressure.
5 . Turn knob or switch on top of valve to ON . 6 . Remove cap from regulator
screw (see Figure 29) and adjust pressure in accordance with Table 22 by
turning
regulator screw IN (clockwise) to increase pressure or OUT (counterclockwise)
to decrease pressure . 7 . Turn up thermostat . Depress and hold door safety
switch . 8 . Cycle burner once or twice to properly seat adjustment spring in
valve and recheck outlet pressure . When pressure
corresponds to Table 22, disconnect manometer and install cap on regulator
screw . 9 . Check for leakage at 1/8-inch outlet pressure tap fitting .
Correct as necessary . 10 . Connect manometer to inlet pressure tap (see
Figure 29) . While heater is operating, measure inlet pressure,
which should be between 5 and 13 .5 IN WC for natural gas or between 10 and 13
.5 IN WC for propane . 11 . If inlet pressure is not between 5 and 13 .5 IN WC
for natural gas or between 10 and 13 .5 IN WC for propane,
inlet pressure must be corrected by adjusting manifold (outlet) pressure in
accordance with steps 3 through 6 .
NOTE: The inputs and capacity of the heater varies depending on elevation.
12 . Refer to Table 23 for input and capacity values for elevation of
installation . a . Use permanent marker to fill in appropriate input and
capacity values on high-elevation adjustment label from literature bag
provided with unit . b . Select location for label on outside of heater access
panel that will be conspicuous to anyone operating or servicing unit . c .
Ensure that surface is clean and dry and affix label .
13 . Observe heater operation for at least one complete cycle to check for
safe and proper operation . Depress and hold safety door switch .
48
UEZ-IOM (07-24) 1034347-L
Table 23. Inputs and Capacities by Elevation
Unit Size (MBTUh)
Elevation (Feet (Meters))
55 NI TOC
85 NI TOC
110 NI TOC
130 NI TOC
180 NI TOC
260 NI TOC
310 NI TOC
BTUh
US
02000 (0610)
55,000 51,150 85,000 79,050 110,000 102,300 131,000 121,830 175,000 159,250 260,000 239,200 305,000 277,550
20013000 (611915)
52,800 49,104 81,600 75,888 105,600 98,208 123,140 114,520 164,500 149,695 244,400 224,848 286,700 260,897
30014000 (9161220)
50,688 47,140 78,336 72,852 101,376 94,280 120,520 112,084 161,000 146,510 239,200 220,064 280,600 255,346
40015000 (12211525)
48,660 45,254 75,203 69,938 97,321 90,508 117,900 109,647 157,500 143,325 234,000 215,280 274,500 249,795
50016000 (15261830)
46,714 43,444 72,194 67,141 93,428 86,888 115,280 107,210 154,000 140,140 228,800 210,496 268,400 244,244
60017000 (18312135)
44,845 41,706 69,307 64,455 89,691 83,413 112,660 104,774 150,500 136,955 223,600 205,712 262,300 238,693
70018000 (21362440)
43,052 40,038 66,534 61,877 86,103 80,076 110,040 102,337 147,000 133,770 218,400 200,928 256,200 233,142
80019000 (24412745)
41,330 38,437 63,873 59,402 82,659 76,873 107,420 99,901 143,500 130,585 213,200 196,144 250,100 227,591
900110,000 (27463045)
39,676 36,899 61,318 57,026 79,353 73,798 104,800 97,464 140,000 127,400 208,000 191,360 244,000 222,040
Canada
02000 (0610)
55,000 51,150 85,000 79,050 110,000 102,300 131,000 121,830 175,000 159,250 260,000 239,200 305,000 277,550
20014500 (6111373)
48,660 45,254 75,203 69,938 97,321 90,508 117,900 109,647 157,500 143,325 234,000 215,280 274,500 249,795
*NI = normal input . TOC = thermal output capacity .
Converting Unit from Natural Gas to Propane
The heater is shipped factory-equipped for use with natural gas . A propane
conversion kit is provided with each heater . Ensure that components in the
kit are available (refer to Table 24) and install the kit as follows: 1 .
Install propane regulator spring kit in combination gas valve in accordance
with valve manufacturer’s instructions
included with kit . 2 . Attach propane disk near combination gas valve . 3 .
Carefully remove natural gas orifice(s) (see Figure 26) from heater and
install propane orifice(s) . 4 . Install labels:
a . Use permanent marker to fill in appropriate information on conversion
label from kit . b . Select location for label near rating plate . c . Ensure
that surface is clean and dry and affix conversion label and regulated propane
label from kit . 5 . During heater startup, check valve outlet pressure in
accordance with Measure and Adjust Manifold (Outlet) Gas Pressure section .
Component
Conversion kit Regulator spring kit
Burner orifice
Label Gas disk
Table 24. Propane Conversion Kit Components
Unit Size (MBTUh)
Description
55
85
110
130
180
260
310
PN
Package PN
1041262
261647 1036196R 1036197R 221445
Honeywell #396221
260605
260605
—
Honeywell #393691
—
—
98720
PN 661057 661079 661082 120145 196899 1034352 196903
Drill size #57
1 .2 mm 1 .25 mm 3 .3 mm
24
4 .6 mm
8
Quantity
4
5
6
1
Conversion
64391
64391
Regulated propane
79718
79718
Propane
37752
37752
UEZ-IOM (07-24) 1034347-L
49
MAINTENANCE
WARNING
· If you turn OFF the electrical power supply, turn OFF the gas.
· Eye protection is recommended when cleaning unit.
CAUTION
· When any service is completed, ensure that the unit is reassembled correctly
so that no unsafe conditions are created.
· When re-lighting, always follow the lighting instructions on the heater. ·
If any of the original wire supplied with the appliance must be replaced, it
must be replaced
with wiring material having a temperature rating of at least 105°C, except for
limit control, flame rollout, and sensor lead wires which must be rated at
150°C.
· If replacement parts are required, use only factory-authorized parts.
NOTE: To ensure long life and satisfactory performance, a heater that is
operated under normal conditions should be inspected and cleaned at the start
of each heating season. If the heater is operating in an area where an unusual
amount of dust or soot or other impurities are present in the air, more
frequent maintenance is recommended.
The unit is designed to operate with a minimum of maintenance . However, to
ensure long life and satisfactory performance, routine service is recommended
. When servicing, follow standard safety procedures and those specific
instructions and warnings in this manual .The following is designed to aid a
qualified service person in maintaining and servicing this equipment .
Service Checklist
At a minimum, perform the following annually (see Figure 26 for component
locations): Inspect burner/control compartment annually to determine if
cleaning is necessary . Clean all dirt, lint, and grease from combustion air
opening and venter assembly . Clean all dirt, lint, and grease from fan blade,
fan guard, and motor . Clean condensate drain traps . Check heat exchanger
both internally and externally . Check burner for scale, dust, or lint
accumulation and clean if needed . Check gas valve to ensure that gas flow is
being shut off completely . Check vent or vent/combustion air system for
soundness and clean openings . Replace any parts that do not appear sound .
Check for any damaged wiring and replace as necessary .
Maintenance Procedures
Burner Maintenance (Unit Sizes 55110)
NOTE: Burner cleaning is not normally necessary for unit sizes 55, 85, and
110, but may be required if the unit is in a dirty location.
Visually inspect the burner compartment (see Figure 30) . If there is an
accumulation of dirt, dust, and/or lint, clean the compartment and remove and
clean the burners as follows:
50
UEZ-IOM (07-24) 1034347-L
IGNITOR FLAME ROLLOUT SWITCH
INSHOT BURNER BURNER RACK
FLAME SENSOR GAS MANIFOLD COMBINATION GAS VALVE
Figure 30. Burner Compartment (Unit Sizes 55110)
1 . Remove gas and electric supply: a . Shut OFF gas supply ahead of union at
manual valve outside cabinet . b . Turn OFF electric supply . c . Disconnect
gas supply at union outside of cabinet .
2 . Remove burner assembly (see Figure 30): a . Remove access panel . b .
Disconnect gas train . c . Mark and disconnect wires at combination gas valve,
ignitor, flame sensor, and flame rollout switch .
CAUTION
Take care not to damage the ignitor while removing or cleaning the burner
assembly.
3 . Remove screws that secure gas manifold to burner box and carefully remove
burner assembly .
NOTE: If, upon inspection, any burner components are damaged or deteriorated,
replace the burner assembly.
4 . Shine flashlight on burners and use compressed air or vacuum cleaner to
loosen and remove any accumulated dust or debris .
5 . Re-install burner assembly (see Figure 30): a . Install burner assembly
and gas manifold and secure gas manifold to burner box using screws removed in
step 3 . b . Reconnect wires to combination gas valve, ignitor, flame sensor,
and flame rollout switch . c . Reconnect gas train . d . Install access panel
. e . Reconnect gas supply at union outside of cabinet . f . Leak test
connection using leak detecting solution . If leak is detected, tighten
connection . If leak cannot be stopped by tightening connection, replace
part(s) .
6 . Turn ON electric and gas . 7 . Check for proper operation .
UEZ-IOM (07-24) 1034347-L
51
MAINTENANCE–CONTINUED
Maintenance Procedures–Continued
Burner Maintenance (Unit Sizes 130310)
NOTE: The unit is equipped with a TCORE2® burner.
Visually inspect the burner compartment (see Figure 31) . If there is an
accumulation of dirt, dust, and/or lint, clean the compartment and remove and
clean the burner as follows: 1 . Remove gas and electric supply:
a . Shut OFF gas supply ahead of union at manual valve outside cabinet . b .
Turn OFF electric supply . c . Disconnect gas supply at union outside of
cabinet . 2 . Remove burner assembly (see Figure 31): a . Remove access panel
. b . Disconnect gas train:
(1) Mark and disconnect wires at combination gas valve . (2) Carefully remove
burner orifice and orifice adapter locking nut . (3) Slide orifice adapter out
through bracket on burner while pushing gas train to right . This will move
gas
train out of way .
BURNER BODY SUPPORT
SECONDARY AIR SHIELD
BURNER ASSEMBLY
ORIFICE ADAPTER LOCKING NUT
VENTURI TUBE
SECONDARY AIR BAFFLE
GAS VALVE
Figure 31. Burner Compartment (Unit Sizes 130310)
c . Detach control assembly: (1) Remove two screws that secure control
assembly bracket . (2) Being careful not to disconnect any wires, slide
control assembly to right .
d . Remove secondary air baffle(s): (1) Locate flat plate(s) identified as
secondary air baffle(s)–vertical along right side of burner . Quantity of
baffles could be one to four depending on heater size . Each baffle is held in
place by one screw . (2) For correct re-assembly on secondary air shield, mark
location (top and bottom) of each baffle . (3) Remove screw(s) and remove
baffle(s) (all) .
52
UEZ-IOM (07-24) 1034347-L
e . Locate burner body supports–depending on size, burner will have two or
more supports . At each support, remove one screw that secures support to
secondary air shield .
f . While holding venturi tube, slide entire burner assembly slightly to right
to disengage burner from supports on left . g . Rotate open end of venturi
tube inward toward heater and carefully pull burner assembly out of cabinet .
3 . Inspect and clean burner:
NOTE: If, upon inspection, any of the burner components are damaged or
deteriorated, replace the burner assembly.
a . With burner assembly removed, shine flashlight on burner ribbons . Look
for carbon buildup, scale, dust, lint, and/or anything that might restrict
flow through spaces between burner ribbons .
b . While holding burner assembly so that any foreign material will fall away
from burner, use stiff bristle brush to loosen and remove any foreign
material(s) .
c . If burner is excessively dirty, remove one burner end cap: (1) Remove four
screws that secure end cap to burner housing . (2) Lightly tap end cap to
remove it .
d . Clean all foreign material from burner and venturi . e . When burner is
thoroughly clean, replace end cap, ensuring that it is tight against burner
housing . 4 . Inspect lower part of heat exchanger: a . With burner assembly
removed, shine bright light into each heat exchanger section at burner flame
entrance
of each tube . b . With light shining into heat exchanger, observe outside for
visible light . Repeat for each heat exchanger section . c . If any light is
observed, replace heat exchanger . 5 . Re-install burner assembly (see Figure
31): a . Attach burner assembly:
(1) While holding venturi tube, slide entire burner assembly into position .
(2) Align supports on left side with slots in burner shield and slide supports
into slots . (3) On right, install screw that secures each burner body support
to secondary air shield . b . Re-install secondary air baffles–install screw
that secures each baffle(s)–baffles may be different sizes and each must be
installed in correct location as marked . c . Attach control assembly: (1)
Carefully slide control assembly into position and secure using same screws .
(2) Check to ensure that all wire connections are secure . d . Reconnect gas
train: (1) Slide gas train into position so that orifice adapter is slid
through bracket on burner . (2) Secure gas train to bracket using locking nut
. (3) Install gas orifice and reconnect wires to combination gas valve . e .
Install access panel . f . Reconnect gas supply at union outside of cabinet .
g . Leak test connection using leak detecting solution . If leak is detected,
tighten connection . If leak cannot be stopped by tightening connection,
replace part(s) . 6 . Turn ON electric and gas . 7 . Check for proper
operation .
UEZ-IOM (07-24) 1034347-L
53
MAINTENANCE–CONTINUED
Maintenance Procedures–Continued
Burner Orifice Maintenance
The burner orifice usually needs to be replaced only when installing a gas
conversion kit . When ordering a replacement orifice only, provide BTUh
content and specific gravity of gas as well as the model and serial number of
the unit . When removing or replacing the burner orifice, take care not to
damage the venturi tube and/or the bracket .
Heat Exchanger Maintenance
NOTE: Inspection of the lower portion of the heat exchanger is done with the
burner removed. Refer to the Burner Maintenance (Unit Sizes 130310) section
for information on inspecting the lower portion of the heat exchanger.
1 . Remove burner in accordance with Burner Maintenance (Unit Sizes 55110) or
Burner Maintenance (Unit Sizes 130310) section .
2 . Remove any external dirt or dust accumulation . 3 . Visually inspect heat
exchanger for cracks and holes . 4 . If crack or hole is found, replace heat
exchanger . 5 . Install burner in accordance with Burner Maintenance (Unit
Sizes 55110) or Burner Maintenance (Unit Sizes
130310) section .
Ignition System Maintenance
· The DSI control module (circuit board, see Figure 25) monitors the operation
of the heater including ignition . The only replaceable component is the 3-amp
Type ATC or ATO fuse (color code: violet, PN 201685) . If the fuse is blown,
the problem is most likely an external overload . Correct the problem and
replace the fuse .
· Do not attempt to disassemble the control module . However, check the lead
wires each heating season for insulation deterioration and good connections .
· For the flame sensor (see Figure 26 for location), disconnect the wire and
remove the screw and the flame sensor . Clean flame sensor with an emery cloth
before reinstalling .
· Proper operation of the direct spark ignition system requires a minimum
flame signal of 1 .0 microamps as measured by a microampmeter .
CAUTION
When reassembling, the brown ground wire must remain attached to the ignitor
for unit sizes 55, 85, and 110.
· For the ignitor (see Figure 26 for location), disconnect the wire and remove
the screw and ignitor . Clean the ignitor assembly with an emery cloth before
reinstalling .
WARNING
Due to high voltage on the spark wire and electrode, do not touch when
energized.
· The spark gap (see Figure 32) must be maintained to 1/8 inch .
54
UEZ-IOM (07-24) 1034347-L
Figure 32. Ignitor Spark Gap
Fan and Motor Assembly Maintenance
Inspect and clean the motor, fan guard, and blades . Remove any dirt and
grease . Take care when cleaning the fan blades so as prevent causing
misalignment or imbalance . Check to ensure that the hub of the fan blades is
secure to the shaft . If necessary, replace the assembly as follows: 1 . If
heater has been installed, turn OFF gas and disconnect electric power . 2 .
Remove access panel and disconnect fan motor wi
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>