TRANE TTA300K C Split System Air Conditioners Installation Guide

September 13, 2024
Trane

TTA300K C Split System Air Conditioners

“`html

Product Information

Specifications:

  • Product: Split System Air Conditioners OdysseyTM with SymbioTM
    Controls

  • Cooling Condenser: R-454B

  • Capacity: 6 to 25 Tons (60 Hz)

  • Models: TTA072KA/D, TTA090KA/D, TTA120KC/D, TTA150KD,
    TTA180KC/D, TTA240KC/D, TTA300K*C

Product Usage Instructions:

Installation:

1. Only qualified personnel should install the equipment.

2. Follow the installation instructions provided in the
manual.

3. Ensure proper field wiring and grounding as per NEC and local
electrical codes.

Operation:

1. Read the manual thoroughly before operating the unit.

2. Use only R-454B rated service equipment and components due to
the flammable nature of the refrigerant.

3. Follow all safety precautions mentioned in the manual and on
the equipment labels.

Maintenance:

1. Regularly inspect and clean the unit as per maintenance
schedule.

2. Ensure proper refrigerant handling and pressure relief
procedures.

3. Contact local representative for specific concerns related to
R-454B refrigerant handling.

FAQ:

Q: Can I install the equipment myself?

A: No, only qualified personnel should install and service the
equipment to ensure safety and proper functioning.

Q: What should I do in case of refrigerant leakage?

A: In case of refrigerant leakage, contact a qualified
technician to handle the issue safely and effectively.

“`

Installation, Operation, and Maintenance
Split System Air Conditioners OdysseyTM with SymbioTM Controls
Cooling Condenser, R-454B 6 to 25 Tons

(60 Hz) TTA072KA/D TTA090KA/D TTA120KC/D TTA150KD TTA180KC/D TTA240KC/D TTA300K*C
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

August 2024

SS-SVX014A-EN

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION NOTICE

Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
· Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/ sleeves, butyl gloves, safety glasses, hard hat/ bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

©2024

SS-SVX014A-EN

Introduction

WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
· All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
· Non-Trane personnel should always follow local regulations.
WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage. The equipment described in this manual uses R-454B refrigerant which is flammable (A2L). Use ONLY R454B rated service equipment and components. For specific handling concerns with R-454B, contact your local representative.
WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage. System contains refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.

WARNING
Explosion Hazard!
Failure to follow instructions below could result in an explosion which could result in death or serious injury, and equipment damage. NEVER bypass system safeties in order to pump down the unit component’s refrigerant into the microchannel heat exchanger (MCHE) coil. Do NOT depress the compressor contactor since it effectively bypasses the high-pressure control.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Product Safety Information
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Maximum altitude of use 3000 meters.
This appliance incorporates an earth connection for functional purposes only.

SS-SVX014A-EN

3

Table of Contents
Model Number Description . . . . . . . . . . . . . . . . . . . 5
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . . 5
General Information . . . . . . . . . . . . . . . . . . . . . . . . . 6
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
A2L Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
A2L Work Procedures . . . . . . . . . . . . . . . . . . . . . . 7 Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Leak Detection . . . . . . . . . . . . . . . . . . . . . . . . 8 Refrigerant Removal and Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Refrigerant Charging . . . . . . . . . . . . . . . . . . . 8 Decommissioning . . . . . . . . . . . . . . . . . . . . . . 9
A2L Application Considerations. . . . . . . . . . . . . . 9 Ignition Sources in Ductwork. . . . . . . . . . . . . 9 Ignition Sources in Unit . . . . . . . . . . . . . . . . . 9 Minimum Room Area Limits (Refrigerant charge greater than 3.91 lb per circuit) . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Leak Detection System(Refrigerant charge greater than 3.91 lb per circuit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Field Piping Installation and Charging . . . . . . . 12
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Inspection Checklist . . . . . . . . . . . . . . . . . . . 13
Testing for Leaks . . . . . . . . . . . . . . . . . . . . . . . . . 13
Lifting Recommendations . . . . . . . . . . . . . . . . . . 13
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Structural Preparation . . . . . . . . . . . . . . . . . 14 Rooftop Mounting . . . . . . . . . . . . . . . . . . . . . 14 Ground Level Mounting . . . . . . . . . . . . . . . . 14
Installation Checklist . . . . . . . . . . . . . . . . . . . . . . 14 Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . 14 Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . 14
Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . 15
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . 24
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Refrigerant Piping Guidelines . . . . . . . . . . . . . . 25
Refrigerant Piping Procedures (Outdoor Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Refrigerant Piping Procedures (Indoor Unit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Leak Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 System Evacuation. . . . . . . . . . . . . . . . . . . . 28
Insulating and Isolating Refrigerant Lines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Refrigerant Charging Procedure . . . . . . . . . . . . 29 Charging Levels . . . . . . . . . . . . . . . . . . . . . . 30
Liquid Charging . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Unit Power Supply . . . . . . . . . . . . . . . . . . . . 31 Low Voltage Wiring. . . . . . . . . . . . . . . . . . . . 31 SymbioTM Controls . . . . . . . . . . . . . . . . . . . . 31 Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Refrigerant Circuit. . . . . . . . . . . . . . . . . . . . . 33
Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Control Circuit Features . . . . . . . . . . . . . . . . . . . 34 Discharge Temperature Limit (DTL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Low Outdoor Ambient Cooling . . . . . . . . . . 34 Evaporator Defrost Control (EDC) . . . . . . . 34 Low Pressure Cut-Out (LPC) . . . . . . . . . . . 34 High Pressure Cut-Out (HPCO) . . . . . . . . . 34 Internal Overload Protector (IOL) . . . . . . . . 34 Refrigerant Leak Detector Input . . . . . . . . . 34
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Leak Detection System . . . . . . . . . . . . . . . . . . . . 35
Service Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Annually (Cooling Season) . . . . . . . . . . . . . . . . . 37
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Microchannel (MCHE) Coils . . . . . . . . . . . . 37
Maintenance Log . . . . . . . . . . . . . . . . . . . . . . . . . 38
Charging Data and Pressure Curves. . . . . . . . . 39
Wiring Diagram Matrix and Device Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
For Commercial Unitary Equipment Rated 25 Tons and Under and Related Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Basic Warranty . . . . . . . . . . . . . . . . . . . . . . . 41 Exclusions and Limitations . . . . . . . . . . . . . 41

4

SS-SVX014A-EN

Model Number Description
Cooling Condenser

Digit 1, 2, 3– Unit Function
TTA = Split System Cooling
Digit 4, 5, 6 — Tonnage
072 = 6 Tons (60 Hz) 090 = 7.5 Tons (60 Hz) 120 = 10 Tons (60 Hz) 150 = 12.5 Tons (60 Hz) 180 = 15 Tons (60 Hz) 240 = 20 Tons (60 Hz) 300 = 25 Tons (60Hz) Digit 7 — Refrigerant
K = R-454B
Digit 8 — Voltage
3 = 208-230 Vac – 3 PH (60Hz) 4 = 460 Vac – 3 PH (60Hz) Digit 9 — Refrigeration Circuit/Stage
A = 1 Compressor/1 Line/1 Stage (Single) C = 2 Compressors/1 Line/2 Stage (Manifold) D = 2 Compressors/2 Line/2 Stage (Dual) Digit 10 — Major Design Sequence
A = Rev A
Digit 11 — Minor Design Sequence
A = Rev A
Digit 12, 13 — Service Digits
**

Digit 14 — Efficiency Generation
B = Generation B
Digit 15 — Controls
S = SymbioTM
Digit 16 — None
0 = None
Digit 17 — Coil Protection
0 = Standard Coil 1 = Standard Coil w/ Coil Guard 4 = Complete Coat Condenser Coil (MCHE) 5 = Complete Coat Condenser Coil with Coil Guard (MCHE) Digit 18, 19, 20 — None
0 = None
Digit 21 — Communications Options
0 = No Option 1 = Advanced Diagnostics and BACnet® BAS 2 = Advanced Diagnostics and LonTalk® Communications Interface (LCI) Digit 22 to 40 — None
0 = None

SS-SVX014A-EN

5

General Information
This manual describes proper installation, operation, and maintenance procedures for air-cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be performed to help assure trouble free operation. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
Important: All phases of this installation must comply with the NATIONAL, STATE and LOCAL CODES. In addition to local codes, the installation must conform with National Electric Code -ANSI/ NFPA NO. 70 LATEST REVISION.
Any individual installing, maintaining, or servicing this equipment must be properly trained, licensed and qualified.
Important: Do not remove the VFD without first contacting technical support! For performance-related questions and diagnostic VFD support in North America, request Live Tech Support via the link: https://support.trane.com/hc/en-us. Any return or escalation to the VFD manufacturer requires a Trane Technical Support ticket number FIRST. Removal of the VFD prior to this step will void the unit’s warranties.
Installation procedures should be performed in the sequence that they appear in this manual. Do not destroy or remove the manual from the unit. The manual should

remain weather-protected with the unit until all installation procedures are complete.
Note: It is not the intention of this manual to cover all possible variations in systems that may occur or to provide comprehensive information concerning every possible contingency that may be encountered during an installation. If additional information is required or if specific problems arise that are not fully discussed in this manual, contact your local sales office.
Use the “Installation Checklist,” p. 14 provided in this manual to verify that all necessary installation procedures have been completed. Do not use the checklist as a substitute for reading the information contained in this manual. Read this entire manual before beginning installation procedures.
Unit Description
These condensers come with single, dual and manifolded compressor options. Single compressor outdoor units feature a single refrigeration circuit requiring only one set of refrigerant lines. Dual compressor/dual circuit models give true stand-by protection; if one compressor fails, the second will automatically start-up. During light load conditions, only one compressor will operate to save energy.The dual manifolded scroll compressors come with two stages of capacity modulation and a single refrigeration circuit.

6

SS-SVX014A-EN

A2L Information
A2L Work Procedures WARNING
Risk of Fire — Flammable Refrigerant!
Failure to follow instructions below could result in death or serious injury, and equipment damage.
· To be repaired only by trained service personnel.
· Do not puncture refrigerant tubing.
· Dispose of properly in accordance with federal or local regulations.
WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage. System contains refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
The units described in this manual use R-454B refrigerant. Use ONLY R-454B rated service equipment or components with these units. For specific handling concerns with R-454B, contact your local Trane representative.
Installation, repair, removal, or disposal should be performed by trained service personnel.
At all times, Trane’s maintenance and service guidelines shall be followed. If in doubt, contact Trane technical support for assistance.
Servicing
Prior to initiating work on equipment, check the area with an appropriate refrigerant detector. Ensure the service personnel are properly trained regarding work in potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants, i.e. non-sparking, adequately
SS-SVX014A-EN

sealed, or intrinsically safe. Be aware that the refrigerant does not contain an odor.
If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fire extinguishing equipment shall be available on hand. A dry powder or CO2 fire extinguisher should be located adjacent to the charging area.
At all times, Trane’s maintenance and service guidelines shall be followed. If in doubt, contact Trane technical support for assistance.
All maintenance staff and others working in the local area shall be instructed on the nature of the work being carried out. Work in confined spaces shall be avoided.
Ignition Source Mitigation
Do not use any sources of ignition when working on the refrigeration system.
Keep all ignition sources, including cigarette smoking, away from the site of installation, repair, removal or disposal, during which refrigerant can potentially be released to the surrounding space.
Survey the area around the equipment before initiating work to ensure no flammable hazards or ignition risks are present.
“No Smoking” signs shall be displayed.
Do not use devices that can be a source of ignition to accelerate defrosting of components. Use only defrost and cleaning procedures recommended by Trane. Do not pierce or burn.
Ventilation
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. If present, check that the ventilation system, including outlets, are operating adequately and are not obstructed.
Refrigerating Equipment
Refrigerant piping or components should not be installed in locations where substances which may corrode them are present.
Check that equipment hazard markings are visible and legible. Replace them if they are not.
For equipment using secondary fluids, like water or glycol, check that refrigerant is not present in the secondary fluid loop before conducting any hot work.
Electrical Devices
Do not apply power to the circuit if a fault exists which compromises safety. If the fault cannot be corrected immediately, but it is necessary to continue operation, an
7

A2L Information

adequate temporary solution shall be used. This shall be reported to the owner of the equipment, so all parties are advised.
Initial safety checks shall include:
· Cabling is not subject to wear, corrosion, excessive pressure, vibration, sharp edges, or any other adverse environmental effects. Account for the effects of aging or continual vibration from sources such as compressors or fans.
· Capacitors are discharged. This shall be done in a safe manner to avoid possibility of sparking.
· No live electrical components and wiring are exposed while charging, recovering, or purging the system.
· Verify continuity of earth bonding.
· Replace electrical components with Trane replacement parts, or those meeting the same ratings and qualified for flame arrest protection, UL LZGH2 category.
Leak Detection
Never use an open flame to detect leaks. A halide torch should not be used. Use only approved leak detection methods per this instruction manual.
The following leak detection methods are deemed acceptable for all refrigerant systems.
Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity may not be adequate, or may need recalibration. (Detection equipment shall be calibrated in a refrigerant- free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL gas (25% maximum) is confirmed.
Leak detection fluids are also suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
Examples of leak detection fluids are:
· Bubble method
· Fluorescent method agents
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a refrigerant leak is found which requires brazing, all refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak.
Refrigerant Removal and Evacuation
When breaking into the refrigerant circuit to make repairs ­ or for any other purpose ­ conventional procedures shall be used. However, for flammable refrigerants it is important that best practice be followed, since flammability is a consideration.
The following procedure shall be adhered to:
8

1. Safely remove refrigerant following local and national regulations.
2. Evacuate.
3. Purge the circuit with inert gas.
4. Evacuate (optional for A2L).
5. Continuously flush or purge with inert gas when using flame to open circuit.
6. Open the circuit.
Prior to refrigerant removal, open all appropriate valves, including solenoid and electronic expansion valves (EXVs). Use control settings, where available. When not available, manually open all electronically controlled valves using acceptable service procedures.
The recovery equipment shall be in good working order with instructions available. Equipment shall be suitable for the recovery of the flammable refrigerant. For specific handling concerns, contact the manufacturer. Ensure all hose connections are checked for tightness to avoid refrigerant leaks.
The refrigerant shall be recovered into the correct recovery cylinders if venting is not allowed by local and national codes. Do not mix refrigerants in recovery unit and especially not in cylinders.
Refrigerant recovery unit should be purged with an inert gas after each use or before using with a different refrigerant Class ­ for example, A2L to A1.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The compressor body shall not be heated by an open flame or other ignition sources to accelerate this process. When oil is drained from a system, it shall be carried out safely.
The system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This process might need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems.
The system shall be vented down to atmospheric pressure to enable work to take place.
The outlet for the vacuum pump shall not be close to any potential ignition sources, and ventilation shall be available.
Refrigerant Charging
In addition to conventional charging procedures, the following requirements shall be followed.
· Ensure that contamination of different refrigerants does not occur when using charging equipment.
· Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
· Cylinders shall be kept in an appropriate position according to the instructions.
SS-SVX014A-EN

A2L Information

· Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
· Label the system when charging is complete (if not already).
· Extreme care shall be taken not to overfill the refrigerating system.
Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leaktested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
Prior to refrigerant charging, open all appropriate valves, including solenoid and electronic expansion valves (EXVs). Use control settings, where available. When not available, manually open all electronically controlled valves using acceptable service procedures.
Decommissioning
Before carrying out the decommissioning procedure, it is essential that the trained service personnel is completely familiar with the equipment and all its details. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is available before the task is commenced.
1. Become familiar with the equipment and its operation.
2. Isolate system electrically.
3. Before attempting the procedure, ensure that:
a. Mechanical handling equipment is available, if required, for handling refrigerant cylinders.
b. All personal protective equipment is available and being used correctly.
c. The recovery process is supervised at all times by a competent person.
d. Recovery equipment and cylinders conform to the appropriate standards.
4. Pump down refrigerant system, if possible.
5. If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
6. Make sure that cylinder is situated on the scales before recovery takes place.
7. Start the recovery machine and operate in accordance with instructions.
8. Do not overfill cylinders (no more than 80% volume liquid charge).
9. Do not exceed the maximum working pressure of the cylinder, even temporarily.
10. When the cylinders have been filled correctly and the process completed, make sure that the cylinders and
SS-SVX014A-EN

the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
11. Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked.
12. When equipment has been decommissioned, attach a signed label which includes the date of decommissioning.
A2L Application Considerations
This product is listed to UL standard 60335-2-40, Household and Similar Electrical Appliances ­ Safety ­ Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers, which defines safe design and use strategies for equipment using A2L refrigerants. This standard limits the refrigerant concentration in a space in the event of a refrigerant leak. To meet the requirements, the UL standard defines minimum room area, refrigerant charge limit, minimum circulation airflow and/or ventilation airflow requirements, and limits the use of ignition sources in spaces. The standard may require a unit refrigerant leak detection system.
For equipment with R-454B and charge amounts less than or equal to 3.91 lbs per circuit, this UL standard does not prescribe a room area limit and does not require a refrigerant leak detection system or any circulation airflow or ventilation airflow mitigation strategies. However, ignition sources in ductwork must be evaluated.
Depending on the application, a specific requirement of ANSI/ASHRAE Standard 15, Safety Standard for Refrigeration Systems, could be more stringent than UL 60335-2-40 requirements. See Refrigeration Systems and Machinery Rooms Application Considerations for Compliance with ASHRAE® Standard 15-2022 Application Engineering Manual (APP-APM001*-EN) for more information.
Ignition Sources in Ductwork
Do not install open flames in the ductwork. Hot surfaces exceeding 700°C (1290°F) should not be installed in the ductwork unless the average airflow velocity is not less than 1.0 ms (200 ftmin) across the heater and proof of airflow is verified before system is energized.
Electric heaters can exceed the surface temperature limit if airflow distribution is poor, or insufficient airflow is provided over the heater.
Surface temperatures of most gas heaters do not exceed the surface temperature limits due to ANSI construction requirements.
Ignition Sources in Unit
This UL-listed unit does not contain any ignition sources. All potential ignition sources, (including factory or field installed accessory electric heaters, gas heaters, relays, and contactors) were evaluated during product UL listing.
9

A2L Information

Minimum Room Area Limits (Refrigerant charge greater than 3.91 lb per circuit)
Equipment with R­454B charge amounts greater than 3.91 lb per circuit may require additional circulation or ventilation airflow mitigation strategies. In this case, there are two minimum room area (Amin) thresholds.
· The first threshold defines when equipment serving a single room is required to provide circulation airflow, either continuous or activated by a leak detection system. A ducted system requires circulation airflow unless the smallest room it serves is larger than the adjusted Amin threshold. This product contains a leak detection system if a circuit charge is greater than 3.91 lbs. As a result, no further leak detection system evaluation is needed.

· The second threshold defines when additional ventilation airflow is required. If the room area, A or TA, is below the adjusted Amin or TAmin threshold, additional ventilation is required to remove refrigerant in the event of a leak. Refer to UL 60335-2-40 Clause GG.8 and ANSIASHRAE Standard 15 Section 7 for natural and mechanical ventilation requirements. See equipment nameplate and table below for minimum room area.
Split systems minimum room area requirements need to be determined after final field charging. Use the following figures and the largest final circuit charge to determine the systems Amin value. Record the final charge value on the label provided on the condensing unit.

Figure 1. Charge vs min room area (IP)

Charge vs Min Room Area (IP)

3000

2800 2600 2400 2200 2000 1800

Release Height-0.6m Release Height-1.0m Release Height-1.4m Release Height-1.8m Release Height-2.2m

Minimum Room Area (ft2)

1600

1400

1200

1000

800

600

400

200

0 2.0 4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0 30.0 32.0 34.0 36.0 38.0 40.0 42.0 44.0 46.0 48.0 50.0
Charge (lbs)

10

SS-SVX014A-EN

A2L Information

Figure 2. Charge vs min room area (SI)
Charge vs Min Room Area (SI)

280.0

260.0 240.0 220.0 200.0

Release Height-0.6m Release Height-1.0m Release Height-1.4m Release Height-1.8m Release Height-2.2m

Minimum Room Area (m2)

180.0

160.0

140.0

120.0

100.0

80.0

60.0

40.0

20.0

0.0

0.0

2.0

4.0

6.0

8.0

10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0

Charge (kg)

Release height is the vertical distance from the floor to the lowest point in a space refrigerant would leak from first. The minimum value is 0.6 m from the floor. This point is typically the bottom of free return openings or supply diffusers. For fully ducted units, the release height is 2.2 meters.

Minimum Room Area (Amin) Adjustments
Use equation below to adjust the minimum room area, as applicable, based on the unit’s installation height, altitude, and occupancy level it serves.

Table 1. Altitude adjustment factor

Altitude (ft)
Amin Adjustment

Sea Level to 2000
1

2001 to 4000
1.05

4001 to 6000
1.11

6001 to 8000
1.17

Amin.adj = Nameplate Amin x Altitude Adj x Height Adj x Focc
Multiply the altitude adjustment factor in the table below by Amin listed on the unit nameplate or in the Installation, Operation, and Maintenance (IOM) manual.

8001 to 10000
1.24

10001 to 12000
1.32

12001 to 14000
1.41

14001 to 15000
1.51

Over 15000 1.57

In addition, Amin can be adjusted if the unit is installed in a room at a height that is higher than the minimum height shown on the unit. To adjust Amin, multiply by the ratio of the unit minimum release height (in meters) / actual release height (in meters). Use 0.6 m in the ratio for unit minimum installation heights less than or equal to 0.6 m.
For institutional occupancies, ASHRAE Standard 15 applies an additional adjustment factor Focc to the amount of a charge allowed in a space. To calculate the adjusted
SS-SVX014A-EN

Amin for institutional occupancies, multiply the Amin on the nameplate by two. EXAMPLE 1: 20 Ton Packaged Rooftop Multi-Zone VAV System Serving an Institutional Occupancy Space The packaged unit serves 7600 ft2 of a nursing home located at an attitude of 4000 ft. The unit has two equally charged 10 ton refrigeration circuits. Each circuit has 12 lbs
11

A2L Information

of refrigerant with a minimum room area requirement of 180 ft2 with a 2.2 m release height.
TAmin.adj = 180 ft2 x 1.05 x 2 = 378 ft2
No additional ventilation is required.
EXAMPLE 2: 10 Ton Split System Serving a Single Commercial Occupancy Space
The split system serves a 1500 ft2 manufacturing space at 5000 ft altitude. The final installed charge of the single circuit 10 ton unit is 20 lb. The unit has an open return with a release height of 1 m and ducted supply air. The unit Amin is 660 ft2.
Amin.adj = 660 ft2 x 1.11 = 733 ft2
No additional ventilation is required.
Determining Room Area (A or TA)
The room area (A) is the room area enclosed by the projection to the floor of the walls, partitions, and doors of the space that the equipment serves. For ducted systems, total room area (TA) of all rooms connected by ducts, may be used instead of A.
Rooms connected by drop ceilings only are not considered a single room.
Rooms on the same floor of the building, and connected by an open passageway, can be considered part of the same room if the passageway is a permanent opening, extends to the floor and is intended for people to walk through.
Adjacent rooms on the same floor of the building and connected by permanent openings in the walls and/or doors between rooms (including gaps between the wall and the floor), can be considered part of the same room if the openings meet the following criteria.
· The opening is permanent and cannot be closed.
· Openings extending to the floor, such as door gaps, need to be at least 20 mm above the floor covering surface.
· Natural ventilations opening areas must meet the requirements of ANSIASHRAE Standard 15-2022, Section 7.2.3.2.
Rooms that are connected by a mechanical ventilation system can be considered a single room area if the

mechanical ventilation system meets the requirements of ANSIASHRAE Standard 15-2022, Section 7.6.4.
Leak Detection System (Refrigerant charge greater than 3.91 lb per circuit)
The leak detection system consists of one or more refrigerant detection sensors. When the system detects a leak, the following mitigation actions will be initiated until refrigerant has not been detected for at least 5 minutes:
· Energize the supply fan(s) to deliver a required minimum amount of circulation airflow.
· Disable compressor operation.
· Provide an output signal to fully open all zoning dampers, such as VAV boxes.
· Provide an output to energize additional mechanical ventilation (if needed).
· Units without airflow proving will disable electric heat sources.
Building fire and smoke systems may override this function.
If the refrigerant sensor has a fault, is at the end of its life, or is disconnected, the unit will initiate the mitigation actions. Mitigation actions may be verified by disconnecting the sensor.
The refrigerant sensors do not need service. Use only manufacturer-approved sensors when replacement is required.
Field Piping Installation and Charging
When refrigerant piping is routed indoors, protect from physical damage in operation or service, and verify installation complies with national and local codes. All joints must be accessible for inspection prior to being covered.
Follow the Refrigerant Charging procedure. Prior to refrigerant charging, check field-made indoor joints for leaks using an instrument with a sensitivity of 5 grams per year refrigerant. Pressurize the system to 25% of the maximum allowable pressure. Verify no leaks are detected.

12

SS-SVX014A-EN

Pre-Installation
Unit Inspection
Inspect material carefully for any shipping damage. If damaged, it must be reported to, and claims made against the transportation company. Compare the information that appears on the unit nameplate with ordering and submittal data to ensure the proper unit was shipped. Available power supply must be compatible with electrical characteristics specified on component nameplates. Replace damaged parts with authorized parts only. Important: Units ordered with a VFD cannot be field
converted to 460 V from 208-230 or from 208230 V to 460 V.
Inspection Checklist
To protect against loss due to damage incurred in transit, complete the following checklist upon receipt of the unit. Inspect individual pieces of the shipment before
accepting the unit. Check for obvious damage to the unit or packing material. Inspect the unit for concealed damage before it is stored and as soon as possible after delivery. Concealed damage must be reported within 15 days. If concealed damage is discovered, stop unpacking the shipment. Do not remove damaged material from the receiving location. Take photos of the damage if possible. The owner must provide reasonable evidence that the damage did not occur after delivery. Notify the carrier’s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee. Notify the sales representative and arrange for repair. Do not repair the unit until the damage is inspected by the carrier’s representative.
Testing for Leaks
All units are shipped with a holding charge of nitrogen in each circuit and should be leak tested before installation. 1. Remove the access panel. 2. Locate the liquid line or suction line access valve for
each circuit. 3. Install gauges to determine if the circuits are still
pressurized. If not, the charge has escaped and should be repaired as required to obtain a leak-free circuit.
SS-SVX014A-EN

Lifting Recommendations
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Test lift unit approximately 24 inches (61 cm) to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
NOTICE
Equipment Damage!
Use spreader bars to prevent straps from damaging the unit. Install the bars between lifting straps, both underneath the unit and above the unit to prevent the straps from crushing the unit cabinet or damaging the finish.
Before preparing the unit for lifting, estimate the approximate center of gravity for lifting safety. Because of placement of internal components, the unit weight may be unevenly distributed. See “Weights,” p. 24 for approximate unit weights.
The crated unit can be moved using a forklift of suitable capacity. For lifting the unit, attach lifting straps or slings securely to the lifting holes at each corner (see unit drawings in “Weights,” p. 24). Use spreader bars to protect the unit casing from damage. Test lift the unit to determine proper balance and stability.
Clearances
Provide enough space around the unit to allow unrestricted access to all service points. Refer to the “Dimensional Data,” p. 15 for unit dimensions and minimum required service and free air clearances. Observe the following points to ensure proper unit operation.
1. Do not install the unit under a low overhang. Condenser discharge must not be restricted, refer to notes in “Dimensional Data,” p. 15. Important: Do not obstruct condenser discharge air. This can result in warm air recirculation through the coil.
2. Do not locate the unit in a position where runoff water, or falling snow from roof, can fall into the fan discharge openings.
3. Condenser intake air is supplied from three or four sides of the unit. Adhere to the minimum required clearances given in unit dimensional drawings (see “Dimensional Data,” p. 15).
13

Pre-Installation

Unit Mounting
WARNING
Risk of Roof Collapsing!
Failure to ensure proper structural roof support could cause the roof to collapse, which could result in death or serious injury and property damage. Confirm with a structural engineer that the roof structure is strong enough to support the combined weight of the roofcurb, the unit, and any accessories.

Structural Preparation
NOTICE
Roof Damage!
System contains oil and refrigerant under high pressure. Roofs should be protected from exposure to oils and refrigerant in the system. If rooftop is not protected, damage to the roof may occur.
Important: Refer to local building codes for proper installation. All installation must comply with local building codes.

Rooftop Mounting
If the unit will be roof mounted, determine for certain that the structure is strong enough to support the unit and any required accessories, see “Weights,” p. 24. The unit should be elevated on a level, field fabricated four-inch steel or wood 4-inch x 4-inch mounting frame. Complete the frame and secure it into position before lifting the unit to the roof. The mounting frame must support a minimum of three of the unit’s four sides and should span roof supports to distribute the load on the roof.
Figure 3. Roof mounted unit

Outdoor Unit
Gas (Suction) Line – Insulated

Liquid Line Insulated
Unit Mounting Channels
Elevation (Mounting Frame)

6″ Radius

Roof Trussing 14

Roof Construction
Ceiling

Ground Level Mounting
For ground level installation, the unit base should be adequately supported and hold the unit near level. The installation must meet the guidelines set forth in local codes. The support should extend two inches beyond the unit base channels at all points. The unit and support must be isolated from any adjacent structure to prevent possible noise or vibration problems. Any ground level location must comply with required clearances given in the unit dimensional drawings (see “Dimensional Data,” p. 15).
Installation Checklist
Complete this checklist once the unit is installed to verify that all recommended procedures have been accomplished before starting the system. Do not operate the system until all items covered by this checklist are complete. Inspect unit location for proper required service
clearances. Inspect unit location for proper free air clearances. Inspect unit location for secure, level mounting position. Remove coil protection boards on microchannel units. Verify condenser fans turn freely without rubbing and
are properly tightened on the shafts.
Refrigerant Piping
Properly sized/constructed liquid and suction lines connected to stubs at both the indoor and outdoor units?
Insulated the entire suction line? Insulated portions of liquid line exposed to extremes in
temperature? Performed initial leak test? Evacuated each refrigerant circuit to 500 microns? Charged each circuit with proper amount of R-454B?
Electrical Wiring
Provided unit power wiring (with disconnect) to proper terminals in the unit control enclosure?
Installed system indoor thermostat or zone sensor? Installed system low voltage interconnecting wiring to
proper terminals of outdoor unit, indoor unit and system thermostat or zone sensor? Checked all electrical connections to verify all are properly tightened and connected? Verified operation of crankcase heaters?
SS-SVX014A-EN

Dimensional Data
Cooling Condenser
Figure 4. Height, width and depth measurements

H

H W

D

W

TTA072, 090 TTA120 TTA150
TTA180, 240 TTA300

H – in. (mm) 39.2 (996) 39.2 (996) 45.2 (1150) 45.2 (1150) 51.2 (1302)

Note: Full dimensional data available on next pages.

W – in. (mm) 42.1 (1070) 51.9 (1317) 51.9 (1317) 94.8 (2407) 94.8 (2407)

D
D – in. (mm) 36.3 (922) 39.3 (999) 39.3 (999) 45.4 (1152) 45.4 (1152)

SS-SVX014A-EN

15

Dimensional Data

Figure 5. 6, 7.5 ton condensing, single compressor ­ in (mm)

SEE NOTE 3 SERVICE PANEL

NOTES: 1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY. 2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36″ ( 914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72″ (1828.8). RECOMMENDED SERVICE CLEARANCE 48″ (1219.2) 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100″ (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT 4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 4

HAIL GUARD (OPTIONAL)

SERVICE CLEARANCE 48″ (1219.2) (SEE NOTE 2 FOR CLEARANCE) HAIL GUARD (OPTIONAL)
SUCTION LINE LIQUID LINE

4 5/16″ (109)
1 5/16″ (33) LINE VOLTAGE CONTROL WIRING

36 5/16″ (922)
WITH HAIL GUARD
34 15/16″ (887)

SEE NOTE 1 REFRIGERANT GUAGE ACCESS

35 3/8″ (898) 27 13/16″ (706)
16 5/16″ (415)
9 5/16″ (236)
2 13/16″ (72) 3 3/16″ (81)

1/16″ (1.2)
6″ (152)

3″ (76)

SERVICE PANEL
22 11/16″ (577)
34 11/16″ (881)

39 3/16″ (996)

CONTROL WIRING
(OPTIONAL)

20 15/16″ (531) 17 7/16″ (442) 11 13/16″ (300)

6″ (152)

1 7/8″ (47) 2 7/8″ (74)

SERVICE PANEL SIDE

7/16″ (11.11) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES – 4 PLACES)

41 1/8″ (1044)
41 15/16″ (1065)
WITH HAIL GUARD

35 1/16″ 41 15/16″ (890)
(1065)

BOTTOM OF UNIT

1 13/16″ (47)

2 5/16″ (59)
28 11/16″ (729)

2 5/16″ (59)

16

SS-SVX014A-EN

Dimensional Data

Figure 6. 6, 7.5 ton condensing, dual compressor ­ in (mm)

SEE NOTE 3 SERVICE PANEL

NOTES: 1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY. 2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36″ ( 914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72″ (1828.8). RECOMMENDED SERVICE CLEARANCE 48″ (1219.2) 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100″ (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT 4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 4

HAIL GUARD (OPTIONAL)

SERVICE CLEARANCE 48″ (1219.2) (SEE NOTE 2 FOR CLEARANCE) HAIL GUARD (OPTIONAL)
SUCTION LINE LIQUID LINE

4 5/16″ (109) 1 5/16″ (33)
LINE VOLTAGE
CONTROL WIRING

6 3/8″ (162)

9 5/16″ (236)

35 3/8″ (898)
27 13/16″ (706)

11 5/16″ (288)

7 13/16″ (199)
2 1/4″ (57)
4 3/8″ (111)

1/16″ (1.2)
6″ (152)

3″ (76)

36 5/16″ (922)
WITH HAIL GUARD
34 15/16″ (887)

SEE NOTE 1 REFRIGERANT GUAGE ACCESS

SERVICE PANEL
22 11/16″ (577)
34 11/16″ (881)

39 3/16″ (996)

CONTROL WIRING (OPTIONAL)

20 15/16″ (531) 17 7/16″ (442) 11 13/16″ (300)

6″ (152)

1 7/8″ (47) 2 7/8″ (74)

SERVICE PANEL SIDE

7/16″ (11.11) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES – 4 PLACES)

41 1/8″ (1044)
41 15/16″ (1065)
WITH HAIL GUARD

35 1/16″ 41 1/16″ (890) (1042)

BOTTOM OF UNIT

1 13/16″ (47)

2 5/16″ (59)
28 11/16″ (729)

2 5/16″ (59)

SS-SVX014A-EN

17

Dimensional Data

Figure 7. 10 ton manifolded compressor ­ in (mm)
SEE NOTE 3

SERVICE PANEL

SEE NOTE 4

HAIL GUARD (OPTIONAL)

NOTES: 1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY. 2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36″ ( 914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72″ (1828.8). RECOMMENDED SERVICE CLEARANCE 48″ (1219.2) 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100″ (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT 4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

HAIL GUARD (OPTIONAL)

SERVICE CLEARANCE 48″ (1219.2) (SEE NOTE 2 FOR CLEARANCE)
LINE VOLTAGE

SUCTION LINE LIQUID LINE

4 1/4″ (109) 1 1/4″ (33)
CONTROL WIRING

39 5/16″ (999)
WITH HAIL GUARD
37 15/16″ (964)

35 3/8″ (898)

9 5/16″ (236)

27 13/16″ (706)
16 5/16″ (415)

2 13/16″ (72) 3 3/16″ (81)

6″ (152)

SERVICE PANEL
25 11/16″ (653)
37 11/16″ (958)

39 3/16″ (996)

CONTROL WIRING (OPTIONAL)

20 15/16″ (531) 17 7/16″ (442) 11 13/16″ (300)

1 7/8″ (47) 2 7/8″ (73)

6″ (152)

SEE NOTE 1 REFRIGERANT GAUGE ACCESS
50 7/8″ (1293) 51 11/16″ (1312) WITH HAIL GUARD

3″ (76)

SERVICE PANEL SIDE

7/16″ (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES – 4 PLACES)

44 3/4″ 50 3/4″ (1137) (1290)

BOTTOM OF UNIT

1 11/16″ (43)

2 3/16″ (56)
31 11/16″ (805)

1 11/16″ (43)

18

SS-SVX014A-EN

Dimensional Data

Figure 8. 10 ton condensing, dual compressor ­ in (mm)
SEE NOTE 3
SERVICE PANEL

SEE NOTE 4

HAIL GUARD (OPTIONAL)

NOTES: 1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY. 2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36″ ( 914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72″ (1828.8). RECOMMENDED SERVICE CLEARANCE 48″ (1219.2) 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100″ (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT 4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SERVICE CLEARANCE 48″ (1219.2) (SEE NOTE 2 FOR CLEARANCE)

HAIL GUARD (OPTIONAL)

LINE VOLTAGE

SUCTION LINE LIQUID LINE

4 5/16″ (109) 1 5/16″ (33)
CONTROL WIRING

39 5/16″ (999)
WITH HAIL GUARD
37 15/16″ (964)

6 3/8″ (162)

9 5/16″ (236)

35 3/8″ (898) 27 13/16″ (706)

11 5/16″ (288)

7 13/16″ (199)
2 1/4″ (56) 4 3/8″ (110)

[288]

6″ (152)

SERVICE PANEL
25 11/16″ (653)
37 11/16″ (958)

39 3/16″ (996)

CONTROL WIRING (OPTIONAL)

20 15/16″ (531)

17 3/8″ (441)

11 13/16″ (300)

1 7/8″ (47) 2 7/8″ (73)

6″ (152)

SEE NOTE 1 REFRIGERANT GAUGE ACCESS
50 3/4″ (1290) 51 11/16″ (1312) WITH HAIL GUARD

3″ (76)

SERVICE PANEL SIDE

7/16″ (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES – 4 PLACES)

44 3/4″ 50 3/4″ (1137) (1290)

BOTTOM OF UNIT

1 11/16″ (43)

2 3/16″ (56)
31 11/16″ (805)

1 11/16″ (43)

SS-SVX014A-EN

19

Dimensional Data

Figure 9. 12.5 ton condensing, dual compressor ­ in (mm)
SEE NOTE 2
SERVICE PANEL

SEE NOTE 3

HAIL GUARD (OPTIONAL)

NOTES:
1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36″ ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72″ (1828.8). RECOMMENDED SERVICE CLEARANCE 48″ (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100″ (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SERVICE CLEARANCE 48″ (1219.2) (SEE NOTE 1 FOR CLEARANCE)

HAIL GUARD (OPTIONAL)

LINE VOLTAGE

SUCTION LINE LIQUID LINE

4 5/16″ (109) 1 5/16″ (33)
CONTROL WIRING

39 5/16″ (999)
WITH HAIL GUARD
37 7/8″ (962)

6 3/8″ (162)

9 5/16″ (236)

33 13/16″ (859)

41 3/8″ (1050)

11 3/8″ (288)

7 7/8″ (199)
2 1/4″ (56) 3 3/16″ (80)

[288]

6″ (152)

SERVICE PANEL
25 11/16″ (653)
37 11/16″ (958)

45 1/4″ (1150)

CONTROL WIRING (OPTIONAL)

26 15/16″ (684)

23 7/16″ (595)

14 5/16″ (363)

1 7/8″ (47) 2 7/8″ (73)

6″ (152)

SEE NOTE 1 REFRIGERANT GAUGE ACCESS
50 7/8″ (1293) 51 11/16″ (1312) WITH HAIL GUARD

3″ (76)

SERVICE PANEL SIDE

7/16″ (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES – 4 PLACES)

44 3/4″ 50 3/4″ (1137) (1290)

BOTTOM OF UNIT

1 11/16″ (43)

2 3/16″ (56)
31 11/16″ (805)

1 11/16″ (43)

20

SS-SVX014A-EN

Dimensional Data

Figure 10. 15, 20 ton dual compressor ­ in (mm)
SEE NOTE 2

NOTES:
1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36″ ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72″ (1828.8). RECOMMENDED SERVICE CLEARANCE 48″ (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100″ (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 3 DETAIL A
SERVICE CLEARANCE 48″ (1219.2) (SEE NOTE 1 FOR CLEARANCE)

SERVICE PANEL

94 3/4″ (2407)
WITH HAIL GUARD

CONTROL WIRING

14 5/16″ (364)

LINE VOLTAGE

10 1/8″ (257)

HAIL GUARD (OPTIONAL)
WITHOUT HAIL GUARD (UNIT COIL)

1/2″ (13)

45 3/8″ (1152) WITH HAIL GUARD
44″ (1118)

HAIL GUARD (OPTIONAL)

SUCTION LINES LIQUID LINES
13 1/2″ (343)

93 1/32″ (2363)

10 9/16″ (268)
12 11/16″ (322)
35 1/16″ (891)

7/16″ (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES – 4 PLACES)
SERVICE PANEL SIDE

BOTTOM OF UNIT

3 3/16 (81)

87″ (2210)
93 3/8″ (2372)

24 5/8″ (625)

35 7/16″

(900) 40 11/16″

27 1/8″

(1033)

(689)

HAIL GUARD (OPTIONAL)
44 3/4″ (1137)

8 5/8″ (219) 3/16″ (5)

1/16″ (2)

9″ (229)

25 5/8″ (651)

9″ (229)

LINE VOLTAGE SUCTION LINES

REFRIGERANT ACCESS

41 9/16″ (1056)
36 15/16″ (938)

14 1/2″ 12 5/8″ (368) (321)
4 1/4″ 5 5/8″ (108) (143)
SUCTION LINES

2 5/16″ 6 15/16″

(59)

(176)

9 3/16″ (233) 7 1/16″ (179) 6 9/16″ (167)
37 1/16″ 34 5/8″ (941) 31 7/8″ (879) (810) 20 1/16″ 14 1/2″ (510) (368)
LIQUID LINES 9 1/4 (235) 6 5/8 (168) 6 5/16 (160) 3 11/16 (94) 3 3/8 (86) 15/16 (24)

SS-SVX014A-EN

21

Dimensional Data

Figure 11. 15, 20 ton condensing, manifolded compressor ­ in (mm)

SEE NOTE 2

NOTES:
1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36″ ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72″ (1828.8). RECOMMENDED SERVICE CLEARANCE 48″ (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100″ (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 3 DETAIL A
SERVICE CLEARANCE 48″ (1219.2) (SEE NOTE 1 FOR CLEARANCE)

SERVICE PANEL

94 3/4″ (2407)
WITH HAIL GUARD

CONTROL WIRING

14 5/16″ (364)

LINE VOLTAGE

10 1/4″ (260)

HAIL GUARD (OPTIONAL)
WITHOUT HAIL GUARD (UNIT COIL)

1/2″ (13)

45 3/8″ (1152) WITH HAIL GUARD
44″ (1118)

HAIL GUARD (OPTIONAL)

SUCTION LINES LIQUID LINES

13 9/16″ (344)

93 11/32″ (2363)

10 9/16″ (268)
35 1/16″ (891)

7/16″ (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES – 4 PLACES)
SERVICE PANEL SIDE

BOTTOM OF UNIT

3 3/16 (81)

87″ (2210)
93 3/8″ (2372)

12 1/4″ (311)
11 1/8″ (283)
3/16″ (5)

35 7/16″ (900) 40 11/16″ (1033)

HAIL GUARD (OPTIONAL)
44 3/4″ (1137)

1/16″ (2)

9″ (229)

25 5/8″ (651)

9″ (229)

LINE VOLTAGE SUCTION LINES

REFRIGERANT ACCESS

41 9/16″ (1056)
36 15/16″ (938)

14 1/2″ 12 9/16″ (368) (321)
4 1/4″ 5 5/8″ (108) (143)
SUCTION LINES

2 5/16″ 6 15/16″

(59)

(176)

9 3/16″ (233)
7 1/16″ (179) 6 9/16″ (167)

14 1/2″ (368)

37 1/16″ 34 5/8″ (941) 31 7/8″ (879) (810) 20 1/16″ (510)

LIQUID LINES
9 1/4 (235) 6 5/8 (168) 6 5/16 (160) 3 11/16 (94) 3 3/8 (86) 15/16 (24)

22

SS-SVX014A-EN

Dimensional Data

Figure 12. 25 ton condensing, manifolded compressor ­ in (mm)

SEE NOTE 2

NOTES:
1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36″ ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72″ (1828.8). RECOMMENDED SERVICE CLEARANCE 48″ (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100″ (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

HAIL GUARD (OPTIONAL)

SERVICE PANEL
SEE NOTE 3 DETAIL A SERVICE CLEARANCE 48″ (1219.2) (SEE NOTE 1 FOR CLEARANCE)

HAIL GUARD (OPTIONAL)

CONTROL WIRING LINE VOLTAGE

14 3/16″ (360)

10 1/8″ (257)

SUCTION LINE LIQUID LINE

10 7/16″ (266)

13 5/8″

35 3/16″

(346)

(893)

93 1/4″ (2369)

OPTIONAL REAR ACCESS DIMENSIONAL DETAIL
SERVICE PANEL SIDE

BOTTOM OF UNIT

3″

87″ (2211)

(76)

93″ (2363)

1/2″ (13)
HAIL GUARD (OPTIONAL)

41 7/16″ 50 3/4″

(1052) (1289)

46 11/16″

12″

(1186)

(304)

45 3/8″ (1152) WITH HAIL GUARD
44 3/16″ (1122)

10 1/4″ (260)

9″ (229)

25 5/8″ (651)

9″ (229)

7/16″ (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES – 4 PLACES)

4 5/8″ (118)
34 5/8″ (880) 4 5/8″ (118)
2 3/16″ (55)

LINE VOLTAGE CONTROL WIRING
SUCTION LINE
REFRIGERANT GAUGE ACCESS
14 1/2″ (368)
4 3/16″ (107) LIQUID LINE
8 1/4″ (210)

9 1/16″ (230) 7″ (177) 6 1/2″ (164)

40 5/8″

(1032) 43 1/16″

37 7/8″

(1093)

24 3/8″ (962)

(620)

13/16″ (21) 1 9/16″ (40) 6 3/16″ (157)
FRONT DETAIL A DIMENSIONAL DETAIL

SS-SVX014A-EN

23

Weights

Cooling Condenser

Table 2. TTA R-454B unit and corner weights — lbs (60 Hz)

Tons

Model No.

Shipping Max (lbs)

Net Max (lbs)

1

Corner Weights

2

3

4

TTA072K*A

324

288

84

89

55

59

6

TTA072K*D

348

316

100

92

66

59

TTA090K*A

342

309

88

95

60

66

7.5

TTA090K*D

399

367

114

107

75

71

TTA120K*D

443

404

117

116

87

85

10

TTA120K*C

473

433

128

128

88

88

12.5

TTA150K*D

504

454

136

136

91

91

TTA180K*D

806

715

197

198

160

160

15

TTA180K*C

806

707

193

193

161

160

TTA240K*D

872

755

210

210

167

168

20

TTA240K*C

892

802

225

227

174

176

25

TTA300K*C

1020

930

263

265

200

202

Figure 13. TTA072, 090, 120, 150 #3

Figure 14. TTA180, 240, 300

4

4 #1

2

ASCECREVSICSE

1

3

ASCECREVSICSE

2

ASCECREVSICSE

LIFTING HOLES (BOTH SIDES)

LIFTING HOLES (BOTH SIDES)

24

SS-SVX014A-EN

Installation
Refrigerant Piping Guidelines
Figure 15. Allowable elevation difference: TTA above indoor unit
For TTA units, contact the manufacturer for review.
Figure 16. Allowable elevation difference: TTA below indoor unit
For TTA units contact manufacturer for review. Not allowed for TWA units.
Acceptable liquid-riser height based on total liquid-line length (below indoor unit)
Note: Route refrigerant piping for minimum linear length, minimum number of bends and fittings. Important: Read Split System Air Conditioners Odyssey Application Guide (SS-APG017*-EN) thoroughly before installing this
unit.

SS-SVX014A-EN

25

Installation

Refrigerant Piping Procedures (Outdoor Units)
WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage. The equipment described in this manual uses R-454B refrigerant which is flammable (A2L). Use ONLY R454B rated service equipment and components. For specific handling concerns with R-454B, contact your local representative.
WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage. System contains refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
WARNING
Explosion Hazard!
Failure to follow instructions below could result in an explosion which could result in death or serious injury, and equipment damage. NEVER bypass system safeties in order to pump down the unit component’s refrigerant into the microchannel heat exchanger (MCHE) coil. Do NOT depress the compressor contactor since it effectively bypasses the high-pressure control.
Each unit ships with a holding charge of dry nitrogen. The nitrogen should be removed and the entire system evacuated (at the proper time) to avoid possible contamination.
1. Remove the compressor service access panel.
2. Locate the liquid and suction line access valves. Check that the piping connection stubs (see Figure 17, p. 26) line up properly with the holes in the unit cabinet.

Figure 17. Outdoor units – refrigerant piping (with dry nitrogen)
Red Tag
Manifold Gauges
Gas Line Gauge Port Liquid Line Gauge Port 3. Install gauges to determine if the circuits are still pressurized. If not, the charge has escaped and should be repaired as required to obtain a leak-free circuit. If the circuits are still pressurized, use the gauges to slowly release the nitrogen charge to the atmosphere and remove both seal caps from the outdoor unit connection stubs.
NOTICE
System Component Damage!
Do not remove the seal caps from refrigerant connections until prepared to braze refrigerant lines to the connections. Excessive exposure to atmosphere (> 5 min.) may allow moisture or dirt to contaminate the system, damaging valve seals and causing ice formation in system components.

26

SS-SVX014A-EN

Installation

WARNING
Explosion Hazard and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.
4. Cut, fit and braze tubing, starting at the outdoor unit and work toward the indoor unit. See “Charging Levels,” p. 30.
Note: Use long radius ells for all 90° bends.
All brazing should be done using a 2 to 3 psig dry nitrogen purge flowing through the pipe being brazed, see Figure 17, p. 26.
NOTICE
System Component Damage!
Install a regulating valve between the nitrogen source and the gauge manifold. Unregulated pressure can damage system components.
NOTICE
System Component Damage!
Wet-wrap all valves and protect painted surfaces from excessive heat. Heat can damage system components and the unit finish.
5. Shut off nitrogen supply. Shut off the manifold valve for the line that is connected to the suction line access valve. Disconnect the line from the access valve.
6. Reinstall the red tags, if they are removed during brazing.

Refrigerant Piping Procedures (Indoor Unit)
Once liquid and suction lines are complete to the refrigerant connections on the indoor unit, remove the gauge port core(s) on the indoor unit connection stubs to release the dry nitrogen charge.
NOTICE
Unit Damage!
Do not apply heat to remove seal caps until the gauge port cores have been removed. If seal caps are intact, application of heat may generate excessive pressure in the unit and result in damage to the coil or expansion valve.
1. Remove both seal caps from the indoor unit connection stubs.
NOTICE
Unit Damage!
Failure to follow instructions below could result in damaging the unit. Do not remove the seal caps from refrigerant connections until prepared to braze refrigerant lines to the connections. Due to the high hygroscopic properties of the POE oil, excessive exposure to atmosphere will allow moisture to contaminate the system, damaging the compressor.
2. Turn on nitrogen supply. Nitrogen enters through the liquid line gauge port.
3. Braze the liquid line connections.
4. Open the gauge port on the suction line and then braze the suction line to the connection stub. Nitrogen will bleed out the open gauge port on the suction line.
5. Shut-off nitrogen supply.
6. Reinstall the red tags, if they are removed during brazing.

SS-SVX014A-EN

27

Installation

Leak Check
WARNING
Explosion Hazard!
Failure to follow these instructions could result in death or serious injury or equipment or property-only damage. Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use hydrogen mixtures containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant, when used as a trace gas should only be mixed with dry nitrogen for pressurizing units.
WARNING
Explosion Hazard!
Failure to follow safe leak test procedures below could result in death or serious injury or equipment or property-only-damage. Never use an open flame to detect gas leaks. Use a leak test solution for leak testing.
After the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed, the field brazed connections must be checked for leaks. Pressurize the system through the gauge port with dry nitrogen to 200 psi. Use soap bubbles or other leak-checking methods listed under A2L Work Procedures section to ensure that all field joints are leak free. If not, release pressure, repair and repeat leak test.

System Evacuation
1. After completion of leak check, evacuate the system.
2. Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps. Note: Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of R-454B and vacuum pump.
3. Attach center hose of manifold gauges to vacuum pump.
NOTICE
Operating Under Vacuum!
Failure to follow these instructions will result in compressor failure. Do not operate or apply power to the compressor while under a vacuum.
4. Evacuate the system to hold a 500 micron vacuum.
5. Close off valve to vacuum pump and observe the micron gauge. If gauge pressure rises above 500 microns in one minute, then evacuation is incomplete or the system has a leak.
6. If vacuum gauge does not rise above 500 microns in 10 minutes, the evacuation should be complete.
NOTICE
Equipment Damage!
Charge with access port on the liquid line only.

28

SS-SVX014A-EN

Installation

Insulating and Isolating Refrigerant Lines
Insulate the entire suction line with refrigerant piping insulation. Also insulate any portion of the liquid line exposed to temperature extremes. Insulate and isolate liquid and suction lines from each other. Isolate refrigerant lines from the structure and any duct work.
Important: 1. To prevent possible noise or vibration problems, be certain to isolate refrigerant lines from the building.
2. All suction and hot gas bypass piping (if installed) should be insulated from the termination in the air handler to the condensing unit cabinet entry. Failure to do so can cause condensate drip off and performance degradation.
3. Prior to starting a unit, it is advisable to have the approved oils available in the event oil needs to be added to the system.
4. Refer to Split System Air Conditioners Odyssey Application Guide (SS- APG017*-EN) for units needing additional oil and for oil amounts.

NOTICE
Equipment Damage!
This is POE oil, which readily absorbs moisture. Always use new oil and never leave containers open to atmosphere while not in use.

Table 3. R-454B TTA approved oils

Unit Model Number
TTA072KA, TTA072KD, TTA090KD, TTA090KA, TTA120KC, TTA120KD, TTA150KD, TTA180KD, TTA180KC, TTA240KD
TTA240KC, TTA300KC

Approved Oils
Trane Oil Part Number OIL00094 (1 quart container)
Trane Oil Part Number OIL00079 (1 quart container) or OIL00080 (1
gallon container)

For units equipped with compressors containing site glasses, the oil level must be visible through the sight glass when the compressor is running under stabilized conditions and a few minutes after the compressor has stopped.
Refrigerant Charging Procedure
If charging by weight, refer to “Charging Levels,” p. 30 for starting change. If refrigerant adjustments are needed because of length of line, refer to the Charging Charts and Superheat values available on unit access panels.

Charge by weight through the gauge port on the liquid line. Follow the requirements listed under A2L Work Procedures section.

Notes: ·

Refrigerant should only be charged in the liquid state.

· When possible, always charge the refrigerant into the liquid line of the unit.

· If the entire charge cannot be charged into the liquid line, the balance of the unit charge can be metered through a charging manifold set as liquid — preferably through a schrader valve into the suction line to the compressor — only while the compressor is running.

· Check and adjust superheat using the superheat table, then re-check charging charts to determine if charge corrections are necessary.

NOTICE
Equipment Damage!
Never charge liquid refrigerant into the suction line of the unit with the compressor off.

Figure 18. Outdoor units – refrigerant piping

Red Tag

Manifold Gauges

Gas Line Gauge Port Liquid Line Gauge Port

SS-SVX014A-EN

29

Installation

Charging Levels
Important: For the correct line diameter, for line lengths greater than 25 feet, see the Split System Air

Conditioners Odyssey Application Guide (SS-APG017*-EN) available through e-Library or your local sales office.

Table 4. Estimated charge levels at AHRI rated line lengths (25 feet)

Matched Set

Refrigerant Charge

Circuit 1

Circuit 2

Per Circuit

Liquid Line Diameter

Vapor Line Diameter

TTA072KA(a) w/ TWE090KA

8.6

0.5 (1/2″)

1.125 (1 1/8″)

TTA072KD w/ TWE072KB

6.3

6.3

0.5 (1/2″)

0.875 (7/8″)

TTA090KA w/ TWE090KA

8.7

0.5 (1/2″)

1.375 (1 3/8″)

TTA0904KD w/ TWE090KB

6.0

6.1

0.5 (1/2″)

1.125 (1 1/8″)

TTA120KD w/ TWE120KB

7.0

7.5

0.5 (1/2″)

1.125 (1 1/8″)

TTA120KC w/ TWE120KA

11.1

0.5 (1/2″)

1.375 ( 1 3/8″)

TTA150KD w/ TWE150KB

8.6

8.4

0.5 (1/2″)

1.125 (1 1/8″)

TTA180KD w/ TWE180KB

9.4

9.4

0.5 (1/2″)

1.375 (1 3/8″)

TTA180KC w/ TWE180KB

18.5

0.625 (5/8″)

1.625 (1 5/8″)

TTA240KD w/ TWE240KB

9.9

9.7

0.5 (1/2″)

1.375 (1 3/8″)

TTA240KC w/ TWE240KB

19.4

0.625 (5/8″)

1.625 (1 5/8″)

TTA300KC(b) w/ TWE300KB

25.6

0.625 (5/8″)

2.125 (2 1/8″)

Note: For line lengths other than 25-inch, refer to the Split System Air Conditioners Odyssey Application Guide (SS-APG017*-EN) for charge levels,oil addition and line sizes.

(a) TTA072K*A needs a reducer for vapor line. (1.375 to 1.125 inch) (1 3/8″ to 1 1/8″).

(b) TTA300K*C is provided with a transition tube to be installed outside of the unit for front or rear access, (1.625 to 2.125-inch) (1 5/8 to 2 1/8-inch). See Refrigerant Charging

Procedure for transition tube location and electrical connections.

Liquid Charging
This procedure is accomplished with the unit operating. Electrical connections must be complete. Do not proceed until the system is ready to operate. Note: The compressor access panel must be installed
when the unit is running and being charged. Manifold hoses must be routed through refrigerant gauge access hole(s). See “Dimensional Data,” p. 15 for specific locations.

only) as required to obtain correct discharge pressure and liquid temperature.
3. Check suction line superheat and condenser subcooling to ensure the unit is operating properly.
4. Disconnect all power to the unit. Important: If the unit is charged and left without power until a later date, the crankcase heater should be energized for a minimum of 8 hours prior to powering the compressor(s).

WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When it is necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
1. Turn on power to the unit. Allow the system to run for 15 minutes to stabilize operating conditions.
2. Measure airflow across the indoor coil. Compare the measurements with the fan performance data in the Data/Submittal. Once proper airflow is established, compare discharge pressure and liquid temperature to the charging charts. Add or remove refrigerant (liquid

WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
5. Remove the charging system from the unit.

30

SS-SVX014A-EN

Installation

6. Reinstall the red tags on the schrader valves, if they were removed while charging.
7. Replace all panels.
Electrical Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
Field wiring consists of providing power supply to the unit, installing the system indoor thermostat or zone sensor and providing low voltage system interconnecting wiring. Access to electrical connection locations is shown in “Dimensional Data,” p. 15. Determine proper wire sizes and unit protective fusing requirements by referring to the unit nameplate. Field wiring diagrams for accessories are shipped with the accessory.
Unit Power Supply
The installer must provide line voltage circuit(s) to the unit main power terminals as shown by the unit wiring diagrams. Adhesive backed diagrams are affixed inside the control box cover panel. Wiring diagrams are also available through e-Library or by contacting a local sales office. Power supply must include a disconnect switch in a location convenient to the unit. Ground the unit according to local codes and provide flexible conduit if codes require and/or if vibration transmission may cause noise problems. Important: All wiring must comply with applicable local and
national (NEC) codes. Type and location of disconnect switches must comply with all applicable codes.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
SS-SVX014A-EN

NOTICE
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as the equipment was not designed or qualified to accept other types of conductors.
Low Voltage Wiring
Mount the indoor thermostat, zone sensor, or programmable zone sensor in accordance with the corresponding thermostat installation instructions. Install color-coded, weather-proof, multi-wire cable according to the Split System Air Conditioners OdysseyTM with SymbioTM Controls Wiring and Start-Up Installation Guide (SS-SVN017*-EN). Note: Refer to thermostat or zone sensor wire installation
guide for proper wire gauge.
SymbioTM Controls
Wiring shown with dashed lines is to be furnished and installed by the customer. All customer supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes may require line of sight between disconnect switch and unit.
Figure 19. SymbioTM jobsite connections
Disconnect Switch (By Others) See Note 1

B
Electric Heat Accessory

Air Handler

See Note 4

C

E

B D A

Disconnect Switch (By Others) See Note 1
Disconnect Switch (By Others)

T’stat Zone Sensor See Note 2 See Note 2
Power Wires
A. 3 wires, line voltage for 3 phase, 1 grounding wire
B. 3 wires, line voltage for 3 phase, (2 wires for single phase) 1 grounding wire

Control Wires
C. Cooling only (or Cooling with Heat) thermostat: 4 to 7 wires depending on stages of cooling and electric heat
D. Wiring between indoor and outdoor unit: 5 to 11 wires depending on unit control options
E. Zone Sensor: 4 to 7 wires depending on zone sensor model

31

Installation

Communication signal wires require shielded twisted pairs.
Use Comlink cable with a PVC jacket, 18/1 PR, stranded shield, 25 PF/FT plenum rated for the field communication signal wiring. Refer to wiring diagram schematics for identification of shielded twisted pairs.
Notes: 1. When electric heater accessory is used, single point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only. 2. *Choose only one of the following; Thermostat, Mechanical Zone Sensor, Programmable Zone Sensor Panel or BAS Zone Sensor. 3. *
WARNING
Electrical Shock Hazard!
Failure to follow instructions below could result in death or serious injury. Properly connect the system’s oversized protective earthing (grounding) terminal(s).
4. Once power wire connections are complete inside the air handler control box, seal the sheet metal entry points of the control box by using parts (neoprene gasket, grommet, and plug) shipped along with the air handler unit package.
5. For detailed controls wiring instructions, see Split System Air Conditioners OdysseyTM with SymbioTM Controls Wiring and Start-Up Installation Guide (SS-SVN016
-EN).

Important: For the EDC switch to be functional and thereby facilitate reliable unit operation, make the EDC connections from the indoor to the outdoor control boxes.
Table 5. Recommended thermostat wire size

Wire Size

Maximum Wire Length

(Gauge)

Physical distance between Unit and T’stat

22

30 Feet

20

50 Feet

18

75 Feet

16

125 Feet

14

200 Feet

Table 6. Zone sensor module wiring

Distance from Unit to Control 0-150 feet (0-45.7 m) 151-240 feet (46-73.1 m) 241-305 feet (73.5-117.3 m) 386-610 feet (117.7-185.9 m) 611-970 feet (186.2-295.7 m)

Recommended Wire Size 22 gauge (0.33 mm2) 20 gauge (0.50 mm2) 18 gauge (0.75 mm2) 16 gauge (1.31 mm2) 14 gauge ( 2.08 mm2)

Field Wiring
Refer to the latest version of Split System Air Conditioners OdysseyTM with SymbioTM Controls Wiring and Start-Up Installation Guide (SS-SVN017*-EN) for instructions on field wiring connections.

32

SS-SVX014A-EN

Refrigerant Circuit

Figure 20. Typical split system cooling refrigerant circuit — microchannel

COOLING ONLY CIRCUIT DIAGRAM

GAUGE CONNECTION

DISCHARGE TEMPERATURE
LIMIT (DTL)

HIGH PRESSURE SWITCH (HPCO)

D

S COMPRESSOR

EXPANSION VALVE BULB

FIELD SUPPLIED INTER-CONNECTING
TUBING

AIR
GAUGE CONNECTION

EQUALIZER TUBE

LOW PRESSURE SWITCH (LPCO)

TXV

Installation
NOTE A AIR

OUTDOOR COIL INDOOR COIL

INDICATES DIRECTION OF REFRIGERANT FLOW

FILTER DRIER

NOTE A
NOTE A: ONLY ONE INDOOR COIL REFRIGERANT ENTRY AND EXIT CIRCUIT IS SHOWN. ALL MODELS HAVE MULTIPLE ENTRY AND EXIT CIRCUITS.
NOTE B: DUAL CIRCUIT MODELS HAVE 2 REFRIGERATION CIRCUITS. MANIFOLD CIRCUIT MODELS HAVE 2 COMPRESSORS BUT 1 REFRIGERATION CIRCUIT.

SS-SVX014A-EN

33

Pre-Start
Control Circuit Features
Note: Not all of these features may be required for your unit, check electrical schematic.
Discharge Temperature Limit (DTL)
The control’s sensor is located on the discharge line. This device will shut off the compressor and the outdoor fan(s) if the discharge temperature exceeds the DTL setting. Once the discharge temperature has returned to normal, the compressor will cycle back on.
Low Outdoor Ambient Cooling
All Odyssey units with SymbioTM 700 controls have cooling capabilities down to 0°F as standard. At temperatures below 55ºF for single compressor units and 40ºF for dual compressor units, some reduction in cooling capacity can be expected. At this temperature, equipment can provide approximately 60% of the mechanical cooling capacity. When the optional Low Ambient Accessory kit is field installed, the full capacity of the unit is available down to 0° F.
Evaporator Defrost Control (EDC)
This control is located in the Air Handler. The control’s sensing tube is embedded vertically in the evaporator coil, near the center. This device will stop the compressor if the indoor coil temperature drops below its setting. The indoor air will still circulate across the coil bringing the temperature of the coil back up to the cut-in temperature of the evaporator defrost control.
Low Pressure Cut-Out (LPC)
This control’s sensor is located in the suction (gas) line, near the compressor. This control will stop the compressor and the outdoor fans if suction pressure drops below the Low Pressure Cut-Out setting. Once the suction pressure

has returned to normal, the compressor and outdoor fans will cycle back on.
High Pressure Cut-Out (HPCO)
This control’s sensor is located in the discharge line. This device will shut off the compressor and the outdoor fan(s) if the discharge pressure exceeds the High Pressure CutOut’s setting. Once the discharge pressure has returned to normal, the compressor will cycle back on.
WARNING
Prevent Injury!
Due to agency safety requirements, no schrader core is to be installed beneath the HPCO. Removal of the HPCO without evacuating the system charge could cause injury and release of refrigerant.
Internal Overload Protector (IOL)
This device is embedded in the compressor. It will shut off the compressor if the discharge temperature of the compressor exceeds its design trip temperature. Note: The IOL will put the compressor back in operation
once the compressor motor heat has dropped below the trip setting; however, a check of the refrigerant and electrical systems should be made to determine the cause and be corrected.
Refrigerant Leak Detector Input
All Odyssey units with SymbioTM 700 controls have a dedicated binary input for notification of a refrigerant leak event. This input will receive a normally closed 24 Vac source and when open, triggers a refrigerant leak diagnostic allowing the Symbio 700 to take mitigation actions.

34

SS-SVX014A-EN

Troubleshooting
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When it is necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
Refer to the latest version of the SymbioTM 700 Controller with Odyssey Split Systems Applications Guide (ACC-APG001*-EN) for details on troubleshooting the control system.
Leak Detection System
Note: The leak detection system referenced in this document refers specifically to a matched system containing only a TTA/TWE matched combination. If the installed system utilizes condensing units or AHUs other than listed above, it is the installers responsibility to ensure all necessary leak detection system hardware and communication is provided and installed for safe equipment installation and operation.

The leak detection sensor offers a visual diagnostic status in the form of one green and one red LED to indicate diagnostic error state.
Table 7. Leak detection system LED status

State Power up initiate
Failure resulting in a ‘Power-UP Self-Test’ Fail-safe State
Warm Up Delay
Normal Runtime Mode
LFL Alarm
Failure resulting in a Fail-safe State
Near end of life
Warning

Green LED ON
ON ON
Heartbeat OFF
OFF Blinking ON

Red LED OFF
ON OFF
OFF ON Blinking Heartbeat Heartbeat

SS-SVX014A-EN

35

Service Test Mode
The SymbioTM 700 supports a Service Test Mode that can be used to energize the various components of the system, either to support general system startup tasks or to support troubleshooting. The user can initiate Service Test Mode through the controller user interfaces, including the Symbio Service and Installation mobile application.
The modes shown below can be initiated. Depending on the equipment configuration, the controller will energize the
Figure 21. Symbio 700 service test mode

appropriate outputs. A user-selected timeout value will determine how long the controller will remain in any given state once initiated. For detailed information on how each Service Test State is interpreted based on the equipment’s configuration, refer to the SymbioTM 700 Controller with Odyssey Split Systems Applications Guide (ACC-APG001*-EN).

36

SS-SVX014A-EN

Maintenance
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
NOTICE
Operating Under Vacuum!
Failure to follow these instructions will result in compressor failure. Do not operate or apply power to the compressor while under a vacuum.
Perform all of the indicated maintenance procedures at the intervals scheduled. This will prolong the life of the unit and reduce the possibility of costly equipment failure.
Monthly
Conduct the following maintenance inspections once per month.
Check unit wiring to ensure all connections are tight and that the wiring insulation is intact.
Inspect the condenser coils for dirt and debris. If the coils appear dirty, clean them.
With the unit operating in the cooling mode, check the suction and discharge pressures and compare them with Pressure Curve values. Record these readings on the “Maintenance Log,” p. 38.
Annually (Cooling Season)
The following maintenance procedures must be performed at the beginning of each cooling season to ensure efficient unit operation.
Perform all of the monthly maintenance inspections.
With the unit operating, check unit superheat and record the reading in the “Maintenance Log,” p. 38.
Remove any accumulation of dust and/or dirt from the unit casing.
Remove corrosion from any surface and repaint. Check the gasket around the control panel door to ensure it
SS-SVX014A-EN

fits correctly and is in good condition to prevent water leakage.
Inspect the control panel wiring to ensure that all connections are tight and that the insulation is intact. Note: Condenser fan motors are permanently lubricated.
Check refrigerant piping and fittings for leaks
Inspect the condenser coils for dirt and debris. If the coils appear dirty, clean them.
Coil Cleaning
Regular coil maintenance, including annual cleaningenhances the unit’s operating efficiency by minimizing:
· compressor head pressure and amperage draw · water carryover · fan brake horsepower · static pressure losses
At least once each year — or more often if the unit is located in a “dirty” environment — clean the coil using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils.
Microchannel (MCHE) Coils
NOTICE
Coil Damage!
Failure to follow instructions below could result in coil damage. DO NOT use any detergents with microchannel condenser coils. Use pressurized water or air ONLY, with pressure no greater than 600psi. For additional information regarding the proper microchannel coil cleaning procedure, refer to RTSVB83*-EN
Due to the soft material and thin walls of the MCHE coils, the traditional field maintenance method recommended for Round Tube Plate Fin (RTPF) coils does not apply to microchannel coils. Moreover, chemical cleaners are a risk factor to MCHE due to the material of the coil. The manufacturer does not recommend the use of chemical cleaners to clean microchannel coils. Using chemical cleaners could lead to warranty claims being further evaluated for validity and failure analysis.
The recommended cleaning method for microchannel condenser coils is pressurized water or air with a nonpinpoint nozzle and an ECU of at least 180 with pressure no greater than 600 psi. To minimize the risk of coil damage, approach the cleaning of the coil with the pressure washer aimed perpendicular to the face of the coil during cleaning. Optimum clearance between the sprayer nozzle and the microchannel coil is 1-inch to 3-inch.
37

Maintenance
Maintenance Log

38

Date

Ambient Temp. (°F)

Evaporator Entering Air

Dry Bulb

Wet Bulb

Compressor

Suction Pressure

Discharge Pressure

(C1)

(C2)

(C1)

(C2)

Superheat (°F) (at compressor)

Subcooling (°F) (at liquid line)

Circuit #1

Circuit #2

Circuit #1

Circuit #2

SS-SVX014A-EN

Note: Perform each inspection once per month (during cooling season) while unit is operating.

Charging Data and Pressure Curves

Table 8. TTA Charging data and pressure curves

Condenser
TTA072KA TTA072KD TTA090KA TTA090KD TTA120KC TTA120KD TTA150KD TTA180KD TTA180KC TTA240KD TTA240KC TTA300KC

Air Handler
TWE090KA TWE072KB TWE090KA TWE090KB TWE120KA TWE120KB TWE150KB TWE180KB TWE180KB TWE240KB TWE240KB TWE300KB

Refrigerant Charging Curve Superheat and Charge Table
436768210001 436768220001 436768230001 436768240001 436768250001 436768260001 436768270001 436768280001 436768290001 436768300001 436768310001 436768320001

Pressure Curves
436768210001 436768410001 436768230001 436768420001 436768250001 436768430001 436768440001 436768280001 436768290001 436768300001 436768310001 436768320001

SS-SVX014A-EN

39

Wiring Diagram Matrix and Device Location

Table 9. TTA wiring diagrams

Part Number 1213-4781 1213-4782

Description
Power Schematic (Wiring Diagram) for units with Dual Compressors and Dual Fans
Power Schematic (Wiring Diagram) for units with Dual Compressors and Single Fans

1213-4780

Power Schematic (Wiring Diagram) for units with Single Compressors and Single Fan

1213-4765

Control Schematic (Wiring Diagram) for units with Single compressor and Single Fan

1213-4767

Control Schematic (Wiring Diagram) for units with Dual compressor and Single Fan

1213-4768 1213-4766

Control Schematic (Wiring Diagram) for units with Dual compressor and Dual Fans
Control Schematic (Wiring Diagram) for units with Single Compressor (Unloading) and Single Fan

1213-4769

Control Schematic (Wiring Diagram) for units with Dual compressor (Unloading) and Single Fan

1213-4770

Control Schematic (Wiring Diagram) for units with Dual compressor (Unloading) and Dual Fans

Applicability
All Units with Digit 4-6 = 180/240/300
All Units with Digit 4-6 = 072/090/120/150 and Digit 9 = C or D
All Units with Digit 4-6 = 072/090/120 and Digit 9 = A
All TTA Units with Digit 4-6 = 072/090/120 and Digit 9 = A All TTA Units with Digit 4-6 = 072/090/120/150 and Digit 9 = D, Digit 4-6 = 120, and Digit 9 = C All TTA Units with Digit 4-6 = 180/240/300 and Digit 9 = C or D
All TTA Units with Digit 4-6 = 090 and Digit 9 = A
All TTA Units with Digit 4-6 = 090/120/150 and Digit 9 = D
All TTA Units with Digit 4-6 = 240 and Digit 9 = D

Table 10. TTA device location

Part Number

Description

1213-4823

Device Location Print

1213-4824

Device Location Print

Applicability All TTA Units with Digit 4-6 = 072/090/120/150 All TTA Units with Digit 4-6 = 180/240/300

40

SS-SVX014A-EN

Warranty
For Commercial Unitary Equipment Rated 25 Tons and Under and Related Accessories
Products Covered — This warranty is extended by Trane, and applies to the following products:
· All packaged and split system air conditioners and heat pumps have a rated capacity of 25 tons and under.
· All packaged combinations gas/electric air conditioners having a rated capacity of 25 tons and under.
· All packaged combination gas/electric air conditioners having a rated capacity of 1.5 through 5 tons single phase electric power and used for commercial applications. (As used in this warranty, a commercial application is any application where the end purchaser uses the product for other than personal, family or household purposes.)
· All accessories for the above products which are sold by Trane and applied in accordance with Trane specifications.
Basic Warranty
The warrantor warrants for a period of twelve (12) months from the initial start-up or eighteen (18) months from date of shipment, whichever is sooner, that the products covered by this warranty (1) are free from defects in material and manufacture, and (2) have the capacities and ratings set forth in the warrantor’s catalogs and bulletins. If any part of your air conditioner fails because of a manufacturing defect, Warrantor will furnish without charge the required replacement part.
If the heat exchanger fails because of a manufacturing defect within five years from the date of start-up, Warrantor will furnish without charge a replacement heat exchanger. In addition, if the optional, factory installed, stainless steel heat exchanger fails because of a manufacturing defect within ten years from the date of start-up, Warrantor will furnish without charge a replacement heat exchanger.
Any local transportation, related service labor and diagnosis calls are not included. In addition, if the sealed motor-compressor fails because of a manufacturing defect within the second through fifth year from the date of original purchase, Warrantor will furnish without charge the required replacement compressor.
Exclusions and Limitations
The warrantor’s obligations and liabilities under this warranty are limited to furnishing F.O.B. factory or

warehouse at the warrantor-designated shipping point, freight allowed to Buyer’s city (or port of export for shipments outside the conterminous United States) a replacement product or, at the option of the warrantor, parts for the repair of the product not conforming to this warranty and which have been returned to the warrantor.
The warrantor’s warranty is conditional on the Customer providing written notice to the warrantor within thirty (30) days of the discovery of the defect. No product shall be returned to the warrantor without the warrantor’s written permission. No liability whatever shall attach to warrantor until said products have been fully paid for and then said liability shall be limited to the purchase price of the equipment shown to be defective.
The warranty does not apply to any compressor or gasfired heat exchanger which has been repaired or altered in such manner as, in the judgement of the warrantor, affects its stability or reliability. This warranty does not cover (1) any heat exchanger which has been fired with an improper type of fuel (2) a heat exchanger which is installed in a beauty parlor, dry cleaning establishment, de-greasing plant or in any corrosive atmosphere; or (3) any heat exchanger which is not shown to be defective by the warrantor’s inspection.
This warranty does not cover damage due to accident, abuse, improper use, external causes, freezing, corrosion, erosion or deterioration. Local transportation, related service labor, air filters, diagnosis calls, refrigerant and related items are not covered.
THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OR MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND ANY IMPLIED WARRANTIES OTHERWISE ARISING FROM THE COURSE OF DEALING OR TRADE. IN NO EVENT SHALL THE WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
The warrantor makes certain further warranty protection available on an optional, extra-cost basis. Any further warranty must be in writing. If you wish further help or information concerning this warranty, contact: Trane — Warrantor, 2701 Wilma Rudolph Blvd., Clarksville, TN 37040

SS-SVX014A-EN

41

Notes

42

SS-SVX014A-EN

Notes

SS-SVX014A-EN

43

Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.

Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

SS-SVX014A-EN 11 Aug 2024 Supersedes (New)

©2024