UPSONIC POWER CSC-A400 Communication Cards User Guide

September 5, 2024
UPSONIC POWER

CSC-A400 Communication Cards

“`html

Product Specifications

  • PCBA Size: 146.2601.6 mm
  • Connector for Dry contact (EK381V4L)
  • RJ45 Connector for RS232
  • Gold Finger for UPS Side

Product Usage Instructions

Packing the Card

The package includes a Dry contact Management Card, Screw, RJ45
to DB9 cable (for RS232), User Manual, Safety Cover, and
Carton.

Card Details

The card features the following components:

  1. PCBA Size: 146.2601.6 mm
  2. Connector for Dry contact (EK381V4L)
  3. RJ45 Connector for RS232
  4. Gold Finger for UPS Side

Interface Specifications

Segment Dry Contact Segment PIN NO Specification/Function Remark

Dry Contact Function

The Dry contact function allows users to configure output and
input signals based on specific segments. Refer to the user manual
for detailed instructions on setting up functions for each
segment.

RS232 Cable Wiring

Refer to Figure 3 for the wiring table of the RJ45 to DB9 cable
for RS232 connection.

Frequently Asked Questions (FAQ)

Q: What should I do if I need to send a UPS On command?

A: If you need to send a UPS On command, push down USER SW2 on
the AS400 Card.

Q: How can I configure the Dry Contact segments for specific

functions?

A: Refer to the Dry Contact Function section in the user manual
for instructions on configuring output signals for different
segments.

“`

Getting Started
This chapter explains: · Packing the card · Installation Checklist · Card defaults · INTERFACE (EK381V4L 14pin & RJ45) · Cable RJ45 TO DB9 (F) · INTERFACE (UPS side) · Dry contact Function · Configuring the Card Introduction
Packing the Card
– Dry contact Management Card – Screw – RJ45 to DB9 cable (for RS232, P/N 720-60679-00) – USER MANUAL – Safety Cover – Carton

User’s Guide

Figure 1. Dry contact Management Card Package Contents 1

Card Details

(1)

(2)

(3)

Figure 2. Component distribution
PCBA Size: 146.2601.6 mm (1) EK381V4L Connector for Dry contact (2) RJ45 Connector for RS232 (3) Gold Finger for UPS Side
2

INTERFACE (EK381V4L 14pin & RJ45)

Segment Dry contact Segment 1 Segment 2 Segment 3 Segment 4 Segment 5 Segment 6
Segment 7
Segment 8

PIN NO

Specification/Function

remark

Pin 9 & Pin 2 240Vac/1A(Max) or 30Vdc/1A(Max) Pin 10 & Pin 3 240Vac/1A(Max) or 30Vdc/1A(Max) Pin 11 & Pin 4 240Vac/1A(Max) or 30Vdc/1A(Max) Pin 12 & Pin 5 240Vac/1A(Max) or 30Vdc/1A(Max) Pin 13 & Pin 6 240Vac/1A(Max) or 30Vdc/1A(Max) Pin 8 & Pin1 NA
Pin 14 & Pin1 NA
Pin 7 & Pin1 NA

Output signal , NO or NC Output signal , NO or NC Output signal , NO or NC Output signal , NO or NC Output signal , NO or NC Input signal (The external contact must be closed between pin8&pin1) Input signal (The external contact must be closed between pin14&pin1) Input signal (The external contact must be closed between pin7&pin1)

RS232 (CABLE RJ45 TO DB9F)

TXD2

RJ45, Pin 3

RXD2

RJ45, Pin 6

GND

RJ45, Pin 4

12Vdc 3mA (Max) 12Vdc 5mA (Max) GND

Power system GND

The crossed-out wheeled bin symbol indicates that waste electrical and electronic equipment should not be discarded together with unseparated household waste, but must be collected separately. The product should be handed in for recycling in accordance with the local environmental regulations for waste disposal. By separating waste electrical and electronic equipment , you will help reduce the volume of waste sent for incineration or land-fills and minimize any potential negative impact on human health and environment.

Segment illustration: 3

USER SW2

USER SW1

AS400 CARD

PIN14 PIN13 PIN12 PIN11 PIN10 PIN9 PIN8
Internal relay

PIN7

PIN6

PIN5

PIN4

PIN3

PIN2

PIN1 GND

USER SW3

Note: Segment 7 (PIN14 & PIN1 / USER SW2) is fixed to UPS On function. Segment 8 (PIN7 & PIN1 / USER SW3) is fixed to UPS Off function. (Refer to Dry contact Function Section at next page of this document) We Suggest User do not push down USER SW2 and SW3 at the same time.
If user pushes down USER SW2, AS400 Card will send a UPS On command to UPS. If user pushes down USER SW3, AS400 Card will send a UPS Off command to UPS. If USER SW2 and SW3 pushed down at the same time, AS400 Card will first send UPS On command to UPS, then send UPS Off command to UPS. And the UPS always follow the last command.

CABLE RJ45 TO DB9 (F)

WIRING TABLE

RJ45

DB9

3

——————

2

4

——————

5

6

——————

3

4

Figure 3. RS232 Cable

INTERFACE (UPS side)
Item Pin Assignment
– Pin 1 – Pin 2 – Pin 3 – Pin 4 – Pin 5 – Pin 6 – Pin 7 – Pin 8 – Pin 9 – Pin 10 – Pin 11~26

Specification/Function
GND SNMPPOW RXDUPS TXDUPS UNUSED UNUSED -VCC SNMPSIG GND +VCC RESERVE

Dry contact Function:
Output signals (Segment 1~5): User can choose one function for a Segment from below table. *Output signal (Segment 1~5):

Description

Meaning

“1”

Utility Fail

Fail

Battery Low

Battery Low

General Alarm

Alarm

Bypass Status (Online UPS)

Bypass Active

Or

Or

AVR Status (Offline/LIA UPS) AVR Active

Summary Alarm

Alarm

Battery Testing

In test mode

Shutdown Processing

UPS Shutdown

Over Load Warning

Over Load

“0” Normal Normal Normal Not Bypass Status Or Not AVR Status Normal Not test mode Normal Normal

5

Input signals (Segment 6): User can choose one function for a Segment from below table. *Input signal (Segment 6):

Meaning Battery mode shutdown
Any mode shutdown Emergency power off
Remote On/Off

Description “1”
Only Battery mode shutdown Shutdown OFF OFF

“0” Normal
Normal Normal
ON

Input signals (Segment 7): Segment 7 is fixed to UPS On function. *Input signal (Segment 7):

Meaning UPS On

Description “1”
ON

“0” Normal

Input signals (Segment 8): Segment 8 is fixed to UPS Off function. *Input signal (Segment 8):

Meaning UPS Off

Description “1”
OFF

“0” Normal

Configuring the Card Introduction
1. General
This document specifies the Serial communication protocol of the Dry contact Management Card. The card provided the following features.
(1) Get UPS internal information by SCI protocol (2) Bridge communication data between PC and ups (3) Configure five output relay signal (4) Configure one input signal for shutdown ups or remote on/off (5) Configure Dry contact normal open and normal close status (6) Configure Dry contact function definition (7) Configure Dry contact active delay time

6

2. Definitions
2.1. Common items (1) Computer (Software) has Initiative for communicate by this protocol. Computer will send command ended with . Dry contact Management Card will respond the information of ended with Note : means ASCII code “Carriage Return” (HEX-code 0D). (2) All the information is provided in ASCII format. (3) Communication start timing Dry contact Management Card should be received the command from PC, and send the right response to PC.

2.2. Serial Data format Dry contact Management Card data will be provided at 2400 baud rate and consist of 1 start bit, 8 data bits, no parity, and 1 stop bit.

BAUD RATE: 2400 band

DATA LENGTH: 8 bits

STOP BIT:

1 bit

PARITY:

NONE

Data format figure:

Start b0

b1

b2

b3

b4

b5

b6

b7

Stop

7

3. Installing
3.1. Installing the Card The Dry contact Management Card can be installed in UPS equipped with a communication bay without turning off the UPS or disconnecting the load. To install the Dry contact Management Card: 1. Remove the communication bay cover from the UPS. Retain the screws. 2. To prevent electrostatic discharge (ESD), place one hand on a metal surface. 3. Slide the card into the open slot and secure with the screws removed in Step 1
Figure4. Installing the Card 3.2.Connecting the Card
To connect the card to the computer and start the configuration: 1. Plug the RJ-45 end of the supplied serial cable into the Settings port on the card 2. Plug the other end of the serial cable into the serial COM port on the computer.
Figure5. Connecting the Card 8

3.3.Configuring the Card To configure the card: 1. Verify that the serial cable (supplied) is connected to the card’s Settings port and the computer’s COM port. 2. Open your terminal emulation program (such as HyperTerminal). a. StartAll ProgramsAccessoriesCommunicationsHyper Terminal
Or type HYPERTRM in Windows OS Run Dialog
b. Name the new connection
Figure6. Hyper Terminal 9

3. Select the serial connection (such as COM1).
Figure7. Select the serial connection 4. Set the serial line to 2400 baud, 8 data bits, No parity, 1 stop bit, no flow control.
Figure8. Configuring Port Settings 10

5. Set the PropertiesSettingsASCII Setup.
Figure9. Set the Properties
4. Setting operation menu
4.1. Password menu Type continuity 3 times, the password menu displays as below
Enter Password to Activate Maintenance Menu: Figure10. Password menu
Enter admin. The main menu displays (see Figure 12). If password incorrect, the menu will prompt enter correct password as below, until type correctly password, the menu will change to main menu
Password Error Please Enter Correct Password:
Figure11. Password incorrect menu 11

4.2. Main menu There are six item can be setting or inquire firmware version, user need base on menu number and enter the correct menu
—————————————————————————-Dry contact Management Card —————————————————————————–
1. Function Segment Logic 2. Output Segment Function Configure 3. Input Segment Function Configure 4. Function Segment Active Delay Time 5. Return to Default Configuration 6. Firmware Version 0. Exit —————————————————————————–
Please Enter Number:
Figure12. Main menu Type any list number then will change to 4.3~4.9 menu, if user enter number not include of list, the window will show “Please Enter Correct Number:” string as below, this menu will possible show in any setting menu, if user do not depend on prompt number and enter a wrong number
Please Enter Correct Number:
Figure13. Un-correct number prompt menu
4.3. Function Segment Logic menu When main menu Type 1 and press Enter. The menu displays the Segment settings logic and current setting status as below, in this menu type 0 number, the menu will return to Figure12. Main menu.
12

—————————————————————————-Function Segment Logic —————————————————————————–
1. Segment 1 Logic, Current Setting(Normal Open) 2. Segment 2 Logic, Current Setting(Normal Open) 3. Segment 3 Logic, Current Setting(Normal Open) 4. Segment 4 Logic, Current Setting(Normal Open) 5. Segment 5 Logic, Current Setting(Normal Open) 6. Segment 6 Logic, Current Setting(Normal Open) 7. Segment 7 Logic, Current Setting(Normal Open) 8. Segment 8 Logic, Current Setting(Normal Open) 0. Exit —————————————————————————–
Please Enter Number:
Figure14. Logic Segment select menu Segment 1 ~ Segment 5 for output signal logic setting, and Segment 6 ~ Segment 8 for input signal logic setting, user can setting “Normal Open” and “Normal Close” type, the default setting is “Normal Open”
When Figure14. Logic Segment select menu Type 1~6 and press Enter. The menu displays Logic select menu as below, in this menu select any list number, the menu will return to Figure14. Logic Segment select menu
—————————————————————————-Segment 1 Logic —————————————————————————–
1. Normal Open 2. Normal Close 0. Exit —————————————————————————–
Please Enter Number:
Figure15. Logic select menu
13

4.4. Output Segment Function Configure menu
When main menu Type 2 and press Enter. The menu displays the Output Segment Function Configure and current setting status as below, in this menu type 0, the menu will return to Figure12. Main menu
—————————————————————————-Output Segment Function Configure —————————————————————————–
1. Segment 1 function, Current Setting(Utility Failure) 2. Segment 2 function, Current Setting(Battery Low) 3. Segment 3 function, Current Setting(General Alarm) 4. Segment 4 function, Current Setting(Bypass Status) 5. Segment 5 function, Current Setting(Summary Alarm) 0. Exit —————————————————————————–
Please Enter Number:
Figure16. Output Segment select menu Default of each Segment 1. Segment 1 function default is Utility Failure 2. Segment 2 function default is Battery Low 3. Segment 3 function default is General Alarm 4. Segment 4 function default is Bypass Status 5. Segment 5 function default is Summary Alarm
When Figure16. Output Segment select menu Type 1~5 and press Enter. The menu displays output function select menu as below, in this menu select any list number, the menu will return to Figure16. Output Segment select menu
—————————————————————————-Segment 1 Function —————————————————————————–
1. Utility Failure 2. Battery Low 3. General Alarm 4. Bypass Status 5. Summary Alarm 6. Battery Testing 7. Shutdown Processing 8. Over Load Warning 9. UPS On 0. Exit —————————————————————————–
Please Enter Number:
Figure17. Output function select menu
14

Function description: 1. Utility Failure: UPS input mains voltage or frequency out of range 2. Battery Low: UPS Battery voltage level is low 3. General Alarm: UPS fail condition 4. Bypass Status: UPS under Bypass mode 5. Summary Alarm: Any one of AS400 “Utility Failure”, “General Alarm”, “Bypass”, “Battery Low”,
“Over Load Warning” active will send this signal 6. Battery Testing: Battery Testing is in progress 7. Shutdown Processing: UPS doing shutdown after received shutdown command via
communication port 8. Over Load Warning: UPS load over spec definition over load warning level 9. UPS On: The UPS is powered on and is capable of providing power to the system (whether
utility power is available or not).
4.5. Input Segment Function Configure menu
When main menu Type 3 and press Enter. The menu displays the Input Segment Function Configure and current setting status as below, in this menu type 0, the menu will return to Figure12. Main menu
—————————————————————————-Input Segment Function Configure —————————————————————————–
1. Segment 6 function, Current Setting(Battery Mode Shutdown) 2. Segment 7 function, Current Setting(UPS On) 3. Segment 8 function, Current Setting(UPS Off) 0. Exit —————————————————————————–
Please Enter Number:
Figure18. Input Segment select menu
Default of each Segment 1. Segment 6 function default is Battery Mode Shutdown 2. Segment 7 function default is UPS On 3. Segment 8 function default is UPS Off Segment 6 function can be configured. Segment 7 and 8 function is fixed to its default function.
When Figure18. Input Segment select menu Type 1 and press Enter. The menu displays input function select menu as below, in this menu select any list number, the menu will return to Figure18. Input Segment select menu
15

—————————————————————————-Segment 6 Function —————————————————————————–
1. Battery Mode Shutdown 2. Any Mode Shutdown 3. Emergency Power Off 4. Remote On/Off 0. Exit —————————————————————————–
Please Enter Number:
Figure19. Input function select menu Function description: 1. Battery Mode Shutdown: If Signal is active and UPS is under bat mode, UPS will cutoff output 2. Any Mode Shutdown: If Signal is active and UPS is under any mode, UPS will cutoff output 3. Emergency Power Off: If Signal is active and UPS is under any mode, UPS will cutoff output,
give out EPO warning, and pressing any button on UPS LCD panel can not turn on UPS 4. Remote On/Off: If Signal is active (close Pin 8 & Pin1 when Segment 6 is configured to Normal Open; or open Pin 8 & Pin1 when Segment 6 is configured to Normal Close ) and UPS is under any mode, UPS will cutoff output. If Signal is not active (open Pin 8 & Pin1 when Segment 6 is configured to Normal Open; or close Pin 8 & Pin1 when Segment 6 is configured to Normal Close ) and UPS is under any mode, UPS will turn on. When Figure18. Input Segment select menu Type 2 or 3 and press Enter, it will reject the number because Segment 7 or 8 function is fixed. User only can type 1 to set Segment 6 function. If user type 0, the menu will return to Figure12. Main menu
This Segment Function can not be set.
Please Enter a Number again:
Figure20. Segment function can not be set
4.6. Function Segment Active Delay Time menu When main menu Type 4 and press Enter. The menu displays the Function Segment Active Delay Time and current setting value as below, in this menu type 0, the menu will return to Figure12. Main menu 16

—————————————————————————-Function Segment Active Delay Time —————————————————————————–
1. Segment 1 Active Delay Time, Current Setting(Immediately) 2. Segment 2 Active Delay Time, Current Setting(Immediately) 3. Segment 3 Active Delay Time, Current Setting(Immediately) 4. Segment 4 Active Delay Time, Current Setting(Immediately) 5. Segment 5 Active Delay Time, Current Setting(Immediately) 6. Segment 6 Active Delay Time, Current Setting(Immediately) 0. Exit —————————————————————————–
Please Enter Number:
Figure21. Active delay time Segment select menu Default of each Segment Every Segment default is immediately, enter 00 is means immediately Type 00 and press Enter means active Immediately, and type 01 and press Enter means active will delay one second, only type one character and press Enter is illegal command, only press Enter means user do not want to change the setting parameter and menu will return to Figure21. Active delay time Segment select menu
—————————————————————————-Segment 1 Active Delay Time —————————————————————————-Please Enter Delay Time 00~99, Only Press Means Abort and Exit Current Setting
Please Enter Delay Time:
Figure22. Active delay time menu 4.7. Return to Default Configuration menu
When main menu Type 5 and press Enter. The menu displays the Return to Default Configuration as below
Return to Default(Y/N)?:
Figure23. Default confirm menu
17

Enter Y or y. below menu will display as below, if enter any other character, the only main menu displays (see Figure 12) and not show “Default All Configuration Parameter” string and do not change to default value
Default All Configuration Parameter
—————————————————————————-Dry contact Management Card —————————————————————————–
1. Function Segment Logic 2. Output Segment Function Configure 3. Input Segment Function Configure 4. Function Segment Active Delay Time 5. Return to Default Configuration 6. Firmware Version 0. Exit —————————————————————————–
Please Enter Number:
Figure24. Default all configuration parameter success menu 4.8. Firmware Version menu
When main menu Type 6 and press Enter. The menu displays the Firmware Version and development data as below, in this menu type 0, the menu will return to Figure12. Main menu
—————————————————————————-Firmware Version —————————————————————————–
Firmware Version:00.05 2010/06/01 0. Exit —————————————————————————–
Please Enter Number:
Figure25. Firmware version menu
4.9. Exit menu
When main menu Type 0 and press Enter. The menu displays the Exit setting mode information as below
18

—————————————————————————-Exit —————————————————————————–
1. Exit and Save 2. Exit and Without Save 0. Not Exit —————————————————————————-Please Enter Number:
Figure26. Exit and save select menu Type 1 and press Enter means exit setting mode and Save change data, the menu string will as below
Exit Setting Mode and Save Data Figure27. Exit and Save menu
Type 2 and press Enter means exit setting mode and without save change data, the menu string will as below
Exit Setting Mode and Without Save Data Figure28. Exit and Without Save menu
Type 0 and press Enter means still stay on setting mode, the menu will return to Figure12. Main menu
19

614-09976-01 20

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals