UPSONIC POWER CSC-A400 Communication Cards User Guide
- September 5, 2024
- UPSONIC POWER
Table of Contents
CSC-A400 Communication Cards
“`html
Product Specifications
- PCBA Size: 146.2601.6 mm
- Connector for Dry contact (EK381V4L)
- RJ45 Connector for RS232
- Gold Finger for UPS Side
Product Usage Instructions
Packing the Card
The package includes a Dry contact Management Card, Screw, RJ45
to DB9 cable (for RS232), User Manual, Safety Cover, and
Carton.
Card Details
The card features the following components:
- PCBA Size: 146.2601.6 mm
- Connector for Dry contact (EK381V4L)
- RJ45 Connector for RS232
- Gold Finger for UPS Side
Interface Specifications
Segment | Dry Contact Segment | PIN NO | Specification/Function | Remark |
---|
Dry Contact Function
The Dry contact function allows users to configure output and
input signals based on specific segments. Refer to the user manual
for detailed instructions on setting up functions for each
segment.
RS232 Cable Wiring
Refer to Figure 3 for the wiring table of the RJ45 to DB9 cable
for RS232 connection.
Frequently Asked Questions (FAQ)
Q: What should I do if I need to send a UPS On command?
A: If you need to send a UPS On command, push down USER SW2 on
the AS400 Card.
Q: How can I configure the Dry Contact segments for specific
functions?
A: Refer to the Dry Contact Function section in the user manual
for instructions on configuring output signals for different
segments.
“`
Getting Started
This chapter explains: · Packing the card · Installation Checklist · Card
defaults · INTERFACE (EK381V4L 14pin & RJ45) · Cable RJ45 TO DB9 (F) ·
INTERFACE (UPS side) · Dry contact Function · Configuring the Card
Introduction
Packing the Card
– Dry contact Management Card – Screw – RJ45 to DB9 cable (for RS232, P/N
720-60679-00) – USER MANUAL – Safety Cover – Carton
User’s Guide
Figure 1. Dry contact Management Card Package Contents 1
Card Details
(1)
(2)
(3)
Figure 2. Component distribution
PCBA Size: 146.2601.6 mm (1) EK381V4L Connector for Dry contact (2) RJ45
Connector for RS232 (3) Gold Finger for UPS Side
2
INTERFACE (EK381V4L 14pin & RJ45)
Segment Dry contact Segment 1 Segment 2 Segment 3 Segment 4 Segment 5 Segment
6
Segment 7
Segment 8
PIN NO
Specification/Function
remark
Pin 9 & Pin 2 240Vac/1A(Max) or 30Vdc/1A(Max) Pin 10 & Pin 3 240Vac/1A(Max) or
30Vdc/1A(Max) Pin 11 & Pin 4 240Vac/1A(Max) or 30Vdc/1A(Max) Pin 12 & Pin 5
240Vac/1A(Max) or 30Vdc/1A(Max) Pin 13 & Pin 6 240Vac/1A(Max) or 30Vdc/1A(Max)
Pin 8 & Pin1 NA
Pin 14 & Pin1 NA
Pin 7 & Pin1 NA
Output signal , NO or NC Output signal , NO or NC Output signal , NO or NC Output signal , NO or NC Output signal , NO or NC Input signal (The external contact must be closed between pin8&pin1) Input signal (The external contact must be closed between pin14&pin1) Input signal (The external contact must be closed between pin7&pin1)
RS232 (CABLE RJ45 TO DB9F)
TXD2
RJ45, Pin 3
RXD2
RJ45, Pin 6
GND
RJ45, Pin 4
12Vdc 3mA (Max) 12Vdc 5mA (Max) GND
Power system GND
The crossed-out wheeled bin symbol indicates that waste electrical and electronic equipment should not be discarded together with unseparated household waste, but must be collected separately. The product should be handed in for recycling in accordance with the local environmental regulations for waste disposal. By separating waste electrical and electronic equipment , you will help reduce the volume of waste sent for incineration or land-fills and minimize any potential negative impact on human health and environment.
Segment illustration: 3
USER SW2
USER SW1
AS400 CARD
PIN14 PIN13 PIN12 PIN11 PIN10 PIN9 PIN8
Internal relay
PIN7
PIN6
PIN5
PIN4
PIN3
PIN2
PIN1 GND
USER SW3
Note: Segment 7 (PIN14 & PIN1 / USER SW2) is fixed to UPS On function. Segment
8 (PIN7 & PIN1 / USER SW3) is fixed to UPS Off function. (Refer to Dry contact
Function Section at next page of this document) We Suggest User do not push
down USER SW2 and SW3 at the same time.
If user pushes down USER SW2, AS400 Card will send a UPS On command to UPS. If
user pushes down USER SW3, AS400 Card will send a UPS Off command to UPS. If
USER SW2 and SW3 pushed down at the same time, AS400 Card will first send UPS
On command to UPS, then send UPS Off command to UPS. And the UPS always follow
the last command.
CABLE RJ45 TO DB9 (F)
WIRING TABLE
RJ45
DB9
3
——————
2
4
——————
5
6
——————
3
4
Figure 3. RS232 Cable
INTERFACE (UPS side)
Item Pin Assignment
– Pin 1 – Pin 2 – Pin 3 – Pin 4 – Pin 5 – Pin 6 – Pin 7 – Pin 8 – Pin 9 – Pin
10 – Pin 11~26
Specification/Function
GND SNMPPOW RXDUPS TXDUPS UNUSED UNUSED -VCC SNMPSIG GND +VCC RESERVE
Dry contact Function:
Output signals (Segment 1~5): User can choose one function for a Segment from
below table. *Output signal (Segment 1~5):
Description
Meaning
“1”
Utility Fail
Fail
Battery Low
Battery Low
General Alarm
Alarm
Bypass Status (Online UPS)
Bypass Active
Or
Or
AVR Status (Offline/LIA UPS) AVR Active
Summary Alarm
Alarm
Battery Testing
In test mode
Shutdown Processing
UPS Shutdown
Over Load Warning
Over Load
“0” Normal Normal Normal Not Bypass Status Or Not AVR Status Normal Not test mode Normal Normal
5
Input signals (Segment 6): User can choose one function for a Segment from below table. *Input signal (Segment 6):
Meaning Battery mode shutdown
Any mode shutdown Emergency power off
Remote On/Off
Description “1”
Only Battery mode shutdown Shutdown OFF OFF
“0” Normal
Normal Normal
ON
Input signals (Segment 7): Segment 7 is fixed to UPS On function. *Input signal (Segment 7):
Meaning UPS On
Description “1”
ON
“0” Normal
Input signals (Segment 8): Segment 8 is fixed to UPS Off function. *Input signal (Segment 8):
Meaning UPS Off
Description “1”
OFF
“0” Normal
Configuring the Card Introduction
1. General
This document specifies the Serial communication protocol of the Dry contact
Management Card. The card provided the following features.
(1) Get UPS internal information by SCI protocol (2) Bridge communication data
between PC and ups (3) Configure five output relay signal (4) Configure one
input signal for shutdown ups or remote on/off (5) Configure Dry contact
normal open and normal close status (6) Configure Dry contact function
definition (7) Configure Dry contact active delay time
6
2. Definitions
2.1. Common items (1) Computer (Software) has Initiative for communicate by
this protocol. Computer will send command ended with
2.2. Serial Data format Dry contact Management Card data will be provided at 2400 baud rate and consist of 1 start bit, 8 data bits, no parity, and 1 stop bit.
BAUD RATE: 2400 band
DATA LENGTH: 8 bits
STOP BIT:
1 bit
PARITY:
NONE
Data format figure:
Start b0
b1
b2
b3
b4
b5
b6
b7
Stop
7
3. Installing
3.1. Installing the Card The Dry contact Management Card can be installed in
UPS equipped with a communication bay without turning off the UPS or
disconnecting the load. To install the Dry contact Management Card: 1. Remove
the communication bay cover from the UPS. Retain the screws. 2. To prevent
electrostatic discharge (ESD), place one hand on a metal surface. 3. Slide the
card into the open slot and secure with the screws removed in Step 1
Figure4. Installing the Card 3.2.Connecting the Card
To connect the card to the computer and start the configuration: 1. Plug the
RJ-45 end of the supplied serial cable into the Settings port on the card 2.
Plug the other end of the serial cable into the serial COM port on the
computer.
Figure5. Connecting the Card 8
3.3.Configuring the Card To configure the card: 1. Verify that the serial
cable (supplied) is connected to the card’s Settings port and the computer’s
COM port. 2. Open your terminal emulation program (such as HyperTerminal). a.
StartAll ProgramsAccessoriesCommunicationsHyper Terminal
Or type HYPERTRM in Windows OS Run Dialog
b. Name the new connection
Figure6. Hyper Terminal 9
3. Select the serial connection (such as COM1).
Figure7. Select the serial connection 4. Set the serial line to 2400 baud, 8
data bits, No parity, 1 stop bit, no flow control.
Figure8. Configuring Port Settings 10
5. Set the PropertiesSettingsASCII Setup.
Figure9. Set the Properties
4. Setting operation menu
4.1. Password menu Type
Enter Password to Activate Maintenance Menu: Figure10. Password menu
Enter admin. The main menu displays (see Figure 12). If password incorrect,
the menu will prompt enter correct password as below, until type correctly
password, the menu will change to main menu
Password Error Please Enter Correct Password:
Figure11. Password incorrect menu 11
4.2. Main menu There are six item can be setting or inquire firmware version,
user need base on menu number and enter the correct menu
—————————————————————————-Dry contact Management Card
—————————————————————————–
1. Function Segment Logic 2. Output Segment Function Configure 3. Input
Segment Function Configure 4. Function Segment Active Delay Time 5. Return to
Default Configuration 6. Firmware Version 0. Exit —————————————————————————–
Please Enter Number:
Figure12. Main menu Type any list number then will change to 4.3~4.9 menu, if
user enter number not include of list, the window will show “Please Enter
Correct Number:” string as below, this menu will possible show in any setting
menu, if user do not depend on prompt number and enter a wrong number
Please Enter Correct Number:
Figure13. Un-correct number prompt menu
4.3. Function Segment Logic menu When main menu Type 1 and press Enter. The
menu displays the Segment settings logic and current setting status as below,
in this menu type 0 number, the menu will return to Figure12. Main menu.
12
—————————————————————————-Function Segment Logic —————————————————————————–
1. Segment 1 Logic, Current Setting(Normal Open) 2. Segment 2 Logic, Current
Setting(Normal Open) 3. Segment 3 Logic, Current Setting(Normal Open) 4.
Segment 4 Logic, Current Setting(Normal Open) 5. Segment 5 Logic, Current
Setting(Normal Open) 6. Segment 6 Logic, Current Setting(Normal Open) 7.
Segment 7 Logic, Current Setting(Normal Open) 8. Segment 8 Logic, Current
Setting(Normal Open) 0. Exit —————————————————————————–
Please Enter Number:
Figure14. Logic Segment select menu Segment 1 ~ Segment 5 for output signal
logic setting, and Segment 6 ~ Segment 8 for input signal logic setting, user
can setting “Normal Open” and “Normal Close” type, the default setting is
“Normal Open”
When Figure14. Logic Segment select menu Type 1~6 and press Enter. The menu
displays Logic select menu as below, in this menu select any list number, the
menu will return to Figure14. Logic Segment select menu
—————————————————————————-Segment 1 Logic —————————————————————————–
1. Normal Open 2. Normal Close 0. Exit —————————————————————————–
Please Enter Number:
Figure15. Logic select menu
13
4.4. Output Segment Function Configure menu
When main menu Type 2 and press Enter. The menu displays the Output Segment
Function Configure and current setting status as below, in this menu type 0,
the menu will return to Figure12. Main menu
—————————————————————————-Output Segment Function Configure
—————————————————————————–
1. Segment 1 function, Current Setting(Utility Failure) 2. Segment 2
function, Current Setting(Battery Low) 3. Segment 3 function, Current
Setting(General Alarm) 4. Segment 4 function, Current Setting(Bypass Status)
5. Segment 5 function, Current Setting(Summary Alarm) 0. Exit
—————————————————————————–
Please Enter Number:
Figure16. Output Segment select menu Default of each Segment 1. Segment 1
function default is Utility Failure 2. Segment 2 function default is Battery
Low 3. Segment 3 function default is General Alarm 4. Segment 4 function
default is Bypass Status 5. Segment 5 function default is Summary Alarm
When Figure16. Output Segment select menu Type 1~5 and press Enter. The menu
displays output function select menu as below, in this menu select any list
number, the menu will return to Figure16. Output Segment select menu
—————————————————————————-Segment 1 Function —————————————————————————–
1. Utility Failure 2. Battery Low 3. General Alarm 4. Bypass Status 5.
Summary Alarm 6. Battery Testing 7. Shutdown Processing 8. Over Load Warning
9. UPS On 0. Exit —————————————————————————–
Please Enter Number:
Figure17. Output function select menu
14
Function description: 1. Utility Failure: UPS input mains voltage or frequency
out of range 2. Battery Low: UPS Battery voltage level is low 3. General
Alarm: UPS fail condition 4. Bypass Status: UPS under Bypass mode 5. Summary
Alarm: Any one of AS400 “Utility Failure”, “General Alarm”, “Bypass”, “Battery
Low”,
“Over Load Warning” active will send this signal 6. Battery Testing: Battery
Testing is in progress 7. Shutdown Processing: UPS doing shutdown after
received shutdown command via
communication port 8. Over Load Warning: UPS load over spec definition over
load warning level 9. UPS On: The UPS is powered on and is capable of
providing power to the system (whether
utility power is available or not).
4.5. Input Segment Function Configure menu
When main menu Type 3 and press Enter. The menu displays the Input Segment
Function Configure and current setting status as below, in this menu type 0,
the menu will return to Figure12. Main menu
—————————————————————————-Input Segment Function Configure
—————————————————————————–
1. Segment 6 function, Current Setting(Battery Mode Shutdown) 2. Segment 7
function, Current Setting(UPS On) 3. Segment 8 function, Current Setting(UPS
Off) 0. Exit —————————————————————————–
Please Enter Number:
Figure18. Input Segment select menu
Default of each Segment 1. Segment 6 function default is Battery Mode Shutdown
2. Segment 7 function default is UPS On 3. Segment 8 function default is UPS
Off Segment 6 function can be configured. Segment 7 and 8 function is fixed to
its default function.
When Figure18. Input Segment select menu Type 1 and press Enter. The menu
displays input function select menu as below, in this menu select any list
number, the menu will return to Figure18. Input Segment select menu
15
—————————————————————————-Segment 6 Function —————————————————————————–
1. Battery Mode Shutdown 2. Any Mode Shutdown 3. Emergency Power Off 4.
Remote On/Off 0. Exit —————————————————————————–
Please Enter Number:
Figure19. Input function select menu Function description: 1. Battery Mode
Shutdown: If Signal is active and UPS is under bat mode, UPS will cutoff
output 2. Any Mode Shutdown: If Signal is active and UPS is under any mode,
UPS will cutoff output 3. Emergency Power Off: If Signal is active and UPS is
under any mode, UPS will cutoff output,
give out EPO warning, and pressing any button on UPS LCD panel can not turn on
UPS 4. Remote On/Off: If Signal is active (close Pin 8 & Pin1 when Segment 6
is configured to Normal Open; or open Pin 8 & Pin1 when Segment 6 is
configured to Normal Close ) and UPS is under any mode, UPS will cutoff
output. If Signal is not active (open Pin 8 & Pin1 when Segment 6 is
configured to Normal Open; or close Pin 8 & Pin1 when Segment 6 is configured
to Normal Close ) and UPS is under any mode, UPS will turn on. When Figure18.
Input Segment select menu Type 2 or 3 and press Enter, it will reject the
number because Segment 7 or 8 function is fixed. User only can type 1 to set
Segment 6 function. If user type 0, the menu will return to Figure12. Main
menu
This Segment Function can not be set.
Please Enter a Number again:
Figure20. Segment function can not be set
4.6. Function Segment Active Delay Time menu When main menu Type 4 and press
Enter. The menu displays the Function Segment Active Delay Time and current
setting value as below, in this menu type 0, the menu will return to Figure12.
Main menu 16
—————————————————————————-Function Segment Active Delay Time
—————————————————————————–
1. Segment 1 Active Delay Time, Current Setting(Immediately) 2. Segment 2
Active Delay Time, Current Setting(Immediately) 3. Segment 3 Active Delay
Time, Current Setting(Immediately) 4. Segment 4 Active Delay Time, Current
Setting(Immediately) 5. Segment 5 Active Delay Time, Current
Setting(Immediately) 6. Segment 6 Active Delay Time, Current
Setting(Immediately) 0. Exit —————————————————————————–
Please Enter Number:
Figure21. Active delay time Segment select menu Default of each Segment Every
Segment default is immediately, enter 00 is means immediately Type 00 and
press Enter means active Immediately, and type 01 and press Enter means active
will delay one second, only type one character and press Enter is illegal
command, only press Enter means user do not want to change the setting
parameter and menu will return to Figure21. Active delay time Segment select
menu
—————————————————————————-Segment 1 Active Delay Time
—————————————————————————-Please Enter Delay Time 00~99, Only Press
Please Enter Delay Time:
Figure22. Active delay time menu 4.7. Return to Default Configuration menu
When main menu Type 5 and press Enter. The menu displays the Return to Default
Configuration as below
Return to Default(Y/N)?:
Figure23. Default confirm menu
17
Enter Y or y. below menu will display as below, if enter any other character,
the only main menu displays (see Figure 12) and not show “Default All
Configuration Parameter” string and do not change to default value
Default All Configuration Parameter
—————————————————————————-Dry contact Management Card
—————————————————————————–
1. Function Segment Logic 2. Output Segment Function Configure 3. Input
Segment Function Configure 4. Function Segment Active Delay Time 5. Return to
Default Configuration 6. Firmware Version 0. Exit —————————————————————————–
Please Enter Number:
Figure24. Default all configuration parameter success menu 4.8. Firmware
Version menu
When main menu Type 6 and press Enter. The menu displays the Firmware Version
and development data as below, in this menu type 0, the menu will return to
Figure12. Main menu
—————————————————————————-Firmware Version —————————————————————————–
Firmware Version:00.05 2010/06/01 0. Exit —————————————————————————–
Please Enter Number:
Figure25. Firmware version menu
4.9. Exit menu
When main menu Type 0 and press Enter. The menu displays the Exit setting mode
information as below
18
—————————————————————————-Exit —————————————————————————–
1. Exit and Save 2. Exit and Without Save 0. Not Exit
—————————————————————————-Please Enter Number:
Figure26. Exit and save select menu Type 1 and press Enter means exit setting
mode and Save change data, the menu string will as below
Exit Setting Mode and Save Data Figure27. Exit and Save menu
Type 2 and press Enter means exit setting mode and without save change data,
the menu string will as below
Exit Setting Mode and Without Save Data Figure28. Exit and Without Save menu
Type 0 and press Enter means still stay on setting mode, the menu will return
to Figure12. Main menu
19
614-09976-01 20
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>