LUMINOR BLACKCOMB 5.1 UV Water Purification System Instructions
- June 9, 2024
- LUMINOR
Table of Contents
BLACKCOMB 5.1 UV Water Purification
System Instructions
Operation & Installation Instructions
NSF/ANSI Standard 55 Class A
**System Tested and Certified by NSF
International against CSA B483.1 and NSF/ANSI 55 for Disinfection
Performance, Class A
System| Rated Flow| System| Rated Flow
LB6-02XA| 1.6 gym| LBH6-05XA| 2.2 gym
LB6-03XA| 2.2 gym| LBH6-10XA| 4.1 gym
LB6-06XA| 3.4 gym| LBH6-15XA| 5.4 gym
LB6-10XA| 6.3 gym| LBH6-25XA| 7.9 gym
LB6-15XA| 7.9 gym| LBH6-40XA| 18 gym
NSF/ANSI Standard 55 Class B
System Tested and Certified by NSF
International against CSA B483.1 and NSF/ANSI 55 for Disinfection
Performance, Class B
System| Rated Flow| System| Rated Flow
LB5-02XB LB6-02XB| 2.9 gym| LBH5-05XB LBH6-05XB| 5.4 gym
LB5-03XB LB6-03XB| 5.2 gym| LBH5-10XB LBH6-10XB| 7.6 gym
LB5-06XB LB6-06XB| 7.6 gym| LBH5-15XB LBH6-15XB| 13 gym
LB5-10XB LB6-10XB| 13 gym| LBH5-25XB LBH6-25XB| 22 gym
LB5-15XB LB6-15XB| 22 gym| LBH5-40XB LBH6-40XB| 28 gym
LUMINOR – Standard Systems**
System| Rated Flow| System| Rated Flow
LB4-02X LB5-02X LB6-02X| 2 gym| LBH4-05X LBH5-05X LBH6-05X| 5 gym
LB4-03X LB5-03X LB6-03X| 3 gym| LBH4-10X LBH5-10X LBH6-10X| 10 gym
LB4-06X LB5-06X LB6-06X| 6 gym| LBH4-15X LBH5-15X LBH6-15X| 15 gym
LB4-10X LB5-10X LB6-10X| 11 gym| LBH4-25X LBH5-25X LBH6-25X| 25
gym
LB4-15X LB5-15X LB6-15X| 15 gym| LBH4-40X LBH5-40X LBH6-40X| 40
gym
LB4-20X LB5-20X LB6-20X| 21 mpg| |
illuminating technologies for life
Note: These instructions are also available in soft copy via email from Luminor Customer Service.
Safety Considerations
It is important that care is taken when operating and/or maintaining your system.
Please read the instructions
- The appliance is not to be used by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
- Children should be supervised so that they do not to play with the appliance.
- WARNING: Do not operate the UV-C emitter when it is removed from the appliance enclosure.
- The appliance is to be supplied through a residual current device (RCD) having a rated residual operating current not exceeding 30 mA.
- This appliance contains a UV-C emitter.
- Unintended use of the appliance or damage to the housing may result in the escape of dangerous UV-C radiation. UV-C radiation may, even in little doses, cause harm to the eyes and skin.
- The appliance must be disconnected from the supply before replacing the UV-C emitter.
- The appliance is intended to be permanently connected to the water mains and not connected by a hose-set.
- Maximum working voltage of built-in UV driver U-OUT=240V
- If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
- Before servicing this equipment, disconnect the power cord from the electrical outlet.
- Energy given off by the UV lamp is harmful to your eyes and skin. NEVER look directly at an illuminated UV lamp without adequate eye protection and always protect your skin from direct exposure to the UV light.
- For complete disinfection , use ONLY genuine replacement parts.
- Do not operate the unit if it has any damaged or missing components.
- To avoid possible electrical shock, use only with a properly grounded electrical outlet.
- Never perform any maintenance to the system unless you are comfortable in doing so. Contact the manufacturer for service instructions if required.
- Do not use this system for any purpose other than what it was intended for. Misuse of this system could potentially cause harm to the user or others.
- Your system is intended to be installed indoors and away from leaking plumbing. DO NOT plug the unit in if the system or any of the components are wet.
- The system should be directly installed into a ground fault circuit interrupter (GFCI). If the use of an extension cord is required, the cord must be manufactured with a minimum of 16 gauge wire and care should be taken to avoid potential tripping hazards.
- We recommend that a licensed plumber or certified technician install the system.
This product is not to be used for general lighting / illumination.
Before You Begin
The following will be needed for installing the UV system:
Tools
- Pipe cutter, hacksaw or other specialized tools required to cut into your existing plumbing (e.g. if you have PEX piping)
- Soldering tools (torch, flux, emery cloth and solder)
- Wrench (for tightening fittings)
Other Materials
- Inlet/outlet connections
- Teflon™ tape
Water Quality Parameters
Treated water should be tested for at the least the parameters listed below.
If the water exceeds the listed parameters LUMINOR strongly recommends that
appropriate pretreatment equipment be installed (equipment required will
depend on parameters being treated):
Hardness:| <7 gig (120 mg/L) – if hardness level is 7 gig or slightly below
the quartz sleeve must be cleaned periodically in order to ensure efficient
UV penetration; if above the water must be softened.
---|---
Iron (Fe):| <0.3 ppm (0.3 mg/L)
Manganese (Mn):| <0.05 ppm (0.05 mg/L)
Turbidity:| < 1 NTU
Tannins (organics):| <0.1 ppm (0.1 mg/L)
UVT (transmittance):| <0.3 ppm (0.3 mg/L)<0.05 ppm (0.05 mg/L) < 1 NTU <0.1
ppm (0.1 mg/L)
You can have your water tested at a private analytical laboratory or by your
local dealer. It is always recommended to install pre-filtration of at least 5
microns prior to a LUMINOR UV disinfection system.
**LUMINOR’s systems are tested for reduction of the MS-2 coliphage
challenge microorganism to demonstrate a log reduction greater than or equal
to the reduction caused by a dose of 40mJ/cm 2 .**
Assembly
Unpack the system and ensure all the components are included with the system.
Your system is shipped with the following components:
System Sizing
All LUMINOR UV systems are rated for a specific flow rate in water that meets
the quality parameters on page 5. PLEASE NOTE that increasing the flow above
this rating or disinfecting water that does not meet the quality parameters
will decrease the dose and therefore compromise the efficacy of the system.
If you need to determine your maximum flow rate, you can fill a 1 gallon
bucket with water and time how long it takes to fill up. It is always better
to oversize your system then to undersize. For example, if your pump delivers
8 gym it is recommended to install any of the BLACKCOMB 10 gym systems.
Location
For Point of Entry (POE) systems, choose a location where the main cold water
line is accessible. The system must be installed after other water treatment
equipment (softener or filters), but before any branches (See Figure 1).
For Point of Use (POU) systems, install the unit just before the faucet.
LUMINOR recommends that a 5 micron filter be installed before the UV system
for a final polishing step before the water is disinfected.
To facilitate lamp removal, ensure
there is enough space at the lamp connector end to safely remove the UV lamp
and/or quartz sleeve (See Figure 2). The controller will require a ground
fault circuit interrupter (GFCI or GFI) outlet and should be mounted beside or
above the reactor.
PLEASE NOTE: All LUMINOR UV disinfection systems are intended for indoor use
only as they should not be exposed to the elements.
Installation
Step 1: The reactor can be installed either horizontally or vertically
using the clamps provided. Vertical installation is the preferred method with
the inlet at the bottom (lamp connection at the top) as it allows any air
that may be in the lines to be easily purged from the system.
Step 2: The use of a by-pass assembly is recommended as it will allow you
to isolate the UV reactor. This will allow for easier access in case
maintenance is required (See Figure 4).
Step 3: Fasten chamber clamps to wall with screws provided. The screws
must anchor securely into solid wood, concrete, or steel structure for
adequate strength. Do not attempt to secure screws into drywall (Figure 3a).
Install Chamber into clamps (Figure 3b).
Step 4: For water supplies where the maximum flow rate is unknown, a flow
restrictor is recommended so that the rated flow of your particular BLACKCOMB
system is not exceeded. The flow restrictor should be installed on the inlet
port of the reactor.
Step 5: It is recommended to have a licensed plumber connect the UV
reactor to the water supply and may be a requirement depending on where you
are located.
Note: Installation of your BLACKCOMB disinfection systems shall comply with applicable provincial/ state & local regulations. **
Step 6: Once the system has been plumbed in, gently remove the quartz sleeve from its packaging being careful not to touch the length with your hands. The use of cotton gloves is recommended for this procedure as oils from the hands can leave residue on the sleeve and lamp which can ultimately block the UV light from getting to the water. Carefully slide the sleeve into the reactor until you can feel it hit the opposite end of the reactor. Align the sleeve so it centered along the length of the reactor, then gently push it in to lock it into the internal centering springs in the far side of the reactor. CAUTION: Pushing too hard when the sleeve is not aligned can damage the centering springs. Slide the o-ring onto the sleeve until it is butted up against the reactor.
Step 7 : Hand tighten the provided gland nut over the quartz sleeve onto
the threaded end of the reactor. It has a positive stop to prevent over-
tightening. A firm force may be required to fully tighten the gland nut, but
DO NOT USE TOOLS for this step. Insert the provided stainless steel
compression spring into the quartz sleeve. The spring works with the lamp and
LUMI-Loc™ connector to create the proper lamp alignment. PLEASE NOTE: DO
NOT install a UV lamp inside the quartz sleeve without the sleeve spring in
place.
Step 8: Install the UV sensor ( BLACKCOMB6.1systems only). Align the
flat portion so it faces the gland nut end and matches up with the half metal
lip on the sensor port (see Figure 6). Insert the sensor so it is fully
seated and hand tighten the sensor nut.
Step 9: The reactor is now ready for water flow. When all plumbing
connections have been completed, slowly turn on the water supply and check for
leaks. Make sure the by-pass valves are functioning properly and that the
water is flowing through the reactor. The most common leak is from the o-ring
not making a proper seal on the reactor. For new installations, review steps 5
and 6. For older systems drain the reactor, remove the o-ring, dry it and
reapply silicon grease. Reinstall the o-ring ensuring that it is properly
sealed against the reactor and check again for leaks.
Step 10: Fasten controller securely to wall with screws provided. Drywall
anchors may be used. Note that the controller must be mounted vertically for
adequate airflow across the aluminum heat sink on back (see Figure 7). For
monitored systems, insert the sensor connector into the IEP located on the
right side of the controller (Figure 8). For the sensor to be recognized by
the controller, the controller power must be plugged in last. Do not plug
the controller power cord in before the last step.
Step 11: Always hold UV lamps by their ceramic ends, not by the lamp
quartz. Remove the lamp from its packaging. Again, the use of cotton gloves is
recommended. Remove the lamp key from the lamp’s connector and set it aside
for the next step. Be careful to not touch the key’s exposed contacts. Insert
the UV lamp into the reactor, being careful not to drop it.
Step 12: Install the lamp key into the controller (BLACKCOMB5.1 ,
BLACKCOMB 6.1 systems only).
The key always comes packaged with the lamp and sits on the connector. With
the key removed from the lamp, orient it so the label is upright and facing
you. The key will plug into the lamp key port on the right side of the
controller (Figure 10).
Step 13 : Plug the LUMI-Loc™ lamp connector into the lamp. Note the
keying for proper alignment (see Figure 9a, 9b). Insert the lamp connector
into the gland nut and turn the connector approximately ¼ turn to lock the
connector to the gland nut as in Figure 11.
Step 14: Tighten the captive ground screw to the ground lug on the UV
reactor to ensure proper grounding.
Step 15: Your system is now ready to be plugged into the appropriate GFCI protected outlet. Refer to the following section before any water is allowed to flow through the system.
System Preparation
With a new installation, or any time the UV system is shut down for service,
without power, or is inoperative for any other reason, the lines in the home
or facility could be contaminated. Use the following steps to prepare the
lines throughout the entire home or facility.
Step 1 : Check for and remove any “dead ends” in the lines throughout the
home as these can harbor dirt and debris. Plug in the UV system and wait until
it is ready for operation.
Step 2: Remove the filter cartridge from the last sump and fill it with
1-2 cups of household bleach (most are 5.25% chlorine). Replace the sump and
slowly turn on the water supply.
Step 3: At a water outlet, run the water until bleach can be smelled.
Repeat this for all faucets, toilets, shower heads, refrigerators, outdoor
taps, the washing machine, dishwasher, etc. at the home or facility. Once
finished, wait a minimum of 30 minutes before continuing.
Step 4: Reinstall the filter cartridge into the sump and flush the
chlorine solution by opening all faucets until chlorine can no longer be
detected. Your BLACKCOMB UV system is ready to use.
Cleaning the Quartz Sleeve
Depending on the water quality, the quartz sleeve may require periodic
cleaning. At a minimum, the quartz sleeve should be cleaned on an annual
basis. The following steps outline a basic cleaning procedure.
Step 1: If a by-pass assembly is installed, shut the inlet valve off to
prevent water flow through the system. Otherwise, turn off main water inlet
valve (and/or turn off the water pump).
Step 2: Disconnect power cord of UV system from electrical outlet.
Step 3: Release water pressure by opening a downstream faucet and then
close the outlet shut-off valve (if any). If there is no outlet shut-off
valve, expect water to drain from the system as the head pressure in the
system will cause the water to flow back down.
Step 4: Remove the captive ground screw from the ground lug on the UV
reactor.
Step 5: Remove the lamp connector from the reactor (gland nut) by pushing
the LUMI-lock connector in and turning it ¼ turn counter-clockwise. Disconnect
the lamp connector from the lamp. CAUTION: the lamp may be hot!
Step 6: Being careful to touch only the ceramic ends, remove the lamp out
of the reactor.
Step 7: Unscrew the gland nut from the reactor exposing the end of the
quartz sleeve.
Step 8: Remove the quartz sleeve and o-ring by gently twisting and
pulling the quartz sleeve.
Step 9: Using a soft, lint-free cloth or towel wipe the sleeve down using
a commercial scale cleaner (i.e. CLR® or LIME-A-WAY®). This removes scaling or
iron deposits that may be on the outside of the quartz sleeve. Be careful not
to get any moisture or liquids inside of the sleeve.
Step 10: Dry the sleeve with separate cloth.
Step 11: Replace the o-ring and slide the sleeve back into the reactor
following steps 7 and 8 from the installation section of the manual.
Cleaning the UV Sensor
Depending on the water quality, the UV sensor may require periodic cleaning.
At a minimum, the UV sensor should be cleaned on an annual basis. The
following steps outline a basic cleaning procedure.
Step 1: If a by-pass assembly is installed, shut the inlet valve off to
prevent water flow through the system. Otherwise, turn off main water inlet
valve (and/or turn off the water pump).
Step 2: Disconnect power cord of UV system from electrical outlet.
Step 3: Release water pressure by opening a downstream faucet and then
close the outlet shut-off valve (if any). If there is no outlet shut-off
valve, expect water to drain from the system as the head pressure in the
system will cause the water to flow back down.
Step 4: Place something under the reactor to catch any water that may
come out of the reactor during the removal of the UV sensor.
Step 5: Unscrew (counterclockwise) sensor nut from the reactor and pull
the sensor slowly out of the sensor port.
Step 6: Holding the sensor in your hand wipe the flat portion (sensor
face) of the sensor with isopropyl alcohol using a clean lint-free cloth.
Step 7: Replace sensor following step 9 from the installation section of the
manual.
Operation
BLACKCOMB systems come with a feature laden controller that incorporates both
the lamp driver (ballast) and control features in one water-tight case. Four
main controllers are available for the BLACKCOMB systems (depending on your
model). All four models feature a power factor corrected, constant current
lamp driver with a universal power input.
Please Note : While the LED or display screen is red and the buzzer is
sounding the water from the system should NOT be consumed. If any water does
pass through the system during this period, please follow the disinfection
procedure as outlined in this manual before the water is consumed. For
BLACKCOMBsystems, even though they have a visual and audible warning built
into the controller, a green LED or status screen does not necessarily
indicate that the water coming from this system is in fact potable (safe to
drink). These systems do not measure the level of disinfection4.1 and
BLACKCOMB 5.1 ; they simply measure the “on-off” status of the lamp.
Please have your water checked for microbiological contaminants on a regular
basis.
Simplistic in operation, these systems feature a tri-colour LED that
indicating system status and a 4-digit display to indicate lamp life
remaining. Pressing the button will change the display to indicate total
running time. When the UV lamp is on and within its operating age, the LED
will be green. When the UV lamp is not on or the lamp life has expired, the
LED will be illuminated red and an audible buzzer will be sounding. To remedy
this condition, the UV lamp must be replaced with a new genuine LUMINOR UV
lamp.
BLACKCOMB5.1 & BLACKCOMB 6.1
Controllers
A full colour LCD screen provides the user with a detailed description of the system’s performance in addition to providing any applicable fault messages and system diagnostics. The controllers used in both the BLACKCOMB5.1 and BLACKCOMB 5.1 are identical. The difference is that the BLACKCOMB 6.1 series of products includes a UV intensity monitor. All BLACKCOMB 6.1 controllers include an “infinite expandability port” located on the right side of the controller. Simply plug in an optional UV sensor module into the expandability port of a BLACKCOMB 5.1 and BLACKCOMB 6.1 controller and the system will now monitor the UV intensity of the system!
BLACKCOMB5.1 & BLACKCOMB6.1Power-up Sequence
On start up, the controller will run through a diagnostic start-up and the
sequence will be displayed as follows on the colour LCD:
Next, the controller checks for and initializes any optional modules that may
be attached to the system.
Optional Modules Check![LUMINOR BLACKCOMB 51 UV Water Purification System
- Modules Check](https://manuals.plus/wp-content/uploads/2023/03/LUMINOR- BLACKCOMB-51-UV-Water-Purification-System-Modules-Check.png)
A final module screen is displayed showing which specific modules were
initialized.
The controller then displays the lamp optimization screen for 60 seconds to
allow the lamp to reach its optimum output. Finally, a final “start-up
complete” screen is is played. The system will now be ready to disinfect **
water flow.
BLACKCOMB5.1 Operational Screens
On systems without the UV monitor, the default screen shows the LUMINOR Home
Screen. At any point during operation the user is able to scroll through the
LUMINOR Home Screen, Lamp life remaining, QR Code, Contact Info and
Maintenance Parts screens by pressing the button located on the front of the
controller.
|
---|---
www.luminoruv.com| http://www.luminoruv.com/LBHO-
QR
www.luminoruv.com
|
www.luminoruv.com| http://www.luminoruv.com/LBHO-
QR
www.luminoruv.com
BLACKCOMB6.1 Operational Screens
On systems with the UV monitor, the system will display the same screens as on
the BLACKCOMB5.1 except the UV Intensity replaces the home screen. The UV
Intensity screen displays the level of UV light detected by the sensor. UV
intensity can be affected by poor water quality, scaling on the quartz sleeve
and/or sensor, lamp failure or lamp expiring. The following screens show the
UV Intensity dropping.
Below 56%, the numbers and warning sign turn red and an audible chirp is given by the ballast every 15 seconds. Below 51%, the screen is solid red and a constant audible alarm is given. This alternates with a screen indicating “water may be unsafe for consumption”. With the solenoid module, the controller de-activates the solenoid valve, shutting off all water flow.
Lamp Countdown Sequence
The system counts down the number of days until a lamp change is required.
At thirty days remaining, the LED or display screen will change to a yellow caution indicator. At seven days remaining, the system will additionally repeat an audible chirp. Past the zero day threshold, the LED or display screen changes to solid red with a continuous buzzer.
At any point during this sequence, the audible chirp or alarm can be deferred for seven days by holding the controller button down for a period of five seconds. The number of deferrals used will be displayed as below. Once the deferral expires, the alarm will sound once again. The deferral can be repeated up to three times. PLEASE NOTE : At any point after lamp expiration, the water may be unsafe for consumption and should not be consumed without another form of disinfection**.
System Service Suggested
BLACKCOMB 5.1 & 6.1 controllers will display the System Service Suggested
Screen every 6 months to remind consumers to maintain both their UV and other
prefiltration. This will serve as a prompt only and will not put the system
into alarm. To clear this condition simply press the button located below the
screen.
Lamp Replacement (BLACKCOMB4.1 systems)
After the lamp is expired, it must be replaced with the same part number as
indicated by the label on the reactor. Begin replacing the lamp by unplugging
the power for the controller, then refer to Installation, starting with step
11 (page 11) for instructions on installing the new lamp. To reset the timer
in the controller, firmly hold down the button on the controller for 10
seconds. The controller will read “rSt3”, “rSt2”, “rSt1” and then beep. The
button can now be released, the lamp countdown timer has been reset.
Lamp Replacement (BLACKCOMB5.1 & BLACKCOMB 6.1 systems)
After the lamp is expired, it must be replaced with the same part number as
indicated on the Maintenance Parts screen or on the label on the reactor. With
the system powered down, remove and discard the lamp key from the controller.
The replacement lamp is packaged with a lamp key on the connector at the end
of the lamp. Remove the key from the lamp and place it in the controller.
Refer to Installation, starting with step 11 (page 11) for instructions on
installing the new lamp.
QR Codes
http://www.luminoruv.com/LBHO-QR
A QR code (Quick Response code) is a matrix barcode first designed for the automotive industry. LUMINOR uses the QR code to store a link to a specific page on our website. Users with a camera phone equipped with the correct reader application can scan the image of the QR code and over a wireless network connect to a LUMINOR web page in the phone’s browser. LUMINOR’s QR webpage has information on how to purchase replacement components as well as a helpful video directory on system servicing (i.e. How to change a UV lamp or quartz sleeve). To access the QR code on the BLACKCOMB controller, press the control button until the QR code screen appears.
System Troubleshooting
Hard Alarms: The following give a constant audible alarm. If present, the solenoid valve is closed, and the 4-20, remote alarm and wife modules transmit the alarm.
System Display | Problem | Resolution |
---|---|---|
The system has detected a problem with the lamp. | Reset lamp protection |
circuit unplug unit for 10 seconds. Replace the lamp with the part as
indicated on the silver label on the reactor or on the Maintenance parts
screen.
| Although the lamp is powered and visibly illuminated, due to the lamp’s age
its UV output is no longer sufficient for proper disinfection**.| Replace the
lamp with the part as indicated on the silver label on the reactor or on the
Maintenance parts screen.
| Low UV Intensity.| Remove and clean the quartz sleeve and sensor. Check
water quality meets requirements on page 5 and add filtration as required.
Replace lamp.
| Wrong lamp or sensor installed.| Replace component with proper model as
indicated.
| The UV sensor is no longer
communicating with the system.| Ensure all modules are connected properly to
the system and to each other.
Modules can be tested individually by plugging in one at a time and cycling
power to the system.
Replace any module that is not detected when plugged directly into the
controller.
| A bad connection has been detected
in the IEP port.
| Missing or incorrect lamp key.| Ensure the lamp key (packed with the lamp, on the connector) is installed. Unplug and reinstall the key. Ensure the key part number matches Lamp on Maintenance Parts screen.
Soft Alarms: The following remaining errors give a 15 second audible chirp only
System Display | Problem | Resolution |
---|---|---|
The module indicated is no longer | ||
communicating to with the system | Ensure all modules are connected properly to |
the system and to each other.
Modules can be tested individually by plugging in one at a time and cycling
power to the system.
Replace any module that is not detected when plugged directly into the
controller.
| Refer to flow meter manual for detailed troubleshooting
Warning: After any hard alarm, the home or facility should be
disinfected. Follow the steps under the “System Preparation” heading.
Boil Water Advisory: If any failure occurs on a BLACKCOMB UV system, the
water must not be used for human consumption until the system is returned to
normal operational mode. If the water is used for human consumption during
this period, the water must be boiled (minimum 20 minutes at a full boil)
prior to consumption.
Temperature Management Devices
Your LUMINOR BLACKCOMB system is designed to run continuously to ensure
optimal disinfection . However, during periods when no water is drawn through
the system, the energy from the disinfection process can cause the
temperature of the water inside the chamber to rise. In extreme situations
elevated water temperature or the fluctuation in temperature can lower the
output of the UV lamp. In these cases, or if the elevated water temperature is
a nuisance, LUMINOR recommends one of the following forms of temperature
management devices.
Cooling Fan
Designed for use on the BLACKCOMB-HO systems, the “LUMI-cool ”™ fan runs
continuously to cool the water by forced convection. The long-life fan is
powered independently using a compact modular power adapter that operates from
100-240V/50-60Hz. ±10%. The cooling fan must only be supplied at SELV. Order
PN 130014.
Temperature Relief Valve (TRV)
On reaching a higher temperature, the TRV is designed to drain a small amount
of water to allow fresh, cooler water to enter the system. The TRV works
without power and comes complete with 10’ of drain line. Order PN 130031
for 1/2” ports, PN 130032 for 3/4” ports, PN 130033 for 1” ports and PN
130034 for 1 1/2” ports.
Expansion Modules
BLACKCOMB5.1and BLACKCOMB6.1 controllers incorporate an “Infinite
Expandability Port” (IEP) which allows for expansion to the UV sensor and
all other modules. Each module (including the sensor) comes with both a male
and female connection. Connect any device to the controller and all subsequent
devices are then connected into the female end of last device added in a
“daisy chain” configuration. The UV sensor must only be supplied at SELV.
The following optional expansion
modules are available for use on BLACKCOMB5.1and BLACKCOMB6.1UV controllers.
Contact your authorized distributor for purchasing information.
REMOTE ALARM CONNECTION MODULE: Allows for a connection to a remote
device such as a buzzer, light, alarm system, PLC, etc., via a pair of
contacts. In normal operation the OK and COM contacts will be connected, and
in a fault condition (Low UV, Lamp fail, Power Fail), the Fault and COM
contacts will be connected. Maximum contact rating is 30V / 1A (use 16-22
AWG). The remote alarm module must only be supplied at SELV. Order PN MOD-RAM.
SOLENOID CONNECTION MODULE: Connects a NORMALLY CLOSED line voltage
solenoid valve to the controller. Maximum contact rating is 240VAC (50-60Hz) /
30VDC / 2A. On a non-monitored system, the solenoid will only close on a lamp
failure error. On a monitored system, the solenoid is closed when the UV level
drops below 50%. Also note that in cases where emergency use of un- treated
water is required, the controller can be placed into a manual override mode
allowing for the flow of water in an alarm condition. Order PN MOD-SOL.
4-20 mA MODULE: Outputs a 4-20mA signal of the UV output to a remote device
such as a data logger or computer. The 4-20mA module must only be supplied at
SELV.
Order PN MOD-420.
The WiFi module and accompanying IoT application allows you to connect your UV system to a smart phone, tablet, computer or other connected platform. View system status, receive SMS or email messages of alarm conditions and monitor the health of your UV from anywhere via this connected platform. Connect the device via the APP found on Google Play or the APP Store. Connect your UV device to your router, download the software for your connected device and have peace of mind that your UV system is fully operational. *Not available in all markets.
The Ultrasonic Flow Meter enables your UV system to dim power in times of low to no flow, saving you money on energy, reducing water temperature, and decreasing the risk of fouling. The flow meter module must only be supplied at SELV.
BLACKCOMB Standard Output System Specifications
| LUMINOR EQUIPMENT SPECIFICATIONS
---|---
Multi-Use / Residential systems (standard output lamps)
MODEL| LB4-02X
LB5-02X
LB6-02X| LB4-03X
LB5-03X
LB6-03X| LB4-06X
LB5-06X
LB6-06X| LB4-10X
LB5-10X
LB6-10X| LB4-15X
LB5-15X
LB6-15X| LB4-20X
LB5-20X
LB6-20X
NSF Class A Flow Rate 40mJ/cm2 @ 70% UVT
(add “A” suffix on LB6 models)
| 1.6 gym| 2.2 gym| 3.4 gym| 6.3 gym| 7.9 gym| N/A
6.1 lap| 8.3 lap| 13 lap| 24 lap| 30 lap| N/A
0.36 m3/hr| 0.50 m3/hr| 0.77 m3/hr| 1.4 m3/hr| 1.8 m3/hr| N/A
NSF Class B Flow Rate 16mJ/cm2 @ 70% UVT
(“B” suffix on LB5,LB6 models)| 2.9 gym| 5.2 gym| 7.6 gym| 13 gym| 22 gym| N/A
11 lap| 20 lap| 29 lap| 49 lap| 83 lap| N/A
0.66 m3/hr| 1.2 m3/hr| 1.7 m3/hr| 3.0 m3/hr| 5.0 m3/hr| N/A
Flow Rate 16mJ/cm2 @ 95% UVT
| 3.8 gym| 6.1 gym| 11 gym| 20 gym| 30 gym| 39 gym
15 lap| 23 lap| 41 lap| 77 lap| 110 lap| 150 lap
0.87 m3/hr| 1.4 m3/hr| 2.5 m3/hr| 4.6 m3/hr| 6.8 m3/hr| 8.9 m3/hr
Flow Rate 30mJ/cm2 @ 95% UVT
| 2.0 gym| 3 gym| 6 gym| 11 gym| 15 gym| 21 gym
7.6 lap| 11.4 lap| 22.7 lap| 41 lap| 57 lap| 79 lap
0.45 m3/hr| 0.70 m3/hr| 1.4 m3/hr| 2.5 m3/hr| 3.4 m3/hr| 4.8 m3/hr
Flow Rate 40mJ/cm2 @ 95% UVT
| 1.6 gym| 2.4 gym| 4.4 gym| 8.3 gym| 12 gym| 16 gym
6.1 lap| 9.1 lap| 17 lap| 31 lap| 45 lap| 59 lap
0.36 m3/hr| 0.50 m3/hr| 1.0 m3/hr| 1.9 m3/hr| 2.7 m3/hr| 3.6 m3/hr
Port Size| ½”FNPT| ½”MNPT| ¾”MNPT| ¾”MNPT| 1”MNPT| 1”MNPT
Electrical| 100-240V/50-60Hz. ±10%. 1A Max.
Plug Type| American: NEMA 5-15P *See Note (below)
Lamp Power (Watts)| 8| 15| 22| 39| 50| 42
Power (Watts)| 14| 20| 30| 49| 62| 51
Replacement Lamp| RL-210| RL-290| RL-470| RL-820| RL-999| RL-850
Replacement Sleeve| RQ-210| RQ-290| RQ-470| RQ-820| RQ-999| RQ-850
Reactor Dimensions| 6.4 x 26.2 cm (2.5 x 10.3”)| 6.4 x 36.4 cm (2.5 x 14.3”)|
6.4 x 54.2 cm (2.5 x 21.3”)| 6.4 x 89.5 cm (2.5 x 35.2”)| 6.4 x 101.6 cm (2.5
x 40.0”)| 8.9 x 91.7 cm (3.5 x 36.1”)
Chamber Material| 304 Stainless Steel, A249 Pressure Rated Tubing
Controller Dimensions| 17.2 x 9.2 x 10.2 cm (6.8 x 3.6 x 4”)
Operating Pressure| 0.7-10.3 bar (10-150 psi)
Operating Water Temperature| 2-40° C (36-104° F)
UV Monitor| YES on all “LB6” models. Upgrade available for “LB5” models (NOT
available on LB4 models)
Solenoid Output| YES (optional solenoid module ( MOD-SOL1 ) sold
separately)
Dry Contacts| YES (remote alarm module ( MOD-RAM ) sold separately)
4-20mA Output| YES (4-20mA module ( MOD-420 ) sold separately)
Temperature Mgmt. Valve| NA| PN# 130031| PN# 130032| PN# 130033
Cooling Fan| NO| OPTIONAL (130014)
Lamp Change Reminder| YES
Lamp Out Indicator| YES
Shipping Weight| 2.9 kg (6.3 lbs)| 3.6 kg (7.9 lbs)| 4.4 kg (9.6 lbs)| 6.0 kg
(13.2 lbs)| 6.5 kg (14.4 lbs)| 8.2 kg (18.0 lbs)
*Note: replace “X” with “1” for all 110V systems with North American NEMA 5-15 replace “X” with “2” for all 230V systems with European CEE 7/7 replace “X” with “3” for all 230V systems with British Standard, BS 1363 replace “X” with “4” for all 230V systems with Australian/New Zealand AS/NZ 3112
BLACKCOMB-HO High Output System Specifications
| LUMINOR EQUIPMENT SPECIFICATIONS
---|---
| Residential Crossover systems (high output lamps)
MODEL| LBH4-05X LBH5-05X LBH6-05X| LBH4-10X
LBH5-10X LBH6-10X| LBH4-15X LBH5-15X LBH6-15X|
LBH4-25X LBH5-25X LBH6-25X| LBH4-40X LBH5-40X
LBH6-40X
NSF Class A Flow Rate 40mJ/cm2 @ 70% UVT (add “A” suffix on LBH6 models)| 2.2
gym| 4.0 gym| 5.4 gym| 7.9 gym| 18 gym
8.3 lap| 15 lap| 20 lap| 30 lap| 68.1 lap
0.50 m3/hr| 0.91 m3/hr| 1.2 m3/hr| 1.8 m3/hr| 4.08 m3/hr
NSF Class B Flow Rate 16mJ/cm2 @ 70% UVT (“B” suffix on LBH5,LBH6 models)| 5.4
gym| 7.6 gym| 13 gym| 22 gym| 28 gym
20 lap| 29 lap| 49 lap| 83 lap| 110 lap
1.2 m3/hr| 1.7 m3/hr| 3.0 m3/hr| 5.0 m3/hr| 6.4 m3/hr
Flow Rate 30mJ/cm2 @ 95% UVT| 5.0 gym| 10 gym| 15 gym| 25 gym| 40 gym
18.91 lap| 37.9 lap| 57 lap| 95 lap| 151 lap
1.1 m3/hr| 2.3 m3/hr| 3.4 m3/hr| 5.7m3/hr| 9.3m3/hr
Flow Rate 40mJ/cm2 @ 95% UVT| 3.0 gym| 7.0 gym| 11 gym| 19 gym| 31 gym
11 lap| 26 lap| 42 lap| 72 lap| 120 lap
0.68 m3/hr| 1.6 m3/hr| 2.5 m3/hr| 4.3 m3/hr| 7.0 m3/hr
Flow Rate Hot Water (-HW suffix) model 30mJ/cm2 @ 75% UVT| 2.8 gym| 7.0 gym|
9.8 gym| 16 gym| 28 gym
11 lap| 26 pm| 37 lap| 61 lap| 110 lap
0.6 m3/hr| 1.6 m3/hr| 2.2 m3/hr| 3.6 m3/hr| 6.4 m3/hr
Flow Rate Low UVT (-50 suffix) model 30mJ/cm2 @ 50% UVT| 1.7 gym| 4.2 gym| 6.1
gym| 10 gym| 17 gym
6.4 lap| 16 lap| 23 lap| 38 lap| 64 lap
0.4 m3/hr| 1.0 m3/hr| 1.4 m3/hr| 2.3 m3/hr| 3.9 m3/hr
Flow Rate TOC (-TOC suffix) model 150mJ/cm2 @ 98% UVT| 0.8 gym| 2.0 gym| 2.8
gym| 5.1 gym| 8.0 gym
3.0 lap| 7.6 lap| 11 lap| 19 lap| 30 lap
0.2 m3/hr| 0.5 m3/hr| 0.6 m3/hr| 1.1 m3/hr| 1.8 m3/hr
Port Size| ¾”MNPT| ¾”MNPT| 1”MNPT| 1”MNPT| 1 ½”MNPT
Electrical| 100-240V/50-60Hz. ±10%. 1.5A Max.
Plug Type| American: NEMA 5-15P *See Note (page 22)
Lamp Power (Watts)| 18| 34| 45| 67| 101
Power (Watts)| 20| 36| 48| 72| 108
Replacement Lamp| RL-210HO| RL-330HO| RL-420HO| RL-600HO| RL-950HO
Replacement Sleeve| RQ-210| RQ-330| RQ-420| RQ-600| RQ-950
Reactor Dimensions| 8.9 x 29.8 cm (3.5 x 11.7”)| 8.9 x 41.8 cm (3.5 x 16.5”)|
8.9 x 50.8 cm (3.5 x 20.0”)| 8.9 x 68.3 cm (3.5 x 26.9”)| 8.9 x 103.4 cm (3.5
x 40.7”)
Chamber Material| 316L Stainless Steel, A249 Pressure Rated Tubing
Controller Dimensions| 21.7 x 10.8 x 10.2 cm (8.6 x 4.2 x 4”)
Operating Pressure| 0.7-10.3 bar (10-150 psi)
Operating Water Temperature| 2-40° C (36-104° F)
UV Monitor| YES on all LBH6 models. Upgrade available for LBH5 models (NOT
available on LBH4 models)
Solenoid Output| YES (optional solenoid module ( MOD-SOL1 ) sold
separately)
Dry Contacts| YES (remote alarm module ( MOD-RAM ) sold separately)
4-20mA Output| YES (4-20mA module ( MOD-420 ) sold separately)
Temperature Mgmt. Valve| PN# 130032| PN# 130033| PN# 130034
Cooling Fan| OPTIONAL (130014 sold separately)
Lamp Change Reminder| YES
Lamp Out Indicator| YES
Shipping Weight| 4.4 kg (9.7 lbs)| 5.2 kg (11.5 lbs)| 5.6 kg (12.9 lbs)| 7.0
kg (15.5 lbs)| 9.6 kg (21.1 lbs)
Performance Data Sheet (on all NSF/ANSI Standard 55, Class A Systems)
System Tested and Certified by NSF International against CSA B483.1 and NSF/ANSI 55 for Disinfection Performance, Class A**
** Model| LB6-02XA
LB6-02A-12V| LB6-03XA
LB6-03A-12V| LB6-06XA| LB6-10XA| LB6-15XA| LBH6-05XA| LBH6-10XA| LBH6-15XA|
LBH6-25XA| LBH6-40XA
| LB6-02A- 4V| LB6-03A-24V| | | | | | | |
NSF Class A Flow Rate (40mJ/cm2 @ 70% UVT)| 1.6 gym
6.1 lap
0.4 m3/hr| 2.2 gym
8.3 lap
0.5 m3/hr| 3.4 gym 13 lap
0.8 m3/hr| 6.3 gym 24 lap
1.4 m3/hr| 7.9 gym 30 lap
1.8 m3/hr| 2.2 gym
8.3 lap
0.5 m3/hr| 4.1 gym 15 lap
0.9 m3/hr| 5.4 gym 20 lap
1.2 m3/hr| 7.9 gym 30 lap
1.8 m3/hr| 18 gym
\68.1 lap
4.08 m3/hr
Port Size| ½”FNPT| ½”MNPT| ¾”MNPT| ¾”MNPT| 1” MNPT| ½”MNPT| ¾”MNPT| 1” MNPT|
1” MNPT| 1½”MNPT
Electrical| 100-240V/50-60Hz. ±10%. 1A Max| 100-240V/50-60Hz. ±10%. 1.5A Max
Operating Pressure| 0.7-10.3 bar (10-150 psi)
Operating Water Temperature| 2-40° C (36-104° F)
Note:** replace “X” with “1” for all 110V systems with North American NEMA
5-15 replace “X” with “2” for all 230V systems with European CEE 7/7replace
“X” with “3” for all 230V systems with British Standard, BS 1363 replace “X”
with “4” for all 230V systems with Australian/New Zealand AS/NZ 3112
Lamp Life: LB6 series UV lamps are rated for 9,000 hours of continuous
use (one-year of operation). LBH6 series UV lamps are rated for 10,000 hours
of continuous use (approximately 14 months of operation)
General Operation and Maintenance: UV lamps are to be replaced on an
annual basis. Quartz sleeves and UV sensors are to be cleaned every 6-12
months and replaced every 5 years. This Class A system conforms to NSF/ANSI
55 for the disinfection ** of microbiologically contaminated water that meets
all other public health standards. The system is not intended to convert
wastewater or raw sewage to drinking water. The system is intended to be
installed on visually clear water.
NSF/ANSI 55 defines wastewater to include human and/or animal body waste,
toilet paper, and any other material intended to be deposited in a receptacle
designed to receive urine and/or feces (blackwater), and other waste
materials deposited in plumbing fixtures (greywater).
If this system is used for the treatment of untreated surface waters or ground
water under the direct influence of surface water, a device found to be in
conformance for cyst reduction under the appropriate NSF/ANSI standard shall
be installed upstream of the system.
While testing was performed under standard laboratory conditions, actual
performance may vary.
The systems and installation shall comply with applicable provincial/state and
local regulations.
Performance Data Sheet (on all NSF/ANSI Standard 55, Class B Systems)
System Tested and Certified by NSF International against CSA B483.1 and NSF/ANSI 55 for Disinfection Performance, Class B**
Model| LB5-03XB| LB5-06XB LB6-06XB| LB5-10XB LB6-10XB| LB5-15XB LB6-15XB|
LBH5-05XB LBH6-06XB| LBH5-10XB LBH6-10XB| LBH5-15XB LBH6-15XB| LBH5-25XB
LBH6-25XB| LBH5-40XB LBH6-40XB
NSF Class B Flow Rate (16mJ/cm2 @ 70% UVT)| 5.2 gym 11 lap
1.2 m3/hr| 7.6 gym 29 lap
1.7 m3/hr| 13 gym
49 lap
3.0 m3/hr| 22 gym
83 lap
5.1 m3/hr| 5.4 gym 20 lap
1.2 m3/hr| 7.6 gym 29 lap
1.7 m3/hr| 13 mpg
49 lap
3.0 m3/hr| 22 gym
83 lap
5.1 m3/hr| 28 gym
110 lap
6.4 m3/hr
Port Size| ½”MNPT| ¾”MNPT| ¾”MNPT| 1” MNPT| ½”MNPT| ¾”MNPT| 1” MNPT| 1” MNPT|
1” MNPT
Electrical| 100-240V/50-60Hz. ±10%. 1A Max| 100-240V/50-60Hz. ±10%. 1.5A Max
Operating Pressure| 0.7-10.3 bar (10-150 psi)
Operating Water Temperature| 2-40° C (36-104° F)
Note: replace “X” with “1” for all 110V systems with North American NEMA 5-15
replace “X” with “2” for all 230V systems with European CEE 7/7 replace “X”
with “3” for all 230V systems with British Standard, BS 1363 replace “X” with
“4” for all 230V systems with Australian/New Zealand AS/NZ 3112
Lamp Life: LB5, LB6 series UV lamps are rated for 9,000 hours of
continuous use (on year of operation). LBH5, LBH6 series UV lamps are rated
for 10,000 hours of continuous use (approximately 14 months of operation)
General Operation and Maintenance: UV lamps are to be replaced on an
annual basis. Quartz sleeves and UV sensors are to be cleaned every 6-12
months and replaced every 5 years.
This Class B system or component conforms to NSF/ANSI 55 for the supplemental
bactericidal treatment disinfected** public drinking water or other drinking
water that has been tested and deemed acceptable for human consumption by the
state or local health agency having jurisdiction. The system is only designed
to reduce normally occurring non-pathogenic nuisance microorganisms. Class B
systems are not intended for treatment of contaminated water.
While testing was performed under standard laboratory conditions, actual
performance may vary.
The system and installation shall comply with applicable provincial/state and
local regulations.
Limited Warranty Statement:
Products manufactured by LUMINOR Environmental Inc., (LUMINOR) are warranted
to the original user only to be free of defects in material and workmanship
for a period as specified below. This warranty only applies to the original
purchaser and is not transferable.
UV SYSTEMS
Ten (10) year Limited Warranty on the stainless steel reactors, from the date
of original purchase, or installation (proper documentation required for
verification).
ELECTRONICS
Three (3) year Limited Warranty on the ballasts and controllers, from the date
of original purchase, or installation (proper documentation required for
verification).
UV LAMPS, UV SENSORS & QUARTZ SLEEVES
One (1) year Limited Warranty on all LUMINOR ultraviolet lamps, UV sensors and
quartz sleeves from the date of original purchase, or installation (proper
documentation required for verification).
LUMINOR warrants that it will repair, replace or refund, at LUMINOR’s sole
option, any ultraviolet system or component that is defective in materials or
workmanship for the period as outlined above, subject to the “Limitations of
Warranty” as outlined below. LUMINOR’s liability under this warranty shall be
limited to repairing or replacing at LUMINOR’s option, without charge, F.O.B.
LUMINOR’s factory or authorized service depot, any product that LUMINOR
manufactures. LUMINOR will not be liable for any costs of removal,
installation, transportation, or any other charges which may arise in
connection with a warranty claim. Products which are sold but not manufactured
by LUMINOR are subject to the warranty provided by the manufacturer of said
products and not by LUMINOR’s warranty. LUMINOR will not be liable for damage
or wear to products caused by abnormal operating conditions, accident, abuse,
misuse, unauthorized alteration or repair, or if the product was not installed
in accordance with LUMINOR’s printed installation and operating instructions.
LIMITATIONS OF WARRANTY
This warranty does not apply to any of the following:
- Water Quality Parameters lie outside of the following ranges
- Hardness > 120 mg/L (7 gig)
- Iron > 0.3 mg/L (ppm)
- Manganese > 0.05 mg/L (ppm)
- Tannins > 0.1 mg/L (ppm)
- Turbidity > 1 NTU
- Transmittance (UVT) < 75%
- A product that has been incorrectly installed according to the owners manual.
- A product that has been modified in any manner, unless approved by the manufacturer.
- A product where the serial number has been altered defaced or removed.
- Damage caused by the use of parts that are not compatible, suitable and/or authorized by LUMINOR for use with the product (e.g. non-original lamps or sleeves).
- Damage caused during shipment of the product.
- Water damage is found inside ballast housing or controllers.
- Product is installed outdoors in direct contact with the environment (rain).
- Product is installed in freezing temperatures.
- Product is used in conditions that exceed LUMINOR’s specifications.
TO GET WARRANTY SERVICE
To obtain service under this warranty, you must first contact where the
product was originally purchased to obtain a Warranty Return Authorization.
You will require proof of purchase and installation date, failure date, and
any other requested data. Unless otherwise provided, the Dealer or Distributor
will contact LUMINOR for instructions on returning the product. Any defective
product to be returned to LUMINOR must be sent freight prepaid; documentation
supporting the warranty claim and/or a Return Goods Authorization must be
included if so instructed.
LUMINOR WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES CAUSED
BY FIRE, FLOOD, OR ACTS OF GOD, LOSSES, OR EXPENSES ARISING FROM INSTALLATION,
USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTIES,
INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND
BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE.
THIS LIMITED WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY MADE BY LUMINOR WITH
RESPECT TO THE PRODUCT, AND IS GIVEN IN LIEU OF ANY OTHER WARRANTY. TO THE
EXTENT ALLOWED BY APPLICABLE LAW, ANY AND ALL EXPRESS OR IMPLIED WARRANTIES
NOT SET FORTH HEREIN ARE WAIVED AND DISCLAIMED, INCLUDING ANY IMPLIED WARRANTY
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR USE. LUMINOR LIABILITY UNDER
THIS LIMITED WARRANTY IS LIMITED SOLELY TO THOSE LIABILITIES SET FORTH ABOVE.
IN THE EVENT THAT ANY PROVISION OF THIS LIMITED WARRANTY SHOULD BE OR BECOME
INVALID OR UNENFORCEABLE UNDER APPLICABLE LAW, THE REMAINING TERMS AND
CONDITIONS HEREOF SHALL REMAIN IN FULL FORCE AND EFFECT AND SUCH INVALID OR
UNENFORCEABLE PROVISION SHALL BE CONSTRUED IN SUCH A MANNER AS TO BE VALID AND
ENFORCEABLE.
Warranty Registration
It is imperative that you complete the warranty registration process. This not
only registers your UV disinfection system for the provided manufacturer’s
warranty, but also allows the factory to provide you with any important
product updates or technical bulletins concerning your product. The
registration process is simple and can ONLY be done online. When registering
please ensure that ALL information is filled in, including a valid e-mail
address. PLEASE NOTE : This information is for the sole purpose of
technical support for your disinfection system and will not be used, or
sold, to any other organization for any other purpose. Please refer to
LUMINOR’s Privacy Policy statement at luminoruv.com/privacy-
policy for further information.
For Parts and Service Call
LUMINOR Environmental Inc.
80 Southgate Dr., Unit 4
Guelph, ON, N1G 4P5 Canada
Toll-free: 1.855.837.3801
Email: info@luminoruv.com 80
Southgate Drive, Unit 4
Guelph, Ontario, CANADA N1G 4P5
P: 519-837-3800
TF: 855-837-3801
F: 519-837-3808
info@luminoruv.com
www.luminoruv.com
PN: 910001
Version Date: 03-2023
References
- Privacy Policy | Luminor
- Canada's Leading Manufacturer of Ultraviolet Water Disinfection Solutions | Luminor
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>