BRADFORD WHITE RE Series Aerotherm Residential Heat Pump Instruction Manual
- June 3, 2024
- Bradford White
Table of Contents
WHITE RE Series Aerotherm Residential Heat Pump
Instruction Manual
RE Series Aerotherm Residential Heat Pump
Recommended clearances:
It is recommended to have a 7” (17.8 cm) clearance between any object and the
rear and sides of the water heater in the event service is needed. A minimum
8“ (20.3cm) learance above the water heater to remove the filter for cleaning
and for service access, and clear access to the front of the water heater, is
recommended. Installations that require less than 7” (17.8 cm) clearance on
the right side or rear of the water heater for earthquake straps are also
acceptable (see Minimum Required Clearances section in the Installation and
Operations Manual for more information) In these cases, additional clearance
must be provided on the opposite side of the unit to allow for service access.
The hot and cold water plumbing and electrical connections must not interfere
with the removal of the filter.
If a separate ducting kit is purchased, additional space is required above and
to the rear of the water heater for installation. Consult the ducting kit
manual for specific instructions.
TYPICAL INSTALLATION
Room size:
Because this unit draws in air from the room to heat the water, the room must
be at least 10’ x 10’ x 7’ (700ft³) [3.05m x 3.05m x 2.13m (19.82m³)] or
larger. If the room is smaller there must be a louvered door or a ducting kit
installed.
Protect Unit:
During installation cover and protect upper part of the unit from potential
installation debris.
Installation Checklist:
-
Tank location:
– Does room size require louvered door, ducting, or similar ventilation? 10’ x 10’ x 7’ (700 cu. ft.) or 240 square inches (0.15 m 2 ) open air-flow area needed.
– Back of unit away from wall by 7 inches (17.5 cm), and sides have at least 7 inches (17.5 cm) clearance. (Additional clearance for earthquake strap installations).
– Front of unit is free and clear.
– Is the water heater level? If no, add shims under the base of the unit to ensure proper function of sensors. -
Verify Air Filter is installed. (Located in packaging).
-
Plumbing connections:
– Does not prevent air filter removal.
– No leaks after filling the tank with water, either when water is flowing or not. -
Condensate lines are in place:
– Main flexible or rigid drain line installed and directed to a drain or condensate pump. Reducer fittings are not recommended. -
Temperature and pressure-relief valve is working and drain line completed per local code.
-
Electrical: Verify 208/240 VAC to L1 and L2 at tank.
-
Electrical connection does not prevent air filter removal.
-
Verify control panel displays 120°F (49°C) Hybrid mode. Assist user in how to adjust temperature and modes (see “Temperature Adjustment” section of the Installation and Operation Manual).
Normal Startup Conditions:
Once the tank is full and power is energized, you may experience the
following:
Elapsed Time | HEWH Actions | Comments |
---|---|---|
0 to 2 minutes | Unit will go through self-check and display countdown. | This |
2-minute off-time prevents compressor damage.
2 to 22 minutes| Compressor and fan turn on.| This 20-minute period is used to
ensure the tank is full of water (Dry-fire prevention algorithm).
22 minutes and
beyond| Compressor and fan turn off, heating elements turn on. After initial
heat-up, elements turn off and compressor turns on.| The water heater is
operating in Hybrid mode, quickly providing an initial amount of hot water
before switching to
the efficient heat pump for the
majority of heating.
NOTE: Heat Pump operating range is 35°F – 120°F (2°C-49°C).
238-52325-00B 06/22
Printed in USA
Documents / Resources
|
BRADFORD WHITE RE Series Aerotherm Residential Heat
Pump
[pdf] Instruction Manual
RE Series, Aerotherm Residential Heat Pump, RE Series Aerotherm Residential
Heat Pump, Residential Heat Pump, Heat Pump, Pump
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>