TRANE BAYECON354 Packaged Cooling and Gas Electric Installation Guide

August 31, 2024
Trane

BAYECON354 Packaged Cooling and Gas Electric

“`html

Specifications:

  • Product Name: FoundationTM Packaged Cooling and
    Gas/Electric

  • Model Number: BAYECON354*

  • Capacity: 3 to 5 Tons

  • Compatible Units: E/GB036-060 E/GD036-060

Product Usage Instructions:

Installation:

1. Only qualified personnel should install the equipment.

2. Follow the provided installation instructions carefully.

3. Ensure proper field wiring and grounding as per NEC and local
electrical codes.

Operation:

1. Read the manual thoroughly before operating the unit.

2. Observe all safety warnings and precautions.

3. Use only R-454B rated service equipment and components for
maintenance.

Maintenance:

1. Regularly inspect and clean the unit to ensure proper
functioning.

2. Follow recommended maintenance schedules provided in the
manual.

FAQ:

Q: Who should install the equipment?

A: Only qualified personnel should install and
service the equipment to ensure safety and proper functioning.

Q: What refrigerant does the equipment use?

A: The equipment uses R-454B refrigerant, which
is flammable (A2L). Use ONLY R-454B rated service equipment and
components.

“`

Installation Instructions
0 to 100% Low Leak Economizer ­ Horizontal
FoundationTM Packaged Cooling and Gas/Electric 3 to 5 Tons

Model Number: BAYECON354*

Used With: E/GB036-060 E/GD036-060

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

August 2024

ACC-SVN205E-EN

Introduction

Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING

Indicates a potentially hazardous situation which, if not avoided, could

result in death or serious injury.

CAUTION

Indicates a potentially hazardous situation which, if not avoided, could

result in minor or moderate injury. It could

also be used to alert against unsafe

practices.

NOTICE

Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
· Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

©2024

ACC-SVN205E-EN

WARNING Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury. · All Trane personnel must follow the company’s
Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies. · Non-Trane personnel should always follow local regulations.
WARNING R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage. The equipment described in this manual uses R-454B refrigerant which is flammable (A2L). Use ONLY R-454B rated service equipment and components. For specific handling concerns with R-454B, contact your local representative.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
ACC-SVN205E-EN

Introduction
3

Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . 5 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Field Supplied Part . . . . . . . . . . . . . . . . . . . . 5
Field Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Economizer Controller . . . . . . . . . . . . . . . . . . . . 10
Controller User Interface and Keypad . . . . . 10 Use of the Keypad When Working with Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Time-out and Screensaver . . . . . . . . . . . . . 11 Controller Menu Structure . . . . . . . . . . . . . 11
Sequence of Operation . . . . . . . . . . . . . . . . . 16 Initiation of Operating Modes . . . . . . . . . . . . 17 Economizer Setup and Configuration (Field and Factory Installed Option) . . . . . . . . . . . . . . . . . . . . . . . 17 Enthalpy Settings . . . . . . . . . . . . . . . . . . . . . . 17 Powered Exhaust . . . . . . . . . . . . . . . . . . . . . . 18 CO2 Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Occupancy Sensor . . . . . . . . . . . . . . . . . . . . 18 Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Power Loss . . . . . . . . . . . . . . . . . . . . . . . . 19 Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Checkout Tests . . . . . . . . . . . . . . . . . . . . . 19 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 19 To Clear an Alarm . . . . . . . . . . . . . . . . . . . 20 Fault Detection and Diagnostics (FDD) Certification . . . . . . . . . . . . . . . . . . . . . 20
4

ACC-SVN205E-EN

General Information

Inspection

Table 1. Major economizer component list

1. Check carefully for shipping damage. If any damage is

Item

Description

Qty

found, report it immediately, and file a claim against the

3

Panel Fresh air hood, RH

1

transportation company. Replace damaged parts with

4

Panel Fresh air hood, top

1

authorized parts only.

5

Mist eliminator

1

2. Compare the order number on the shipping label with the

6

Panel Fresh air hood, bottom

1

accessory identification information on the ordering and

7

Bracket bottom, Mist eliminator

2

shipping documents to verify that the correct accessory

8

End panel

1

has been received.

9

Installation bag with screws

1

Parts List

10

Harness, mixed air sensor

1

11

Bracket, mixed air sensor

1

Table 1 lists components shown in Figure 1.

12

Roll of Gasket

1

Table 1. Major economizer component list

13

Literature

1

14

Mixed air sensor

1

Item

Description

Qty

15

Label

1

1

Low leak economizer assembly

1

2

Panel Fresh air hood, LH

1

Figure 1. Major economizer components — field installed option

7

3

2

11

10

15

9

7 14
13 12

4
5 6
2 8
Field Supplied Part
NOTICE Corrosion Damage!
Failure to use recommended caulking/sealant could cause corrosion related failures to refrigerant components.

Qty

Decsription

1

Tube Sealant – Trane recommends Sikaflex 221 (SEL00439)

ACC-SVN205E-EN

5

Field Installation

WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

Figure 1. Panel removal

Filter Access Panel
End Panel

HZ Return Panel
2. Install the horizontal return panel onto downflow return opening removed in previous step using nine screws. Figure 3.
Figure 2. Return panel installation

CAUTION Heavy Object!
Failure to follow instructions below could result in severe injury and equipment damage. Economizer weighs over 50 pounds and should be installed by two people.
NOTICE Equipment Damage!
Forcibly turning the motor shaft can damage the gear train and motor beyond repair. Never turn the motor shaft by hand or with a wrench.
1. Remove the filter access panel, unit end panel and horizontal return panel. Retain screws for later use. Discard unit end panel. See Figure 2.

HZ Return Panel
3. Install economizer onto unit. Align edge of both sides of the economizer panel flange with LH and RH side post as shown in Figure 4. Economizer should rest on return base pan as shown.

6

ACC-SVN205E-EN

Figure 3. Economizer installation

Field Installation
c. Attach 7 to 2 and 3 using two screws on each side. d. Attach 4 to 6 using three screws. e. Attach assembly built in Step d to 2 and 3 using five
screws on each side. f. Apply gasket to the fresh air hood assembly, aligning
with three sides of the assembly. g. Insert and slide 8 through 9.
Figure 5. Air hood assembly

HZ Return

Cover Side

Post

Side Post

Base Pan

1

Should Align

Economizer

Economizer

Base Pan

HZ Return Cover

4. Install item 8 onto unit using 10 screws. See Figure 5. Figure 4. Economizer panel installation

Gasket 3

4

Gasket

Gasket

6 2 Gasket

5

7

Gasket 4

6

8
5. Build the fresh air hood assembly per Figure 6. a. Apply gasket to 6, aligning to top edge of 6. b. Apply gasket to 2 and 3 as shown.
ACC-SVN205E-EN

2
6. Install Mixed Air Sensor; refer to Figure 7: a. Remove the front access panel and unit top cover of the unit. b. Remove mixed air sensor, two #6 screws and bracket from kit bag (item 11). Attach mixed air sensor to bracket using the two screws. c. Remove mixed air sensor wire harness from the bag (item 10). Connect harness to the economizer controller MAT pin.
7

Field Installation
d. Route the mixed air sensor wire harness through the bushing located at the top of the evaporator coil and connect to the sensor.
Figure 6. Mixed air temperature sensor installation
Top Cover

Access Panel

Mixed Air Temperature

Sensor Wire

Mixed Air Temperature

Harness

Sensor Wire Harness

Grommet

Pop-in wire tie

Sensor mounting Screws (x2)

Mixed Air Temperature Sensor Mounting Bracket

Pop-in wire tie

a. Locate economizer fault relay (EFR) wire harness (wires 163A and 164A looped near economizer section).
b. Secure unterminated end of the harness with a wire tie in the control panel to the left side of the power terminal block (near the Customer Connection LTB terminal strip).
c. Connect economizer fault relay (EFR) to smart thermostat. Strip 163A and 164A wires and individually wirenut them to the two fault input wires from the thermostat. Terminate the fault input wires on the appropriate input terminals on the thermostat. The thermostat wires need to be rated for 600V, 105C, and UL 1230 or 1231.
d. After mounting and powering the thermostat, configure the thermostat to display a fault message (e.g., Economizer Fault) whenever the dry contact input goes high. Consult thermostat’s user manual for detailed instructions.
e. Configure the thermostat Wi-Fi for connection to the Internet. Consult thermostat’s user manual for detailed instructions.
Figure 8. Economizer fault relay harness (EFR) routing
Top Cover

Mounting Bracket
Screws (x2)

Control Box Access Panel

Mixed Air Temperature Sensor Wire Harness end connection
7. Locate unit economizer control wiring harness plug PPM2A. The plug is located in the upper front section of the return air (attached to unit divider panel). Remove the mating connector plug and connect PPM2A to the economizer wire harness. See Figure 8.
Figure 7. Mating connector plug removal
PPM2A Mating
Connector Plug
8. Remove unit top cover and control box access panel. Route relay harness as shown in Figure 9.
8

Access Panel Route Relay Harness

Relay

Route Relay Harness

EFR (Economizer Fault Relay) Harness ACC-SVN205E-EN

9. Install the fresh air hood build in Step 5 on unit using nine screws and filter access door assembly using 13 screws. See Figure 10.
Figure 9. Fresh air hood installation

Field Installation
Figure 11. End panel and fresh air hood sealing

Seal along with End
Panel Flanges (both sides)
Fresh Air Hood
10. Reinstall filter access panel onto unit using two screws. See Figure 11.
Figure 10. Reinstall filter access panel

Fresh Air Hood Seal along with Fresh Hood Flanges (both sides)

Filter Access Panel
11. Using field supplied silicone sealant, seal all seams, cracks and gaps around the outdoor air damper as illustrated in Figure 12.

ACC-SVN205E-EN

9

Economizer Controller

NOTICE Electrostatic Discharge!
Electrostatic discharge can short equipment circuitry. Ensure that you are properly grounded before handling sensitive electronic equipment.
Notes:
· At power up or after a power outage or brownout (or if power goes below 18 Vac), the controller begins a 5 minute power up delay before enabling mechanical cooling. Power must be above 18 Vac for the delay to become functional.
· The controller will be in Setup mode for the first 60 minutes after powered. If a sensor for outside air or one of the Sylk Bus devices (sensor or actuator) is disconnected during the set up mode, the controller will not alarm that failure. The mixed air temperature sensor is a system critical sensor; if it is removed during the set up mode the controller will alarm. After 60 minutes the controller will change to Operation mode and all components removed or failed will alarm in the operation mode.
· The terminals on MAT, OAT and S-BUS sensors are polarity insensitive.
Controller User Interface and Keypad
The user interface consists of an LCD display and a 4-button keypad on the front of the economizer module. The LCD is a 16 character by 2 line dot matrix display.
Figure 1. Controller user interface and keypad

Table 1. Economizer module – left hand terminal blocks

Label
MAT MAT OAT OAT S-BUS S-BUS
IAQ 2-10 IAQ COM IAQ 24V ACT 2-10 ACT COM ACT 24V

Type

Description

Top Left Terminal Block

20k NTC and Mixed Air Temperature Sensor (polarity COM insensitive connection)

20k NTC and Outdoor Air Temperature Sensor (polarity COM insensitive connection)

SYLK Bus

Sylk Bus Sensor (polarity insensitive connection)

Bottom Left Terminal Block

2 to 10 Vdc Air Quality Sensor Input (e.g. CO2 sensor)

COM Air Quality Sensor Common

24 Vac Air Quality Sensor 24 Vac Source

2 to 10 Vdc Damper Actuator Output (2 to 10 Vdc)

COM Damper Actuator Output Common

24 Vac Damper Actuator 24 Vac Source

n/a

The last pin is not used

Table 2. Economizer module – right hand terminal blocks

Label
AUX2 I OCC E-GND EXH1 AUX1 O
Y2-I Y2-O Y1-I Y1-O
C R

Type

Description

Top Right Terminal Block

n/a

The first pin is not used

24 Vac IN

Shut Down (SD) or Heat (W) Conventional only or Heat Pump Changeover (O/B) in Heat Pump mode

24 Vac IN Occupied / Unoccupied Input

EGND Earth Ground – System Required

24 Vac OUT Exhaust Fan 1 Output

Programmable: 24 Vac OUT Exhaust fan 2 Output or ERV or System Alarm
output

Bottom Right Terminal Block

24 Vac IN

Y2 in – Cooling Stage 2 Input from Space Thermostat

24 Vac OUT

Y2 out – Cooling Stage 2 Output to Stage 2 Mechanical Cooling

24 Vac IN

Y1 in – Cooling Stage 1 Input from Space Thermostat

24 Vac OUT

Y1 out – Cooling Stage 1 Output to Stage 1 Mechanical Cooling

COM 24 Vac Common

24 Vac 24 Vac Power (Hot)

10

ACC-SVN205E-EN

Economizer Controller

Use of the Keypad When Working with Menus

· Navigate to the desired menu.
· Press the button (Enter) to display the first item in the currently displayed menu.

· Use the and parameter.

buttons to scroll to the desired

· Press the button (Enter) to display the value of the currently displayed item.

· Press the button to increase (change) the displayed parameter value.

· Press the button to decrease (change) the displayed parameter value.

Note: When values are displayed, pressing and holding the or buttons causes the display to automatically
increment.

· Press the button to accept the displayed value and store it in non-volatile RAM.

· CHANGE STORED displays.

· Press the button (Menu Up) to return to the menu list.

Time-out and Screensaver

When no buttons have been pressed for 10 minutes, the LCD displays a screensaver, which cycles through the Status items. Each Status item displays in turn and cycles to the next item after 5 seconds.

Controller Menu Structure

Important:

Table 4, p. 12 illustrates the complete hierarchy. Menu parameters will be different depending on your configuration. If you do not have a DCV (CO2) sensor, then none of the DCV parameters appear and only MIN POS will display. If you have a CO2 sensor, the DCV MIN and DCV MAX will appear AND if you have 2 speed fan DCV MIN (high and low speed) and DCV MAX (high and low speed) will appear.

The menus in display order are:

· STATUS

· SETPOINTS

· SYSTEM SETUP

· ADVANCED SETUP

· CHECKOUT

· ALARMS

ACC-SVN205E-EN

11

Economizer Controller

Table 3. Controller menu structure

Menu

Parameter ECON AVAIL(c) ECONOMIZING(c)

Parameter Default Value
NO
NO

OCCUPIED(c)

NO

HEAT PUMP

N/A

STATUS

COOL Y1-IN(c)
COOL Y1-OUT(c) COOL Y2-IN(c)
COOL Y2-OUT(c) MA TEMP(c) DA TEMP OA TEMP(c)
OA HUM(c)
RA TEMP(c)
RA HUM(c)

OFF
OFF OFF OFF . ºF . ºF . ºF
%
. ºF
%

IN CO2(c)

_ ppm

DCV STATUS(c) DAMPER OUT(c)
ACT POS(c) ACT COUNT(c)
ACTUATOR(c)
EXH1 OUT(c)
EXH2 OUT ERV
MECH COOL ON(c) FAN SPEED(c) W (HEAT IN)(c)

N/A 2.0V N/A N/A
N/A
OFF
OFF OFF
0 N/A N/A

Parameter Range and Increment(a)
YES/NO YES/NO
YES/NO
COOL HEAT
ON/OFF
ON/OFF N/A N/A
-40 to 140°F -40 to 140°F -40 to 140°F
0 to 100%
0 to 140°F
0 to 100%
0 to 2000 ppm
ON/OFF 2.0 to 10.0 V
0 to 100% 1 to 65,535 OK/Alarm (on Alarm menu)
ON/OFF ON/OFF ON/OFF 0, 1, or 2 LOW or HIGH ON/OFF

Parameter Recommended
Value(b) N/A N/A
N/A

Notes
YES = Economizing available; the system can use Outdoor Air for free cooling when required.
YES = Outdoor Air being used for 1st stage cooling.
YES = OCC signal received from space thermostat or unitary controller.
YES = 24 Vac on terminal OCC No = 0 Vac on terminal OCC.

N/A

HEAT PUMP is not available.

Y1-I signal from space thermostat or unitary controller for

cooling stage 1.

N/A

ON = 24 Vac on term Y1-I

OFF = 0 Vac on term Y1-I

N/A

Cool Stage 1 Relay Output to mechanical cooling (Y1-OUT terminal).

N/A

COOL Y2-IN is not available.

N/A

COOL Y2-OUT is not available.

N/A

Displays value of measured mixed air from MAT sensor. Displays –.- if not connected, short, or out- of-range.

N/A

DA TEMP is not available.

Displays measured value of outdoor air temperature.

N/A

Displays –°F if sensor sends invalid value, if not connected,

short or out-of-range.

Displays measured value of outdoor humidity from OA Sylk

N/A

Bus sensor. Displays –% if not connected, short, or out- of-

range.

Displays measured value of return air temperature from RA

N/A

Sylk Bus sensor. Displays –°F if sensor sends invalid value,

if not connected, short or out-of-range.

Displays measured value of return air humidity from RA

N/A

Sylk Bus sensor. Displays –% if sensor sends invalid value,

if not connected, short or out-of-range.

Displays value of measured CO2 from CO2 sensor. Invalid

if not connected, short or out-of-range. May be adjusted in

N/A

Advanced menu by Zero offset and Span. 0 to 10 Vdc CO2

sensors require CO2 ZERO to be 400 and CO2 SPAN to be

1600 in Advanced Setup menu.

N/A

Displays ON if above setpoint and OFF if below setpoint, and ONLY if a CO2 sensor is connected.

N/A

Displays output voltage or position to the damper actuator.(d)

N/A

Displays actual position of actuator.

N/A

Displays number of times actuator has cycled. 1 Cycle equals the sum of 180° of movement in any direction.

N/A

Displays Error if voltage or torque is below actuator range

Output of EXH1 terminal. Displays ON when damper

N/A

position reaches programmed percentage setpoint.

ON = 24 Vac Output; OFF = No Output.

N/A

EXH2 OUT is not available.

N/A

ERV is not available.

N/A

Displays number of mechanical cooling stages that are active.

N/A

Displays speed of fan on a 2-speed fan unit

N/A

Displays status of heat on a 2-speed fan unit.

12

ACC-SVN205E-EN

Economizer Controller

Table 3. Controller menu structure (continued)

Menu SETPOINTS

Parameter MAT SET(c) LOW T LOCK(c) DRYBLB SET(c) ENTH CURVE(c) DCV SET(c) MIN POS(c)
VENTMAX(c)
VENTMIN(c) ERV OAT SP EXH1 SET(c)
EXH2 SET

Parameter Default Value 53ºF 32ºF 63ºF ES3 1100ppm 2.8 V
2.8 V
2.25 V
32ºF 50% 75%

Parameter
Range and Increment(a)

Parameter
Recommended Value(b)

Notes

38 to 70°F; increment by 1

53ºF

The economizer will modulate the OA damper to maintain the mixed air temperature at the setpoint.

-45 to 80°F; increment by 1

32ºF

Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on. Commonly referred to as the Compressor lockout. At or below the setpoint the Y1-O will not be energized on the controller.

48 to 80°F; increment by 1

67ºF

Setpoint determines where the economizer will assume outdoor air temperature is good for free cooling; e.g.; at 63ºF setpoint unit will economizer at 62ºF and below and
not economize at 64 ºF and above. There is a a 2ºF deadband.

ES1, ES2, ES3, ES4, or ES5

Enthalpy boundary curves for economizing using single

ES3

enthalpy.

See Table for description of enthalpy curves.

500 to 2000 ppm
increment by 100

1100ppm

Displays ONLY if a CO2 sensor is connected. Setpoint for Demand Control Ventilation of space. Above the setpoint, the OA dampers will modulate open to bring in additional
OA to maintain a space ppm level below the setpoint.

2 to 10 Vdc

Displays ONLY if a CO2 sensor is NOT connected. With 2-

2.8V/3.2V LO/2.8V HI

speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan) settings are required. Default for MIN

POS L is 3.2V and MIN POS H is 2.8V.

2 to 10 Vdc or
100 to 9990 cfm increment by 10

Displays only if a CO2 sensor is connected. Used for Vbz

(ventilation max cfm) setpoint. VENTMAX is the same

setting as MIN POS would be if you did not have the CO2

2.8V/3.2V LO/2.8V HI

sensor. Displays 2 to 10 V if <3 sensors (RA,OA and MA). In DCV CAL ENABLE AUTO mode dampers controlled by

CFM With 2-speed fan units VENTMAX L (low speed fan)

and VENTMAX H (high speed fan) settings are required.

Default for VENTMAX L is 3.2V and VENTMAX H is 2.8V.

2 to 10 Vdc or
100 to 9990 cfm increment by 10

Displays only if CO2 sensor is connected. Used for Va

(ventilation min cfm) setpoint. This is the ventilation for less

than maximum occupancy of the space. Displays 2 to 10 V

2.25V/2.5V LO/2.25V if <3 sensors (RA,OA and MA). Va is only set if DCV is used.

HI

In DCV CAL ENABLE AUTO mode dampers controlled by

CFM With 2-speed fan units VENTMIN L (low speed fan)

and VENTMIN H (high speed fan) settings are required.

Default for VENTMIN L is 2.5V and VENTMIN H is 2.25V.

0 to 50°F;

increment by 1

N/A

ERV OAT SP is not available.

1 to 100%; increment by 1

Setpoint for OA damper position when exhaust fan 1 is powered by the economizer.
50%/65% LO/50% HI With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%

0 to 100%; increment by 1

N/A

EXH2 SET is not available.

ACC-SVN205E-EN

13

Economizer Controller

Table 3. Controller menu structure (continued)

Menu
SYSTEM SETUP
ADVANCED SETUP

Parameter INSTALL(c) UNITS DEG(c) EQUIPMENT(c)
AUX2 I(c)
FAN SPEED(c)
FAN CFM(c) AUX1 OUT
OCC(c) FACTORY DEFAULT(c)
MA LO SET(c) FREEZE POS(c)
CO2 ZERO(c) CO2 SPAN(c)
STG3 DLY

Parameter Default Value 1/1/2011 ºF CONV
N/A
1 speed
5000cfm
NONE
INPUT NO 45ºF CLO 0ppm
2000ppm 2.0h

Parameter
Range and Increment(a)

Parameter
Recommended Value(b)

Notes

Present date

Display order = MM/DD/YY Setting order = DD, MM, then YY.

°F or °C

ºF

Sets economizer controller in degrees Fahrenheit or Celsius.

CONV HP

CONV

CONV = conventional. HP is not available.

Shutdown (SD) Heat (W1) HP(O) HP(B)

Heat (W1)

In CONV mode: SD = Enables configuration of shutdown (default); W = Informs controller that system is in heating mode. NOTE: If using 2-speed fan mode, you must program CONV mode for W. Shutdown is not available in the two-
speed fan mode. In HP O/B mode: HP(O) = energize heat pump on Cool (default); HP(B) = energize heat pump on Heat.

1 speed/ 2 speed

See unit nameplate: Digit 15 = 0 or 1 – 1
speed; Digit 15 = 7 or 9 – 2
speed

Sets economizer controller for operation of 1 speed or 2 speed supply fan. The controller does not control the fan but positions the OA and RA dampers to the heating or
cooling mode. See
page 23 for modes and position.
NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In.

100 to 15000 cfm;
increment by 100

5000cfm

This is the capacity of the RTU. The value is found in the Unit Catalog. The cfm of the fan is only used with DCV CAL
ENABLE AUO

NONE ERV EXH2 SYS

NONE

AUX1 OUT is a programmable output used for System Alarm output.

INPUT or ALWAYS

ALWAYS

When using a setback thermostat with occupancy out (24 Vac), the 24 Vac is input INPUT to the OCC terminal. If no
occupancy output from the thermostat then change program to ALWAYS OR add a jumper from terminal R to
OCC terminal.

NO or YES

Resets all set points to factory defaults when set to YES.

NO

LCD will briefly flash YES and change to NO but all

parameters will change to factory default values.

35 to 55°F; increment by 1°F

45ºF

Temp to activate Freeze Protection (close damper or modulate to MIN POS if temp falls below set value)

CLO MIN

CLO

Damper position when freeze protection is active (closed or MIN POS).

0 to 500 ppm; increment by 10

0ppm

CO2 ppm level to match CO2 sensor start level. 0 to 10 Vdc CO2 sensors require CO2 ZERO to be 400.

1000 to 3000 ppm;
increment by 50

2000ppm

CO2 ppm span to match CO2 sensor; e.g.; 500 to 1500 sensor output would be 500 CO2 zero and 1000 CO2 span. 0 to 10 Vdc CO2 sensors require CO2 SPAN to be 1600.

0 min, 5 min, 15 min, then 15 min intervals.
Up to 4h or OFF

Delay after stage 2 for cool has been active. Turns on 2nd

stage of mechanical cooling when economizer is 1st stage

2.0h

call and mechanical cooling is 2nd stage call. Allows three

stages of cooling, 1 economizer and 2 mechanical. OFF =

no Stage 3 cooling.

14

ACC-SVN205E-EN

Economizer Controller

Table 3. Controller menu structure (continued)

Menu

Parameter

Parameter Default Value

Parameter
Range and Increment(a)

Parameter
Recommended Value(b)

Notes

SD DMPR POS

CLO

CLO OPN

CLO

Indicates shutdown signal from space thermostat or unitary controller. When controller receives 24 Vac input on the SD terminal in conventional mode, the OA damper will open if
programmed for OPN and OA damper will close if programmed for CLO. All other controls, e.g., Y1-O, EXH1,
etc. will shutoff.

DCVCAL ENA

MAN

MAN (manual) AUTO

MAN

Turns on the DCV automatic control of the dampers. Resets ventilation based on the RA, OA and MA sensor conditions.
Requires all sensors (RA, OA, MA and CO2). This operation is not operable with a 2-speed fan unit.

ADVANCED SETUP

MAT T CAL(c) OA T CAL(c)

0.0 F° 0.0 F°

(+/-2.5°F) (+/-2.5°F)

0.0 F° 0.0 F°

Allows for the operator to adjust for an out of calibration temperature sensor
Allows for the operator to adjust for an out of calibration temperature sensor

OA H CAL(c)

0% RH

(+/-10% RH)

0% RH

Allows for the operator to adjust for an out of calibration humidity sensor

RA T CAL(c)

0.0 F°

(+/-2.5°F)

0.0 F°

Allows for the operator to adjust for an out of calibration temperature sensor

RA H CAL(c) DA T CAL(c)

0% RH 0.0 F°

(+/-10% RH) (+/-2.5°F)

0% RH 0.0 F°

Allows for the operator to adjust for an out of calibration humidity sensor
DA T CAL is not available.

2SP FAN DELAY(c)

5 Minutes

0 to 20 minutes in 1 minute increments.

5 Minutes

When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling
before the first stage mechanical cooling is enabled.

DAMPER VMIN-HS

N/A

N/A

N/A

Positions damper to VMIN position.

DAMPER VMAX-HS (LS)(c)

N/A

N/A

N/A

Positions damper to VMAX position. With 2-speed fan units the damper will position to VMAX low speed fan.

DAMPER OPEN(c)

N/A

N/A

DAMPER CLOSE(c)

N/A

N/A

Positions damper to the full open position. Exhaust fan

contacts enable during the DAMPER OPEN test.

N/A

Make sure you pause in this mode to allow for exhaust

contacts to energize due to the delay in the system.

N/A

Positions damper to the fully closed position.

CHECKOUT

CONNECT Y1-O(c)

N/A

N/A

N/A

CONNECT Y2-O(c)

N/A

N/A

N/A

Closes the Y1-O relay (Y1-O). See “Electrostatic Discharge!,” p. 17
N/A

CONNECT AUX1-O(c)

N/A

N/A

CONNECT EXH1(c)

N/A

N/A

CONNECT AUX1 O energizes the AUX1-O output. If

AUX1-O setting is:

· NONE — No action taken

N/A

· ERV — 24 Vac out. Turns on or signals an ERV that the

conditions are not good for economizing but are good for

ERV operation.

· SYS — 24 Vax out. Issues a system alarm.

N/A

Closes the power exhaust fan 1 relay (EXH1)

MAT SENS ERR

N/A

N/A

N/A

CO2 SENS ERR(c)

N/A

N/A

N/A

OAT SENS ERR(c)

N/A

N/A

N/A

DA ENTHL ERR

N/A

N/A

ALARMS(_)(e)

SYS ALARM

N/A

N/A

ACT UNDER V(c)

N/A

N/A

ACT OVER V(c)

N/A

N/A

ACT STALLED(c)

N/A

N/A

N/A

DA ENTHL ERR is not available.

N/A

When AUX1-O is set to SYS and there is any alarm the AUX1-O terminal has 24 Vac out.

N/A

Voltage received by Actuator is above expected range

N/A

Voltage received by Actuator is below expected range

N/A

Actuator stopped before achieving commanded position

(a) When values are displayed, pressing and holding the Up or Down button causes the display to automatically increment. (b) N/A = Not Applicable (c) This parameter is directly associated with the LLE economizer. (d) The HoneywellTM communicating actuator will report in XX.X% open versus XX.X Vdc for damper out. (e) Alarms display only when they are active. The menu title ALARMS (_) includes the number of active alarms in parenthesis ().

ACC-SVN205E-EN

15

Economizer Controller
Sequence of Operation

Table 4. Dry bulb operation no DCV (CO2 sensor) – 1 speed fan

OA Good to

DCV

economize?

Y1-I

FAN SPD

None

No

Off

High

On

High

Off

High

None

Yes

On

High

On

High

Y1-O 0-v/Off 24-v/On 0-v/Off 0-v/Off 24-v/On

Table 5. Dry bulb operation with DCV (CO2 sensor) – 1 speed fan

OA Good to

DCV

economize?

Y1-I

FAN SPD

Off

High

No

On

High

Below CO2 set

Off

High

Yes

On

High

On

High

Off

High

No

On

High

Above CO2 set

Off

High

Yes

On

High

On

High

Y1-O 0-v/Off 24-v/On 0-v/Off 0-v/Off 24-v/On 0-v/Off 24-v/On 0-v/Off 0-v/Off 24-v/On

Table 6. Enthalpy operation no DCV (CO2 sensor) – 1 speed fan

DCV

OA Good to

economize?

Y1-I

FAN SPD

None

No

Off

High

On

High

Off

High

None

Yes

On

High

On

High

Y1-O 0-v/Off 24-v/On 0-v/Off 0-v/Off 24-v/On

Table 7. Enthalpy operation with DCV (CO2 sensor) – 1 speed fan

OA Good to

DCV

economize?

Y1-I

FAN SPD

Off

High

No

On

High

Below set

Off

High

Yes

On

High

On

High

Y1-O 0-v/Off 24-v/On 0-v/Off 0-v/Off 24-v/On

Occupied MIN POS MIN POS MIN POS MIN POS to Full- Open MIN POS to Full- Open
Occupied VENTMIN VENTMIN VENTMIN VENTMIN to Full- Open VENTMIN to Full- Open VENTMIN to VENTMAX VENTMIN to VENTMAX VENTMIN to VENTMAX VENTMIN to Full- Open VENTMIN to Full- Open
Occupied MIN POS MIN POS MIN POS MIN POS to Full- Open MIN POS to Full- Open
Occupied VENTMIN VENTMIN VENTMIN VENTMIN to Full- Open VENTMIN to Full- Open

Unoccupied Closed Closed Closed
Closed to Full-Open Closed to Full-Open
Unoccupied Closed Closed Closed
Closed to Full-Open Closed to Full-Open
Closed Closed Closed Closed to Full-Open Closed to Full-Open
Unoccupied Closed Closed Closed
Closed to Full-Open Closed to Full-Open
Unoccupied Closed Closed Closed
Closed to Full-Open Closed to Full-Open

16

ACC-SVN205E-EN

Economizer Controller

Table 7. Enthalpy operation with DCV (CO2 sensor) – 1 speed fan (continued)

OA Good to

DCV

economize?

Y1-I

FAN SPD

Y1-O

Occupied

Off

High

0-v/Off

VENTMIN to VENTMAX

No

On

High

24-v/On

VENTMIN L to VENTMAX

Above set

Off

High

0-v/Off

VENTMIN L to VENTMAX

Yes

On

High

0-v/Off

VENTMIN to Full- Open

On

High

DELAY 24-v/On

VENTMIN to Full- Open

Unoccupied Closed Closed Closed
Closed to Full-Open Closed to Full-Open

Initiation of Operating Modes
The JADE controller is able to initiate the following modes: Compressor, Economizer, Fans, Heating System, and Cooling System. Compressor mode is initiated by either the OAT going above the DRYBLB SET setting or by the thermostat initiating a call to cool when the damper is at 100 percent open. The Economizer mode is controlled by the MAT getting above the MAT SET setting while the OAT is below the DRYBLB SET setting. While the fans are not controlled by the controller, the Fan mode is dependent on what state the system is in (OCC or Y1 states will cause the damper to go to a LOW fan speed damper setting, while W state will cause the controller to open the damper to the HIGH fan speed damper setting). The Heating System mode requires an input to the AUX2-1 terminal from the thermostat, and the Cooling System mode requires an input to the Y1 IN terminals from the thermostat.
Economizer Setup and Configuration (Field and Factory Installed Option)
Before being placed into service the controller must be setup and configured for the installed system. Important: During setup, the economizer controller is live
at all times. 1. Using the keypad on the controller scroll through the
Setpoints, System Setup, and Advanced Setup menus and verify or set/change the parameters. See Table 4, p. 12. 2. Install front filter access panel back on to unit and secure with previous screws. Notes: · The W (heating mode) is not controlled by the controller but it requires the status to know where to position the outside air damper for minimum position for the fan speed. · All setpoints and advanced settings are restored after any power loss or interruption.
ACC-SVN205E-EN

Enthalpy Settings

NOTICE
Electrostatic Discharge!
Electrostatic discharge can short equipment circuitry. Ensure that you are properly grounded before handling sensitive electronic equipment.

When the outside air temperature, enthalpy, and dew point are below the respective setpoints, the outdoor air can be used for economizing. See Figure 14, p. 18.
Note: The controller calculates the enthalpy and dew point using the outside air temperature and humidity input from the outside air sensor.
1. There are 5 boundaries (setpoints ES1 through ES5), which are defined by dry bulb temperature, enthalpy and dew point. See Table 9, p. 17.
2. When conditions are below the selected boundary, the economizer sets the economizing mode to YES and economizing is available. When conditions are above the selected boundary, the conditions are not good to economize and the mode is set to NO.
Note: When using the enthalpy (Sylk Bus) sensors, there will be a slight delay while the controller and the sensor communicate. Analog sensors do not communicate on the Sylk Bus and output a 20k ohm signal to the controller with an instantaneous response time.

Table 8. Single enthalpy and dual enthalpy boundaries (parameters ES1 through ES5)

Enth. Curve

Temp. dryBulb (ºF)

Temp. dew point (ºF)

Enth. (btu/lb/
da)

Point P1
Temp. Humid. ºF %RH

Point P2
Temp. Humid. ºF %RH

ES1 80.0 60.0 28.0 80.0 36.8 66.3 80.1

ES2 75.0 57.0 26.0 75.0 39.6 63.3 80.0

ES3 70.0 54.0 24.0 70.0 42.3 59.7 81.4

ES4 65.0 51.0 22.0 65.0 44.8 55.7 84.2

ES5 60.0 48.0 20.0 60.0 46.9 51.3 88.5

HL 86.0 66.0 32.4 86.0 38.9 72.4 80.3

Note: For differential enthalpy there is a high limit boundary. The high limit boundary is ES1 when there are no stages of mechanical cooling energized and HL when a compressor stage is energized.
17

Economizer Controller

Figure 2. Single enthalpy curve and boundaries

ECONOMIZING AVAILABLE NOT AVAILABLE

ENTHALPY

RA HUM (%RH)

DUAL ENTHALPY HIGH LIMIT
SINGLE ENTHALPY P2 (T,RH)
P1 (T,RH)

RA TEMP ABSOLUTE HUMIDITY

TEMPERATURE
Note: When the OA temperature, OA humidity, and the OA dew point are all below the selected boundary, the economizer sets the economizing mode to YES (economizing is available).
Powered Exhaust
To configure the LLE controller, set EXH1 SET in the SETPOINTS menu.
CO2 Sensor
This optional sensor can be added for Demand Control Ventilation (DCV) functionality. To configure the JADE controller, set the following parameters: SETPOINTS Menu: DCV SET = desired CO2 ppm to start DCV VENTMAX = desired maximum position w/DCV and occupied status VENTMIN = desired minimum position w/DCV and occupied status ADVANCED SETUP Menu: CO2 ZERO = set to detectors start level CO2 SPAN = detector’s max level minus start level Attach the sensor to the CO2 and R terminals (at customer connections). Note: When using any 0 to 10 Vdc CO2 sensor with the JADE
set CO2 ZERO to 400 ppm and the CO2 SPAN to 1600 ppm in the ADVANCED SETUP menu.

ES5 ES4 ES3 ES2 ES1 HL M32286
Occupancy Sensor
A customer-supplied occupancy sensor can also be added to provide damper control based on occupied/unoccupied conditions. To configure the JADE controller, set:
SYSTEM SETUP menu: OCC = INPUT
Attach the occupancy sensor to the OCC SENSOR wire and R terminal (at customer connections). The occupancy sensor must utilize a normally open contact for proper operation.
If an occupancy sensor is not used, another option to controlling occupied and unoccupied status is to use the G input (fan is running). Connect the G input to the OCC SENSOR wire (at customer connections). The controller will then operate in the occupied mode every time the indoor fan is running.
Checkout
WARNING Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
Inspect all wiring connections at the economizer modules terminals, and verify compliance with the installation wiring diagrams.
For checkout, review the status of each configured parameter and perform the checkout tests.

18

ACC-SVN205E-EN

Power Up
After the module is mounted and wired, apply power.
Power Up Delay
At power up (or after a power outage or brownout), the controller module begins a 5 minute power up delay before enabling mechanical cooling.
Initial Menu Display
On initial start-up, Honeywell displays on the first line and Economizer W7220 on the second line. After a brief pause, the revision of the software appears on the first line and the second line will be blank.
Power Loss
All setpoints and advanced settings are restored after any power loss or interruption.
Note: If power goes below 18 Vac, the controller module assumes a power loss and the 5 minute power up delay will become functional when power returns above 18 Vac.
Status
Use the Status menu (see Table 4, p. 12) to check the parameter values for the various devices and sensors configured.
Note: See “Controller User Interface and Keypad,” p. 10″ for information about menu navigation and use of the keypad.
Checkout Tests

NOTICE
Compressor Damage!
Failure to ensure enough time for compressor start-up and shutdown between checkout tests could result in compressor damage. Do not short-cycle compressors.

Use the Checkout menu (Table 4, p. 12) to test the damper operation and any configured outputs. Only items that are configured are shown in the Checkout menu.

To perform checkout tests:

1. Scroll to the desired test in the Checkout menu using the and buttons.

2. Press the button to select the item.

3. RUN? is displayed.

4. Press to start the test.

5. The unit pauses and then displays IN PROGRESS.

6. When the test is complete, DONE appears.

7. When all parameters have been tested, press Up) to end the test (e.g. turn off the relay).

(Menu

ACC-SVN205E-EN

Economizer Controller
Notes: · The checkout tests can all be performed at the time of
installation or any time during the operation of the system. · To disable economizer for functional testing (optional), use
10 mm wrench to loosen shaft coupling on actuator. After testing, securely tighten coupling onto damper shaft using minimum 120 lb-in. (13.6 Nm) to maximum 180 lb-in. (20.3 Nm) torque.
Troubleshooting

WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.

NOTICE
Compressor Damage!
Failure to ensure enough time for compressor start-up and shutdown between checkout tests could result in compressor damage. Do not short-cycle compressors.

The economizer controller provides alarm messages that display on the 2-line LCD.
If one or more alarms are present and there has been no keypad activity for at least 5 minutes, the Alarms menu displays and cycles through the active alarms.
You can also navigate to the Alarms menu at any time.
Note: Upon power up, the module waits 60 minutes before checking for alarms. This allows time for all the configured devices (e.g. sensors, actuator) to become operational. The exception is the MA sensor which will alarm immediately.
Table 9. FDD troubleshooting

FAULTS

TESTS

Air temp. Not econo- Econo-

sensor mizing mizing

failure/ when it when it

fault

should should not

Damper not
modulating

Excess outdoor air

Damper Stuck Open

x

x

x

Damper Stuck at Minimum

x

x

Bad or Unplugged Actuator

x

x

x

Sensor Hard Failure x

x

x

x

Actuator Mechanically Disconnected

x

x

x

x

19

Economizer Controller
To Clear an Alarm
Once the alarm has been identified and the cause has been removed (e.g. replaced faulty sensor), the alarm can be cleared from the display. 1. Navigate to the desired alarm. 2. Press . 3. ERASE? is displayed. 4. Press . 5. ALARM ERASED is displayed.
Figure 3. Ultra low leak economizer wiring diagram

6. Press (Menu Up) to complete the action and return to the previous menu.
Note: If an alarm still exists after you clear it, it redisplays within 5 seconds.
Fault Detection and Diagnostics (FDD) Certification
The JADE controller is a certified FDD product (HJW10) by California Title 24, Part 6.

TSAT INPUT

OPTIONAL ULTRA LOW LEAK ECONOMIZER

5 6 MAS 7 122B(BL)

10 ECON-MAT 121B(R) 1 1 122B(BL) 2 2 MAT

126B(BL)

OAT 10

ECON-OAE 125B(R) 1 1 126B(BL) 2 2 OAT

OAE

5 6 7 ECON-OAH

123B(R) 1 1

124B(BL) 2 2 S-BUS

RAE

6

7

ECON-RAE

129B(R)

11

130B(BL)

2 2 S-BUS

ECA

S-BUS 4

BR

S-BUS 3

W

COM 2 BK

24 VAC 1

R

ECON-SBUS BR 1 1 W 22

S-BUS

ECON-IAQ 151C(BK) 1 1
22
33

IAQ 2-10 IAQ COM IAQ 24V+

ECON-ACT 11
BK 2 2 R 33 44

ACT 2-10 ACT COM ACT 24V+

ECON

12 4 EFR

ECON 44

164A(BK)

SD-O/B 3 OCC 2
E-GND 1

3 2 159A(BK) 159A(BK) 1 101AH(G)

2 163A(BK) 164A(BK)
11 159B(BK)

SIGNAL

EXH-1 AUX

ECON-EXH-AUX 2 2 157C(R) 1 1 162A(BK)

ECON-Y1/Y2

Y1-O 1 Y1-I 2 Y2-O 3 Y2-I 4

1 140C(Y) 2 111E(Y) 3 141C(Y) 4 110F(Y)

ECON-RC
C 2 2 101AF(BL) R 1 1 104K(R)

157C(R)

157B(R)

EFR

1

3 100AU(W)

100AU(W) 101AG(BL) LTB2-2 W16(BL)
XFR

PPM2 111E(Y) 1
2
3
4
104K(R) 5 101AG(BL) 6
110F(Y) 7 141C(Y) 8 140C(Y) 9
10
151C(BK) 11 12

EFR-108 9

W16(BL)

157B(R)

OPTIONAL POWER EXHAUST

NOTE. 5 REQUIRED FOR OPTIONAL REFERENCE ENTHALPY CONTROL.

6 REQUIRED FOR OPTIONAL COMPARATIVE ENTHALPY CONTROL.

7 OPTIONAL MAS, RAS, RHS, OHS AND ASSOCIATED WIRING NOT USED WITH MOTORIZED (NON-MODULATING) OR MANUAL OUTSIDE AIR DAMPER.
9 TO INSTALL OPTIONAL ECONOMIZERS, REMOVE PLUG PPM2A FROM PPF2, AND CONNECT ECONOMIZER PLUG PPM2.
10 REQUIRED FOR OPTIONAL DRY BULB CONTROL

11 OPTIONAL OCCUPANCY SENSOR CONNECTOR

12 WIRES ARE ROUTED INTO CONTROL BOX FOR OPTIONAL CUSTOMER CONNECTIONS, IN USE WITH LOW-LEAK ECONOMIZERS.

20

ACC-SVN205E-EN

Notes

ACC-SVN205E-EN

21

Notes

22

ACC-SVN205E-EN

Notes

ACC-SVN205E-EN

23

Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.
Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

ACC-SVN205E-EN 23 Aug 2024
Supersedes ACC-SVN205D-EN (Jul 2024)

©2024

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Trane User Manuals

Related Manuals