TRANE BAYECON354 Packaged Cooling and Gas Electric Installation Guide
- August 31, 2024
- Trane
Table of Contents
BAYECON354 Packaged Cooling and Gas Electric
“`html
Specifications:
-
Product Name: FoundationTM Packaged Cooling and
Gas/Electric -
Model Number: BAYECON354*
-
Capacity: 3 to 5 Tons
-
Compatible Units: E/GB036-060 E/GD036-060
Product Usage Instructions:
Installation:
1. Only qualified personnel should install the equipment.
2. Follow the provided installation instructions carefully.
3. Ensure proper field wiring and grounding as per NEC and local
electrical codes.
Operation:
1. Read the manual thoroughly before operating the unit.
2. Observe all safety warnings and precautions.
3. Use only R-454B rated service equipment and components for
maintenance.
Maintenance:
1. Regularly inspect and clean the unit to ensure proper
functioning.
2. Follow recommended maintenance schedules provided in the
manual.
FAQ:
Q: Who should install the equipment?
A: Only qualified personnel should install and
service the equipment to ensure safety and proper functioning.
Q: What refrigerant does the equipment use?
A: The equipment uses R-454B refrigerant, which
is flammable (A2L). Use ONLY R-454B rated service equipment and
components.
“`
Installation Instructions
0 to 100% Low Leak Economizer Horizontal
FoundationTM Packaged Cooling and Gas/Electric 3 to 5 Tons
Model Number: BAYECON354*
Used With: E/GB036-060 E/GD036-060
SAFETY WARNING
Only qualified personnel should install and service the equipment. The
installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an
unqualified person could result in death or serious injury. When working on
the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
August 2024
ACC-SVN205E-EN
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal
safety and the proper operation of this machine depend upon the strict
observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It could
also be used to alert against unsafe
practices.
NOTICE
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the
earth’s naturally occurring stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified chemicals that may affect
the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs).
Not all refrigerants containing these compounds have the same potential impact
to the environment. Trane advocates the responsible handling of all
refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the
environment, our customers, and the air conditioning industry. All technicians
who handle refrigerants must be certified according to local rules. For the
USA, the Federal Clean Air Act (Section 608) sets forth the requirements for
handling, reclaiming, recovering and recycling of certain refrigerants and the
equipment that is used in these service procedures. In addition, some states
or municipalities may have additional requirements that must also be adhered
to for responsible management of refrigerants. Know the applicable laws and
follow them.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field
wiring MUST be performed by qualified personnel. Improperly installed and
grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring installation and
grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death
or serious injury. Technicians, in order to protect themselves from potential
electrical, mechanical, and chemical hazards, MUST follow precautions in this
manual and on the tags, stickers, and labels, as well as the instructions
below:
· Before installing/servicing this unit, technicians MUST put on all PPE
required for the work being undertaken (Examples; cut resistant
gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing). ALWAYS refer to
appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the
appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and
Labeling of Chemicals) guidelines for information on allowable personal
exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash,
technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other
country-specific requirements for arc flash protection, PRIOR to servicing the
unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT
PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND
EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
©2024
ACC-SVN205E-EN
WARNING Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
· All Trane personnel must follow the company’s
Environmental, Health and Safety (EHS) policies when performing work such as
hot work, electrical, fall protection, lockout/tagout, refrigerant handling,
etc. Where local regulations are more stringent than these policies, those
regulations supersede these policies. · Non-Trane personnel should always
follow local regulations.
WARNING R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result
in equipment failure, and possibly fire, which could result in death, serious
injury, or equipment damage. The equipment described in this manual uses
R-454B refrigerant which is flammable (A2L). Use ONLY R-454B rated service
equipment and components. For specific handling concerns with R-454B, contact
your local representative.
Copyright
This document and the information in it are the property of Trane, and may not
be used or reproduced in whole or in part without written permission. Trane
reserves the right to revise this publication at any time, and to make changes
to its content without obligation to notify any person of such revision or
change.
Trademarks
All trademarks referenced in this document are the trademarks of their
respective owners.
ACC-SVN205E-EN
Introduction
3
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . 5 Inspection
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Parts List . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . 5
Field Supplied Part . . . . . . . . . . . . . . . . . . . . 5
Field Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Economizer Controller . . . . . . . . . . . . . . . . . . . . 10
Controller User Interface and Keypad . . . . . 10 Use of the Keypad When
Working with Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Time-out and Screensaver . . . . . . . . . . . . . 11 Controller Menu
Structure . . . . . . . . . . . . . 11
Sequence of Operation . . . . . . . . . . . . . . . . . 16 Initiation of
Operating Modes . . . . . . . . . . . . 17 Economizer Setup and Configuration
(Field and Factory Installed Option) . . . . . . . . . . . . . . . . . . . . .
. . 17 Enthalpy Settings . . . . . . . . . . . . . . . . . . . . . . 17
Powered Exhaust . . . . . . . . . . . . . . . . . . . . . . 18 CO2 Sensor . .
. . . . . . . . . . . . . . . . . . . . . . . . 18 Occupancy Sensor . . . . .
. . . . . . . . . . . . . . . 18 Checkout . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 18
Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Power Loss . .
. . . . . . . . . . . . . . . . . . . . . . 19 Status . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 19 Checkout Tests . . . . . . . . . . . . .
. . . . . . . . 19 Troubleshooting . . . . . . . . . . . . . . . . . . . . . .
. 19 To Clear an Alarm . . . . . . . . . . . . . . . . . . . 20 Fault
Detection and Diagnostics (FDD) Certification . . . . . . . . . . . . . . . .
. . . . . 20
4
ACC-SVN205E-EN
General Information
Inspection
Table 1. Major economizer component list
1. Check carefully for shipping damage. If any damage is
Item
Description
Qty
found, report it immediately, and file a claim against the
3
Panel Fresh air hood, RH
1
transportation company. Replace damaged parts with
4
Panel Fresh air hood, top
1
authorized parts only.
5
Mist eliminator
1
2. Compare the order number on the shipping label with the
6
Panel Fresh air hood, bottom
1
accessory identification information on the ordering and
7
Bracket bottom, Mist eliminator
2
shipping documents to verify that the correct accessory
8
End panel
1
has been received.
9
Installation bag with screws
1
Parts List
10
Harness, mixed air sensor
1
11
Bracket, mixed air sensor
1
Table 1 lists components shown in Figure 1.
12
Roll of Gasket
1
Table 1. Major economizer component list
13
Literature
1
14
Mixed air sensor
1
Item
Description
Qty
15
Label
1
1
Low leak economizer assembly
1
2
Panel Fresh air hood, LH
1
Figure 1. Major economizer components — field installed option
7
3
2
11
10
15
9
7 14
13 12
4
5 6
2 8
Field Supplied Part
NOTICE Corrosion Damage!
Failure to use recommended caulking/sealant could cause corrosion related
failures to refrigerant components.
Qty
Decsription
1
Tube Sealant – Trane recommends Sikaflex 221 (SEL00439)
ACC-SVN205E-EN
5
Field Installation
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers,
and labels could result in death or serious injury. Technicians, in order to
protect themselves from potential electrical, mechanical, and chemical
hazards, MUST follow precautions in this manual and on the tags, stickers, and
labels, as well as the following instructions: Unless specified otherwise,
disconnect all electrical power including remote disconnect and discharge all
energy storing devices such as capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently
energized. When necessary to work with live electrical components, have a
qualified licensed electrician or other individual who has been trained in
handling live electrical components perform these tasks.
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury. Disconnect all electric power, including
remote disconnects and discharge all motor start/run capacitors before
servicing. Follow proper lockout/ tagout procedures to ensure the power cannot
be inadvertently energized. Verify with a CAT III or IV voltmeter rated per
NFPA 70E that all capacitors have discharged.
Figure 1. Panel removal
Filter Access Panel
End Panel
HZ Return Panel
2. Install the horizontal return panel onto downflow return opening removed
in previous step using nine screws. Figure 3.
Figure 2. Return panel installation
CAUTION Heavy Object!
Failure to follow instructions below could result in severe injury and
equipment damage. Economizer weighs over 50 pounds and should be installed by
two people.
NOTICE Equipment Damage!
Forcibly turning the motor shaft can damage the gear train and motor beyond
repair. Never turn the motor shaft by hand or with a wrench.
1. Remove the filter access panel, unit end panel and horizontal return
panel. Retain screws for later use. Discard unit end panel. See Figure 2.
HZ Return Panel
3. Install economizer onto unit. Align edge of both sides of the economizer
panel flange with LH and RH side post as shown in Figure 4. Economizer should
rest on return base pan as shown.
6
ACC-SVN205E-EN
Figure 3. Economizer installation
Field Installation
c. Attach 7 to 2 and 3 using two screws on each side. d. Attach 4 to 6 using
three screws. e. Attach assembly built in Step d to 2 and 3 using five
screws on each side. f. Apply gasket to the fresh air hood assembly, aligning
with three sides of the assembly. g. Insert and slide 8 through 9.
Figure 5. Air hood assembly
HZ Return
Cover Side
Post
Side Post
Base Pan
1
Should Align
Economizer
Economizer
Base Pan
HZ Return Cover
4. Install item 8 onto unit using 10 screws. See Figure 5. Figure 4. Economizer panel installation
Gasket 3
4
Gasket
Gasket
6 2 Gasket
5
7
Gasket 4
6
8
5. Build the fresh air hood assembly per Figure 6. a. Apply gasket to 6,
aligning to top edge of 6. b. Apply gasket to 2 and 3 as shown.
ACC-SVN205E-EN
2
6. Install Mixed Air Sensor; refer to Figure 7: a. Remove the front access
panel and unit top cover of the unit. b. Remove mixed air sensor, two #6
screws and bracket from kit bag (item 11). Attach mixed air sensor to bracket
using the two screws. c. Remove mixed air sensor wire harness from the bag
(item 10). Connect harness to the economizer controller MAT pin.
7
Field Installation
d. Route the mixed air sensor wire harness through the bushing located at the
top of the evaporator coil and connect to the sensor.
Figure 6. Mixed air temperature sensor installation
Top Cover
Access Panel
Mixed Air Temperature
Sensor Wire
Mixed Air Temperature
Harness
Sensor Wire Harness
Grommet
Pop-in wire tie
Sensor mounting Screws (x2)
Mixed Air Temperature Sensor Mounting Bracket
Pop-in wire tie
a. Locate economizer fault relay (EFR) wire harness (wires 163A and 164A
looped near economizer section).
b. Secure unterminated end of the harness with a wire tie in the control panel
to the left side of the power terminal block (near the Customer Connection LTB
terminal strip).
c. Connect economizer fault relay (EFR) to smart thermostat. Strip 163A and
164A wires and individually wirenut them to the two fault input wires from the
thermostat. Terminate the fault input wires on the appropriate input terminals
on the thermostat. The thermostat wires need to be rated for 600V, 105C, and
UL 1230 or 1231.
d. After mounting and powering the thermostat, configure the thermostat to
display a fault message (e.g., Economizer Fault) whenever the dry contact
input goes high. Consult thermostat’s user manual for detailed instructions.
e. Configure the thermostat Wi-Fi for connection to the Internet. Consult
thermostat’s user manual for detailed instructions.
Figure 8. Economizer fault relay harness (EFR) routing
Top Cover
Mounting Bracket
Screws (x2)
Control Box Access Panel
Mixed Air Temperature Sensor Wire Harness end connection
7. Locate unit economizer control wiring harness plug PPM2A. The plug is
located in the upper front section of the return air (attached to unit divider
panel). Remove the mating connector plug and connect PPM2A to the economizer
wire harness. See Figure 8.
Figure 7. Mating connector plug removal
PPM2A Mating
Connector Plug
8. Remove unit top cover and control box access panel. Route relay harness as
shown in Figure 9.
8
Access Panel Route Relay Harness
Relay
Route Relay Harness
EFR (Economizer Fault Relay) Harness ACC-SVN205E-EN
9. Install the fresh air hood build in Step 5 on unit using nine screws and
filter access door assembly using 13 screws. See Figure 10.
Figure 9. Fresh air hood installation
Field Installation
Figure 11. End panel and fresh air hood sealing
Seal along with End
Panel Flanges (both sides)
Fresh Air Hood
10. Reinstall filter access panel onto unit using two screws. See Figure 11.
Figure 10. Reinstall filter access panel
Fresh Air Hood Seal along with Fresh Hood Flanges (both sides)
Filter Access Panel
11. Using field supplied silicone sealant, seal all seams, cracks and gaps
around the outdoor air damper as illustrated in Figure 12.
ACC-SVN205E-EN
9
Economizer Controller
NOTICE Electrostatic Discharge!
Electrostatic discharge can short equipment circuitry. Ensure that you are
properly grounded before handling sensitive electronic equipment.
Notes:
· At power up or after a power outage or brownout (or if power goes below 18
Vac), the controller begins a 5 minute power up delay before enabling
mechanical cooling. Power must be above 18 Vac for the delay to become
functional.
· The controller will be in Setup mode for the first 60 minutes after powered.
If a sensor for outside air or one of the Sylk Bus devices (sensor or
actuator) is disconnected during the set up mode, the controller will not
alarm that failure. The mixed air temperature sensor is a system critical
sensor; if it is removed during the set up mode the controller will alarm.
After 60 minutes the controller will change to Operation mode and all
components removed or failed will alarm in the operation mode.
· The terminals on MAT, OAT and S-BUS sensors are polarity insensitive.
Controller User Interface and Keypad
The user interface consists of an LCD display and a 4-button keypad on the
front of the economizer module. The LCD is a 16 character by 2 line dot matrix
display.
Figure 1. Controller user interface and keypad
Table 1. Economizer module – left hand terminal blocks
Label
MAT MAT OAT OAT S-BUS S-BUS
IAQ 2-10 IAQ COM IAQ 24V ACT 2-10 ACT COM ACT 24V
Type
Description
Top Left Terminal Block
20k NTC and Mixed Air Temperature Sensor (polarity COM insensitive connection)
20k NTC and Outdoor Air Temperature Sensor (polarity COM insensitive connection)
SYLK Bus
Sylk Bus Sensor (polarity insensitive connection)
Bottom Left Terminal Block
2 to 10 Vdc Air Quality Sensor Input (e.g. CO2 sensor)
COM Air Quality Sensor Common
24 Vac Air Quality Sensor 24 Vac Source
2 to 10 Vdc Damper Actuator Output (2 to 10 Vdc)
COM Damper Actuator Output Common
24 Vac Damper Actuator 24 Vac Source
n/a
The last pin is not used
Table 2. Economizer module – right hand terminal blocks
Label
AUX2 I OCC E-GND EXH1 AUX1 O
Y2-I Y2-O Y1-I Y1-O
C R
Type
Description
Top Right Terminal Block
n/a
The first pin is not used
24 Vac IN
Shut Down (SD) or Heat (W) Conventional only or Heat Pump Changeover (O/B) in Heat Pump mode
24 Vac IN Occupied / Unoccupied Input
EGND Earth Ground – System Required
24 Vac OUT Exhaust Fan 1 Output
Programmable: 24 Vac OUT Exhaust fan 2 Output or ERV or System Alarm
output
Bottom Right Terminal Block
24 Vac IN
Y2 in – Cooling Stage 2 Input from Space Thermostat
24 Vac OUT
Y2 out – Cooling Stage 2 Output to Stage 2 Mechanical Cooling
24 Vac IN
Y1 in – Cooling Stage 1 Input from Space Thermostat
24 Vac OUT
Y1 out – Cooling Stage 1 Output to Stage 1 Mechanical Cooling
COM 24 Vac Common
24 Vac 24 Vac Power (Hot)
10
ACC-SVN205E-EN
Economizer Controller
Use of the Keypad When Working with Menus
· Navigate to the desired menu.
· Press the button (Enter) to display the first item in the currently
displayed menu.
· Use the and parameter.
buttons to scroll to the desired
· Press the button (Enter) to display the value of the currently displayed item.
· Press the button to increase (change) the displayed parameter value.
· Press the button to decrease (change) the displayed parameter value.
Note: When values are displayed, pressing and holding the or buttons causes
the display to automatically
increment.
· Press the button to accept the displayed value and store it in non-volatile RAM.
· CHANGE STORED displays.
· Press the button (Menu Up) to return to the menu list.
Time-out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD displays a screensaver, which cycles through the Status items. Each Status item displays in turn and cycles to the next item after 5 seconds.
Controller Menu Structure
Important:
Table 4, p. 12 illustrates the complete hierarchy. Menu parameters will be different depending on your configuration. If you do not have a DCV (CO2) sensor, then none of the DCV parameters appear and only MIN POS will display. If you have a CO2 sensor, the DCV MIN and DCV MAX will appear AND if you have 2 speed fan DCV MIN (high and low speed) and DCV MAX (high and low speed) will appear.
The menus in display order are:
· STATUS
· SETPOINTS
· SYSTEM SETUP
· ADVANCED SETUP
· CHECKOUT
· ALARMS
ACC-SVN205E-EN
11
Economizer Controller
Table 3. Controller menu structure
Menu
Parameter ECON AVAIL(c) ECONOMIZING(c)
Parameter Default Value
NO
NO
OCCUPIED(c)
NO
HEAT PUMP
N/A
STATUS
COOL Y1-IN(c)
COOL Y1-OUT(c) COOL Y2-IN(c)
COOL Y2-OUT(c) MA TEMP(c) DA TEMP OA TEMP(c)
OA HUM(c)
RA TEMP(c)
RA HUM(c)
OFF
OFF OFF OFF . ºF . ºF . ºF
%
. ºF
%
IN CO2(c)
_ ppm
DCV STATUS(c) DAMPER OUT(c)
ACT POS(c) ACT COUNT(c)
ACTUATOR(c)
EXH1 OUT(c)
EXH2 OUT ERV
MECH COOL ON(c) FAN SPEED(c) W (HEAT IN)(c)
N/A 2.0V N/A N/A
N/A
OFF
OFF OFF
0 N/A N/A
Parameter Range and Increment(a)
YES/NO YES/NO
YES/NO
COOL HEAT
ON/OFF
ON/OFF N/A N/A
-40 to 140°F -40 to 140°F -40 to 140°F
0 to 100%
0 to 140°F
0 to 100%
0 to 2000 ppm
ON/OFF 2.0 to 10.0 V
0 to 100% 1 to 65,535 OK/Alarm (on Alarm menu)
ON/OFF ON/OFF ON/OFF 0, 1, or 2 LOW or HIGH ON/OFF
Parameter Recommended
Value(b) N/A N/A
N/A
Notes
YES = Economizing available; the system can use Outdoor Air for free cooling
when required.
YES = Outdoor Air being used for 1st stage cooling.
YES = OCC signal received from space thermostat or unitary controller.
YES = 24 Vac on terminal OCC No = 0 Vac on terminal OCC.
N/A
HEAT PUMP is not available.
Y1-I signal from space thermostat or unitary controller for
cooling stage 1.
N/A
ON = 24 Vac on term Y1-I
OFF = 0 Vac on term Y1-I
N/A
Cool Stage 1 Relay Output to mechanical cooling (Y1-OUT terminal).
N/A
COOL Y2-IN is not available.
N/A
COOL Y2-OUT is not available.
N/A
Displays value of measured mixed air from MAT sensor. Displays –.- if not connected, short, or out- of-range.
N/A
DA TEMP is not available.
Displays measured value of outdoor air temperature.
N/A
Displays –°F if sensor sends invalid value, if not connected,
short or out-of-range.
Displays measured value of outdoor humidity from OA Sylk
N/A
Bus sensor. Displays –% if not connected, short, or out- of-
range.
Displays measured value of return air temperature from RA
N/A
Sylk Bus sensor. Displays –°F if sensor sends invalid value,
if not connected, short or out-of-range.
Displays measured value of return air humidity from RA
N/A
Sylk Bus sensor. Displays –% if sensor sends invalid value,
if not connected, short or out-of-range.
Displays value of measured CO2 from CO2 sensor. Invalid
if not connected, short or out-of-range. May be adjusted in
N/A
Advanced menu by Zero offset and Span. 0 to 10 Vdc CO2
sensors require CO2 ZERO to be 400 and CO2 SPAN to be
1600 in Advanced Setup menu.
N/A
Displays ON if above setpoint and OFF if below setpoint, and ONLY if a CO2 sensor is connected.
N/A
Displays output voltage or position to the damper actuator.(d)
N/A
Displays actual position of actuator.
N/A
Displays number of times actuator has cycled. 1 Cycle equals the sum of 180° of movement in any direction.
N/A
Displays Error if voltage or torque is below actuator range
Output of EXH1 terminal. Displays ON when damper
N/A
position reaches programmed percentage setpoint.
ON = 24 Vac Output; OFF = No Output.
N/A
EXH2 OUT is not available.
N/A
ERV is not available.
N/A
Displays number of mechanical cooling stages that are active.
N/A
Displays speed of fan on a 2-speed fan unit
N/A
Displays status of heat on a 2-speed fan unit.
12
ACC-SVN205E-EN
Economizer Controller
Table 3. Controller menu structure (continued)
Menu SETPOINTS
Parameter MAT SET(c) LOW T LOCK(c) DRYBLB SET(c) ENTH CURVE(c) DCV SET(c) MIN
POS(c)
VENTMAX(c)
VENTMIN(c) ERV OAT SP EXH1 SET(c)
EXH2 SET
Parameter Default Value 53ºF 32ºF 63ºF ES3 1100ppm 2.8 V
2.8 V
2.25 V
32ºF 50% 75%
Parameter
Range and Increment(a)
Parameter
Recommended Value(b)
Notes
38 to 70°F; increment by 1
53ºF
The economizer will modulate the OA damper to maintain the mixed air temperature at the setpoint.
-45 to 80°F; increment by 1
32ºF
Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on. Commonly referred to as the Compressor lockout. At or below the setpoint the Y1-O will not be energized on the controller.
48 to 80°F; increment by 1
67ºF
Setpoint determines where the economizer will assume outdoor air temperature
is good for free cooling; e.g.; at 63ºF setpoint unit will economizer at 62ºF
and below and
not economize at 64 ºF and above. There is a a 2ºF deadband.
ES1, ES2, ES3, ES4, or ES5
Enthalpy boundary curves for economizing using single
ES3
enthalpy.
See Table for description of enthalpy curves.
500 to 2000 ppm
increment by 100
1100ppm
Displays ONLY if a CO2 sensor is connected. Setpoint for Demand Control
Ventilation of space. Above the setpoint, the OA dampers will modulate open to
bring in additional
OA to maintain a space ppm level below the setpoint.
2 to 10 Vdc
Displays ONLY if a CO2 sensor is NOT connected. With 2-
2.8V/3.2V LO/2.8V HI
speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan) settings are required. Default for MIN
POS L is 3.2V and MIN POS H is 2.8V.
2 to 10 Vdc or
100 to 9990 cfm increment by 10
Displays only if a CO2 sensor is connected. Used for Vbz
(ventilation max cfm) setpoint. VENTMAX is the same
setting as MIN POS would be if you did not have the CO2
2.8V/3.2V LO/2.8V HI
sensor. Displays 2 to 10 V if <3 sensors (RA,OA and MA). In DCV CAL ENABLE AUTO mode dampers controlled by
CFM With 2-speed fan units VENTMAX L (low speed fan)
and VENTMAX H (high speed fan) settings are required.
Default for VENTMAX L is 3.2V and VENTMAX H is 2.8V.
2 to 10 Vdc or
100 to 9990 cfm increment by 10
Displays only if CO2 sensor is connected. Used for Va
(ventilation min cfm) setpoint. This is the ventilation for less
than maximum occupancy of the space. Displays 2 to 10 V
2.25V/2.5V LO/2.25V if <3 sensors (RA,OA and MA). Va is only set if DCV is used.
HI
In DCV CAL ENABLE AUTO mode dampers controlled by
CFM With 2-speed fan units VENTMIN L (low speed fan)
and VENTMIN H (high speed fan) settings are required.
Default for VENTMIN L is 2.5V and VENTMIN H is 2.25V.
0 to 50°F;
increment by 1
N/A
ERV OAT SP is not available.
1 to 100%; increment by 1
Setpoint for OA damper position when exhaust fan 1 is powered by the
economizer.
50%/65% LO/50% HI With 2-speed fan units Exh1 L (low speed fan) and Exh1 H
(high speed fan) settings are required. Default for Exh1 L is 65% and Exh1 H
is 50%
0 to 100%; increment by 1
N/A
EXH2 SET is not available.
ACC-SVN205E-EN
13
Economizer Controller
Table 3. Controller menu structure (continued)
Menu
SYSTEM SETUP
ADVANCED SETUP
Parameter INSTALL(c) UNITS DEG(c) EQUIPMENT(c)
AUX2 I(c)
FAN SPEED(c)
FAN CFM(c) AUX1 OUT
OCC(c) FACTORY DEFAULT(c)
MA LO SET(c) FREEZE POS(c)
CO2 ZERO(c) CO2 SPAN(c)
STG3 DLY
Parameter Default Value 1/1/2011 ºF CONV
N/A
1 speed
5000cfm
NONE
INPUT NO 45ºF CLO 0ppm
2000ppm 2.0h
Parameter
Range and Increment(a)
Parameter
Recommended Value(b)
Notes
Present date
Display order = MM/DD/YY Setting order = DD, MM, then YY.
°F or °C
ºF
Sets economizer controller in degrees Fahrenheit or Celsius.
CONV HP
CONV
CONV = conventional. HP is not available.
Shutdown (SD) Heat (W1) HP(O) HP(B)
Heat (W1)
In CONV mode: SD = Enables configuration of shutdown (default); W = Informs
controller that system is in heating mode. NOTE: If using 2-speed fan mode,
you must program CONV mode for W. Shutdown is not available in the two-
speed fan mode. In HP O/B mode: HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat.
1 speed/ 2 speed
See unit nameplate: Digit 15 = 0 or 1 – 1
speed; Digit 15 = 7 or 9 – 2
speed
Sets economizer controller for operation of 1 speed or 2 speed supply fan. The
controller does not control the fan but positions the OA and RA dampers to the
heating or
cooling mode. See
page 23 for modes and position.
NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In.
100 to 15000 cfm;
increment by 100
5000cfm
This is the capacity of the RTU. The value is found in the Unit Catalog. The
cfm of the fan is only used with DCV CAL
ENABLE AUO
NONE ERV EXH2 SYS
NONE
AUX1 OUT is a programmable output used for System Alarm output.
INPUT or ALWAYS
ALWAYS
When using a setback thermostat with occupancy out (24 Vac), the 24 Vac is
input INPUT to the OCC terminal. If no
occupancy output from the thermostat then change program to ALWAYS OR add a
jumper from terminal R to
OCC terminal.
NO or YES
Resets all set points to factory defaults when set to YES.
NO
LCD will briefly flash YES and change to NO but all
parameters will change to factory default values.
35 to 55°F; increment by 1°F
45ºF
Temp to activate Freeze Protection (close damper or modulate to MIN POS if temp falls below set value)
CLO MIN
CLO
Damper position when freeze protection is active (closed or MIN POS).
0 to 500 ppm; increment by 10
0ppm
CO2 ppm level to match CO2 sensor start level. 0 to 10 Vdc CO2 sensors require CO2 ZERO to be 400.
1000 to 3000 ppm;
increment by 50
2000ppm
CO2 ppm span to match CO2 sensor; e.g.; 500 to 1500 sensor output would be 500 CO2 zero and 1000 CO2 span. 0 to 10 Vdc CO2 sensors require CO2 SPAN to be 1600.
0 min, 5 min, 15 min, then 15 min intervals.
Up to 4h or OFF
Delay after stage 2 for cool has been active. Turns on 2nd
stage of mechanical cooling when economizer is 1st stage
2.0h
call and mechanical cooling is 2nd stage call. Allows three
stages of cooling, 1 economizer and 2 mechanical. OFF =
no Stage 3 cooling.
14
ACC-SVN205E-EN
Economizer Controller
Table 3. Controller menu structure (continued)
Menu
Parameter
Parameter Default Value
Parameter
Range and Increment(a)
Parameter
Recommended Value(b)
Notes
SD DMPR POS
CLO
CLO OPN
CLO
Indicates shutdown signal from space thermostat or unitary controller. When
controller receives 24 Vac input on the SD terminal in conventional mode, the
OA damper will open if
programmed for OPN and OA damper will close if programmed for CLO. All other
controls, e.g., Y1-O, EXH1,
etc. will shutoff.
DCVCAL ENA
MAN
MAN (manual) AUTO
MAN
Turns on the DCV automatic control of the dampers. Resets ventilation based on
the RA, OA and MA sensor conditions.
Requires all sensors (RA, OA, MA and CO2). This operation is not operable with
a 2-speed fan unit.
ADVANCED SETUP
MAT T CAL(c) OA T CAL(c)
0.0 F° 0.0 F°
(+/-2.5°F) (+/-2.5°F)
0.0 F° 0.0 F°
Allows for the operator to adjust for an out of calibration temperature sensor
Allows for the operator to adjust for an out of calibration temperature sensor
OA H CAL(c)
0% RH
(+/-10% RH)
0% RH
Allows for the operator to adjust for an out of calibration humidity sensor
RA T CAL(c)
0.0 F°
(+/-2.5°F)
0.0 F°
Allows for the operator to adjust for an out of calibration temperature sensor
RA H CAL(c) DA T CAL(c)
0% RH 0.0 F°
(+/-10% RH) (+/-2.5°F)
0% RH 0.0 F°
Allows for the operator to adjust for an out of calibration humidity sensor
DA T CAL is not available.
2SP FAN DELAY(c)
5 Minutes
0 to 20 minutes in 1 minute increments.
5 Minutes
When in economizing mode this is the delay for the high speed fan to try to
satisfy the call for second stage cooling
before the first stage mechanical cooling is enabled.
DAMPER VMIN-HS
N/A
N/A
N/A
Positions damper to VMIN position.
DAMPER VMAX-HS (LS)(c)
N/A
N/A
N/A
Positions damper to VMAX position. With 2-speed fan units the damper will position to VMAX low speed fan.
DAMPER OPEN(c)
N/A
N/A
DAMPER CLOSE(c)
N/A
N/A
Positions damper to the full open position. Exhaust fan
contacts enable during the DAMPER OPEN test.
N/A
Make sure you pause in this mode to allow for exhaust
contacts to energize due to the delay in the system.
N/A
Positions damper to the fully closed position.
CHECKOUT
CONNECT Y1-O(c)
N/A
N/A
N/A
CONNECT Y2-O(c)
N/A
N/A
N/A
Closes the Y1-O relay (Y1-O). See “Electrostatic Discharge!,” p. 17
N/A
CONNECT AUX1-O(c)
N/A
N/A
CONNECT EXH1(c)
N/A
N/A
CONNECT AUX1 O energizes the AUX1-O output. If
AUX1-O setting is:
· NONE — No action taken
N/A
· ERV — 24 Vac out. Turns on or signals an ERV that the
conditions are not good for economizing but are good for
ERV operation.
· SYS — 24 Vax out. Issues a system alarm.
N/A
Closes the power exhaust fan 1 relay (EXH1)
MAT SENS ERR
N/A
N/A
N/A
CO2 SENS ERR(c)
N/A
N/A
N/A
OAT SENS ERR(c)
N/A
N/A
N/A
DA ENTHL ERR
N/A
N/A
ALARMS(_)(e)
SYS ALARM
N/A
N/A
ACT UNDER V(c)
N/A
N/A
ACT OVER V(c)
N/A
N/A
ACT STALLED(c)
N/A
N/A
N/A
DA ENTHL ERR is not available.
N/A
When AUX1-O is set to SYS and there is any alarm the AUX1-O terminal has 24 Vac out.
N/A
Voltage received by Actuator is above expected range
N/A
Voltage received by Actuator is below expected range
N/A
Actuator stopped before achieving commanded position
(a) When values are displayed, pressing and holding the Up or Down button causes the display to automatically increment. (b) N/A = Not Applicable (c) This parameter is directly associated with the LLE economizer. (d) The HoneywellTM communicating actuator will report in XX.X% open versus XX.X Vdc for damper out. (e) Alarms display only when they are active. The menu title ALARMS (_) includes the number of active alarms in parenthesis ().
ACC-SVN205E-EN
15
Economizer Controller
Sequence of Operation
Table 4. Dry bulb operation no DCV (CO2 sensor) – 1 speed fan
OA Good to
DCV
economize?
Y1-I
FAN SPD
None
No
Off
High
On
High
Off
High
None
Yes
On
High
On
High
Y1-O 0-v/Off 24-v/On 0-v/Off 0-v/Off 24-v/On
Table 5. Dry bulb operation with DCV (CO2 sensor) – 1 speed fan
OA Good to
DCV
economize?
Y1-I
FAN SPD
Off
High
No
On
High
Below CO2 set
Off
High
Yes
On
High
On
High
Off
High
No
On
High
Above CO2 set
Off
High
Yes
On
High
On
High
Y1-O 0-v/Off 24-v/On 0-v/Off 0-v/Off 24-v/On 0-v/Off 24-v/On 0-v/Off 0-v/Off 24-v/On
Table 6. Enthalpy operation no DCV (CO2 sensor) – 1 speed fan
DCV
OA Good to
economize?
Y1-I
FAN SPD
None
No
Off
High
On
High
Off
High
None
Yes
On
High
On
High
Y1-O 0-v/Off 24-v/On 0-v/Off 0-v/Off 24-v/On
Table 7. Enthalpy operation with DCV (CO2 sensor) – 1 speed fan
OA Good to
DCV
economize?
Y1-I
FAN SPD
Off
High
No
On
High
Below set
Off
High
Yes
On
High
On
High
Y1-O 0-v/Off 24-v/On 0-v/Off 0-v/Off 24-v/On
Occupied MIN POS MIN POS MIN POS MIN POS to Full- Open MIN POS to Full- Open
Occupied VENTMIN VENTMIN VENTMIN VENTMIN to Full- Open VENTMIN to Full- Open
VENTMIN to VENTMAX VENTMIN to VENTMAX VENTMIN to VENTMAX VENTMIN to Full- Open
VENTMIN to Full- Open
Occupied MIN POS MIN POS MIN POS MIN POS to Full- Open MIN POS to Full- Open
Occupied VENTMIN VENTMIN VENTMIN VENTMIN to Full- Open VENTMIN to Full- Open
Unoccupied Closed Closed Closed
Closed to Full-Open Closed to Full-Open
Unoccupied Closed Closed Closed
Closed to Full-Open Closed to Full-Open
Closed Closed Closed Closed to Full-Open Closed to Full-Open
Unoccupied Closed Closed Closed
Closed to Full-Open Closed to Full-Open
Unoccupied Closed Closed Closed
Closed to Full-Open Closed to Full-Open
16
ACC-SVN205E-EN
Economizer Controller
Table 7. Enthalpy operation with DCV (CO2 sensor) – 1 speed fan (continued)
OA Good to
DCV
economize?
Y1-I
FAN SPD
Y1-O
Occupied
Off
High
0-v/Off
VENTMIN to VENTMAX
No
On
High
24-v/On
VENTMIN L to VENTMAX
Above set
Off
High
0-v/Off
VENTMIN L to VENTMAX
Yes
On
High
0-v/Off
VENTMIN to Full- Open
On
High
DELAY 24-v/On
VENTMIN to Full- Open
Unoccupied Closed Closed Closed
Closed to Full-Open Closed to Full-Open
Initiation of Operating Modes
The JADE controller is able to initiate the following modes: Compressor,
Economizer, Fans, Heating System, and Cooling System. Compressor mode is
initiated by either the OAT going above the DRYBLB SET setting or by the
thermostat initiating a call to cool when the damper is at 100 percent open.
The Economizer mode is controlled by the MAT getting above the MAT SET setting
while the OAT is below the DRYBLB SET setting. While the fans are not
controlled by the controller, the Fan mode is dependent on what state the
system is in (OCC or Y1 states will cause the damper to go to a LOW fan speed
damper setting, while W state will cause the controller to open the damper to
the HIGH fan speed damper setting). The Heating System mode requires an input
to the AUX2-1 terminal from the thermostat, and the Cooling System mode
requires an input to the Y1 IN terminals from the thermostat.
Economizer Setup and Configuration (Field and Factory Installed Option)
Before being placed into service the controller must be setup and configured
for the installed system. Important: During setup, the economizer controller
is live
at all times. 1. Using the keypad on the controller scroll through the
Setpoints, System Setup, and Advanced Setup menus and verify or set/change the
parameters. See Table 4, p. 12. 2. Install front filter access panel back on
to unit and secure with previous screws. Notes: · The W (heating mode) is not
controlled by the controller but it requires the status to know where to
position the outside air damper for minimum position for the fan speed. · All
setpoints and advanced settings are restored after any power loss or
interruption.
ACC-SVN205E-EN
Enthalpy Settings
NOTICE
Electrostatic Discharge!
Electrostatic discharge can short equipment circuitry. Ensure that you are
properly grounded before handling sensitive electronic equipment.
When the outside air temperature, enthalpy, and dew point are below the
respective setpoints, the outdoor air can be used for economizing. See Figure
14, p. 18.
Note: The controller calculates the enthalpy and dew point using the outside
air temperature and humidity input from the outside air sensor.
1. There are 5 boundaries (setpoints ES1 through ES5), which are defined by
dry bulb temperature, enthalpy and dew point. See Table 9, p. 17.
2. When conditions are below the selected boundary, the economizer sets the
economizing mode to YES and economizing is available. When conditions are
above the selected boundary, the conditions are not good to economize and the
mode is set to NO.
Note: When using the enthalpy (Sylk Bus) sensors, there will be a slight delay
while the controller and the sensor communicate. Analog sensors do not
communicate on the Sylk Bus and output a 20k ohm signal to the controller with
an instantaneous response time.
Table 8. Single enthalpy and dual enthalpy boundaries (parameters ES1 through ES5)
Enth. Curve
Temp. dryBulb (ºF)
Temp. dew point (ºF)
Enth. (btu/lb/
da)
Point P1
Temp. Humid. ºF %RH
Point P2
Temp. Humid. ºF %RH
ES1 80.0 60.0 28.0 80.0 36.8 66.3 80.1
ES2 75.0 57.0 26.0 75.0 39.6 63.3 80.0
ES3 70.0 54.0 24.0 70.0 42.3 59.7 81.4
ES4 65.0 51.0 22.0 65.0 44.8 55.7 84.2
ES5 60.0 48.0 20.0 60.0 46.9 51.3 88.5
HL 86.0 66.0 32.4 86.0 38.9 72.4 80.3
Note: For differential enthalpy there is a high limit boundary. The high limit
boundary is ES1 when there are no stages of mechanical cooling energized and
HL when a compressor stage is energized.
17
Economizer Controller
Figure 2. Single enthalpy curve and boundaries
ECONOMIZING AVAILABLE NOT AVAILABLE
ENTHALPY
RA HUM (%RH)
DUAL ENTHALPY HIGH LIMIT
SINGLE ENTHALPY P2 (T,RH)
P1 (T,RH)
RA TEMP ABSOLUTE HUMIDITY
TEMPERATURE
Note: When the OA temperature, OA humidity, and the OA dew point are all below
the selected boundary, the economizer sets the economizing mode to YES
(economizing is available).
Powered Exhaust
To configure the LLE controller, set EXH1 SET in the SETPOINTS menu.
CO2 Sensor
This optional sensor can be added for Demand Control Ventilation (DCV)
functionality. To configure the JADE controller, set the following parameters:
SETPOINTS Menu: DCV SET = desired CO2 ppm to start DCV VENTMAX = desired
maximum position w/DCV and occupied status VENTMIN = desired minimum position
w/DCV and occupied status ADVANCED SETUP Menu: CO2 ZERO = set to detectors
start level CO2 SPAN = detector’s max level minus start level Attach the
sensor to the CO2 and R terminals (at customer connections). Note: When using
any 0 to 10 Vdc CO2 sensor with the JADE
set CO2 ZERO to 400 ppm and the CO2 SPAN to 1600 ppm in the ADVANCED SETUP
menu.
ES5 ES4 ES3 ES2 ES1 HL M32286
Occupancy Sensor
A customer-supplied occupancy sensor can also be added to provide damper
control based on occupied/unoccupied conditions. To configure the JADE
controller, set:
SYSTEM SETUP menu: OCC = INPUT
Attach the occupancy sensor to the OCC SENSOR wire and R terminal (at customer
connections). The occupancy sensor must utilize a normally open contact for
proper operation.
If an occupancy sensor is not used, another option to controlling occupied and
unoccupied status is to use the G input (fan is running). Connect the G input
to the OCC SENSOR wire (at customer connections). The controller will then
operate in the occupied mode every time the indoor fan is running.
Checkout
WARNING Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious
injury. Disconnect all electric power, including remote disconnects before
servicing. Follow proper lockout/ tagout procedures to ensure the power can
not be inadvertently energized. Verify that no power is present with a
voltmeter.
Inspect all wiring connections at the economizer modules terminals, and verify
compliance with the installation wiring diagrams.
For checkout, review the status of each configured parameter and perform the
checkout tests.
18
ACC-SVN205E-EN
Power Up
After the module is mounted and wired, apply power.
Power Up Delay
At power up (or after a power outage or brownout), the controller module
begins a 5 minute power up delay before enabling mechanical cooling.
Initial Menu Display
On initial start-up, Honeywell displays on the first line and Economizer W7220
on the second line. After a brief pause, the revision of the software appears
on the first line and the second line will be blank.
Power Loss
All setpoints and advanced settings are restored after any power loss or
interruption.
Note: If power goes below 18 Vac, the controller module assumes a power loss
and the 5 minute power up delay will become functional when power returns
above 18 Vac.
Status
Use the Status menu (see Table 4, p. 12) to check the parameter values for the
various devices and sensors configured.
Note: See “Controller User Interface and Keypad,” p. 10″ for information about
menu navigation and use of the keypad.
Checkout Tests
NOTICE
Compressor Damage!
Failure to ensure enough time for compressor start-up and shutdown between
checkout tests could result in compressor damage. Do not short-cycle
compressors.
Use the Checkout menu (Table 4, p. 12) to test the damper operation and any configured outputs. Only items that are configured are shown in the Checkout menu.
To perform checkout tests:
1. Scroll to the desired test in the Checkout menu using the and buttons.
2. Press the button to select the item.
3. RUN? is displayed.
4. Press to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all parameters have been tested, press Up) to end the test (e.g. turn off the relay).
(Menu
ACC-SVN205E-EN
Economizer Controller
Notes: · The checkout tests can all be performed at the time of
installation or any time during the operation of the system. · To disable
economizer for functional testing (optional), use
10 mm wrench to loosen shaft coupling on actuator. After testing, securely
tighten coupling onto damper shaft using minimum 120 lb-in. (13.6 Nm) to
maximum 180 lb-in. (20.3 Nm) torque.
Troubleshooting
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious
injury. Disconnect all electric power, including remote disconnects before
servicing. Follow proper lockout/ tagout procedures to ensure the power can
not be inadvertently energized. Verify that no power is present with a
voltmeter.
NOTICE
Compressor Damage!
Failure to ensure enough time for compressor start-up and shutdown between
checkout tests could result in compressor damage. Do not short-cycle
compressors.
The economizer controller provides alarm messages that display on the 2-line
LCD.
If one or more alarms are present and there has been no keypad activity for at
least 5 minutes, the Alarms menu displays and cycles through the active
alarms.
You can also navigate to the Alarms menu at any time.
Note: Upon power up, the module waits 60 minutes before checking for alarms.
This allows time for all the configured devices (e.g. sensors, actuator) to
become operational. The exception is the MA sensor which will alarm
immediately.
Table 9. FDD troubleshooting
FAULTS
TESTS
Air temp. Not econo- Econo-
sensor mizing mizing
failure/ when it when it
fault
should should not
Damper not
modulating
Excess outdoor air
Damper Stuck Open
x
x
x
Damper Stuck at Minimum
x
x
Bad or Unplugged Actuator
x
x
x
Sensor Hard Failure x
x
x
x
Actuator Mechanically Disconnected
x
x
x
x
19
Economizer Controller
To Clear an Alarm
Once the alarm has been identified and the cause has been removed (e.g.
replaced faulty sensor), the alarm can be cleared from the display. 1.
Navigate to the desired alarm. 2. Press . 3. ERASE? is displayed. 4. Press .
5. ALARM ERASED is displayed.
Figure 3. Ultra low leak economizer wiring diagram
6. Press (Menu Up) to complete the action and return to the previous menu.
Note: If an alarm still exists after you clear it, it redisplays within 5
seconds.
Fault Detection and Diagnostics (FDD) Certification
The JADE controller is a certified FDD product (HJW10) by California Title 24,
Part 6.
TSAT INPUT
OPTIONAL ULTRA LOW LEAK ECONOMIZER
5 6 MAS 7 122B(BL)
10 ECON-MAT 121B(R) 1 1 122B(BL) 2 2 MAT
126B(BL)
OAT 10
ECON-OAE 125B(R) 1 1 126B(BL) 2 2 OAT
OAE
5 6 7 ECON-OAH
123B(R) 1 1
124B(BL) 2 2 S-BUS
RAE
6
7
ECON-RAE
129B(R)
11
130B(BL)
2 2 S-BUS
ECA
S-BUS 4
BR
S-BUS 3
W
COM 2 BK
24 VAC 1
R
ECON-SBUS BR 1 1 W 22
S-BUS
ECON-IAQ 151C(BK) 1 1
22
33
IAQ 2-10 IAQ COM IAQ 24V+
ECON-ACT 11
BK 2 2 R 33 44
ACT 2-10 ACT COM ACT 24V+
ECON
12 4 EFR
ECON 44
164A(BK)
SD-O/B 3 OCC 2
E-GND 1
3 2 159A(BK) 159A(BK) 1 101AH(G)
2 163A(BK) 164A(BK)
11 159B(BK)
SIGNAL
EXH-1 AUX
ECON-EXH-AUX 2 2 157C(R) 1 1 162A(BK)
ECON-Y1/Y2
Y1-O 1 Y1-I 2 Y2-O 3 Y2-I 4
1 140C(Y) 2 111E(Y) 3 141C(Y) 4 110F(Y)
ECON-RC
C 2 2 101AF(BL) R 1 1 104K(R)
157C(R)
157B(R)
EFR
1
3 100AU(W)
100AU(W) 101AG(BL) LTB2-2 W16(BL)
XFR
PPM2 111E(Y) 1
2
3
4
104K(R) 5 101AG(BL) 6
110F(Y) 7 141C(Y) 8 140C(Y) 9
10
151C(BK) 11 12
EFR-108 9
W16(BL)
157B(R)
OPTIONAL POWER EXHAUST
NOTE. 5 REQUIRED FOR OPTIONAL REFERENCE ENTHALPY CONTROL.
6 REQUIRED FOR OPTIONAL COMPARATIVE ENTHALPY CONTROL.
7 OPTIONAL MAS, RAS, RHS, OHS AND ASSOCIATED WIRING NOT USED WITH MOTORIZED
(NON-MODULATING) OR MANUAL OUTSIDE AIR DAMPER.
9 TO INSTALL OPTIONAL ECONOMIZERS, REMOVE PLUG PPM2A FROM PPF2, AND CONNECT
ECONOMIZER PLUG PPM2.
10 REQUIRED FOR OPTIONAL DRY BULB CONTROL
11 OPTIONAL OCCUPANCY SENSOR CONNECTOR
12 WIRES ARE ROUTED INTO CONTROL BOX FOR OPTIONAL CUSTOMER CONNECTIONS, IN USE WITH LOW-LEAK ECONOMIZERS.
20
ACC-SVN205E-EN
Notes
ACC-SVN205E-EN
21
Notes
22
ACC-SVN205E-EN
Notes
ACC-SVN205E-EN
23
Trane and American Standard create comfortable, energy efficient indoor
environments for commercial and residential applications. For more
information, please visit trane.com or americanstandardair.com.
Trane and American Standard have a policy of continuous product and product
data improvement and reserve the right to change design and specifications
without notice. We are committed to using environmentally conscious print
practices.
ACC-SVN205E-EN 23 Aug 2024
Supersedes ACC-SVN205D-EN (Jul 2024)
©2024
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>