SCHRACK TECHNIK CX Plus Power Factor Controller Instruction Manual
- August 31, 2024
- SCHRACK TECHNIK
Table of Contents
CX Plus Power Factor Controller
“`html
Product Specifications:
-
Brand: Schrack Technik GmbH
-
Model: CX plus
-
Dimensions: 138 x 138 mm
-
Country of Origin: Austria
-
Contact Information: Tel.: +43 1 866 85 5900, Email:
info@schrack.at -
Website: www.schrack.com
Product Usage Instructions:
General Safety Notes:
Failure to observe the following instructions can lead to
serious injury or death:
-
Do not connect devices with damaged or open housings or
terminals to the mains. -
Wait for 10 minutes after disconnecting the device to allow
capacitors to discharge before removing doors or covers. -
Ensure that the compensation system has been de-energized.
Installation and Commissioning:
-
Compare the connection data of the CX plus with the data of the
supply network and installation before installation. -
Disconnect the working area from voltage and secure it against
unauthorized restart. -
Short-circuit the current transformer to prevent high
voltages. -
Disconnect and remove the old reactive power controller.
-
Plug the CX plus into the switch panel section and fix it with
the two mounting brackets. -
Connect the protective conductor to the PE terminal of the
metal back of the CX plus. -
Connect the connecting lines as shown in the wiring
diagram. -
Remove current transformer jumper.
-
Switch on voltage and verify proper connection.
-
Initiate user-guided initial commissioning (FIrSt SEtUP).
Questions During Commissioning:
-
No AUTO display control stopped: Check for manual operation,
switched-off control, high temperature, low current, or voltage/THD
issues. -
U ALARM display voltage out of tolerance: Verify settings for
rated voltage and voltage transformer. -
I Lo ALARM display no current flow: Check for correct
connection from current transformer, removed jumper, transformation
ratio, or lack of current.
Display Information:
The display provides information on stages, operation modes,
settings menu, alarm notifications, and more.
Frequently Asked Questions (FAQ):
Q: What should I do if the device shows a voltage out of
tolerance alarm?
A: Verify settings for rated voltage and voltage transformer in
the SETUP menu.
Q: How do I ensure proper connection during commissioning?
A: Follow the wiring diagram provided with the product and
remove the current transformer jumper.
“`
x
s
English: page 2
Deutsch: Seite 20
Schrack Technik GmbH Seybelgasse 13 1230 Vienna
Austria
Tel.: +43 1 866 85 5900 Fax: +43 866 85 99000 info@schrack.at
www.schrack.com
General safety notes
Failure to observe the following instructions can lead to serious injury or
death !
During installation, there is a risk of electric shock. For this reason,
electrical devices may only be installed, operated, serviced and maintained by
qualified personnel. A qualified person is one who has the ability, experience
and knowledge necessary for the construction, installation and operation of
electrical equipment and is trained in the detection and prevention of
potential hazards. During installation and maintenance, the relevant
regulations for installation of switchgear and for preventing accidents must
be observed and complied with.
Devices with damaged or open housings or terminals may not be connected to the
mains and must be disconnected immediately.
After disconnection of the device, wait for 10 minutes until the capacitors
are discharged before removing doors or covers. After that, check to ensure
that the compensation system has been de- energised.
Beluk GmbH assumes no responsibility or liability for injury to persons or
damage to equipment due to improper installation or installation not for the
intended use carried out by qualified personnel.
New features of the CX plus over the BLR- CX
· Modbus: no longer as an external add- on module, now optionally installed
internally.
· Alarm memory: enables the storage of the last 10 alarms · New alarms: THD I
alarm · I-Low alarm: can be disabled via digital input now:
SETUP/ 500/ 518 “YES” = I-Low alarm blocked · Control algorithm: in addition
to LIFO, AUTOMATIC (best fit) and
PROGRESSIVE, the FIFO algorithm has now also been implemented · Outputs: 6 or
12 stages, separate fan relay (can be used as 7th /13th
stage) · Display: to extend the service life of the backlight, it is turned
off
60 seconds after last usage. · Storage Umax and THD Umax · Digital input:
Choice between target cos1 and target cos2, signalisation of an external alarm
or to disable the I-Low alarm · Temperature sensor: NTC now internal.
Installation and commissioning:
-
Before installation, the connection data of the CX plus must be compared with the data of the supply network and the installation.
-
The working area must be disconnected from voltage and secured against unauthorised and unintentional restart. The absence of voltage must be verified with a standardised instrument/ testing device. The voltage- free system must be grounded and shortcircuited. Adjacent live parts must be covered or placed behind barriers.
-
The current transformer must be short-circuited! A current transformer that has NOT been short-circuited generates very high voltages posing a danger to persons and equipment. The current transformer can thereby be destroyed.
-
Disconnect and remove the old reactive power controller.
-
Plug the CX plus into the switch panel section and fix it with the two mounting brackets. (Section 138 x 138 mm)
-
Connect the protective conductor to the PE terminal of the metal back of the CX plus.
-
Connect the connecting lines as shown in the wiring diagram. (Current transformer: K [power plant] to S1, L [load] to S2)
-
Remove current transformer jumper. 9) Switch on voltage. 10) With a proper connection and correct connection data, the LCD lights
and the LCD test is active for 1 second. 11) Activation of user-guided initial commissioning “FIrSt SEtUP” after
confirming “YES”. Afterwards all required parameters are requested by CX plus. The choice of “NO” requires, that the user implements the following parameters (12) … 15)) manually. 12) The current transformer factor (Ct) must be entered. -
The nominal voltage (Un) and the voltage transformer factor (Pt) must be entered, too. 14) Start the “Automatic initialisation” (AI) or enter the Phaseoffset (PO) manually. 15) If the ,,Automatic initialisation” was successfully finished, the message “AUTO” appears on the LCD. Control starts after the discharge time lock.
Questions during commissioning:
- No AUTO display control stopped Reasons: Manual operation, control is switched off, temperature is too high, current is less than 15 mA, voltage or THD of voltage are not permitted
- U ALARM display voltage out of tolerance Check settings for rated voltage (SETUP/ Un) and voltage transformer (SETUP/ Pt)
- I Lo ALARM display no current flow Possible causes: Connection from the current transformer to the controller is not correct; current transformer jumper is not removed; transformation ratio is too large; no current
- EXPORT display feeding back of active power If there is no real feeding back, connect voltage and check current (phase polarity) section Incorrect connections/ AI automatic initialisation
- Incorrect Cos phi incorrect connection Connect voltage and check current (phase, polarity) section Incorrect connections/ AI automatic initialisation
- Outputs are switched off again immediately section Incorrect connections/ AI automatic initialisation
- Frequent switching of the outputs output of the capacitors first needs to be detected
Display:
I
II
I
II
III
INFO: AUTO: MANUAL: SETUP: ALARM:
Stage database Automatic operation Manual operation Settings menu Alarm memory
EXPORT:
Feeding back of active power
NT:
2nd target cos is active
ALARM:
Flashes if there is an
alarm notification
1st line:
I)
cos / menu items
II) inductive/ capacitive
2nd line:
I)
code of metered and set values
II) metered and set values/ alarm
codes
III) units
Stage display: Status of the stage (on/ off) Stage faulty (flashing)
Operation:
The controller is operated using 4 keys.
Increase values Select menu items
Exit menus/ Esc Cursor to the left Reset alarm (5 sec.)
Decrease values Select menu items
Opens menus/ Enter Cursor to the right Settings
Input parameters:
, Digit adjust (up/ down)
Move to next position
, After the last digit is set, selection of:
– Multiplier k (kilo) or M (Mega)
– Preceding sign i (inductive) or c (capacitive) (flashing of i or c)
Application of values at the end
Abort entry
Main menu:
Select menu items with , , enter the submenu with
Measurement value display: (Change with , )
ULL, ULN, I, P, Q, Q, S, THD U, 3.-19. Har. U,
THD I, 3.-19. Har. I, cos, PF, APF, Hz(F), t(°C), thi (°C), OPh (h), tan, U
hi, THD U hi
INFO stage database: Power and power loss of stages, number of switching
operations, stage type, operating hours. ( section INFO stages database)
MANUAL operation: Intentional switching on and off of switching outputs. (
section MANUAL operation)
SETUP settings menu: Rated voltage (Un), current transformer (Ct), voltage
transformer (Pt), automatic initialisation (AI), control on/ off (PFC), target
cos 1 (CP1), switching time (St), stage type (Out) ( section SETUP settings
menu)
ALARM memory: Memory buffer shows the last 10 alarms. The most recent alarm is
in the first position.
INFO stage database:
Please note: The current status of the outputs is not displayed.
Browse through stages with , and select with . The selected stage flashes. ,
displays the following information:
Current capacitor output The output relates to Un
Output reduction of the capacitor: Current output/ nominal output in %
Number of operation cycles
Stage type: AUTO: Automatically controlled stage Fon: Fixed stage on Foff:
Fixed stage off FLty: Stage faulty and disabled
Operation hours: Shows how many hours the corresponding stage has already been
in operation. Selected stage flashes.
MANUAL operation:
Enter manual operation by pressing for three seconds. Browse stages with , .
The selected stage is displayed in line 2 as a number. switches the stage on
or off. Exit manual operation with .
Important information: – In the menu Manual operation, only stages with stage
type AUTO can
be switched. In LIFO mode, FIFO mode and combined filter mode, the menu Manual
operation is disabled. ( Reference Manual) – The discharge time lock is also
active in manual operation. (Stages are disabled for a certain time after
shutdown) – The voltage must be within the tolerances, otherwise all stages
will shut down. The respective stages can not be switched in Manual operation.
– THD U-, THD I- and overtemperature- Alarm block the switching of stages in
manual mode. – After exiting manual mode, there is automatic control starting
from the set status.
SETUP settings menu:
After opening SETUP, submenu 100 appears. Open menu 100. , Menu 200 – 600 & 800, with optional Modbus: 200 – 800 (locked with password Reference Manual)
Un Rated voltage (correct setting is very important) For voltage monitoring and stages database reference.
Ct Current transformer ratio (must be set) The value is used for calculation and activation of some measurement values in the measurement menu.
Pt Voltage transformer ratio Important as the basis for setting Un
AI Automatic initialisation section Incorrect connection/ AI Automatic initialisation
PFC CONTROL ON/ OFF/ HOLD Switching on, switching off, freezing the control
CP1 Target cos 1 Basis for compensation target
St
Switching time
Defines the speed of the controller
OUt Stage type Defining stage type: AUTO, Fon, Foff, Reset faulty stages (FLty)
Incorrect connection/ AI automatic initialisation:
In case of incorrect connection of the voltage or current path (phase,
polarity), the reactive power controller cannot be operated. Thus, the
connection should be corrected. Since this is not always possible, the CX plus
alternatively provides the following functions:
Automatic initialisation: SETUP/ 100/ AI
The AI switches all outputs on and off several times. This takes a few
minutes. Unused outputs are set to “Foff”. Stage values are not detected
during this process.
After the end of the AI, the function of the controller should be checked.
Requirements for a successful operation of the AI:
– The voltage is within the tolerance – The current transformer is connected
(no simulation) – Capacitor banks are installed, functional and secured
Possible issues for successful AI:
– Load fluctuations – Small current signals
Error messages AI/ Abrt:
AI was aborted because no clear result was possible; the control is OFF.
The Phaseoffset can be entered manually as well: Entering of the correct
Phaseoffset SETUP/ 206 Reference Manual
Stage detection:
During each switching operation, the stage value is determined (except if this
feature is disabled SETUP/ 308 Reference Manual). The detected values are
updated in the stages database. A loss of capacity can be determined there. If
a stage does not work in the first three switching operations, it is
automatically assigned to the stage type Foff.
After commissioning, the existing stages have stage type Foff: Is the current
transformer jumper removed? Is the position of the current transformer
correct? Are all currents and measuring/ operating voltages present?
Faulty stages:
A stage that switches three consecutive times without measurable success is
declared to be faulty. After 24 hours, another test is started. Stage display:
flashes Status: Flty, stage is disabled
Procedure:
Do individual stage symbols flash during operation mode?
Check fuse, contactor and capacitor output of the corresponding stage.
Acknowledgement in SETUP/ 100/ OUt or restart (interruption of the measuring/
supply voltage) of the CX plus.
Alarms:
Alarm system settings: SETUP/ 500 Reference Manual
U
ALARM: Measuring voltage out of tolerance
I Lo
ALARM: Measuring current < 5 mA (check I-measuring path)
SETUP/ 500/ 518 “YES” = I-Low alarm blocked
I Hi
ALARM: Measuring current > 6 A (transformation ratio of the
built-in current transformer is too small)
PFC
ALARM: Compensation target unreachable (check system)
HArU
ALARM: Limit for THD U has been exceeded
HArI
ALARM: Limit for THD I has been exceeded
StEP/ FLtY ALARM: Faulty stages have been detected
SPL/ Nr thi
ALARM: Power loss levels below 75 % Stage number and error code will flash
alternately
ALARM: Overtemperature shutdown of the stages
OPH
ALARM: Max. operation hours device reached (maintenance)
OPC/ Nr OPHS/ Nr AI/ Abrt
ALARM: ALARM:
Max. operation cycles/ operation hours stages reached (maintenance) Stage number and error code will flash alternately Abort of the automatic initialisation Re-start the AI when the grid is calmer or manual setting of the phase offsets (SETUP/ 206 Reference Manual)
Factory settings
SETUP/ 100 IMPORTANT SETTINGS Un/ rated voltage Ct/ current transformer Pt/
voltage transformer AI/ start Ai PFC/ control CP1/ target cos 1 St/ switching
time Out/ stage type
open
400 V 1 1
NO ON
1 10 s AUTO
SETUP/ 200 MEASUREMENT 201/ rated voltage 202/ current transformer 203/ voltage transformer 204/ tolerance voltage 205/ voltage LL 206/ phase offset 207/ start Ai 208/ synchronisation 209/ temperature offset 210/ Option CO2 counter
locked
400 V 1 1
10 % NO 0 NO
AUTO 0°C
SETUP/ 300
locked
CONTROL SETTINGS
301/ sensitivity
60 %
302/ target cos1
1.00
303/ target cos2
i 0.95
304/ EXPORT cos2
NO
305/ switching time
10 s
306/ St stage exchange
2 s
307/ active stage exchange YES
308/ active stage detection YES
309/ lock faulty stages
YES
310/ control on/off/hold
ON
311/ control algorithm
1
312/ offset reactive power 0 var
313/ asymmetry factor
1
314/ Qcap stages Off
NO
315/ stage distribution
NO
316/ detect. def. stages
YES
SETUP/ 400 STAGE DATABASE 401/ discharge time lock 402/ nominal stage value 403/ stage type 404/ operation cycles
locked
75 s c 3 var AUTO
0
405/ stage operation h
0 h
406/ Stage monitoring
YES
Factory settings
SETUP/ 500 ALARM SETTINGS 501/ manual reset 502/ THD U Limit 503/ THD stages off 504/ delay of harm. alarm 505/ I= 0 freeze controller 506/ maintenance alarm 507/ operating cycles limit 508/ limit OPh 509/ limit OPh stage 510/ THD I limit 511/ DI= Hi active 512/ Temp1 limit 513/ Temp2 limit 514/ control alarm 515/ faulty stages alarm 516/ power loss 517/ alarm illumination
locked
NO 20 %
NO 60 s
NO
NO 500 k
65.5 kh 65.5 kh
50 % YES
30 °C 55 °C
NO NO NO NO
407/ fan relay as stage 13
NO
518/ digital input function 519/ info lock I-Low 520/ DI-Alarm switch off
stages 521/ I-Low-Alarm 522/ delay I-High-Alarm 523/ switch off interval 524/
Suppression of the DI alarm
SETUP/ 600 RESET 601/ factory settings 602/ stages database 603/ operating
hours 604/ average power
factor 605/ max. temperature 606/ alarm 607/ firmware info 608/ password
change
CP 2 NO NO YES 10 s 60 s YES locked
242
SETUP/ 700 MODBUS SETTINGS 701/ baud rate 702/ parity 703/ address
SETUP/ 800 Backlight Options 801/ backlight Commissioning-Mode 802/ delay time
DTC / 900 Dynamic transformer compensation 900 / Transorm Rated Power 902 /
relative shortcircuit 903 / Start value 904 / Offset
locked 19200 EVEN
1 locked
NO 0,25 h
DTC 0.0 % 0.0 % 0.0 Var
Technical specifications:
Voltage:
90- 550 V, 1 ph., 50/60 Hz, 6 VA
Current:
5 mA- 6 A, 1 ph., <1 VA,
Switching outputs:
Relay, NO contact,
common contact supply: max. 10 A 250 V AC/ 5 A, 400 V AC/ 1 A
Digital input:
90- 250 V AC
Temperature measurement: NTC, internal
Signal contact:
Pot.- free relay, normally closed contact,
48 V DC/ 1 A, 250 V AC/ 5 A, 400 V AC/ 1 A Optional NO/ NC
Fan control:
Pot.- free relay, 48 V DC/ 1 A, 250 V AC/ 5 A, 400 V AC/ 1 A
Interface:
Optional: RS485 Modbus
Ambient temperature:
Operation: -20 °C to 70 °C Storage: -40 °C to 85 °C
Humidity:
0 %- 95 %, condensing not allowed
Overvoltage category:
300 V LN/ 519 V LL CAT III or 550 V/ CAT II
Connection:
Screw terminals, pluggable
Housing:
Front: Instrument housing, plastic Back: Metal
Protection type:
Front: IP41, Back: IP20
Technical specifications:
Weight:
Approx. 0.6 kg
Dimensions:
Housing: 144 x 144 x 58 mm (WxHxD) Cut-out: 138 (+0.5) x 138 (+0.5) mm
Alarm memory:
Storage of the last 10 alarms
Standards:
IEC 61010- 1 IEC 61000 6- 2 IEC 61000 6- 4: level B IEC 61326- 1
UL 61010
Conformity:
CE, NRTL(UL), c NRTL (cUL), EAC
Algorithms:
AUTOMATIC (best fit) LIFO FIFO PROGRESSIVE
Combined filter
Max. operating height:
2000 m
Max. contamination level: 2
Remark:
Please note that additional more detailed technical information is available
with the following links:
https://image.schrackcdn.com/bedienungsanleitungen/a_fracxp_en_de.pdf https://image.schrackcdn.com/bedienungsanleitungen/a_fracxp12rm_modbus_en_de.pdf
Allgemeine Sicherheitshinweise
Nichtbeachtung der folgenden Anweisungen kann zu schweren Verletzungen oder
zum Tod führen!
Bei der Installation bestehen Gefahren durch elektrischen Stromschlag! Daher
dürfen elektrische Geräte nur von Fachpersonal installiert, betrieben,
gewartet und instandgehalten werden. Eine Fachperson ist die, die die
Fähigkeit, Erfahrung und das nötige Wissen für den Bau, die Installation und
den Betrieb von elektrischen Geräten hat, sowie in der Erkennung und
Vermeidung von möglichen Gefahren unterwiesen ist. Bei der Installation und
Wartung sind die maßgebenden Vorschriften zur Errichtung von Schaltanlagen
sowie zum Unfallschutz zu beachten und einzuhalten.
Geräte mit beschädigten oder offenen Gehäusen oder Anschlussklemmen dürfen
nicht am Netz betrieben werden und sind sofort freizuschalten.
Nach dem Freischalten des Geräts sind 10 Minuten zu warten, bis die
Kondensatoren entladen sind. Erst dann dürfen Türen oder Abdeckungen entfernen
werden. Anschließend ist die Spannungsfreiheit der Kompensationsanlage zu
prüfen.
Die Firma Beluk GmbH übernimmt keine Verantwortung oder Gewährleistung für
Schäden an Mensch und Gerät, die der nicht ordnungsgemäßen und für den
vorgesehenen Gebrauch durch Fachpersonal durchgeführten Installation
geschuldet sind.
Neuerungen vom CX plus gegenüber BLR-CX
· Modbus: bisher externes Zusatzmodul, jetzt optional im Gerät integriert.
· Alarmspeicher: ermöglicht die Speicherung der letzten 10 Alarme · Neue
Alarme: THD I-Alarm · I-Low-Alarm: kann nun über den Digitaleingang
deaktiviert werden:
SETUP/ 500/ 518 ,,YES” = I-Low-Alarm blockiert · Kontrollalgorithmus:
Neben LIFO, AUTOMATIK (best fit) und PROGRESSIVE wurde nun auch der FIFO-
Algorithmus implementiert · Schaltausgänge: 6 oder 12 Stufen, separates
Lüfterrelais (kann als 7. bzw. 13. Stufe verwendet werden) · Display: um die
Lebenszeit der Hintergrundbeleuchtung zu verlängern wird diese nach 60 s ohne
Tastenbetätigung abgeschaltet. · Speicherung Umax und THD Umax · Digitaler
Eingang: entweder zur Umschaltung zwischen Ziel-cos1 und Ziel-cos2,
Unterdrückung des I-Low-Alarms oder Meldung eines externen Alarmsignals ·
Temperatursensor: NTC fest im Gerät integriert.
Installation und Inbetriebnahme:
16) Vor dem Einbau sind die Anschlussdaten des CX plus mit den Daten des
Netzes und der Installation abzugleichen.
17) Grundsätzlich ist der Arbeitsbereich in der Anlage spannungsfrei zu
schalten, sowie gegen unbefugtes und unabsichtliches Wiedereinschalten zu
sichern. Die Spannungsfreiheit ist mit einem genormten Mess-/ Prüfgerät
festzustellen. Die spannungsfreie Anlage ist zu erden und kurzzuschließen.
Benachbarte, unter Spannung stehende Teile sind abzudecken oder abzuschranken.
18) Der Stromwandler ist kurzzuschließen! Ein NICHT kurzgeschlossener
Stromwandler erzeugt sehr hohe Spannungen, die Menschen und Geräte gefährden.
Der Stromwandler wird dadurch zerstört.
19) Den alten Blindleistungsregler abklemmen und entfernen.
20) CX plus in Schalttafelausschnitt stecken und mit den beiden
Befestigungsklammern fixieren. (Ausschnitt 138 x 138 mm)
21) Schutzleiter am PE-Anschluss der Metallrückseite des CX plus anschließen.
22) Verbindungsleitungen gemäß Anschlussschaltbild anschließen. (Stromwandler:
K [Kraftwerk] auf S1 , L [Last] auf S2)
23) Stromwandlerbrücke entfernen.
- Spannung zuschalten. 25) Bei korrektem Anschluss und korrekten
Anschlussdaten leuchtet das
Display auf. Für eine Sekunde wird der Displaytest angezeigt. 26) Aktivierung der benutzergeführten Erstinbetriebnahme ,,FIrSt SEtUP”
durch Auswahl ,,YES”. Anschließend werden sämtliche notwendigen Parameter durch den CX plus abgefragt. Bei Auswahl ,,NO” müssen die folgenden Parameter (12) … 15)) einzeln eingegeben werden. 27) Der Stromwandlerfaktor (Ct) muss eingegeben werden. 28) Die Nennspannung (Un) und der Spannungswandlerfaktor (Pt) müssen ebenfalls eingegeben werden. - ,,Automatische Initialisierung” (AI) ausführen oder den Phasenoffset (PO) manuell eingeben.
- Nach erfolgreicher ,,Automatischer Initialisierung” erscheint im Display die Anzeige ,,AUTO”. Die Regelung beginnt nach Ablauf der Entladezeitsperre.
Fragen während der Inbetriebnahme:
8) Keine Anzeige AUTO Regelung ist gestoppt Gründe: Handbetrieb, Regelung ist
ausgeschaltet, Temperatur ist zu hoch, Strom ist kleiner 15 mA, Spannung oder
THD der Spannung sind unzulässig
9) Anzeige U ALARM Spannung ausserhalb der Toleranz Einstellungen für
Nennspannung (SETUP/ Un) und Spannungswandler (SETUP/ Pt) überprüfen
10) Anzeige I Lo ALARM Kein Stromfluss Mögliche Ursachen: Verbindung vom
Stromwandler zum Regler ist nicht korrekt; Stromwandlerbrücke ist nicht
entfernt; Übersetzungsverhältnis zu groß; kein Strom
11) Anzeige EXPORT Rückspeisung von Wirkleistung Liegt keine reale
Rückspeisung vor, bitte Anschluss von Spannung und Strom prüfen (Phase,
Polarität) Kapitel Falschanschluss/ AI Automatische Initialisierung
12) Falscher Cos phi Falschanschluss Bitte Anschluss von Spannung und Strom
prüfen (Phase, Polarität) Kapitel Falschanschluss/ AI Automatische
Initialisierung
13) Ausgänge werden sofort wieder abgeschaltet Kapitel Falschanschluss/ AI
Automatische Initialisierung
14) Häufiges Schalten der Ausgänge Leistung der Kondensatoren muss erst
erkannt werden
Anzeige:
I
II
I
II
III
INFO: Stufendatenbank AUTO: Automatikbetrieb MANUAL: Handbetrieb SETUP:
Einstellmenü ALARM: Alarmspeicher
EXPORT: Rückeinspeisung von Wirkleistung NT: 2. Ziel-cos ist aktiv ALARM:
blinkt bei Alarmmeldung
1. Zeile: I) cos/ Menüpunkte II) induktiv/ kapazitiv
2. Zeile: I) Kürzel Einstell- und Messwerte II) Einstell- und Messwerte/
Alarmcodes III) Einheiten
Stufenanzeige: Status der Stufe (Ein/ Aus) Stufe defekt (blinkt)
Bedienung:
Die Bedienung des Reglers erfolgt über 4 Tasten.
Erhöhen von Werten Auswahl Menüpunkte
Verlässt Menüs/ Esc Cursor nach links Reset Alarm (5 Sek.)
Öffnet Menüs/ Enter Cursor nach rechts Einstellungen
Verkleinern von Werten Auswahl Menüpunkte
Eingabe Paramter:
, Ziffer wird eingestellt
Anwahl nächste Stelle
, Nach eingestellter letzter Ziffer Auswahl von:
– Multiplikator k (kilo) oder M (Mega)
– Vorzeichen i (induktiv) oder c (kapazitiv) (blinken von i bzw. c)
Übernahme der Werte zum Abschluss
Abbruch der Eingabe
Hauptmenü:
Auswahl der Menüpunkte durch , , Eingang ins Untermenü durch
Messwertanzeige: (Wechsel mit , )
ULL, ULN, I, P, Q, Q, S, THD U, 3.-19. Har. U,
THD I, 3.-19. Har. I, cos, PF, APF, Hz(F), t(°C), thi (°C), OPh (h), tan, U
hi, THD U hi
INFO Stufendatenbank: Leistung und Leistungsverlust der Stufen, Anzahl der
Schaltbeispiele, Stufentyp, Betriebsstunden. ( Kapitel INFO Stufendatenbank)
MANUAL Handbetrieb: Gezieltes zu- und abschalten von Schaltausgängen. (
Kapitel MANUAL Handbetrieb)
SETUP Einstellmenü: Nennspannung (Un), Stromwandler (Ct), Spannungswandler
(Pt), Automatische Initialisierung (AI), Regelung Ein/ Aus (PFC), Ziel-cos 1
(CP1), Schaltzeit (St), Stufentyp (Out) ( Kapitel SETUP Einstellmenü)
ALARM Alarmspeicher: Anzeige der letzten 10 Alarme. Der neuste Alarm steht
dabei an erster Stelle.
INFO Stufendatenbank:
Achtung: Der aktuelle Status der Ausgänge wird nicht angezeigt.
Stufe durch , anwählen und durch auswählen. Die gewählte Stufe blinkt. Durch ,
werden folgende Informationen angezeigt:
Aktuelle Kondensatorleistung
(Current Capacity)
Die Leistung bezieht sich auf Un.
Leistungsminderung des Kondensators: Aktuelle Leistung/ Nennleistung in %
Anzahl Schaltspiele
(Operation Cycles)
Stufentyp: AUTO: Automatisch geregelte Stufe Fon: Feststufe ein Foff:
Feststufe aus FLty: Stufe defekt und gesperrt
Betriebsstunden (Operation Hours): Zeigt wieviele Stunden die entsprechende
Stufe bereits in Betrieb ist. Ausgewählte Stufe blinkt auf.
MANUAL Handbetrieb:
In den Handbetrieb gelangt man durch drücken von für 3 Sekunden Stufe durch ,
Stufe anwählen. Die gewählte Stufe wird in Zeile 2 als Zahl angezeigt. Durch
wird Stufe ein- bzw. abgeschaltet. Der Handbetrieb wird mit verlassen.
Wichtige Informationen: – Im Menü Manual/ Handbetrieb können nur Stufen mit
Stufentyp
AUTO geschaltet werden. Im Modus LIFO, FIFO und Kombifilter ist das Menü
MANUAL (Handbetrieb) gesperrt. ( Referenzhandbuch) – Die Entladezeitsperre
greift auch im Handbetrieb. (Stufen sind nach Abschaltung für eine gewisse
Zeit gesperrt) – Die Spannung muss innerhalb der Toleranz liegen, sonst
erfolgt die Abschaltung aller Stufen bzw Stufen können nicht geschaltet
werden. – THD U-, THD I- und Übertemperatur-Alarm sperren das Zuschalten von
Stufen im Handbetrieb. – Nach Verlassen des Handbetriebs erfolgt die
automatische Regelung ab dem eingestellten Status.
SETUP Einstellmenü:
Nach Aufruf SETUP erscheint Untermenü 100. Aufruf Menü 100. , Menü 200 – 600 &
800, bei optionalem Modbus: 200 – 800 (mit Passwort gesperrt Referenzhandbuch)
Un Nennspannung (Korrekte Einstellung ist sehr wichtig) Für
Spannungsüberwachung und Referenz der Stufendatenbank
Ct Stromwandlerfaktor (muss eingestellt werden) Wert dient der Berechnung und
Freischaltung einiger Messwerte
Pt Spannungswandlerfaktor Wichtig als Basis für Einstellung Un
AI Automatische Initialisierung Kapitel Falschanschluss/ AI Automatische Initialisierung
PFC REGELUNG ON/ OFF/ HOLD Einschalten, Ausschalten, Einfrieren der Regelung
CP1 Ziel- cos 1 Basis für Kompensationsziel
St
Schaltzeit
Definiert die Geschwindigkeit des Reglers
OUt Stufentyp Definieren von Stufentyp: AUTO, Fon, Foff, Rücksetzung defekter Stufen (FLty)
Falschanschluss/ AI Automatische Initialisierung:
Bei Falschanschluss des Spannungs- bzw. Strompfades (Phase, Polarität), kann
ein Blindleistungsregler nicht betrieben werden. In diesen Fällen sollte der
Anschluss korrigiert werden. Da dies nicht immer möglich ist, bietet der CX
plus alternativ folgende Funktionen:
Automatische Initialisierung: SETUP/ 100/ AI
Die AI schaltet alle Ausgänge mehrfach ein und aus. Dies dauert mehrere
Minuten. Nicht belegte Ausgänge werden auf ,,Foff” gestellt. Stufengrößen
werden dabei nicht erkannt.
Nach Ende der AI ist die Funktion des Reglers zu überprüfen.
Vorraussetzungen zum erfolgreichen Betrieb der AI:
– Spannung befindet sich innerhalb der Toleranz – Stromwandler ist
angeschlossen (keine Simulation) – Kondensatorbänke sind installiert,
funktionstüchtig und eingesichert
Mögliche Probleme für erfolgreiche AI:
– Lastschwankungen – Kleine Stromsignale
Fehlermeldungen AI/ Abrt:
AI wurde abgebrochen, da kein eindeutiges Ergebnis möglich war, die Regelung
ist AUS.
Zuletzt bleibt die Möglichkeit der manuellen Korrektur: Eingabe des korrekten
Phasenoffsets SETUP/ 206 Referenzhandbuch
Stufenerkennung:
Bei jeder Schalthandlung wird die Stufengröße ermittelt (außer diese Funktion
ist deaktiviert SETUP/ 308 Referenzhandbuch). Die erkannten Werte werden in
der Stufendatenbank mitgeführt. Ein Kapazitätsverlust kann dort abgelesen
werden.
Funktioniert eine Stufe bei den ersten drei Schalthandlungen nicht, so bekommt
Sie automatisch den Stufentyp Foff.
Nach Inbetriebnahme haben vorhandene Stufen den Stufentyp Foff: Ist
Stromwandlerbrücke entfernt? Stimmt Position des Stromwandlers? Alle Ströme,
Mess- und Betriebsspannungen vorhanden?
Defekte Stufen:
Eine dreimal in Folge ohne messbaren Erfolg geschaltete Stufe wird als defekt
deklariert. Nach 24 Stunden erfolgt eine erneute Prüfung.
Stufenanzeige: blinkt Status: Flty, Stufe ist gesperrt
Vorgehensweise:
Im Betrieb blinken einzelne Stufen?
Sicherung, Schütz und Kondensatorleistung der entspr. Stufe überprüfen.
Quittierung in SETUP/ 100/ OUt oder durch Neustart (Unterbrechung der Mess-/
Versorgungsspannung) des CX plus.
Alarme:
Einstellungen Alarmsystem: SETUP/ 500 Referenzhandbuch
U
ALARM: Messspannung ausserhalb der Toleranz
I Lo
ALARM: Messstrom < 5 mA (Strommesspfad überprüfen)
SETUP/ 500/ 518 ,,YES” = I- Low- Alarm blockiert
I Hi
ALARM: Messtrom > 6 A (Übersetzungsverhältnis des
eingebauten Stomwandlers ist zu klein)
PFC
ALARM: Kompensationsziel nicht erreichbar (Anlage prüfen)
HArU
ALARM: Limit für THD U ist überschritten
HArI
ALARM: Limit für THD I ist überschritten
StEP/ FLtY ALARM: Defekte Stufen sind vorhanden
SPL/ Nr
ALARM: Leistungsverlust von Stufen unter 75 % Stufennummer und Fehlercode blinken im Wechsel
thi
ALARM: Übertemperaturabschaltung der Stufen
OPH
ALARM: Max. Betriebsstunden Regler erreicht (Wartung)
OPC/ Nr ALARM: Max. Schaltspiele/ Betriebsstd. Stufen erreicht (War-
OPHS/ Nr
tung). Stufennr. und Fehlercode blinken im Wechsel
AI/ Abrt
ALARM:
Abbruch der Automatischen Initialisierung Erneuter Start der AI bei ruhigerem Netz oder Manuelle Einstellung des Phasenoffsets (SETUP/ 206 Referenzhandbuch)
Werkseinstellungen bei Auslieferung
SETUP/ 100
Wichtige Einstellungen Un/ Nennspannung Ct/ Stromwandler Pt/ Spannungswandler
AI/ Start AI PFC/ Regelung CP1/ Ziel-cos 1 St/ Schaltzeit Out/ Stufentyp
open
400 V 1 1
NO ON
1 10 s AUTO
SETUP/ 200 MESSUNG 201/ Nennspannung 202/ Stromwandler 203/ Spannungswandler 204/ Toleranz Spannung 205/ Art der Messspannung 206/ Phasenoffset 207/ Start AI 208/ Synchronisierung 209/ Temperaturoffset 210 / CO2 Zähler
locked 400 V
1 1 10 % U-LN 0 NO AUTO 0 °C
SETUP/ 300 REGELUNG 301/ Empfindlichkeit
locked 60 %
302/ Ziel-cos 1 303/ Ziel-cos 2 304/ EXPORT- cos 2 305/ Schaltzeit 306/ St
Stufentausch 307/ Aktiv. Stufentausch 308/ Aktiv. Stufenerkenn 309/ Sperre
Defektstufen 310/ Regelung on/ off/ hold 311/ Regelalgorithmus 312/
Offsetblindleistung 313/ Asymmetriefaktor 314/ Qcap Stufen Aus 315/
Stufenverteilung 316/ Defektstufenerkenn.
SETUP/ 400 STUFENDATENBANK 401/ Entladezeitsperre 402/ Nennwert Stufengr. 403/
Stufentyp 404/ Schaltspiele 405/ Betriebsstd. Stufen
406 / Stage Monitoring
407/ Lüfterrel. als St 13
1.00 i 0.95
NO 10 s
2 s YES YES YES ON
1 0 var
1 NO NO YES
locked
75 s c 3 var AUTO
0 0 h YES NO
Werkseinstellungen bei Auslieferung
SETUP/ 500
ALARMEINSTELLUNG 501/ Reset Manuell 502/ THD U Limit 503/ THD Stufen aus 504/
Verz. Harm. Alarm 505/ I=0 Regler freeze 506/ Wartungsalarm 507/ Limit
Schaltspiele 508/ Limit OPh 509/ Lim. OPh Stufen 510/ THD I Limit 511/ DI=Hi
Aktiv 512/ Temp1 Limit 513/ Temp2 Limit 514/ Regelalarm 515/ Defektstufenalarm
516/ Leistungsverlust 517/ Alarm Beleuchtung 518/ Funktion DI 519/ Info: I-
Low Blocked 520/ DI-Alarm St.-AUS 521/ I-Low-Alarm 522/ Verz. I-High-Alarm
523/ Abschaltintervall
locked
NO 20 %
NO 60 s NO NO 500 k 65.5 kh 65.5 kh 50 % YES 30 °C 55 °C NO NO NO NO CP 2 NO
NO YES 10 s 60 s
524/Unterdrückung DI Alarm
SETUP/ 600 RESET 601/ Werkseinstellungen 602/ Stufendatenbank 603/
Betriebsstunden 604/ Durchschnitts-
leistungsfaktor 605/ max. Temperatur 606/ Alarm 607/ Info Firmware 608/
Änderung Passwort 609/ Neustart Erst-IBN
SETUP/ 700 MODBUS 701/ Baudrate 702/ Parität 703/ Adresse
SETUP/ 800 Hintergrundbeleuchtung 801/ Hintergrundbeleuchtung Inbetriebnahme-
Modus 802/ Verzögerungszeit
YES locked
242 NO locked 19200 EVEN
1 locked
NO
0,25 h
DTC / 900
dynamische Trafokompensation
900 / Trafo Bemessungsleistung
902 /
Kurzschlussspannung 903 / Startwert
DTC 904 / Offset
0.0 %
0.0 % 0.0 Var
Technische Daten:
Spannung: Strom: Schaltausgänge:
Digitaleingang: Temperaturmessung: Meldekontakt:
Lüftersteuerung:
Schnittstelle: Umgebungstemperatur:
Luftfeuchtigkeit: Überspannungskategorie:
Anschluss: Gehäuse:
Schutzart:
90- 550 V, 1ph., 50/ 60 Hz, 6 VA
5 mA- 6 A, 1ph., <1 VA,
Relais, Schließer NO, Versorgung Schaltkontakte: max. 10 A 250V AC/ 5A, 400V
AC/ 1A
90- 250 V AC
NTC, intern
Relais potentialfrei, Schließer geschlossen, 48 V DC/ 1 A, 250 V AC/ 5 A, 400
V AC/ 1 A Optional NO/ NC
Relais potentialfrei, 48 V DC/ 1 A, 250 V AC/ 5 A, 400 V AC/ 1 A
Optional: RS485 Modbus
Betrieb: -20 °C bis 70 °C Lagerung: -40 °C bis 85 °C
0 %- 95 %, Betauung nicht zugelassen
300 V LN/ 519 V LL CAT III oder 550 V/ CAT II
Schraubklemmen, steckbar
Front: Instrumentengehäuse, Kunststoff Rückseite: Metall
Front: IP41, Rückseite: IP20
Technische Daten:
Gewicht:
Ca. 0,6 kg
Abmessungen:
Gehäuse: 144 x 144 x 58 mm (BxHxT) Ausschnitt: 138 (+0,5) x 138 (+0,5) mm
Alarmspeicher:
Speicherung der letzten 10 Alarme
Standards:
IEC 61010-1 IEC 61000 6- 2 IEC 61000 6- 4: level B IEC 61326- 1 UL 61010
Konformität:
CE, NRTL(UL), c NRTL (cUL), EAC
Algorithmen:
AUTOMATIK (best fit) LIFO FIFO PROGRESSIVE
Kombifilter
Max. Betriebshöhe:
2000 m
Max. Verschmutzungsgrad: 2
Hinweis:
Zusätzliche detaillierte technische informationen können unter nachfolgenden Links geladen werden:
https://image.schrackcdn.com/bedienungsanleitungen/a_fracxp_en_de.pdf
https://image.schrackcdn.com/bedienungsanleitungen/a_fracxp12rm_modbus_en_de.pdf
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>