White-Rodgers 21D83M-843 Single Stage HSI Furnace Control Kit Installation Guide
- August 25, 2024
- WHITE RODGERS
Table of Contents
White-Rodgers 21D83M-843 Single Stage HSI Furnace Control Kit Installation
Guide
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
Kit includes:
1 – 50A66-843 ignition control board
1 – Wiring harness (9-pin to 12-pin)
1 – Wiring harness (4-pin to 6-pin)
1 – Mounting panel
4 – Stand-off fasteners
1 – Circuit breaker
1 – 4″ blue wire
2 – Wiring diagrams
The kit includes the 50A66-843 which is an automatic gas interrupted ignition control that employs a microprocessor to continually monitor, analyze, and control the proper operation of the gas burner, inducer, and fan.
These controls incorporate system fault analysis for quick gas flow shut-off, coupled with automatic ignition retry upon sensing a fault correction.
Follow instructions for replacement of your model number under the heading INSTALLATION.
PRECAUTIONS
Installation should be done by a qualified heating and air conditioning
contractor or licensed electrician.
If in doubt about whether your wiring is millivolt, line, or low voltage, have
it inspected by a qualified heating and air conditioning contractor or
licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough
handling or distorting components could cause the control to malfunction.
Following installation or replacement, follow manufacturer’s recommended
installation/service instructions to ensure proper operation.
CAUTION
Do not short out terminals on gas valve or primary control. Short or incorrect wiring may damage the thermostat.
WARNING
Failure to comply with the following warnings could result in personal injury or property damage.
FIRE HAZARD
• Do not exceed the specified voltage.
• Replace existing control with exact model and dash number.
• Protect the control from direct contact with water (dripping, spraying,
rain, etc.).
• If the control has been in direct contact with water, replace the control.
• Label all wires before disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation.
• Route and secure wiring away from flame.
SHOCK HAZARD
• Disconnect electric power before servicing.
• Ensure proper earth grounding of appliance.
• Ensure proper connection of line neutral and line hot wires.
EXPLOSION HAZARD
• Shut off main gas to appliance until installation is complete.
SPECIFICATIONS
TIMING SPECIFICATIONS
(All times are in seconds, unless noted otherwise
*This time will vary depending on option switch position. The control is factory set at 90 seconds HEAT delay-to-fan-off and 45 seconds COOL delay-to-fan-off. See OPERATION section for further information
INSTALLATION
WARNING
FIRE HAZARD
- Do not exceed the specified voltage.
- Replace existing control with exact model and dash number.
- Protect the control from direct contact with water (dripping, spraying, rain, etc.).
- If the control has been in direct contact with water, replace the control.
- Label all wires before disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
- Route and secure wiring away from flame.
SHOCK HAZARD
- Disconnect electric power before servicing.
- Ensure proper earth grounding of appliance.
- Ensure proper connection of line neutral and line hot wires.
EXPLOSION HAZARD
- Shut off main gas to appliance until installation is complete.
CAUTION
Do not short out terminals on gas valve or primary control. Short or incorrect wiring may damage the thermostat.
MOUNTING PANEL
The Mounting Panel is required in Procedure 1 and Procedure 2. It will become
part of the installation for Procedure 1. It will be used as a template for
locations to drill holes in Procedure 2, Step 4A and 4B. It will become part
of the installation in Procedure 2, Step 4C.
PROCEDURE 1
REPLACING 10M9301, 12L6901, 32M8801,
50A65-120, 50A65-121 or 56L8401
- Disconnect all electrical power and shut off the gas supply to the furnace.
- Remove the access panel.
- Disconnect wiring and remove existing ignition control board from the control box.
- Install provided circuit breaker in unit control box or secure circuit breaker to a wire harness using wire ties.
- Position the provided mounting panel with the arrow on the front of the panel pointing up. Position the replacement 50A66-843 ignition control board over the holes marked “A” in figure 1. Insert the replacement control stand-off fasteners into the holes in the mounting panel.
- Insert the four provided stand-off fasteners into the back of the mounting panel in the holes marked “B” in figure 1. Insert the replacement control board assembly into the existing holes in the control box or blower panel.
- Insert provided circuit breaker in series between the blue transformer wire connecting position 3 on the 12-pin connector to the transformer (TH), optional 4″ blue wire provided for transformers that have a quick-connect terminal.
- Connect the remaining 120 VAC hot and neutral wires and the flame sense wire to the replacement control per table 1, page 4.
- Affix wiring diagram 5001-6973 adjacent to the existing unit wiring diagram.
- Replace the access panel.
- Restore the electrical power and gas supply. Refer to the furnace installation instructions for start-up and check-out procedures.
PROCEDURE 2
REPLACING 24L8501, 50A62-120, 50A62-121, 50A62-820, 56L8301, 63K8901 or
97L4801
-
Disconnect all electrical power and shut off the gas supply to the furnace.
-
Remove the access panel.
-
Disconnect wiring and remove existing ignition control board from the control box.
-
A. When replacing original 63K8901 board in upflow or horizontal applications or downflow applications – Look at the existing control board holes as if the unit were installed in the upflow position. Make a mark 1″ to the right of each of the existing mounting holes.
Position the provided mounting panel so that the holes marked “C” in figure 1, page 3 are over the marks. Use the mounting panel as a template to drill 3/16″ holes through each of the holes marked “A”. Install the replacement control in the freshly drilled holes in the blower access panel. Use aluminum tape to seal the unused holes.
B. When replacing original 63K8901 board in downflow applications – Look at the existing control board holes as if the unit were installed in the upflow position. Make a mark 5/8″ ABOVE each of the existing mounting holes. Position the provided mounting panel so that the holes marked “C” in figure 1, page 3 are over the marks. Use the mounting panel as a template to drill 3/16″ holes through each of the holes marked “A”. Install the replacement control in the freshly drilled holes in the blower access panel. Use aluminum tape to seal the unused holes.
C. All other units – Position the provided mounting panel so that the arrow on the front of the panel is pointing up. Position the replacement 50A66-843 ignition control board over the holes marked “A” in figure 1, page 3.
Insert the replacement control stand-off fasteners into the holes in the mounting panel.
80UHG, 90UGF, G23, G26, GHR26, G32, GHR32, G40, G41, G50, G51, G60 and G61 units – Insert the four provided stand-off fasteners into the back of the mounting panel in the holes marked “B” in figure 1. 80MGF, G24M and G27M units – Insert the four provided stand-off fasteners into the back of the mounting panel into the holes marked “C” in figure 1.
Insert the replacement control board assembly into the existing holes in the control box or blower panel. -
Insert provided circuit breaker in series between the blue wire on Pin 3 of the wiring harness (9-pin to 12-pin) and the blue transformer wire. Optional 4″ blue wire provided for transformers that have a quick-connect terminal.
-
Connect the provided 9-pin to 12-pin wiring harness to the unit 9-pin connector.
-
Connect the provided 4-pin to 6-pin wiring harness to the unit 6-pin connector.
-
Connect the yellow wire from position 6 on the 12-pin connector to the yellow transformer wire.
-
Connect GND wire to equipment ground.
-
Connect the remaining 120 VAC hot and neutral wires and the flame sense wire to the replacement control per table 2, page 5 .
-
Affix wiring diagram 5001-6972 adjacent to the existing unit wiring diagram
-
Replace the access panel.
-
Restore the electrical power and gas supply. Refer to the furnace installation instructions for start-up and check-out procedures.
PROCEDURE 3
REPLACING 100925-01, 100925-02, 100925-03, 17W9201, 23W5101, 30W2501,
50A66-122, 50A66-123, 69M0801 or 69M1501
- Disconnect all electric power and shut off gas supply to the furnace.
- Remove the access panel
- Disconnect wiring and remove existing ignition control board.
- Insert the replacement board into existing holes.
- Reconnect wiring.
- Replace access panel.
- Restore the electrical power and gas supply. Refer to the furnace installation instructions for start-up and check-out procedures.
OPERATION
OPTION SWITCHES
The option switches on the 50A66-843 control are used to determine the length
of the heat delay-to-fan-off and cool-delay-to-fan-off periods. The following
table shows the time periods that will result from the various switch
positions.
OPTION SWITCH POSITIONS
HEAT MODE
In a typical system, a call for heat is initiated by closing the thermostat
contacts. This starts the 50A66-843 control’s heating sequence. The inducer
blower and humidifier are energized. After a 15-second pre-purge period, the
768A Silicon Nitride ignitor is powered.
This controller has an adaptive algorithm that reduces ignitor temperature to slightly greater than the minimum temperature required to ignite gas in each particular application. The control measures the line voltage and determines an initial ignitor temperature setting based on the measurement. After each successful ignition, the control lowers the ignitor temperature slightly for the next ignition attempt. The control continues to lower the ignitor temperature until ignition does not occur, and the control goes into retry mode. For the second attempt to ignite gas within the same call for heat, the control increases the ignitor temperature to the value it was on the third previous successful ignition. After ignition is successful, the control sets the ignition temperature at this value for the next 255 calls for heat, after which the control repeats the adaptive algorithm. The control is constantly making adjustments to the ignitor temperature to compensate for changes in the line voltage.
The 80 VAC Silicon Nitride ignitor manufactured by White-Rodgers must be used. These ignitors are spe-cially designed to operate with the 50A66-843’s adap- tive ignition routine to ensure the most efficient ignitor temperature.
At the end of the ignitor warm-up time, both valves in the gas valve are
opened. Flame must be detected within 4 seconds.
If flame is detected, the delay-to-fan-on period begins. After the delay-to-
fan-on period ends, the circulator fan is energized at heat speed. If there is
an optional electronic air cleaner on the system, the electronic air cleaner
and the humidifier are energized. When the thermostat is satisfied, the gas
valve is de-energized. After proof of flame loss, the inducer blower remains
energized to purge the system for 5 seconds and the delay-to-fan-off period
begins. When the purge is complete, the inducer blower and humidifier are de-
energized. After the delay-to-fan-off period ends, the circulator fan and
electronic air cleaner are de-energized.
If flame is not detected, both valves are de-energized, the ignitor is turned off, and the 50A66-843 control goes into the “retry” sequence. The “retry” sequence provides a 15-second wait following an unsuccessful ignition attempt (flame not detected). After this wait, the ignition sequence is restarted. If this ignition attempt is unsuccessful, three more retries will be made before the control goes into system lockout.
If flame is detected, then lost, the 50A66-843 control will repeat the initial
ignition sequence for a total of three “recycles”. After three unsuccessful
“recycle” attempts, the control will go into system lockout.
If flame is established for more than 10 seconds after igni-tion, the
50A66-843 controller will clear the ignition attempt (or retry) counter. If
flame is lost after 10 seconds, it will restart the ignition sequence. This
can occur a maximum of four times before system lockout.
A momentary loss of gas supply, flame blowout, or a shorted or open condition in the flame probe circuit will be sensed within 2 seconds. The gas valve will de-energize and the control will restart the ignition sequence. Recycles will begin and the burner will operate normally if the gas supply returns, or the fault condition is corrected, before the last ignition attempt. Otherwise, the control will go into system lockout.
If the control has gone into system lockout, it may be pos-sible to reset the control by a momentary power interrup-tion of ten seconds or longer. Refer to PRECAUTIONARY, SYSTEM LOCKOUT, AND DIAGNOSTIC FEATURES.
COOL MODE
In a typical system, a call for cool is initiated by closing the thermostat
contacts. This energizes the 50A66-843 control’s cooling sequence. The
compressor is energized and the delay-to-fan-on period begins. After the
delay-to-fan-on periods ends, the circulator fan is energized at cool speed.
The electronic air cleaner (optional) is also energized. After the thermostat
is satisfied, the compres-sor is de-energized and the delay-to-fan-off period
begins. After the delay-to-fan-off period ends, the circulator fan and
electronic air cleaner (optional) are de-energized.
MANUAL FAN ON MODE
If the thermostat fan switch is moved to the ON position, the circulator fan
(heat speed) and optional electronic air cleaner are energized. When the fan
switch is returned to the AUTO position, the circulator fan and electronic air
cleaner (optional) are de-energized.
SYSTEM LOCKOUT AND DIAGNOSTIC FEATURES
SYSTEM LOCKOUT FEATURES
When system lockout occurs, the gas valve is de-energized. The circulator
blower is energized at heat speed for some faults, and if flame is sensed, the
inducer blower is en-ergized. The diagnostic indicator light will flash or
glow continuously to indicate system status. (System lockout will never
override the precautionary features.)
To reset the control after system lockout, do one of the following:
- Interrupt the call for heat at the thermostat for at least one second, but less than 20 seconds (if flame is sensed with the gas valve de-energized, interrupting the call for heat at the thermostat will not reset the control).
- Interrupt the 24 VAC power at the control for at least ten seconds. You may also need to reset the flame rollout sensor switch.
- After one hour in lockout, the control will automatically reset itself.
DIAGNOSTIC FEATURES
The 50A66-843 control continuously monitors its own operation and the
operation of the system. If a failure occurs, the DS 1 (red) and DS 2 (green)
LEDs will indicate a failure code as shown on next page.
TROUBLESHOOTING
DIAGNOSTIC TABLE
White-Rodgers is a business of Emerson Electric Co.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
white-rodgers.com
emersonclimate.com
Read More About This Manual & Download PDF:
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>