GIRA 5011 00 Pushbutton Sensor 4 Standard Komfort System 55
Product Information
Specifications
- Product Name: Pushbutton Sensor 4
- Variants: Standard, Komfort
- System Compatibility: System 55
- Order Numbers:
- Standard, 1-gang: 5011 00
- Standard, 2-gang: 5012 00
- Standard, 3-gang: 5013 00
- Komfort, 1-gang: 5041 00
- Komfort, 2-gang: 5042 00
- Komfort, 3-gang: 5043 00
Product Usage Instructions
Safety Instructions
Electrical devices should only be mounted and connected by electrically
skilled persons to prevent serious injuries, fire, or property damage. Always
follow the manual instructions carefully to avoid danger of electric shock.
Device Components
The device components include operating rockers, status LED, buttons
assignment, rear connections for remote sensor and bus connection, retaining
clips for fixation, and supporting frame.
System Information
The device is part of the KNX system and complies with KNX directives.
Detailed technical knowledge from KNX training courses is necessary for proper
understanding. Firmware updates can be done
with the Gira ETS Service App. The device is KNX Data Secure capable for
protection against manipulation in building automation.
Intended Use
The pushbutton sensor is intended for functions like switching, dimming,
color temperature control, brightness control, Venetian blind operation, scene
extension, and more. It offers status LED with various color options and
functions like orientation lighting and night reduction.
Product Characteristics
The product supports various functions including switching, dimming, color
control, Venetian blind operation, scene extension, and more. LED functions
like orientation lighting and night reduction can be adjusted separately.
FAQ
-
Q: How can I update the firmware of the device?
A: Firmware updates can be easily done using the Gera ETS Service App. Make sure to follow the instructions provided in the manual for a successful update process. -
Q: Can the status LED colors be customized?
A: Yes, the status LED colors are adjustable per button. You can choose from a range of colors including red, green, blue, yellow, cyan, orange, violet, and white.
Operating instructions
- Pushbutton sensor 4 Standard, 1-gang System 55 Order no. 5011 00
- Pushbutton sensor 4 Standard, 2-gang System 55 Order no. 5012 00
- Pushbutton sensor 4 Standard, 3-gang System 55 Order no. 5013 00
- Pushbutton sensor 4 Komfort, 1-gang System 55 Order no. 5041 00
- Pushbutton sensor 4 Komfort, 2-gang System 55 Order no. 5042 00
- Pushbutton sensor 4 Komfort, 3-gang System 55 Order no. 5043 00
Safety instructions
Electrical devices may be mounted and connected only by electrically skilled
persons.
Serious injuries, fire or property damage are possible. Please read and follow
the manual fully. Danger of electric shock. During installation and cable
routing, comply with the regulations and standards which apply for SELV
circuits. This manual is an integral part of the product, and must remain with
the customer.
Device components
Front view
Figure 1: Device components 3-gang (“standard installation position”, horizontal rockers
Figure 2: Device components 3-gang (installation position “turned by -90°”, vertical rockers)
- Operating rockers (accessory)
- Status LED
- 1…6 Buttons assignment and status LED
Rear view
- (c) Device connection terminal for remote sensor
- (d) Bus connection
- (e) Retaining clips for device fixation at the supporting frame
- (f) Supporting frame
System information
This device is a product of the KNX system and complies with the KNX
directives. Detailed technical knowledge obtained in KNX training courses is a
prerequisite to proper understanding.
The function of this device depends upon the software. Detailed information on
loadable software and attainable functionality as well as the software itself
can be obtained from the manufacturer’s product database. The device can be
updated. Firmware can be easily updated with the Gira ETS Service App
(additional software). The device is KNX Data Secure capable. KNX Data Secure
offers protection against manipulation in building automation and can be
configured in the ETS project. Detailed technical knowledge is required. A
device certificate, which is attached to the device, is required for safe
commissioning. During mounting, the device certificate must be removed from
the device and stored securely. Planning, installation and commissioning of
the device are carried out with the aid of the ETS, version 5.7.5 and above.
Intended use
- Operation of loads, e.g. light on/off, dimming and colour temperature control, colour control and brightness, Venetian blinds up/down, 1-byte values, 2-byte values, 3-byte values and 6-byte values, rightness values, temperatures, colour temperature values, calling up and saving light scenes as scene extension
- Calling up and saving device-internal light scenes (only for “comfort” device variant)
- Measurement of room temperature
- Measurement of the room temperature (only for “comfort” device variant)
- Indication of an alarm (only for “comfort” device variant)
- For use as orientation lighting
- Mounting in appliance box with dimensions according to DIN 49073
- Horizontal installation position in the “standard installation position” or vertical installation position in the “turned by -90°” installation position
Product characteristics
Product characteristic per product variant | Comfort | Standard |
---|
Push-button sensor functions switching, dimming and colour temperature
control, colour control and brightness, Venetian blind, value transmitter,
scene extension, 2-channel operation and controller extension adjustable| √| √
Controller extension with operating mode selection, forced operating mode
switch over, presence function and setpoint shift| √| √
Status LED – optionally red, green, blue – adjustable per button| √| √
Status LED – optionally red, green, blue, yellow, cyan, orange, violet, white
– adjustable per button| √| –
LED functions orientation lighting and night reduction can be set separately|
√| √
LED functions orientation lighting, alarm signalling and night reduction can
be set separately| √| –
Brightness of LED adjustable and switchable while in operation| √| √
Disable or function switch-over of all or of individual button functions
possible with disabling function| √| √
Scene control of up to 8 scenes with 8 scene outputs each| √| –
Temperature measurements optionally with device internal sensor and external
sensor connected via communication object| √| √
Temperature measurements optionally with device internal sensor, wired sensor
to the device connection terminal and external sensor connected via
communication object| √| –
Room humidity measurement with internal device humidity sensor| √| –
Integrated bus coupling unit| √| √
Operation
Depending on the programming, a rocker can have up to two functions assigned to it. Operation is carried out by a short or long press on the buttons and depends on the specific function configured.
Examples for operating various standard applications
- Switch: Short press on button.
- Dim: Long press on button. The dimming process ends when the button is released.
- Move Venetian blind: Long press on button.
- Stop or adjust Venetian blind: Short press on button.
- Set value, e.g. brightness or temperature setpoint: Short press on button.
- Open scene: Short press on button.
- Save scene: Long press on button.
- Execute channel 1: Short press on button.
- Execute channel 2: Long press on button.
- Operate controller extension: Short press on button.
Information for electrically skilled persons
Mounting and electrical connection
DANGER!
Electric shock when live parts are touched. Electric shocks can be fatal.
Cover up live parts in the installation environment.=
The push-button sensor (see figure 4) can be installed horizontally (“standard
installation position”) or vertically (“turned by -90°” installation
position).
For horizontal installation (“standard installation position”) the top of the
push-button sensor is labelled with TOP.
For vertical installation (“turned by -90°” installation position) the left
side of the push-button sensor is labelled with TOP.
- (e) Retaining clips for device fixation at the supporting frame
- (g) Programming button
- (h) Programming LED
- (i) Temperature sensor
Mounting and connecting the device
- (a) Operating rockers (accessory)
- (e) Retaining clips for device fixation at the supporting frame
- (f) Supporting frame
- (k) Cover frame (accessory)
- (l) Push-button sensor
- (m) Box screws
The device should be used in an air-tight appliance box. Otherwise temperature and humidity reading can be negatively influenced by draughts. In secure operation (preconditions):
- Secure commissioning is activated in the ETS.
- Device certificate entered/scanned or added to the ETS project. A high resolution camera should be used to scan the QR code.
- Document all passwords and keep them safe.
Precondition: The installation position of the push-button sensor is defined.
■ Mount supporting frame in the right orientation, “standard installation
position” or “turned by -90°”, on an appliance box.
Note the TOP marking.
Use the supplied box screws.
■ Pull off commissioning rockers from push-button sensor.
The push-button sensor is delivered with commissioning rockers. The operating
rockers suitable for the push-button sensor must be ordered separately (see
accessories).
■ Connect push-button sensor to the KNX using KNX device connection terminal
(red = +, black = -).
■ In secure operation: The device certificate must be removed from the device
and stored securely.
■ Optional (only for “comfort” device variant): Connect remote sensor (see
accessories) to the connection for the remote sensor. The relevant device
connection terminal is included with the remote sensor.
■ Fit the cover frame flushly. The cover frame is fixed via the push-button
sensor.
■ Attach the push-button sensor with cover frame onto the supporting frame.
Push-button sensor can be put into operation.
Make sure the that the retaining clips properly fit in the supporting frame.
The physical address is programmed (see chapter “Commissioning”Page 11) in the
next work step. The rockers can then be mounted (see chapter “Mounting the
rockers” } Page 14).
Commissioning
Programming the physical address and application program
Project design and commissioning with ETS from version 5.7.5 and above. The
programming button is located under the first rocker.
Precondition: The device is connected and ready for operation. The first
rocker is dismantled.
■ Activating Programming mode: push the programming button.
The programming LED lights up red. Programming mode is activated.
■ Programming the physical address.
The programming LED goes out. Physical address is programmed.
■ Programming the application program.
The device is for use.
All status LEDs are switched off while the application program is programmed.
As soon as the programming is successfully completed, the status LEDs carry
out their parameterised function.
Only for “comfort” device variant: When the application program is discharged
and the bus voltage is connected, all status LEDs initially light up white.
Whenever a button is actuated, the respective illuminated status LED changes
colour (white → red → green → blue → yellow → cyan → orange → violet → white→
…).
Only for “standard” device variant: When the application program is discharged and the bus voltage is connected, all status LEDs initially light up green. Whenever a button is actuated, the respective illuminated status LED changes colour (green → red → blue → green → …).
Safe-state mode
The safe-state mode stops the execution of the loaded application program.
If the device does not work properly – for instance as a result of errors in
the project design or during commissioning – the execution of the loaded
application program can be halted by activating the safe-state mode. The
device remains passive in safe-state mode, since the application program is
not being executed (state of execution: terminated).
Only the system software of the device is still functional. ETS diagnosis functions and programming of the device are possible.
Activating safe-state mode
■ Switch off the voltage.
■ Press and hold down the programming button.
■ Switch on voltage.
The safe-state mode is activated. The programming LED flashes slowly (approx.
1 Hz).
Release the programming button only after the programming LED starts flashing.
Deactivating safe-state mode
■Switch off the voltage or carry out ETS programming.
Master reset
The master reset restores the basic device settings (physical address
15.15.255, firmware remains in place). The device must then be recommissioned
with the ETS.
In secure operation: A master reset deactivates device security. The device
can then be recommissioned with the device certificate.
Devices can be reset to factory settings with the ETS Service App. This
function uses the firmware contained in the device that was active at the time
of delivery (delivered state). Restoring the factory settings causes the
devices to lose their physical address and configuration.
If the device – for instance as a result of errors in the project design or
during commissioning – does not work properly, the loaded application program
can be deleted from the device by performing a master reset. The master reset
resets the device to delivery state. Afterwards, the device can be put into
operation again by programming the physical address and application program.
Performing a master reset
Precondition: The safe-state mode is activated.
■ Press and hold down the programming button for > 5 seconds until the
programming LED starts flashing quickly.
■ Release the programming button.
The device performs a master reset. The programming LED is switched on. The
device restarts and is in delivery state.
Mounting the rockers
■Slide the side of the rocker into place (see figure 6).
■Press in the middle of the rocker (see figure 7).The rocker snaps into place.
Device is ready for operation.
In order to optimise the gap dimensions between the rockers and the cover
frame, the rockers can be moved slightly after snapping into place.
Dismantling
■ Carefully pull the push-button sensor forward together with the cover
frame.
■ Pull the rockers on one side to loosen them from the push-button sensor.
Exchanging labelling field
The rocker has a labelling field
■ Search for a notch in the cover of the labelling field by feeling with a
finger (see figure 9).
■ Pull on one side at the notch in the cover of the labelling field to
separate from the rocker (see figure 10).
The labelling field is uncovered.■ Exchange the labelling field.
■ Press the cover of the labelling field onto the rocker so that it snaps into
place. The labelling field is exchanged.
Technical data
- KNX
KNX medium TP256
- Commissioning mode S mode
- Rated voltage DC 21 … 32 V SELV
- Current consumption KNX 8 … 18 mA
- Connection mode KNX Standard device connection terminal
- Connecting cable KNX EIB-Y (St)Y 2x2x0.8
- Protection class III
Installation dimensions (see figure 11)
- Construction height A = 11.9 mm
- A = 12.5 mm (stainless steel rocker set)
- Installation depth B = 13.8 mm
Connection cable remote sensor (see accessories)
- Cable type extension NYM-J 3×1.5 or
- J-Y(St)Y 2×2×0.8
- Total length remote sensor line Max. 30 m
Ambient conditions
- Ambient temperature -5 … +45°C
- Storage/transport temperature -20 … +70°C
Accessories
Individually labelled rocker sets are available from the Gera inscription service www.beschriftung.gira.de.
- Rocker set, 1-gang for pushbutton sensor 4 Order no. 5751 ..
- Rocker set, 1-gang, inscribable, for pushbutton sensor 4 Order no. 5761 ..
- Rocker set, 1-gang, inscribable, for pushbutton sensor 4 Order no. 5771 ..
- Rocker set, 2-gang for pushbutton sensor 4 Order no. 5752 ..
- Rocker set, 2-gang, inscribable, for pushbutton sensor 4 Order no. 5762 ..
- Rocker set, 2-gang, inscribable, for pushbutton sensor 4 Order no. 5772 ..
- Rocker set, 4-gang for pushbutton sensor 4 Order no. 5753 ..
- Rocker set, 4-gang, inscribable, for pushbutton sensor 4 Order no. 5763 ..
- Rocker set, 4-gang, inscribable, for pushbutton sensor 4 Order no. 5773 ..
- Remote sensor Order no. 1493 00
Warranty
The warranty is provided by the specialist trade in accordance with statutory requirements. Please submit or send faulty devices postage paid together with a fault description to your responsible salesperson (specialist trade / installation company / electrical specialist trade). They will forward the devices to the Gira Service Center.
Gira
Giersiepen GmbH & Co. KG
Elektro-Installations-Systeme
Industriegebiet Mermbach
Dahlienstraße
42477 Radevormwald
Postfach 12 20
42461 Radevormwald
Deutschland
Tel +49(0)21 95 – 602-0
Fax +49(0)21 95 – 602-191
www.gira.de
info@gira.de
References
- Suche
- Suche
- Suche
- Suche
- Suche
- Suche
- Suche
- Suche
- Suche
- Suche
- Gira Inscription Service
- Schalter, Steckdosen & smarte Technik | Gira
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>