HOBO RX3000 Water Level Sensor Interface Instruction Manual
- August 20, 2024
- Hobo
Table of Contents
- HOBO RX3000 Water Level Sensor Interface Instruction Manual
- Adding a Sensor Node to the HOBOnet® Wireless Sensor Network
- Installing the Bracket and Sensor Node
- Deploying the Water Level Sensor
- Suspending the direct-read cable and water level sensor
- Suspending the direct-read cable and water level sensor
- · Option 2: Using the mounting hole on the endcap
- Water Level Scaling in HOBOlink
- Scenario 1: Setting a Reference Water Level
- Read More About This Manual & Download PDF:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
HOBO RX3000 Water Level Sensor Interface Instruction Manual
Adding a Sensor Node to the HOBOnet® Wireless Sensor Network
-
Press the Select button on the station to switch to the module with the manager (module 2 on RX2105 or RX2106 stations).
-
Press the Search button on the station. The magnifying glass icon blinks while the station is in search mode waiting for sensor nodes to join the network
-
Connect the interface connector to the sensor with the direct-read cable in between as shown here. The end of the cable with the longer housing connects to the interface connector as shown below.
-
Open the door on the sensor node and install the rechargeable batteries. Press the button on the sensor node for 3 seconds.
-
Watch the sensor node LCD while it joins the network:
This signal strength iconblinks while the sensor node searches for a network.
Once the sensor node finds a network, the icon stops blinking and the bars
cycle from left to right.
This network connection “x” icon blinks while the sensor node completes the
registration process, which may take up to five minutes.
Once the sensor node has finished joining the network, the “x” icon no longer
appears. The channel count on the station LCD increases by four.
Press the Search button on the station again to stop the search for sensor nodes.
Go to www.hobolink.com to monitor the status and health of the sensor node. See the HOBOlink Help for details.
Installing the Bracket and Sensor Node
-
Orient the bracket so the text TOP is facing upwards.
-
To install the bracket onto a wall, use the two long screws included in the package. Screw the bracket to a wall using the two holes on the mid-section of the bracket.
-
To install the bracket onto a pole, slip a cable tie through each of the channels on the bracket and fasten the tie around the pole.
-
Insert the bottom of the sensor node into the retaining clips on the bottom of the bracket then press the top of the sensor node into the clips at the top of the bracket.
-
Use the short screw included in the package to fasten the sensor node to the bracket.
-
Close the sensor node and use a padlock to keep it secure.
Note: Ensure that the node seal is clean from foreign debris
Mounting and Positioning the Sensor Node
- Position the sensor node towards the sun, making sure the solar panel is oriented so that it receives optimal sunlight throughout each season. You may need to periodically adjust the position of the sensor node as the path of the sunlight changes throughout the year or if tree and leaf growth alters the amount of sunlight reaching the solar
- Make sure the sensor node is mounted a minimum of 1.8 m (6 feet) from the ground or vegetation to help maximize distance and signal
- Consider using plastic poles such as PVC to mount the sensor node as certain types of metal could decrease the signal strength.
- Place the sensor node so there is full line of sight with the next sensor node. Use a repeater if there is an obstruction between sensor nodes.
- There should not be more than five sensor nodes in any direction from a repeater or the manager. Data from sensor nodes travels or “hops” across the network and may not reach the station if the sensor node is more than five hops
Deploying the Water Level Sensor
Warning: Do not suspend anything from the 6-foot cable. The 6-foot cable is not designed to support the weight of the direct-read cable and sensor
Suspending the direct-read cable and water level sensor
- Option 1 (preferred): Using the long direct-read cable (CABLE-DR-xxx) and a compatible well-cap
Suspending the direct-read cable and water level sensor
- Option 1 (preferred): Using the long direct-read cable (CABLE-DR-xxx) and a compatible well-cap
· Option 2: Using the mounting hole on the endcap
The endcap contains a loop that allows you to use a carabiner (rated to 50 lbs. or grater) or some other reliable method to suspend the interface connector.
Water Level Scaling in HOBOlink
The following sections provide information on how to measure the reference water level and account for water density.
Scenario 1: Setting a Reference Water Level
-
Deploy the water level sensor in water and secure it in position (for example, hang it in a well).
-
Make sure your RX Station is logging and connecting fast enough for you to see the current water depth readings. (Press connect on the RX Station to see the latest logged value).
-
Enable Scaling for the HOBOnet water level In HOBOlink:
-
Select Devices, RX Devices, then select your
-
Select the wrench at the top of the page and select Module/Sensor Configuration from the
-
Select Water Level for the appropriate On the right side of the page, ensure that Enable Scaling is selected.
-
Enter the scaling values:
-
Enter the Scaled Units: for example meters or This should match the units shown in Latest Value, or you will need to adjust the multiplier to convert.
-
E nter the multiplier in the Multiplier
**Multiplier***
Fresh water| 1
Brackish water| 0.99
Salt water| 0.9765
-
Enter 0 in the Offset field for
-
Enter the Scaled Measurement Type, for example “ Pond Water Level ”.
-
Click save and note the Latest
-
Take a reference water level
-
Note this as a negative number if the water level surface is below the reference point, such as groundwater level referenced to the top of the well ( Figure 1 ).
-
Note this as a positive number if the water level surface is above the reference point, such as the bottom of the stream or the zero on a staff gauge ( Figure 2 ).
-
Calculate the offset, which is equal to the reference water level reading (from step 6) minus the current water depth reading (from HOBOlink in step 5).
-
Enter the calculated offset in the Offset
-
Click
-
Verify latest value matches the correct water
-
Enter the scaling values:
-
Enter the Scaled Units: for example meters or This should match the units shown in Latest Value, or you will need to adjust the multiplier to convert.
-
E nter the multiplier in the Multiplier
**Multiplier***
Fresh water| 1
Brackish water| 0.99
Salt water| 0.9765
-
Enter 0 in the Offset field for
-
Enter the Scaled Measurement Type, for example “ Pond Water Level ”.
-
Click save and note the Latest
-
Take a reference water level
- Note this as a negative number if the water level surface is below the reference point, such as groundwater level referenced to the top of the well ( Figure 1 ).
- Note this as a positive number if the water level surface is above the reference point, such as the bottom of the stream or the zero on a staff gauge ( Figure 2 ).
-
Calculate the offset, which is equal to the reference water level reading (from step 6) minus the current water depth reading (from HOBOlink in step 5).
-
Enter the calculated offset in the Offset
-
Click
-
Verify latest value matches the correct water
For specifications, complete mounting guidelines, and other details about
this sensor node, refer to the full product manual. Scan the code at left or
go to:
www.onsetcomp.com/resources/documentation/28084-User-
Guide-RXW-WL
*The Multiplier represents the density of the water, which is a function of its salinity. This is equal to 1 divided by the true density of the water in g/cm3 (e.g., 1/1.025 for typical salt water).