IMI Hydronic DN 15-50 Differential Pressure Controller Instruction Manual

August 17, 2024
IMI Hydronic

IMI Hydronic DN 15-50 Differential Pressure Controller

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
PRODUCT

Product Information

  • Intended use: For measuring and control in heating and cooling systems.
  • The water quality requirements described in VDI2035 should be respected.
  • TA-Smart can be cleansed with a damped cloth and a lenient cleaning agent.
  • Insulated wires and cables shall retard flame propagation with a flammability RATING of UL 2556 VW-1 or equivalent.

24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-2

Service/Repair

  • IMI Hydronic Engineering

Precautions

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-3

  • If the TA-Smart is used in any other application than specified by IMI Hydronic Engineering the protection provided by the equipment may be impaired.

We reserve the right to introduce technical alterations without prior notice.

Technical Specifications

Technical specifiactions valid at an altitude of max. 2000 m.

  • -20°C – +70°C (-4°F – +158°F)
    • (5-95%RH, non-condensing)
  • 0°C – +50°C (32°F – +122°F)
    • (5-95%RH, non-condensing)
  • Input signal : 0-10 VDC
  • Output signal: 0-10 VDC
  • Control mode: Flow
  • Flow setting : qnom
  • Media: H2O
  • Characteristic: EQM

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-7

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-8

Dimensions

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-9

ISO

DN| d| L

[mm]

| H

[mm]

| W

[mm]

15| G3/4| 167| 173| 97
20| G1| 180| 174| 97
25| G1 1/4| 187| 174| 97
32| G1 1/2| 200| 199| 97
40| G2| 218| 198| 97
50| G2 1/2| 239| 198| 97

Size| d| L

[in]

| H

[in]

| W

[in]

1/2”| G3/4| 6.57| 6.81| 3.82
3/4”| G1| 7.09| 6.85| 3.82
1”| G1 /4| 7.36| 6.85| 3.82
1 1/4”| G1 1/2| 7.87| 7.83| 3.82
1 1/2”| G2| 8.58| 7.79| 3.82
2”| G2 1/2| 9.41| 7.79| 3.82

ISO NPT
D1 L1

[mm]

| H1

[mm]

| D1| L1

[mm]

| H1

[mm]

G1/2| 48| 55| 1/2”| 52| 55
G3/4| 60| 56| 3/4”| 55| 56
G1| 62| 61| 1”| 64| 61
G1 1/4| 70| 71| 1 1/4”| 66| 71
G1 1/2| 70| 77| 1 1/2”| 67| 77
G2| 78| 89| 2”| 68| 89

 | D1| L1

[in]

| H1

[in]

1/2”| 2.05| 2.17
3/4”| 2.17| 2.20
1”| 2.52| 2.40
1 1/4”| 2.60| 2.79
1 1/2”| 2.64| 3.03
2”| 2.68| 3.50

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-10

Installation Instructions

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-11

Optional!

Art. No.

  • DN 15-25 (3/4” – 1”) : 322230-00401, L = 14 mm (0.55 in.)
  • DN 32-50 (1 1/4” – 2”): 322230-00400, L = 30 mm (1.18 in.)

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-14

Warning

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-15

Dimension

PipeDN (in. size)

(DIN 2440, ISO 65)

|

L

|

Lt

|

D

---|---|---|---
15-25 (1/2”-1”)| <15 mm

<0.59 in.

| <15 mm

<0.59 in.

|

G1/4

32-50 (1 1/4” – 2”)| <20 mm

< 0.79 in.

| <20 mm

< 0.79 in.

LiYY or similar

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-18

Dimension

Installation

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-20..

Wiring Diagrams

Terminal Description
L24 Power supply 24 VAC/VDC.
M* Neutral for power supply 24 VAC/VDC and signals.
XV Output signal 0(2)-10 VDC, max. 8 mA or min. load resistance 1.25 kW.
M (0V)* Neutral for signal.
Y Input signal 0(2)-10 VDC, 47 kΩ or 0(4)-20 mA, 500 Ω (selectable by jumper

XX).

Ethernet|
RX –| Ethernet connector wire position 6
RX +| Ethernet connector wire position 3
TX –| Ethernet connector wire position 2
TX +| Ethernet connector wire position 1

RS485|
A| RS485 Data +
B| RS485 Data –
M (0V)*| Neutral for signal.信号中性点

  • USB Only for IMI use
  • Serial Debug Only for IMI use

*) All M terminals are internally connected.

HW00 / HW01

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-21

  • To prevent any possible damage to the product caused by incorrect cabling or wiring, we have introduced a version of the TA-Smart PCBA (HW01) with improved electrical wiring.
  • Both PCBA versions are fully functional, but have slightly different wiring configurations.
  • Ensure to choose the correct technical documentation based on the PCBA’s HW version.
  • The PCBA version (HW00 or HW01) can be found on the sticker in the SmartBox and the wiring instruction for each hardware version. HW00 and HW01.
HW00

HW00 (Standard – Modbus RTU / BACnet MS/TP – Modbus TCP / BACnet IP)

Standard
HW00

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-22

Note:

  1. A, B and M terminals are NOT isolated from all other terminals.
  2. GND (M – 0V) is common to power supply, analog signals and RS 485.
  3. In case of AC power supply, L24 and M should be connected to the same phase for each TA-Smart.
  4. GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.

Modbus RTU / BACnet MS/TP
HW00

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-23

Note:

  1. A, B and M terminals are NOT isolated from all other terminals.
  2. GND (M – 0V) is common to power supply, analog signals and RS 485.
  3. In case of AC power supply, L24 and M should be connected to the same phase for each TA-Smart.
  4. GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.
  5. GND (0V) of RS 485 should be connected to 0 VAC/VDC on the controller side.

Modbus TCP / BACnet IP
HW00

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-24

Note:

  1. A, B and M terminals are NOT isolated from all other terminals.
  2. GND (M – 0V) is common to power supply, analog signals and RS 485.
  3. In case of AC power supply, L24 and M should be connected to the same phase for each TA-Smart.
  4. GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.
  5. Ethernet cable shall be Cat 5e or Cat 6 cable. Wire colour indication is for T568B pinout.
HW01

HW01 (Standard – Modbus RTU / BACnet MS/TP – Modbus TCP / BACnet IP)

Standard
HW01

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-25..

Note:

  1. A, B and M terminals are isolated from all other terminals.
  2. GND (M – 0V) is common to power supply and analog signals.
  3. GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.

Modbus RTU / BACnet MS/TP
HW01

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-26

Note:

  1. A, B and M terminals are isolated from all other terminals.
  2. GND (M – 0V) is common to power supply and analog signals.
  3. GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.

Modbus TCP / BACnet IP
HW01

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-27

Note:

  1. A, B and M terminals are isolated from all other terminals.
  2. GND (M – 0V) is common to power supply and analog signals.
  3. GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.
  4. Ethernet cable shall be Cat 5e or Cat 6 cable. Wire colour indication is for T568B pinout.

24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.

LED

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-29

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-30

HyTune

For setting of control parameters use HyTune app.

IMI-Hydronic-DN-15-50-Differential-Pressure-Controller-
FIG-31

FAQ

  • Q: What should I do if the TA-Smart is used in an application not specified by IMI Hydronic Engineering?
    • A: Using the TA-Smart in unauthorized applications may impair the equipment’s protection. It is recommended to only use the device as intended by the manufacturer to ensure proper functioning.
  • Q: How do I clean the TA-Smart?
    • A: The TA-Smart can be cleaned with a damp cloth and a mild cleaning agent. Avoid using harsh chemicals or abrasive materials that may damage the device.

TA-Smart

We reserve the right to introduce technical alterations without prior notice.